The TEC22x4-3 thermostats are LONWORKS® networked devices providing control of single- or multi-stage unitary rooftop units with economizers. The TEC2204-3 is non-programmable; the TEC2264-3 adds programmability (schedules, clock). Both provide remote monitoring via BAS LONWORKS network communication for efficient space temperature control.
Ключові дані
| Power supply | 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or SELV |
|---|---|
| Economizer output | 0 to 10 VDC into 2k ohm Resistance (Minimum) |
| Relay contact rating | 30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or SELV |
| Temperature accuracy | ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated |
| Display range | -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments (backlit) |
| Heating control range | 40.0°F/4.5°C to 90.0°F/32.0°C |
| Cooling control range | 54.0°F/12.0°C to 100.0°F/38.0°C |
| Ambient operating conditions | 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing |
Застосування
- Control of single- or multi-stage unitary rooftop units with economizers
- Remote monitoring and programmability for efficient space temperature control via LONWORKS network
Особливості
- Backlit, plain-text 2-line, 8-character LCD readable in any condition
- Three LEDs indicate fan status, call for heat, call for cooling
- Five-key intuitive user interface with Auto Help
- Economizer actuator output (0–10 VDC) with minimum position and changeover setpoint configuration
- Two configurable digital inputs (DI1/DI2): Service alarm, Filter alarm, Remote Override, or Remote Night Setback
- Auxiliary output for peripheral devices (lighting equipment, exhaust fans, economizers)
- Frost protection with minimum heating setpoint of 42.0°F/5.5°C
- Anti-short cycle timer, heating/cooling cycles-per-hour limits, configurable deadband
- Outdoor temperature-based heating/cooling lockout and economizer changeover
- Neuron® ID broadcast for network commissioning
Технічні дані
| Parameter | Value |
|---|---|
| Power Requirements | 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV) |
| Economizer Output Rating | 0 to 10 VDC into 2k ohm Resistance (Minimum) |
| Accuracy | ±3% |
| Relay Contact Rating | 30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or SELV |
| Digital Inputs | Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2 |
| Wire Size | Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended |
| LONWORKS Network Standard | 64 Devices Maximum without repeater, 128 Devices Maximum with repeater; 6,250 ft (1,905 m) Maximum Length (Bus Topology) |
| Temperature Sensor Type | Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor |
| Temperature Range Display | -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments, backlit |
| Heating Control | 40.0°F/4.5°C to 90.0°F/32.0°C |
| Cooling Control | 54.0°F/12.0°C to 100.0°F/38.0°C |
| Accuracy Temperature | ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated |
| Minimum Deadband | 2F°/1C° between Heating and Cooling |
| Ambient Operating Conditions | 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing |
| Storage | -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing |
| Shipping Weight | 0.75 lb (0.34 kg) |
Terminal identification
| Number | Label | Function |
|---|---|---|
| 1 | Y2 | Energizes on a call for second-stage cooling |
| 2 | Y1 | Energizes on a call for first-stage cooling |
| 3 | G | Energizes fan in accordance with selected fan mode |
| 4 | RC | 24 VAC from equipment transformer |
| 5 | C | 24 VAC (Common) from equipment transformer |
| 6 | RH | 24 VAC for heating stage |
| 7 | W1 | Energizes on a call for first-stage heating |
| 8 | W2 | Energizes on a call for second-stage heating |
| 9 | EC | 0 to 10 VDC Economizer Actuator Output |
| 10 | Aux | Auxiliary output |
| 11 | DI1 | Configurable Digital Input 1 |
| 12 | DI2 | Configurable Digital Input 2 |
| 13 | RS | Remote Room Temperature Sensor |
| 14 | Scom | Sensor Common |
| 15 | OS | Auxiliary/Outdoor Air Sensor |
| 16 | MS | Mixed Air Temperature Sensor |
Варіанти замовлення
Accessories (order separately):
| Code Number | Description |
|---|---|
| SEN-600-1 | Remote Indoor Air Temperature Sensor |
| SEN-600-4 | Remote Indoor Air Temperature Sensor with Occupancy Override and LED |
| TE-6361M-1 | Duct Mount Air Temperature Sensor |
| TE-636S-11 | Strap-on Temperature Sensor |
Related literature: LONWORKS Network Layout Technical Bulletin (LIT-1162150), TEC226x-3 and TEC220x-3 Series LONWORKS® Network Configurable Staged Thermostats Technical Bulletin (LIT-12011196), TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320).
