| Вид документа | Інструкція |
|---|---|
| Виробник | JCI |
| Моделі | TM-1100, TM-1141-0000, TM-1151-0000, TM-1161-0000, TM-1161-0002, TM-1161-0005, TM-1161-0007, TM-1191-0000 |
| Група обладнання | temperature |
| Мова документа | англійська |
| Розмір файлу | 0.2 МБ |
Про документ
A wall-mounted room command module providing room temperature sensing and local setpoint adjustment for fan coil operations, designed as an input for TC-9102 Series controllers. Some models add fan speed override via a dial, an occupancy button to switch from Unoccupied to Temporarily Occupied, and an optional mode LED. Wiring is also described for TC-9109 and TCU Series controllers.
Ключові дані
| Output element | RTD Thermistor NTC, 2,252 ohms at 77°F (25°C) |
|---|---|
| Setpoint range | 55 to 85°F (12 to 28°C) or ±5F° (±3C°) depending on suffix |
| Accuracy | ±0.9°F (±0.5°C) |
| Ambient operating conditions | 32 to 122°F (0 to 50°C); 10 to 95% RH noncondensing |
| Protection | IP30 (EN 60529) |
| Housing material | ABS + PC, self-extinguishing HB UL94 |
| Field connection | 18 to 26 AWG; 22 AWG recommended |
| Compliance | CE Mark, EMC Directive 89/336/EEC, EN-61000-6-3, EN-61000-6-2 |
Застосування
- Room temperature sensing in fan coil operations
- Local room temperature setpoint adjustment
- Fan speed override (model-dependent)
- Occupancy override from Unoccupied to Temporarily Occupied (model-dependent)
Особливості
- Temperature setpoint adjustment via rotating dial
- Fan speed override with mechanically-guided potentiometer positions (Auto, Off, I, II, III)
- Occupancy button (momentary contact)
- Optional Mode LED indicator
- Wallbox mount with included No. 6-32 x 7/8 in. screws
Технічні дані
| Parameter | Value |
|---|---|
| Models | TM-1141-0000: Temperature output only; TM-1151-0000: Temperature output with occupancy override; TM-1161-000x: Temperature output with setpoint adjustment and occupancy override and optional fan speed adjustment; TM-1191-000x: Temperature output with setpoint adjustment |
| Power requirements | Powered from controller: TC-9102 Series |
| Power consumption | N/A: Refer to individual component specification |
| Inputs | None |
| Adjustments | Temperature setpoint, fan speed (optional by model) |
| Mode indicator | Green LED (5 V, 4 mA) |
| Occupancy button | Momentary contact (switches 5 V at 1 mA) |
| Output element | Resistance Temperature Device (RTD) Thermistor Negative Temperature Coefficient (NTC), 2,252 ohms at 77°F (25°C) |
| Fan speed output | 10k ohm potentiometer with mechanically-guided positions at 0, 25, 50, 75, and 100% for Auto, Off, I (Low Speed), II (Medium Speed), III (High Speed) |
| Setpoint range | -00001: 10k ohm potentiometer marked for 55 to 85°F (12 to 28°C); -00021: same plus fan speed adjustment Auto, Off, I, II, III; -00051: 10k ohm potentiometer marked for ±5F° (±3C°); -00071: same plus fan speed adjustment Auto, Off, I, II, III |
| Accuracy | ±0.9°F (±0.5°C) |
| Field connection | 18 to 26 AWG (1.0 to 0.4 mm diameter); 22 AWG (0.6 mm diameter) recommended |
| Mounting | Wallbox mount |
| Housing material | ABS + PC, self-extinguishing HB UL94 |
| Protection | IP30 (EN 60529) |
| Ambient operating conditions | 32 to 122°F (0 to 50°C); 10 to 95% RH (noncondensing) |
| Ambient storage conditions | -4 to 158°F (-20 to 70°C); 10 to 90% RH (noncondensing) |
| Dimensions | TM-1140, TM-1150: 4.72 x 3.15 x 1.26 in. (120 x 80 x 32 mm); TM-1160, TM-1190: 4.72 x 3.15 x 1.38 in. (120 x 80 x 35 mm) |
| Shipping weight | 0.44 lb (0.2 kg) |
| Wire gauge note | Use 20 AWG (0.8 mm diameter) minimum between controller and module |
| Max wire length | Do not exceed 164 ft. (50 m) between controller and command module |
Варіанти замовлення
Setpoint potentiometer suffix digits (final four digits of model numbers): -00001 = setpoint scale 55 to 85°F (12 to 28°C); -00021 = same scale plus fan speed adjustment; -00051 = ±5F° (±3C°) offset scale; -00071 = offset scale plus fan speed adjustment.
Optional mounting tool: T-4000-119.
