LONWORKS Networked Multi-Stage Economizer Thermostat TEC22x4-3

Вид документаІнструкція
ВиробникJCI
МоделіTEC2204-3, TEC2264-3
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.3 МБ

Про документ

The TEC22x4-3 thermostats are LONWORKS® networked devices providing control of single- or multi-stage unitary rooftop units with economizers. The TEC2204-3 is non-programmable; the TEC2264-3 adds programmability (schedules, clock). Both provide remote monitoring via BAS LONWORKS network communication for efficient space temperature control.

Ключові дані

Power supply19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or SELV
Economizer output0 to 10 VDC into 2k ohm Resistance (Minimum)
Relay contact rating30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or SELV
Temperature accuracy±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Display range-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments (backlit)
Heating control range40.0°F/4.5°C to 90.0°F/32.0°C
Cooling control range54.0°F/12.0°C to 100.0°F/38.0°C
Ambient operating conditions32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing

Застосування

  • Control of single- or multi-stage unitary rooftop units with economizers
  • Remote monitoring and programmability for efficient space temperature control via LONWORKS network

Особливості

  • Backlit, plain-text 2-line, 8-character LCD readable in any condition
  • Three LEDs indicate fan status, call for heat, call for cooling
  • Five-key intuitive user interface with Auto Help
  • Economizer actuator output (0–10 VDC) with minimum position and changeover setpoint configuration
  • Two configurable digital inputs (DI1/DI2): Service alarm, Filter alarm, Remote Override, or Remote Night Setback
  • Auxiliary output for peripheral devices (lighting equipment, exhaust fans, economizers)
  • Frost protection with minimum heating setpoint of 42.0°F/5.5°C
  • Anti-short cycle timer, heating/cooling cycles-per-hour limits, configurable deadband
  • Outdoor temperature-based heating/cooling lockout and economizer changeover
  • Neuron® ID broadcast for network commissioning

Технічні дані

Parameter Value
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV)
Economizer Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum)
Accuracy ±3%
Relay Contact Rating 30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or SELV
Digital Inputs Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2
Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended
LONWORKS Network Standard 64 Devices Maximum without repeater, 128 Devices Maximum with repeater; 6,250 ft (1,905 m) Maximum Length (Bus Topology)
Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
Temperature Range Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments, backlit
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband 2F°/1C° between Heating and Cooling
Ambient Operating Conditions 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Shipping Weight 0.75 lb (0.34 kg)

Terminal identification

Number Label Function
1 Y2 Energizes on a call for second-stage cooling
2 Y1 Energizes on a call for first-stage cooling
3 G Energizes fan in accordance with selected fan mode
4 RC 24 VAC from equipment transformer
5 C 24 VAC (Common) from equipment transformer
6 RH 24 VAC for heating stage
7 W1 Energizes on a call for first-stage heating
8 W2 Energizes on a call for second-stage heating
9 EC 0 to 10 VDC Economizer Actuator Output
10 Aux Auxiliary output
11 DI1 Configurable Digital Input 1
12 DI2 Configurable Digital Input 2
13 RS Remote Room Temperature Sensor
14 Scom Sensor Common
15 OS Auxiliary/Outdoor Air Sensor
16 MS Mixed Air Temperature Sensor

Варіанти замовлення

Accessories (order separately):

Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor
SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TE-6361M-1 Duct Mount Air Temperature Sensor
TE-636S-11 Strap-on Temperature Sensor

Related literature: LONWORKS Network Layout Technical Bulletin (LIT-1162150), TEC226x-3 and TEC220x-3 Series LONWORKS® Network Configurable Staged Thermostats Technical Bulletin (LIT-12011196), TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320).

Допуски та стандарти

  • United States: UL Listed, File E27734, CCN XAPX, under UL 873, Temperature Indicating and Regulating Equipment
  • United States: FCC Compliant to CFR 47, Part 15, Subpart B, Class A
  • LONMARK® Certification: 3.4 (pending)
  • Canada: UL Listed, File E27734, CCN XAPX7, under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
  • Canada: Industry Canada, ICES-003
  • Europe: CE Mark, EMC Directive 89/336/EEC
  • Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant

Текст документа

TEC22x4-3 LONWORKS® Networked
Multi-Stage Economizer Thermostats
                                                                                  Part No. 24-9890-501, Rev. —
Installation Instructions                                                                Issued September 8, 2006