Допуски та стандарти
- United States: UL Listed, File E27734, CCN XAPX, under UL 873, Temperature Indicating and Regulating Equipment
- United States: FCC Compliant to CFR 47, Part 15, Subpart B, Class A
- LONMARK® Certification: 3.4 (pending)
- Canada: UL Listed, File E27734, CCN XAPX7, under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
- Canada: Industry Canada, ICES-003
- Europe: CE Mark, EMC Directive 89/336/EEC
- Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant
Текст документа
TEC22x4-3 LONWORKS® Networked
Multi-Stage Economizer Thermostats
Part No. 24-9890-501, Rev. —
Installation Instructions Issued September 8, 2006
Applications Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
The TEC2204-3 non-programmable and
brouilleur du Canada.
TEC2264-3 programmable thermostats are
LONWORKS® networked devices that provide control of Installation
single- or multi-stage unitary rooftop units with
economizers. The technologically advanced Location Considerations
TEC22x4-3 thermostats feature a Building Automation Locate the TEC22x4-3 thermostat:
System (BAS) LONWORKS network communication
• on a partitioning wall, approximately 5 ft (1.5 m)
capability that enables remote monitoring and
above the floor in a location of average
programmability for efficient space temperature control.
temperature
IMPORTANT: The TEC22x4-3 thermostats are • away from direct sunlight, radiant heat, outside
intended to provide an input to equipment under walls, behind doors, air discharge grills, stairwells,
normal operating conditions. Where failure or or outside doors
malfunction of the thermostat could lead to personal
injury or property damage to the controlled • away from steam or water pipes, warm air stacks,
equipment or other property, additional precautions unconditioned areas (not heated or cooled), or
must be designed into the control system. sources of electrical interference
Incorporate and maintain other devices such as Note: Allow for vertical air circulation to the
supervisory or alarm systems or safety or limit TEC22x4-3 thermostat.
controls intended to warn of, or protect against,
failure or malfunction of the thermostat. To install the thermostat:
1. Use a Phillips-head screwdriver to remove the
North American Emissions Compliance security screw on the bottom of the thermostat
United States cover.
This equipment has been tested and found to comply 2. Pull the bottom edge of the thermostat cover and
with the limits for a Class A digital device pursuant to open the thermostat as illustrated in Figure 1.
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference,
in which case the user will be required to correct the
interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing FIG:cvr_rmvl
Equipment Regulations.
Figure 1: Removing the Thermostat Cover
TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats 1
Installation Instructions
3. Carefully pull the locking tabs on the right side of 8. Swing the PCB back to the right and carefully snap
the thermostat mounting base and unlock the it into the locking tabs on the thermostat mounting
Printed Circuit Board (PCB). Open the PCB to the base.
left as illustrated in Figure 2. 9. Pull the pull tabs on each of the connectors and
remove the screw terminal blocks as illustrated in
Figure 4.
PCB
Locking
Tabs
FIG:prntd_crct_brd
Figure 2: Opening the Thermostat PCB
4. Pull approximately 6 in. (152 mm) of wire from the FIG:trmnl_blcks
wall and insert the wire through the hole in the
thermostat mounting base. Figure 4: Removing the Screw Terminal Blocks
5. Align the thermostat mounting base on the wall and
use the base as a template to mark the two Wiring
mounting hole locations.
When an existing thermostat is replaced, remove and
Note: Be sure to position the thermostat mounting label the wires to identify the terminal functions. When
base so that the arrow on the base points upward to a TEC22x4-3 thermostat is replaced, simply remove
indicate the top of the thermostat. the old screw terminal blocks and reinsert them onto
6. Drill a 3/16 in. (5 mm) hole at each of the two the PCB of the replacement thermostat.
marked locations and tap nylon anchors (included
with the thermostat) flush to the wall surface. CAUTION: Risk of Electric Shock.
Disconnect the power supply before
7. Position the thermostat mounting base on the wall
and use the two mounting screws (included with
! making electrical connections to avoid
electric shock.
the thermostat) to secure the base to the surface
as illustrated in Figure 3. CAUTION: Risk of Property Damage.