Допуски та стандарти
- CE Mark (European Union): EMC Directive 89/336/EEC, EN-61000-6-3, EN-61000-6-2
- IP30 per EN 60529
- Housing self-extinguishing HB per UL94
Позиції каталогу з цим документом
Текст документа
TM-1100 Series Room Command Module
Installation Instructions
Part No. 24-10225-4, Rev. —
Issued January 19, 2006
Applications Installation
The TM-1100 Series Room Command Module Parts Included
provides room temperature sensing in fan coil
The TM-1100 comes with two No. 6-32 x 7/8 in.
operations and can work as a local room temperature
(22 mm) wallbox mounting screws.
setpoint adjustment. Some models provide fan speed
override. Johnson Controls designed the TM-1100 as Special Tools Needed
an input for the TC-9102 Series controllers. To mount the TM-1100 Series Room Command Module
Some of the TM-1100 models allow the local user to to a wall, order the optional tool (T-4000-119) from the
adjust the temperature setpoint and fan speed by Johnson Controls® representative.
turning one of the dials. With those models, the user
can override the Command Mode from Unoccupied to
Temporarily Occupied by pressing the Occupancy
Button (shown in Figure 2 and Figure 3) on the side of
the module that also features an optional Mode
Light-Emitting Diode (LED).
IMPORTANT: The TM-1100 Series Room
Command Modules are intended to provide an input
to equipment under normal operating conditions.
Where failure or malfunction of the TM-1100
Command Module could lead to personal injury or
property damage to the controlled equipment or
other property, other precautions must be designed
into the control system. Incorporate and maintain
other devices such as supervisory or alarm systems
or safety or limit controls intended to warn of, or
protect against, failure or malfunction of the
TM-1100 Command Module.
TM-1100 Series Room Command Module Installation Instructions 1
Dimensions TM-1161 Modules
TM-1141 Modules
1.38 (35)
1.26 (32)
3.15 (80)
3.15 (80)
Fan
Speed
Dial
4.72
4.72 (120)
Mode
(120) LED
Occupancy
Button
Setpoint
TM-1100 ii03.cdr
Adjustment
TM1100 ii01.cdr
Dial
Figure 3: TM-1161 Dimensions, in. (mm)
Figure 1: TM-1141 Dimensions, in. (mm)
TM-1191 Modules
TM-1151 Modules
1.38 (35)
1.26 (32)
3.15 (80)
3.15 (80)
Mode
LED
4.72
4.72 (120)
(120)
Occupancy
Button
Setpoint
TM-1100 ii04.cdr
Adjustment
TM-1100 ii02.cdr
Dial
Figure 4: TM-1191 Dimensions, in. (mm)
Figure 2: TM-1151 Dimensions, in. (mm)
2 TM-1100 Series Room Command Module Installation Instructions
Installing the TM-1100 • Install modules in areas where the temperature is
To install the TM-1100 Series Room Command representative of the general room conditions.
Module: Wiring
1. Remove the base from the cover by inserting a flat To wire a TC-9102, TC-9109, or TCU Series controller
or pointed tool (T-4000-119) into the small hole at to the TM-1100 Series Room Command Module, see
the center top of the cover, while gently pressing the appropriate wiring diagram (Figure 5 to Figure 9).
down to pry the base from the cover.
Note: Use 20 AWG (0.8 mm diameter) wire minimum.
2. Pull the wires through the base and then position Do not exceed 164 ft. (50 m) between the controller
the base on the wallbox with the tabs facing down. and the command module.
3. Mount the base to the wallbox using the two Table 1: Nominal Values for 2,252 ohm Sensors
No. 6-32 mounting screws (included).
Temperature Resistance
4. See the Wiring section for correct wiring. °F °C 2,252 ohms
5. Attach the cover to the base and tighten the cover 20 -7 10,595
screw.
30 -1 7,739.2
Mounting 40 4 6,010.0
Location Considerations 50 10 4,482.3
Mount the TM-1100 Series Room Command Module 60 16 3,378.3
on a wall in the room to be controlled where the 70 21 2,689.6
occupant can easily read and adjust the setpoint dial or 80 27 2,063.9
fan speed override adjustment knob. Following are
90 32 1,666.9
more mounting location guidelines:
100 38 1,300.2
• Avoid areas subject to excessive vibration,
110 43 1,063.9
electrical noise, direct sunlight, or the effects of
radiant heat. 120 49 842.47
130 54 697.65
• Keep electrical wiring as short as possible to
minimize temperature error.