Applications                                                Cet appareil numérique de la Classe (A) respecte
                                                            toutes les exigences du Règlement sur le matériel
The TEC2204-3 non-programmable and
                                                            brouilleur du Canada.
TEC2264-3 programmable thermostats are
LONWORKS® networked devices that provide control of         Installation
single- or multi-stage unitary rooftop units with
economizers. The technologically advanced                   Location Considerations
TEC22x4-3 thermostats feature a Building Automation         Locate the TEC22x4-3 thermostat:
System (BAS) LONWORKS network communication
                                                            •   on a partitioning wall, approximately 5 ft (1.5 m)
capability that enables remote monitoring and
                                                                above the floor in a location of average
programmability for efficient space temperature control.
                                                                temperature
 IMPORTANT: The TEC22x4-3 thermostats are                   •   away from direct sunlight, radiant heat, outside
 intended to provide an input to equipment under                walls, behind doors, air discharge grills, stairwells,
 normal operating conditions. Where failure or                  or outside doors
 malfunction of the thermostat could lead to personal
 injury or property damage to the controlled                •   away from steam or water pipes, warm air stacks,
 equipment or other property, additional precautions            unconditioned areas (not heated or cooled), or
 must be designed into the control system.                      sources of electrical interference
 Incorporate and maintain other devices such as             Note: Allow for vertical air circulation to the
 supervisory or alarm systems or safety or limit            TEC22x4-3 thermostat.
 controls intended to warn of, or protect against,
 failure or malfunction of the thermostat.                  To install the thermostat:
                                                            1. Use a Phillips-head screwdriver to remove the
North American Emissions Compliance                            security screw on the bottom of the thermostat
United States                                                  cover.
This equipment has been tested and found to comply          2. Pull the bottom edge of the thermostat cover and
with the limits for a Class A digital device pursuant to       open the thermostat as illustrated in Figure 1.
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference,
in which case the user will be required to correct the
interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing                                                        FIG:cvr_rmvl


Equipment Regulations.
                                                                 Figure 1: Removing the Thermostat Cover




                                   TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats                     1
                                                                               Installation Instructions
3. Carefully pull the locking tabs on the right side of                           8. Swing the PCB back to the right and carefully snap
   the thermostat mounting base and unlock the                                       it into the locking tabs on the thermostat mounting
   Printed Circuit Board (PCB). Open the PCB to the                                  base.
   left as illustrated in Figure 2.                                               9. Pull the pull tabs on each of the connectors and
                                                                                     remove the screw terminal blocks as illustrated in
                                                                                     Figure 4.



                                           PCB
                                           Locking
                                           Tabs




                                                             FIG:prntd_crct_brd




      Figure 2: Opening the Thermostat PCB

4. Pull approximately 6 in. (152 mm) of wire from the                                                                       FIG:trmnl_blcks


   wall and insert the wire through the hole in the
   thermostat mounting base.                                                        Figure 4: Removing the Screw Terminal Blocks
5. Align the thermostat mounting base on the wall and
   use the base as a template to mark the two                                     Wiring
   mounting hole locations.
                                                                                  When an existing thermostat is replaced, remove and
Note: Be sure to position the thermostat mounting                                 label the wires to identify the terminal functions. When
base so that the arrow on the base points upward to                               a TEC22x4-3 thermostat is replaced, simply remove
indicate the top of the thermostat.                                               the old screw terminal blocks and reinsert them onto
6. Drill a 3/16 in. (5 mm) hole at each of the two                                the PCB of the replacement thermostat.
   marked locations and tap nylon anchors (included
   with the thermostat) flush to the wall surface.                                            CAUTION: Risk of Electric Shock.
                                                                                              Disconnect the power supply before
7. Position the thermostat mounting base on the wall
   and use the two mounting screws (included with
                                                                                       !      making electrical connections to avoid
                                                                                              electric shock.
   the thermostat) to secure the base to the surface
   as illustrated in Figure 3.                                                                CAUTION: Risk of Property Damage.
                                                                                              Do not apply power to the system before
Note: Be careful not to overtighten the mounting
screws.                                                                                !      checking all wiring connections. Short
                                                                                              circuited or improperly connected wires
                                                                                              may result in permanent damage to the
                                                                                              equipment.

                                                                                   IMPORTANT: Make all wiring connections in
                                                                                   accordance with local, national, and regional
                                                                                   regulations. Do not exceed the electrical ratings of
                                                                                   the TEC22x4-3 thermostat.