Do not apply power to the system before
Note: Be careful not to overtighten the mounting
screws. ! checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the TEC22x4-3 thermostat.
To wire the thermostat:
FIG:mntng_bs 1. Strip the ends of each wire 1/4 in. (6 mm) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
Figure 3: Securing the Thermostat
Mounting Base to the Wall
2 TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Note: For more details on wiring the
LONWORKS network, refer to the Table 1: Terminal Identification (See Figure 5.)
LONWORKS Network Layout Technical Bulletin
Number Label Function
(LIT-1162150).
1 Y2 Energizes on a call for second-stage
2. Carefully push any excess wire back into the wall. cooling.
Seal the hole in the wall with fireproof material to 2 Y1 Energizes on a call for first-stage
prevent drafts from affecting the ambient cooling.
temperature readings. 3 G Energizes fan in accordance with
3. Reinsert the screw terminal blocks onto the PCB. selected fan mode.
4 RC 24 VAC from equipment transformer
4. Reattach the LONWORKS communication wires to
the LON terminal block. See Figure 5. 5 C 24 VAC (Common) from equipment
transformer
Note: If inserting multiple wires into the terminals, be
6 RH 24 VAC for heating stage
sure to properly twist wires together prior to inserting
them in the terminal connectors. 7 W1 Energizes on a call for first-stage
heating.
5. Reattach the thermostat cover to the mounting 8 W2 Energizes on a call for second-stage
base (top side first). heating.
6. Use a Phillips-head screwdriver to reinstall the 9 EC 0 to 10 VDC Economizer Actuator
security screw on the bottom of the thermostat Output
cover. 10 Aux Auxiliary output
11 DI1 Configurable Digital Input 1
Five-Pole Three-Pole
Left Top Connector Right Top Connector 12 DI2 Configurable Digital Input 2
RH W1 W2
13 RS Remote Room Temperature Sensor
LONWORKS Y2 Y1 G RC C
Bus Terminals 14 Scom Sensor Common
1 2 3 4 5 6 7 8
15 OS Auxiliary/Outdoor Air Sensor
FIG:econ_term
16 MS Mixed Air Temperature Sensor
Eight-Pole Bottom Connector Blank Blank LONWORKS Bus
EC Aux DI1 DI2 RS Scom OS MS
9 10 11 12 13 14 15 16
Figure 5: Terminal Blocks
Isolated Contact
• Lighting
• On/Off Actuation LONWORKS
Bus Terminal
• Exhaust Fan
Y2 Y1 G RC C RH W1 W2 EC Aux DI1 DI2 RS Scom OS MS
Heat 1 Heat 2 24VAC 0-10
Supervisory
Common VDC
Controller
Cool 2 Cool 1 Fan Aux
FIG:TEC22x4_wrng
Remote
Remote Auxiliary/ Monitoring
If using the same power source Room Outdoor Supply
24 VAC for the thermostat and heating loads, Sensor Air Sensor Temperature
Thermostat Power install a jumper across RC and RH. Sensor
Figure 6: Wiring the TEC22x4-3 Thermostats
TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions 3
Connecting the LONWORKS Network The LONWORKS network requires proper termination
The wiring rules for the LONWORKS network differ from and biasing at the end of a segment (a segment is a
the wiring rules for the Metasys® N2 Bus and the physically continuous length of wire). The thermostat is
BACnet® MS/TP Bus. For more details on wiring the not equipped with the ability to provide this termination;
LONWORKS network, refer to the LONWORKS Network therefore, it cannot be located at the physical end of a
Layout Technical Bulletin (LIT-1162150). LONWORKS network segment unless a terminator is
attached. Refer to LONWORKS Network Layout
To connect the thermostat to the LONWORKS network: Technical Bulletin (LIT-1162150) for end-of-line
solutions.
1. Connect the LONWORKS network wires to the Setup and Adjustments
LONWORKS network terminal block on the
thermostat (Figure 5, Figure 6, and Figure 7). Thermostat Operation Overview
LONWORKS
Bus Terminals
Supervisory
Controller
LONWORKS Backlit, plain text
LONWORKS LCD is easy to read
Network Wires Network in any condition. Room Temp
Terminal Block 70.0ºF
LEDs indicate
system activity. YES NO
Twist wires together
before inserting them into
the terminals.