TM-1100 Series Room Command Module Installation Instructions 3
TM-1141-0000 TM-1161-0002 and TM-1161-0007
Room Command Room Command
Controller Module Controller Module
51 51 Three-Speed Fan
Override
14 14 Occupancy Button
TM-1100 ii05.cdr
20 20 NTC Sensor
15 15 Mode LED
20 20 NTC Sensor
21 21 Common
TM-1100 ii08.cdr
23 23 Temperature Setpoint
Figure 5: Wiring to an NTC Room Sensor
21 21 Common
22 22 DC +5 V
TM-1151-0000
Figure 8: Wiring to a Room Command Module
Room Command
Controller Module
Featuring an NTC Sensor with Temperature
Setpoint Adjustment, Occupancy Override, and
14 14 Occupancy Button
Three Speed Fan Override
15 15 Mode LED
TM-1191-0000 and TM-1191-0005
TM-1100 ii06.cdr
20 20 NTC Sensor
Room Command
Controller Module
21 21 Common
Figure 6: Wiring to a Room Command Module
Featuring an NTC Sensor with Occupancy
20 20 NTC Sensor
Override
TM-1100 ii09.cdr
23 23 Temperature Setpoint
TM-1161-0000 and TM-1161-0005 21 21 Common
22 22 DC +5 V
Room Command
Controller Module
Figure 9: Wiring to a Room Command Module
14 14 Occupancy Button
Featuring an NTC Sensor with Temperature
15 15 Mode LED Setpoint Adjustment without Occupancy
20 20 NTC Sensor Override
TM-1100 ii07.cdr
23 23 Temperature Setpoint
21 21 Common
22 22 DC +5 V
Figure 7: Wiring to a Room Command Module
Featuring an NTC Sensor with Temperature
Setpoint Adjustment, and Occupancy Override
4 TM-1100 Series Room Command Module Installation Instructions
The following messages apply to wiring this product.
IMPORTANT: Use copper conductors only. Make
CAUTION: Risk of Electric Shock. all wiring connections in accordance with local,
national, and regional regulations. Do not exceed
! Disconnect power supply before making
electrical connections to avoid electric
shock.
the Command Module electrical ratings.
Setup and Adjustments
CAUTION: Risk of Property Damage. Make temperature or fan speed adjustments to the
appropriate modules using the rotating dial, shown in
! Do not run low voltage cable in the same
conduit or wiring troughs with high
voltage wires. Running low and high
Figure 3 and Figure 4.
Repairs and Replacement
voltage wires in the same conduit or
Do not field repair the TM-1100 Series Room
wiring troughs may damage the
Command Module. As with any electrical device, keep
equipment or cause system malfunction.
the air vents clean and free from dust and obstruction.
To order replacement parts, contact the nearest
CAUTION: Risk of Property Damage. Johnson Controls representative.
! Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
Technical Specifications
TM-1100 Series Room Command Module (Part 1 of 2)
Models TM-1141-0000 Temperature Output Only
TM-1151-0000 Temperature Output with Occupancy Override
TM-1161-000x Temperature Output with Setpoint Adjustment and Occupancy
Override and Optional Fan Speed Adjustment
TM-1191-000x Temperature Output with Setpoint Adjustment
Power Requirements Powered from Controller: TC-9102 Series
Power Consumption N/A: Refer to individual component specification.
Inputs None
Adjustments Temperature Setpoint, Fan Speed (Optional by Model)
Mode Indicator Green LED (5 V, 4 mA)
Occupancy Button Momentary Contact (Switches 5 V at 1 mA)
Output Temperature Sensing Resistance Temperature Device (RTD) Thermistor Negative
Element Temperature Coefficient (NTC) 2,252 ohms at 77°F (25°C)
Fan Speed 10k ohm Potentiometer, with Mechanically-Guided Positions
at 0, 25, 50, 75, and 100% for Auto, Off, I (Low Speed),
II (Medium Speed), and III (High Speed)
Setpoint Range -00001 = 10k ohm Potentiometer marked for: 55 to 85°F (12 to 28°C)
-00021 = 10k ohm Potentiometer marked for: 55 to 85°F (12 to 28°C);
Fan Speed Adjustment: Auto, Off, I, II, and III
-00051 = 10k ohm Potentiometer marked for: ±5F° (±3C°)
-00071 = 10k ohm Potentiometer marked for: ±5F° (±3C°);
Fan Speed Adjustment: Auto, Off, I, II, and III
Accuracy ±0.9°F (±0.5°C)
Field Connection 18 to 26 AWG (1.0 to 0.4 mm diameter);
22 AWG (0.6 mm diameter) recommended
Mounting Wallbox Mount
TM-1100 Series Room Command Module Installation Instructions 5
TM-1100 Series Room Command Module (Part 2 of 2)
Housing Material ABS + PC, Self-Extinguishing HB UL94
Protection IP30 (EN 60529)
Ambient Operating Conditions Temperature 32 to 122°F (0 to 50°C)
Humidity 10 to 95% RH (Noncondensing)
Ambient Storage Conditions Temperature -4 to 158°F (-20 to 70°C)
Humidity 10 to 90% RH (Noncondensing)
Dimensions TM-1140, TM-1150 4.72 x 3.15 x 1.26 in. (120 x 80 x 32 mm)
TM-1160, TM-1190 4.72 x 3.15 x 1.38 in. (120 x 80 x 35 mm)
Shipping Weight 0.44 lb (0.2 kg)
Compliance European Union CE Mark: EMC Directive 89/336/EEC, EN-61000-6-3,
EN-61000-6-2
1. This number refers to the final four digits of the TM-1100 series model numbers.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Controls Group Metasys® is a registered trademark of Johnson Controls, Inc.
507 E. Michigan Street All other marks herein are the marks of their respective owners.
Milwaukee, WI 53202 © 2006 Johnson Controls, Inc.
6 TM-1100 Series Room Command Module Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.