                                                                                  To wire the thermostat:
                                              FIG:mntng_bs                        1. Strip the ends of each wire 1/4 in. (6 mm) and
                                                                                     connect them to the appropriate screw terminals as
                                                                                     indicated in Figure 5.
         Figure 3: Securing the Thermostat
             Mounting Base to the Wall




2     TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Note: For more details on wiring the
LONWORKS network, refer to the                                                                        Table 1: Terminal Identification (See Figure 5.)
LONWORKS Network Layout Technical Bulletin
                                                                                                       Number      Label                     Function
(LIT-1162150).
                                                                                                       1           Y2          Energizes on a call for second-stage
2. Carefully push any excess wire back into the wall.                                                                          cooling.
   Seal the hole in the wall with fireproof material to                                                2           Y1          Energizes on a call for first-stage
   prevent drafts from affecting the ambient                                                                                   cooling.
   temperature readings.                                                                               3           G           Energizes fan in accordance with
3. Reinsert the screw terminal blocks onto the PCB.                                                                            selected fan mode.
                                                                                                       4           RC          24 VAC from equipment transformer
4. Reattach the LONWORKS communication wires to
   the LON terminal block. See Figure 5.                                                               5           C           24 VAC (Common) from equipment
                                                                                                                               transformer
Note: If inserting multiple wires into the terminals, be
                                                                                                       6           RH          24 VAC for heating stage
sure to properly twist wires together prior to inserting
them in the terminal connectors.                                                                       7           W1          Energizes on a call for first-stage
                                                                                                                               heating.
5. Reattach the thermostat cover to the mounting                                                       8           W2          Energizes on a call for second-stage
   base (top side first).                                                                                                      heating.
6. Use a Phillips-head screwdriver to reinstall the                                                    9           EC          0 to 10 VDC Economizer Actuator
   security screw on the bottom of the thermostat                                                                              Output
   cover.                                                                                              10          Aux         Auxiliary output
                                                                                                       11          DI1         Configurable Digital Input 1
                   Five-Pole                       Three-Pole
                   Left Top Connector              Right Top Connector                                 12          DI2         Configurable Digital Input 2

                                                       RH    W1 W2
                                                                                                       13          RS          Remote Room Temperature Sensor
  LONWORKS         Y2     Y1    G        RC   C
 Bus Terminals                                                                                         14          Scom        Sensor Common
                    1      2        3    4    5        6      7    8
                                                                                                       15          OS          Auxiliary/Outdoor Air Sensor

                                                                        FIG:econ_term
                                                                                                       16          MS          Mixed Air Temperature Sensor

                    Eight-Pole Bottom Connector                                                        Blank       Blank       LONWORKS Bus

                    EC Aux DI1 DI2 RS               Scom     OS MS

                     9    10        11   12   13       14    15    16

                 Figure 5: Terminal Blocks




                                                                                                                    Isolated Contact
                                                                                                                    • Lighting
                                                                                                                    • On/Off Actuation                     LONWORKS
                                                                                                                                                           Bus Terminal
                                                                                                                    • Exhaust Fan

   Y2      Y1       G          RC        C        RH        W1     W2                   EC            Aux   DI1   DI2     RS     Scom   OS       MS


                                                           Heat 1 Heat 2                24VAC  0-10
                                                                                                                                                         Supervisory

                                                                                        Common VDC
                                                                                                                                                          Controller
 Cool 2   Cool 1    Fan                                                                               Aux



                                                                                                                                                                          FIG:TEC22x4_wrng
                                                                                                                                                    Remote
                                                                                                                        Remote      Auxiliary/     Monitoring
                                                       If using the same power source                                    Room        Outdoor        Supply
       24 VAC                                          for the thermostat and heating loads,                            Sensor      Air Sensor    Temperature
   Thermostat Power                                    install a jumper across RC and RH.                                                           Sensor

                                              Figure 6: Wiring the TEC22x4-3 Thermostats



TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions                                                                                                   3
Connecting the LONWORKS Network                                            The LONWORKS network requires proper termination
The wiring rules for the LONWORKS network differ from                      and biasing at the end of a segment (a segment is a
the wiring rules for the Metasys® N2 Bus and the                           physically continuous length of wire). The thermostat is
BACnet® MS/TP Bus. For more details on wiring the                          not equipped with the ability to provide this termination;
LONWORKS network, refer to the LONWORKS Network                            therefore, it cannot be located at the physical end of a
Layout Technical Bulletin (LIT-1162150).                                   LONWORKS network segment unless a terminator is
                                                                           attached. Refer to LONWORKS Network Layout
To connect the thermostat to the LONWORKS network:                         Technical Bulletin (LIT-1162150) for end-of-line
                                                                           solutions.
1. Connect the LONWORKS network wires to the                               Setup and Adjustments
   LONWORKS network terminal block on the
   thermostat (Figure 5, Figure 6, and Figure 7).                          Thermostat Operation Overview
                                      LONWORKS
                                     Bus Terminals


            Supervisory
             Controller



     LONWORKS                                                                        Backlit, plain text
                     LONWORKS                                                      LCD is easy to read
    Network Wires      Network                                                       in any condition.                  Room Temp
                    Terminal Block                                                                                      70.0ºF
                                                                                        LEDs indicate
                                                                                        system activity.          YES   NO


                                     Twist wires together
                                     before inserting them into
                                     the terminals.