FIG:frnt_vw
Five keys on the thermostat
FIG:LON_wir
make operation easy and intuitive.
Figure 8: Front Cover of Thermostat
Figure 7: Thermostat to Network Connection
Thermostat User Interface Keys
Note: There is no polarity when connecting the
The TEC22x4-3 thermostat user interface consists of
LONWORKS network wires to the thermostat; however,
five keys on the front cover (as illustrated in Figure 8).
we recommend keeping the polarity consistent
The function of each key is as follows:
throughout the network.
• Use the YES/SCROLL key to:
2. After the LONWORKS network wires are connected
to the first thermostat, continue in a daisy-chained - confirm menu selections and to advance to the
fashion to the next device. next menu item
Note: The LONWORKS network wiring must be twisted- - stop the Status Display Menu from scrolling
pair lines. and to manually scroll to the next parameter on
the menu
Do not run the LONWORKS network wiring in the same
conduit as line voltage wiring (30 VAC or above) or Note: When the thermostat is left unattended for
other wiring that switches power to highly inductive 45 seconds, the thermostat display resumes scrolling.
loads (such as contactors, coils, motors, or
• Use the NO key to decline a parameter change and
generators).
to advance to the next menu item.
4 TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
• Use the MENU key to: The Installer Configuration Menu is used to set up
the thermostat for application-specific operation. To
- access the Main User Menu or to exit the menu
access this menu, press and hold the MENU key for
(See the Main User Menu section.)
approximately 8 seconds.
- access the Installer Configuration Menu or to
exit the menu (See the Configuring the
Configuring the TEC22x4-3 Thermostats
TEC22x4-3 Thermostat section.) The TEC22x4-3 thermostats come from the factory
with default settings for all configurable parameters.
• Use the UP/DOWN arrow keys to change the The default settings are shown in Table 2. To
configuration parameters and to activate a setpoint reconfigure the parameters via the thermostat, follow
adjustment. the steps in this section.
Backlit Liquid Crystal Display (LCD) 1. To access the Installer Configuration Menu, press
The TEC22x4-3 thermostat includes a 2-line, and hold the MENU key for approximately
8-character backlit display. Low-level backlighting is 8 seconds.
present during normal operation, and it brightens when
2. Once the Installer Configuration Menu begins,
any user interface key is pressed. The backlight returns
press the NO key to scroll through the parameters
to low level when the thermostat is left unattended for
listed in Table 2.
45 seconds.
3. When the desired parameter is displayed, use the
Light-Emitting Diodes (LEDs) YES key to choose the desired selection option.
Three LEDs are included to indicate the fan status, call
4. Press the YES key and then the NO key to
for heat, or call for cooling:
continue scrolling through the parameters.
• The FAN LED is on when the fan is on.
To exit the Installer Configuration Menu any time, press
• The HEAT LED is on when heating is on. the MENU key, and at the exit prompt, press the YES
key. To pass over a parameter without changing it,
• The COOL LED is on when cooling is on.
press the NO key.
Programming Overview When the thermostat is in the Installer Configuration
There are three menus used to view, program, and Menu and left unattended for approximately 8 seconds,
configure the TEC22x4-3 thermostats. the thermostat reverts to the Status Display Menu.
The Status Display Menu is displayed during normal For additional information on commissioning and
thermostat operation. This menu continuously scrolls configuring thermostats, adding thermostats to a
through the following parameters: Network Automation Engine (NAE), thermostat
• Room Temperature mapping, and remote themostat commanding, refer to
TEC226x-3 and TEC220x-3 Series LONWORKS®
• Clock (TEC2264-3 only) Network Configurable Staged Thermostats Technical
• System Mode Bulletin (LIT-12011196).
• Occupancy Status – Occupied/Unoccupied/ Configuring the Thermostat’s Neuron®
Override Identification
• Outdoor Temperature – An outdoor air temperature Press and hold the UP/DOWN arrow keys
sensor must be connected. simultaneously for five seconds to broadcast the
thermostat’s Neuron Identification on the LONWORKS
• Applicable Alarms – The backlight lights up as an network.
alarm condition is displayed.