                                                                                                                                    FIG:frnt_vw
                                                                                       Five keys on the thermostat

                                                             FIG:LON_wir
                                                                                       make operation easy and intuitive.

                                                                                      Figure 8: Front Cover of Thermostat
    Figure 7: Thermostat to Network Connection

                                                                           Thermostat User Interface Keys
Note: There is no polarity when connecting the
                                                                           The TEC22x4-3 thermostat user interface consists of
LONWORKS network wires to the thermostat; however,
                                                                           five keys on the front cover (as illustrated in Figure 8).
we recommend keeping the polarity consistent
                                                                           The function of each key is as follows:
throughout the network.
                                                                           •   Use the YES/SCROLL key to:
2. After the LONWORKS network wires are connected
   to the first thermostat, continue in a daisy-chained                        -      confirm menu selections and to advance to the
   fashion to the next device.                                                        next menu item
Note: The LONWORKS network wiring must be twisted-                             -      stop the Status Display Menu from scrolling
pair lines.                                                                           and to manually scroll to the next parameter on
                                                                                      the menu
Do not run the LONWORKS network wiring in the same
conduit as line voltage wiring (30 VAC or above) or                        Note: When the thermostat is left unattended for
other wiring that switches power to highly inductive                       45 seconds, the thermostat display resumes scrolling.
loads (such as contactors, coils, motors, or
                                                                           •   Use the NO key to decline a parameter change and
generators).
                                                                               to advance to the next menu item.




4     TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
•   Use the MENU key to:                                   The Installer Configuration Menu is used to set up
                                                           the thermostat for application-specific operation. To
    -   access the Main User Menu or to exit the menu
                                                           access this menu, press and hold the MENU key for
        (See the Main User Menu section.)
                                                           approximately 8 seconds.
    -   access the Installer Configuration Menu or to
        exit the menu (See the Configuring the
                                                           Configuring the TEC22x4-3 Thermostats
        TEC22x4-3 Thermostat section.)                     The TEC22x4-3 thermostats come from the factory
                                                           with default settings for all configurable parameters.
•   Use the UP/DOWN arrow keys to change the               The default settings are shown in Table 2. To
    configuration parameters and to activate a setpoint    reconfigure the parameters via the thermostat, follow
    adjustment.                                            the steps in this section.
Backlit Liquid Crystal Display (LCD)                       1. To access the Installer Configuration Menu, press
The TEC22x4-3 thermostat includes a 2-line,                   and hold the MENU key for approximately
8-character backlit display. Low-level backlighting is        8 seconds.
present during normal operation, and it brightens when
                                                           2. Once the Installer Configuration Menu begins,
any user interface key is pressed. The backlight returns
                                                              press the NO key to scroll through the parameters
to low level when the thermostat is left unattended for
                                                              listed in Table 2.
45 seconds.
                                                           3. When the desired parameter is displayed, use the
Light-Emitting Diodes (LEDs)                                  YES key to choose the desired selection option.
Three LEDs are included to indicate the fan status, call
                                                           4. Press the YES key and then the NO key to
for heat, or call for cooling:
                                                              continue scrolling through the parameters.
•   The FAN LED is on when the fan is on.
                                                           To exit the Installer Configuration Menu any time, press
•   The HEAT LED is on when heating is on.                 the MENU key, and at the exit prompt, press the YES
                                                           key. To pass over a parameter without changing it,
•   The COOL LED is on when cooling is on.
                                                           press the NO key.
Programming Overview                                       When the thermostat is in the Installer Configuration
There are three menus used to view, program, and           Menu and left unattended for approximately 8 seconds,
configure the TEC22x4-3 thermostats.                       the thermostat reverts to the Status Display Menu.
The Status Display Menu is displayed during normal         For additional information on commissioning and
thermostat operation. This menu continuously scrolls       configuring thermostats, adding thermostats to a
through the following parameters:                          Network Automation Engine (NAE), thermostat
•   Room Temperature                                       mapping, and remote themostat commanding, refer to
                                                           TEC226x-3 and TEC220x-3 Series LONWORKS®
•   Clock (TEC2264-3 only)                                 Network Configurable Staged Thermostats Technical
•   System Mode                                            Bulletin (LIT-12011196).

•   Occupancy Status – Occupied/Unoccupied/                Configuring the Thermostat’s Neuron®
    Override                                               Identification
•   Outdoor Temperature – An outdoor air temperature       Press and hold the UP/DOWN arrow keys
    sensor must be connected.                              simultaneously for five seconds to broadcast the
                                                           thermostat’s Neuron Identification on the LONWORKS
•   Applicable Alarms – The backlight lights up as an      network.
    alarm condition is displayed.
                                                           If the cover is removed, you can see a green LED
Note: Press the YES/SCROLL key to temporarily stop         under the LON board flash when the thermostat
this menu from scrolling.                                  broadcasts the Neuron ID. The Neuron ID is on a label
The Main User Menu is used to access and change            on the Echelon® chip.
the basic operating parameters of the thermostat.          You cannot send the Neuron ID while in the Installer
Access this menu by pressing the MENU key during           Configuration menu.
normal thermostat operation.




TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions                          5
Configuring Inputs DI1 and DI2                                   Both inputs can be configured to the Selection Options
When DI1 and DI2 are configured for an alarm                     included in Table 2.
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
Table 2: Installer Configuration Menu (Part 1 of 5)
 Parameter       Description and Default                 Selection Options
 Appearing
 on Display
 DI11            Configuration of Digital Input 1.       (None): No function is associated with an input.
                 Default: None                           (Service): A Service alarm is displayed on the thermostat when the
                                                         input is energized. This input can be tied into the air conditioning unit
                                                         control card, which provides an alarm should there be a malfunction.
                                                         (Filter): A Filter alarm is displayed. This alarm can be connected to
                                                         a differential pressure switch that monitors a filter.
                                                         (RemOVR): Temporary occupancy request via a remote input. This
                                                         override function is controlled by a manual remote occupancy
                                                         override. When enabled, this condition disables the override
                                                         capability of the thermostat.
                                                         (RemNSB): Remote Night Setback (NSB) via a time clock input, an
                                                         occupancy sensor, or from a voltage-free contact.
                                                         Contact open = Occupied; contact closed = Unoccupied.
 DI21            Configuration of Digital Input 2.       (None): No function is associated with an input.
                 Default: None                           (Service): A Service alarm is displayed on the thermostat when the
                                                         input is energized. This input can be tied into the air conditioning unit
                                                         control card, which provides an alarm should there be a malfunction.
                                                         (Filter): A Filter alarm is displayed. This alarm can be connected to
                                                         a differential pressure switch that monitors a filter.
                                                         (RemOVR): Temporary occupancy request via a remote input. This
                                                         override function is controlled by a manual remote occupancy
                                                         override. When enabled, this condition disables the override
                                                         capability of the thermostat.
                                                         (RemNSB): Remote Night Setback (NSB) via a time clock input, an
                                                         occupancy sensor, or from a voltage-free contact.
                                                         Contact open = Occupied; contact closed = Unoccupied.
 Lockout         Selectable Lockout Levels for           Function                               Lockout Level
                 limiting end-user keypad interaction.
                                                                                  (0)             (1)                  (2)
                 Default: 0
                                                         Occupancy            Access       Access             No Access
                                                         Override
                                                         Permanent            Access       No Access          No Access
                                                         Temperature
                                                         Setpoints
                                                         Temporary            Access       Access             No Access
                                                         Temperature
                                                         Setpoints
                                                         System Mode          Access       No Access          No Access
                                                         Setting
                                                         Fan Mode             Access       No Access          No Access
                                                         Setting
                                                         Schedules            Access       No Access          No Access
                                                         Setting4
                                                         Clock Setting4       Access       Access             Access




6       TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 2: Installer Configuration Menu (Part 2 of 5)
 Parameter     Description and Default                Selection Options
 Appearing
 on Display
 Pwr del2      Sets the delay time period at          Range: 10.0 to 120.0 sec
               thermostat power up, or at each
               time power is removed and
               reapplied, before any operation
               (fan, heating, or cooling) is
               authorized. Also can be used to
               sequence the startup of multiple
               units in one location.
               Default: 10.0 sec
 Frost pr      Provides a minimum heating             (on): Enabled
               setpoint of 42.0°F/5.5°C to prevent    (off): Disabled
               freezing in the zone controlled by
               the thermostat.
               Default: off
 Heat max3     Sets the Occupied and Unoccupied       Range: 40.0°F/4.5°C to 90.0°F/32.0°C
               maximum Heating setpoint values.
               Default: 90.0°F/32.0°C
 Cool min3     Sets the Occupied and Unoccupied       Range: 54.0°F/12.0°C to 100.0°F/37.5°C
               minimum Cooling setpoint values.
               Default: 54.0°F/12.0°C
 Anticycl      Anti-Short Cycle timer sets the        Range: 0.0 to 5.0 min adjustable in 1-minute increments
               minimum on/off times for heating       Set the anti-short cycle timer to 0.0 min for equipment that already
               and cooling stages.                    has its own anti-short cycle timer.
               Default: 2.0 min
 Heat cph      Sets the maximum number of             Range: 3.0 to 8.0 cycles per hour
               Heating cycles per hour.
               Default: 4.0
 Cool cph      Sets the maximum number of             Range: 3.0 or 4.0 cycles per hour
               Cooling cycles per hour.
               Default: 4.0
 Deadband      Sets the minimum deadband              Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
               between the heating and cooling        increments
               setpoints.
               Default: 2.0F°/1.0C°
 Fan cont      Determines how the fan is activated    (off): The thermostat will not activate the fan in response to a call
               in response to a call for heating.     for heating. The fan is activated by the equipment fan and limit
               Fan cont applies to W1 & W2 and        control.
               Fan Mode auto only. Fan cont           (on): Enables the thermostat to activate the fan in response to a call
               does not affect fan operation on a     for heating or cooling.
               call for cooling (Y1 & Y2).
               Default: on
 Fan del       Fan delay extends fan operation        (on): Extends fan operation by 60 seconds after a heating or cooling
               after a heating or cooling cycle has   cycle has ended.
               ended.                                 (off): No extension of fan operation after a heating or cooling cycle
               Default off                            has ended.
                                                      The fan delay is only active when the fan is in the Auto mode.




TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions                                     7
Table 2: Installer Configuration Menu (Part 3 of 5)
 Parameter     Description and Default                Selection Options
 Appearing
 on Display
 TOccTime      Sets the duration of the Tempo-        Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
               rary Occupancy Time (when the
               thermostat is in the Unoccupied
               mode) when a Schedule Over-
               ride Function is enabled using ei-
               ther the Main User Menu or DI1
               or DI2 configured as a temporary
               override remote contact
               (RemOVR).
               Sets the effective duration of the
               Temporary heating or cooling
               setpoints set using the up/down
               arrow keys.
               default: 3.0 hrs
 Cal RS        Sets the desired room air              Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
               temperature sensor calibration         increments
               (offset). The offset can be added to
               or subtracted from the actual
               displayed room temperature.
               Default: 0.0F°/0.0C°C
 Cal OS        Sets the desired outdoor air           Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
               temperature sensor calibration         increments
               (offset). The offset can be added to
               or subtracted from the actual
               displayed room temperature.
               Default: 0.0F°/0.0C°
 H stage       Reverts the operation of a two-stage   (1.0): One Stage
               thermostat to a single-stage           (2.0): Two Stages
               thermostat when the second heating
               stage is not needed.
               Default: 2.0
 C stage       Reverts the operation of a two-stage   (1.0): One Stage
               thermostat to a single-stage           (2.0): Two Stages
               thermostat when the second cooling
               stage is not needed.
               Default: 2.0
 H lock        Discontinues heating operation in      Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
               response to the outdoor air
               temperature. Requires that an
               outdoor air temperature sensor be
               installed and connected.
               Default: 120°F/49°C
 C lock        Discontinues cooling operation in      Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
               response to the outdoor air
               temperature. Requires that an
               outdoor air temperature sensor be
               installed and connected. C lock
               does not disable economizer free
               cooling operation.
               Default: -40°F/-40°C
 2/4event4     Sets the number of events within a     (2.0): Two events (one occupied and one unoccupied) within a
               24-hour period.                        24-hour period
               Default: 2.0                           (4.0): Four events (two occupied and two unoccupied) within a
                                                      24-hour period




8     TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 2: Installer Configuration Menu (Part 4 of 5)
 Parameter     Description and Default                  Selection Options
 Appearing
 on Display
 Aux cont      Energizes peripheral devices             (n.c.): Contact open = Occupied; contact closed = Unoccupied
               (lighting equipment, exhaust fans,       (n.o.): Contact closed = Occupied; contact open = Unoccupied
               and economizers).                        The contact toggles with the internal Occupied/Unoccupied
               Default: n.o.                            schedule (or the NSB contact on one of the digital inputs, if used).
 Prog rec4     Provides the desired occupied            (on): Enabled (provides the desired occupied temperature at the
               temperature either at the start of the   start of the occupied schedule)
               occupied schedule or after the           (off): Disabled (provides the desired occupied temperature after the
               occupied schedule begins.                occupied schedule begins)
               Note: Progressive recovery is
                      disabled if either DI1 or DI2
                      is configured as remote NSB
               Default: off
 Chngstpt3     Sets the economizer changeover           Range: 14.0°F/-10.0°C to 70.0°F/21.0°C
               strategy, based on the outdoor air
               temperature. Requires that an
               outdoor air temperature sensor be
               installed and connected.
               When the OA temperature is below
               the changeover setpoint, free
               cooling is used (economizer
               operation). When the OA
               temperature is above the setpoint,
               mechanical cooling is used
               (compressor operation).
               Default: 55.0°F/13.0°C
 Min pos       Sets the minimum position for the        Range: 0.0 to 100.0% equals 0 to 10 VDC output range
               OA dampers on the economizer.
               These dampers are energized to                      % OA                    Setting for        Setting for
               minimum position when the fan                                              0 to 10 VDC        2 to 10 VDC
               (Terminal G) is energized and the                                            Actuator           Actuator
               thermostat is in the Occupied mode.
                                                                   (0.0%)                      0%               0 to 20%
               When the schedule is in the
               Unoccupied mode, the minimum                        (5.0%)                      5%                 24%
               position is 0%.
                                                                   (10.0%)                     10%                28%
               Default: 0.0%
                                                                   (15.0%)                     15%                32%
                                                                   (20.0%)                     20%                36%
                                                                   (25.0%)                     25%                40%
                                                                   (30.0%)                     30%                44%
 C mech        Determines whether to allow              (on): Typically applies when the MS is installed before the
               mechanical cooling (compressor           mechanical cooling refrigeration coils in the mixing plenum. In this
               operation) if free cooling               scenario, mechanical cooling is allowed when free cooling cannot
               (economizer operation) cannot            maintain the cooling setpoint.
               maintain the cooling setpoint.           (off): Typically applies when the remote Mixed air Sensor (MS) is
               Default: off                             installed after the mechanical cooling refrigeration coils. In this
                                                        scenario, mechanical cooling will never operate at the same time as
                                                        free cooling.
 Mix stpt3     Establishes the mixed air                Range: 50.0°F/10.0°C to 90.0°/32.0°C
               temperature when operating in the
               economizer mode.
               Default: 55.0°F/13.0°C




TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions                                     9
Table 2: Installer Configuration Menu (Part 5 of 5)
 Parameter        Description and Default               Selection Options
 Appearing
 on Display
 Display MS       Displays the mixed air temperature.   The mixed air temperature can be used to help service and
                  Requires that an MS be installed      troubleshoot the equipment and the economizer operation. The
                  and connected.                        mixed air temperature is only accessible via the Installer
                  Default: N/A                          Configuration Menu.

1.   Setting DI1 or DI2 to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables
     schedules and the Schedule menu. (TEC2264-3 only)
2.   When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
     hold the UP or DOWN arrow key to change the numeric value in increments of ten.
3.   When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
     and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
4.   TEC2264-3 only

Operation                                                      2. Press the YES key to enable the temporary
                                                                  override. The thermostat returns to the Status
Programming/Operating the TEC22x4-3                               Display Menu.
Thermostats
                                                               When scrolling through the Status Display Menu,
Once the thermostat is configured via the Installer
                                                               Override now appears for the schedule status
Configuration Menu, its operating parameters can be
                                                               parameter.
programmed via the Main User Menu. Access this
menu by pressing the MENU key during normal                    Resuming the Programmed Schedule
thermostat operation. The Main User Menu contains              This menu only appears when the thermostat is in the
the basic operating features of the thermostat.                unoccupied override mode.
The Main User Menu also uses Auto Help, which is               To resume the schedule while in the Main User Menu:
displayed automatically in the menu when there is a
pause in programming activity. To exit Auto Help,              1. Press the NO key to all prompts until the
continue with the programming selection. When the                 Cancel ovrd Y/N prompt appears. If the thermostat
thermostat is in the Main User Menu and is left                   is in the unoccupied override state, this is the first
unattended for 45 seconds, the menu reverts to the                prompt.
Status Display Menu.                                           2. Press the YES key to resume the programmed
Enabling Override Schedule                                        schedule.
Note: Enabling Override Schedule only appears when             The thermostat returns to the Status Display Menu.
in the Unoccupied Mode.
                                                               Entering Permanent Temperature Setpoints
The override schedule prompt only appears when the             The first prompt appearing in the Main User Menu of
thermostat is in the unoccupied override state. This           the thermostat when in the occupied state is to set the
menu selection gives the user the option of overriding         permanent temperature setpoint. Permanent setpoints
the unoccupied setpoints with the occupied setpoints           are stored in the programmed schedule.
for the amount of time specified under the TOccTime
parameter. See the Configuring the TEC22x4-3                   To enter the permanent heating and cooling setpoints
Thermostat section.                                            for the Occupied and Unoccupied Modes, follow the
                                                               steps in Table 3. When changing the temperatures,
Note: If one of the digital inputs is configured to            press the keys once to change the temperature in
operate as a remote override contact, this menu is             0.5F°/0.5C° increments; press and hold down the keys
disabled.                                                      to change the temperature in 5.0F°/5.0C° increments.
To override the unoccupied state while in the Main User        Entering Temporary Temperature Setpoints
Menu:
                                                               To temporarily change the setpoint, press the
1. Press the NO key to all prompts until the Cancel            UP/DOWN arrow keys to change the temporary
   ovrd prompt appears. If the thermostat is in the            setpoint for the current mode of operation.
   unoccupied state, this is the first prompt.