If the cover is removed, you can see a green LED
Note: Press the YES/SCROLL key to temporarily stop under the LON board flash when the thermostat
this menu from scrolling. broadcasts the Neuron ID. The Neuron ID is on a label
The Main User Menu is used to access and change on the Echelon® chip.
the basic operating parameters of the thermostat. You cannot send the Neuron ID while in the Installer
Access this menu by pressing the MENU key during Configuration menu.
normal thermostat operation.
TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions 5
Configuring Inputs DI1 and DI2 Both inputs can be configured to the Selection Options
When DI1 and DI2 are configured for an alarm included in Table 2.
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
Table 2: Installer Configuration Menu (Part 1 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
DI11 Configuration of Digital Input 1. (None): No function is associated with an input.
Default: None (Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
DI21 Configuration of Digital Input 2. (None): No function is associated with an input.
Default: None (Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
Lockout Selectable Lockout Levels for Function Lockout Level
limiting end-user keypad interaction.
(0) (1) (2)
Default: 0
Occupancy Access Access No Access
Override
Permanent Access No Access No Access
Temperature
Setpoints
Temporary Access Access No Access
Temperature
Setpoints
System Mode Access No Access No Access
Setting
Fan Mode Access No Access No Access
Setting
Schedules Access No Access No Access
Setting4
Clock Setting4 Access Access Access
6 TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 2: Installer Configuration Menu (Part 2 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
Pwr del2 Sets the delay time period at Range: 10.0 to 120.0 sec
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
Frost pr Provides a minimum heating (on): Enabled
setpoint of 42.0°F/5.5°C to prevent (off): Disabled
freezing in the zone controlled by
the thermostat.
Default: off
Heat max3 Sets the Occupied and Unoccupied Range: 40.0°F/4.5°C to 90.0°F/32.0°C
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Cool min3 Sets the Occupied and Unoccupied Range: 54.0°F/12.0°C to 100.0°F/37.5°C
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Anticycl Anti-Short Cycle timer sets the Range: 0.0 to 5.0 min adjustable in 1-minute increments
minimum on/off times for heating Set the anti-short cycle timer to 0.0 min for equipment that already
and cooling stages. has its own anti-short cycle timer.
Default: 2.0 min
Heat cph Sets the maximum number of Range: 3.0 to 8.0 cycles per hour
Heating cycles per hour.
Default: 4.0
Cool cph Sets the maximum number of Range: 3.0 or 4.0 cycles per hour
Cooling cycles per hour.
Default: 4.0
Deadband Sets the minimum deadband Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
between the heating and cooling increments
setpoints.
Default: 2.0F°/1.0C°
Fan cont Determines how the fan is activated (off): The thermostat will not activate the fan in response to a call
in response to a call for heating. for heating. The fan is activated by the equipment fan and limit
Fan cont applies to W1 & W2 and control.
Fan Mode auto only. Fan cont (on): Enables the thermostat to activate the fan in response to a call
does not affect fan operation on a for heating or cooling.
call for cooling (Y1 & Y2).
Default: on
Fan del Fan delay extends fan operation (on): Extends fan operation by 60 seconds after a heating or cooling
after a heating or cooling cycle has cycle has ended.
ended. (off): No extension of fan operation after a heating or cooling cycle
Default off has ended.
The fan delay is only active when the fan is in the Auto mode.
TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions 7
Table 2: Installer Configuration Menu (Part 3 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
TOccTime Sets the duration of the Tempo- Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
rary Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Over-
ride Function is enabled using ei-
ther the Main User Menu or DI1
or DI2 configured as a temporary
override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default: 3.0 hrs
Cal RS Sets the desired room air Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
temperature sensor calibration increments
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Cal OS Sets the desired outdoor air Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
temperature sensor calibration increments
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
H stage Reverts the operation of a two-stage (1.0): One Stage
thermostat to a single-stage (2.0): Two Stages
thermostat when the second heating
stage is not needed.
Default: 2.0
C stage Reverts the operation of a two-stage (1.0): One Stage
thermostat to a single-stage (2.0): Two Stages
thermostat when the second cooling
stage is not needed.
Default: 2.0
H lock Discontinues heating operation in Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
C lock Discontinues cooling operation in Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected. C lock
does not disable economizer free
cooling operation.
Default: -40°F/-40°C
2/4event4 Sets the number of events within a (2.0): Two events (one occupied and one unoccupied) within a
24-hour period. 24-hour period
Default: 2.0 (4.0): Four events (two occupied and two unoccupied) within a
24-hour period
8 TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 2: Installer Configuration Menu (Part 4 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
Aux cont Energizes peripheral devices (n.c.): Contact open = Occupied; contact closed = Unoccupied
(lighting equipment, exhaust fans, (n.o.): Contact closed = Occupied; contact open = Unoccupied
and economizers). The contact toggles with the internal Occupied/Unoccupied
Default: n.o. schedule (or the NSB contact on one of the digital inputs, if used).
Prog rec4 Provides the desired occupied (on): Enabled (provides the desired occupied temperature at the
temperature either at the start of the start of the occupied schedule)
occupied schedule or after the (off): Disabled (provides the desired occupied temperature after the
occupied schedule begins. occupied schedule begins)
Note: Progressive recovery is
disabled if either DI1 or DI2
is configured as remote NSB
Default: off
Chngstpt3 Sets the economizer changeover Range: 14.0°F/-10.0°C to 70.0°F/21.0°C
strategy, based on the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
When the OA temperature is below
the changeover setpoint, free
cooling is used (economizer
operation). When the OA
temperature is above the setpoint,
mechanical cooling is used
(compressor operation).
Default: 55.0°F/13.0°C
Min pos Sets the minimum position for the Range: 0.0 to 100.0% equals 0 to 10 VDC output range
OA dampers on the economizer.
These dampers are energized to % OA Setting for Setting for
minimum position when the fan 0 to 10 VDC 2 to 10 VDC
(Terminal G) is energized and the Actuator Actuator
thermostat is in the Occupied mode.
(0.0%) 0% 0 to 20%
When the schedule is in the
Unoccupied mode, the minimum (5.0%) 5% 24%
position is 0%.
(10.0%) 10% 28%
Default: 0.0%
(15.0%) 15% 32%
(20.0%) 20% 36%
(25.0%) 25% 40%
(30.0%) 30% 44%
C mech Determines whether to allow (on): Typically applies when the MS is installed before the
mechanical cooling (compressor mechanical cooling refrigeration coils in the mixing plenum. In this
operation) if free cooling scenario, mechanical cooling is allowed when free cooling cannot
(economizer operation) cannot maintain the cooling setpoint.
maintain the cooling setpoint. (off): Typically applies when the remote Mixed air Sensor (MS) is
Default: off installed after the mechanical cooling refrigeration coils. In this
scenario, mechanical cooling will never operate at the same time as
free cooling.
Mix stpt3 Establishes the mixed air Range: 50.0°F/10.0°C to 90.0°/32.0°C
temperature when operating in the
economizer mode.
Default: 55.0°F/13.0°C
TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions 9
Table 2: Installer Configuration Menu (Part 5 of 5)
Parameter Description and Default Selection Options
Appearing
on Display
Display MS Displays the mixed air temperature. The mixed air temperature can be used to help service and
Requires that an MS be installed troubleshoot the equipment and the economizer operation. The
and connected. mixed air temperature is only accessible via the Installer
Default: N/A Configuration Menu.
1. Setting DI1 or DI2 to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables
schedules and the Schedule menu. (TEC2264-3 only)
2. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
3. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
4. TEC2264-3 only
Operation 2. Press the YES key to enable the temporary
override. The thermostat returns to the Status
Programming/Operating the TEC22x4-3 Display Menu.
Thermostats
When scrolling through the Status Display Menu,
Once the thermostat is configured via the Installer
Override now appears for the schedule status
Configuration Menu, its operating parameters can be
parameter.
programmed via the Main User Menu. Access this
menu by pressing the MENU key during normal Resuming the Programmed Schedule
thermostat operation. The Main User Menu contains This menu only appears when the thermostat is in the
the basic operating features of the thermostat. unoccupied override mode.
The Main User Menu also uses Auto Help, which is To resume the schedule while in the Main User Menu:
displayed automatically in the menu when there is a
pause in programming activity. To exit Auto Help, 1. Press the NO key to all prompts until the
continue with the programming selection. When the Cancel ovrd Y/N prompt appears. If the thermostat
thermostat is in the Main User Menu and is left is in the unoccupied override state, this is the first
unattended for 45 seconds, the menu reverts to the prompt.
Status Display Menu. 2. Press the YES key to resume the programmed
Enabling Override Schedule schedule.
Note: Enabling Override Schedule only appears when The thermostat returns to the Status Display Menu.
in the Unoccupied Mode.
Entering Permanent Temperature Setpoints
The override schedule prompt only appears when the The first prompt appearing in the Main User Menu of
thermostat is in the unoccupied override state. This the thermostat when in the occupied state is to set the
menu selection gives the user the option of overriding permanent temperature setpoint. Permanent setpoints
the unoccupied setpoints with the occupied setpoints are stored in the programmed schedule.
for the amount of time specified under the TOccTime
parameter. See the Configuring the TEC22x4-3 To enter the permanent heating and cooling setpoints
Thermostat section. for the Occupied and Unoccupied Modes, follow the
steps in Table 3. When changing the temperatures,
Note: If one of the digital inputs is configured to press the keys once to change the temperature in
operate as a remote override contact, this menu is 0.5F°/0.5C° increments; press and hold down the keys
disabled. to change the temperature in 5.0F°/5.0C° increments.
To override the unoccupied state while in the Main User Entering Temporary Temperature Setpoints
Menu:
To temporarily change the setpoint, press the
1. Press the NO key to all prompts until the Cancel UP/DOWN arrow keys to change the temporary
ovrd prompt appears. If the thermostat is in the setpoint for the current mode of operation.
unoccupied state, this is the first prompt.
10 TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 3: Entering Permanent Temperature Table 3: Entering Permanent Temperature
Setpoints (Part 1 of 2) Setpoints (Part 2 of 2)
Thermostat Description Thermostat Description
Display Display
Press the MENU key while in the Press the YES key to set the display
RoomTemp Status Display Menu to enter the °F/°C units to °F or °C. Press the NO key to
75.0°F Main User Menu. advance to the temperature setpoint
set? Y/N
type menu.
Press the NO key to all prompts until Press the YES key to return to the
Temperat the temperature setpoint prompt Exit? Status Display Menu or press the NO
set? Y/N appears on the display (it may be the Y/N key to reenter the temperature
first prompt). Press the YES key to setting menu.
enter the temperature setting menu.
Press the YES key to change the
Cooling occupied cooling setpoint. Press the Note: Whether the thermostat is heating or cooling,
set? Y/N NO key to advance to the occupied the respective setpoint is temporarily adjusted. To
heating setpoint menu. toggle between the temporary heating and cooling
setpoints, press the NO key while changing the
Press the UP/DOWN arrow keys to temporary setpoints.
Cooling set the temperature. Press the YES
key to store the value and advance to Ending Temporary Temperature Setpoints
75.0°F
the next menu. The temporary setpoints remain in effect for the
duration set in the TOccTime parameter or until
manually released.
Press the YES key to change the
Heating occupied heating setpoint. Press the To release the temporary setpoint sooner, while in the
set? Y/N NO key to advance to the unoccupied
Main User Menu:
cooling setpoint menu.
1. Press the YES key to the first prompt that appears.
Press the UP/DOWN arrow keys to 2. If the thermostat does not immediately return to the
Heating set the temperature. Press the YES Status Display Menu, press the MENU key again
68.0°F key to store the value and advance to
and press the YES key to exit the Main User Menu.
the next menu.
The setpoint reverts to the Permanent Temperature
Setpoint.
Press the YES key to change the
Unocc CL unoccupied cooling setpoint. Press Selecting the System Mode
set? Y/N the NO key to advance to the
unoccupied heating setpoint. The thermostat has four system modes:
• Automatic Mode (auto): Automatic changeover
Press the UP/DOWN arrow keys to between heating and cooling. This is the default
Unocc CL set the temperature. Press the YES setting.
80.0°F key to store the value and advance to
the next menu. • Cooling Mode (cool): Cooling operation only
• Heating Mode (heat): Heating operation only
Press the YES key to change the • Off Mode (off): The thermostat is off; however,
Unocc HT unoccupied heating setpoint. Press
when frost protection (Frost pr parameter) is
set? Y/N the NO key to advance to the
temperature display units. enabled, the thermostat still calls for heat
(if required).
Press the UP/DOWN arrow keys to To set the system mode while in the Main User Menu:
Unocc HT set the temperature. Press the YES
1. Press the NO key to all prompts until the system
62.0°F key to store the value and advance to
the next menu. mode prompt appears on the display. Press the
YES key to select the desired system mode.
TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions 11
2. Press the UP/DOWN arrow keys to locate the To set the time schedule for a two-event schedule,
desired system mode. Press the YES key to select follow the steps in Table 4. See Table 6, Events 1
the desired system mode. and 2, for an example of a two-event office schedule.
3. Press the YES key to return to the Status Display Table 4: Programming the Daily Schedule –
Menu or press the NO key to return to the system Two-Event (Part 1 of 2)
mode selection menu. Thermostat Description
Selecting the Fan Mode Display
The thermostat has three fan mode settings: Press the MENU key while in the
RoomTemp Status Display Menu to enter the
• On Fan Mode (on): Energizes the fan all the time 75.0°F Main User Menu.
for both occupied and unoccupied states, even if
the system mode is set to off.
• Automatic Fan Mode (auto): Energizes the fan Press the NO key to all prompts until
only on a call for heating or cooling, for both Schedule the schedule set prompt appears on
set? Y/N the display. Press the YES key to
occupied and unoccupied states. enter the scheduling menu.
• Smart Fan Mode (smart): Energizes the fan all
the time for occupied states, and only on a call for Press the YES key to set the
heating or cooling in unoccupied states. This is the schedule for Monday or press the NO
Monday
default setting. set? Y/N key to advance to Tuesday.
To select the fan mode while in the Main User Menu:
1. Press the NO key to all prompts until the fan mode Press the YES key to set the
prompt appears on the display. Press the YES key occupied start time for Monday or
Occupied
to set the fan mode. day? Y/N press the NO key to advance to
Tuesday. Selecting NO will leave the
2. Press the UP/DOWN arrow keys to locate the thermostat in the unoccupied state
desired fan mode. Press the YES key to select the for the entire day.
desired fan mode. Press the UP/DOWN arrow keys to
3. Press the YES key to return to the Status Display Occupied set the occupied start time. Press the
12:00 AM YES key to enter the time.
Menu or press the NO key to return to the fan
mode selection menu.
Selecting Schedule (TEC2264-3 Only) Press the UP/DOWN arrow keys to
Programming the Daily Schedule – Two-Event Unoccup set the unoccupied start time. Press
12:00 AM the YES key to enter the time.
The schedule-setting menu is used to enter the
occupied or unoccupied states for each day of the
week. The schedule-setting menu reflects either a
Press the YES key to set the
two- or a four-event schedule per day, based on what
Tuesday schedule for Tuesday or press the
was selected in the 2/4event parameter during the NO key to advance to Wednesday.
set? Y/N
configuration process. If the schedule-setting menu
does not reflect a two-event schedule, select two
events in the 2/4event parameter of the Installer
Press the YES key to copy the
Configuration Menu.
Copy Y/N schedule from the previous day.
When changing the time, press the UP/DOWN arrow previous Press the NO key to set a different
schedule.
keys once to change the time in 1-minute increments;
press and hold down the keys to change the time in
30-minute increments.
Note: Programming one of the digital inputs to remote
NSB disables the menu.
12 TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 4: Programming the Daily Schedule – Table 5: Programming the Daily Schedule –
Two-Event (Part 2 of 2) Four-Event (Part 2 of 2)
Thermostat Description Thermostat Description
Display Display
If the YES key was pressed, the next Press the YES key to set the
Wednesda prompt is for Wednesday. Repeat the Monday schedule for Monday or press the NO
set? Y/N procedure for the rest of the days of set? Y/N key to advance to Tuesday.
the week.
After setting the schedule for all the Press the YES key to set the
Exit? days of the week, following the last Occupied occupied start time for Monday or
Y/N entry for Sunday, press the YES key day? Y/N press the NO key to advance to
to return to the Status Display Menu Tuesday. SelectinПоказано початок документа. Повний текст — у PDF за посиланням вище.