10     TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 3: Entering Permanent Temperature                   Table 3: Entering Permanent Temperature
         Setpoints (Part 1 of 2)                                   Setpoints (Part 2 of 2)
 Thermostat       Description                                 Thermostat        Description
 Display                                                      Display
                  Press the MENU key while in the                               Press the YES key to set the display
   RoomTemp       Status Display Menu to enter the              °F/°C           units to °F or °C. Press the NO key to
   75.0°F         Main User Menu.                                               advance to the temperature setpoint
                                                                set? Y/N
                                                                                type menu.


                  Press the NO key to all prompts until                         Press the YES key to return to the
   Temperat       the temperature setpoint prompt               Exit?           Status Display Menu or press the NO
   set? Y/N       appears on the display (it may be the                 Y/N     key to reenter the temperature
                  first prompt). Press the YES key to                           setting menu.
                  enter the temperature setting menu.

                  Press the YES key to change the
   Cooling        occupied cooling setpoint. Press the    Note: Whether the thermostat is heating or cooling,
   set? Y/N       NO key to advance to the occupied       the respective setpoint is temporarily adjusted. To
                  heating setpoint menu.                  toggle between the temporary heating and cooling
                                                          setpoints, press the NO key while changing the
                  Press the UP/DOWN arrow keys to         temporary setpoints.
   Cooling        set the temperature. Press the YES
                  key to store the value and advance to   Ending Temporary Temperature Setpoints
   75.0°F
                  the next menu.                          The temporary setpoints remain in effect for the
                                                          duration set in the TOccTime parameter or until
                                                          manually released.
                  Press the YES key to change the
   Heating        occupied heating setpoint. Press the    To release the temporary setpoint sooner, while in the
   set? Y/N       NO key to advance to the unoccupied
                                                          Main User Menu:
                  cooling setpoint menu.
                                                          1. Press the YES key to the first prompt that appears.
                  Press the UP/DOWN arrow keys to         2. If the thermostat does not immediately return to the
   Heating        set the temperature. Press the YES         Status Display Menu, press the MENU key again
   68.0°F         key to store the value and advance to
                                                             and press the YES key to exit the Main User Menu.
                  the next menu.
                                                          The setpoint reverts to the Permanent Temperature
                                                          Setpoint.
                  Press the YES key to change the
   Unocc CL       unoccupied cooling setpoint. Press      Selecting the System Mode
   set? Y/N       the NO key to advance to the
                  unoccupied heating setpoint.            The thermostat has four system modes:
                                                          •     Automatic Mode (auto): Automatic changeover
                  Press the UP/DOWN arrow keys to               between heating and cooling. This is the default
   Unocc CL       set the temperature. Press the YES            setting.
   80.0°F         key to store the value and advance to
                  the next menu.                          •     Cooling Mode (cool): Cooling operation only
                                                          •     Heating Mode (heat): Heating operation only
                  Press the YES key to change the         •     Off Mode (off): The thermostat is off; however,
   Unocc HT       unoccupied heating setpoint. Press
                                                                when frost protection (Frost pr parameter) is
   set? Y/N       the NO key to advance to the
                  temperature display units.                    enabled, the thermostat still calls for heat
                                                                (if required).

                  Press the UP/DOWN arrow keys to         To set the system mode while in the Main User Menu:
   Unocc HT       set the temperature. Press the YES
                                                          1. Press the NO key to all prompts until the system
   62.0°F         key to store the value and advance to
                  the next menu.                             mode prompt appears on the display. Press the
                                                             YES key to select the desired system mode.




TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions                           11
2. Press the UP/DOWN arrow keys to locate the               To set the time schedule for a two-event schedule,
   desired system mode. Press the YES key to select         follow the steps in Table 4. See Table 6, Events 1
   the desired system mode.                                 and 2, for an example of a two-event office schedule.
3. Press the YES key to return to the Status Display        Table 4: Programming the Daily Schedule –
   Menu or press the NO key to return to the system                  Two-Event (Part 1 of 2)
   mode selection menu.                                      Thermostat         Description
Selecting the Fan Mode                                       Display
The thermostat has three fan mode settings:                                     Press the MENU key while in the
                                                               RoomTemp         Status Display Menu to enter the
•    On Fan Mode (on): Energizes the fan all the time          75.0°F           Main User Menu.
     for both occupied and unoccupied states, even if
     the system mode is set to off.
•    Automatic Fan Mode (auto): Energizes the fan                               Press the NO key to all prompts until
     only on a call for heating or cooling, for both           Schedule         the schedule set prompt appears on
                                                               set? Y/N         the display. Press the YES key to
     occupied and unoccupied states.                                            enter the scheduling menu.
•    Smart Fan Mode (smart): Energizes the fan all
     the time for occupied states, and only on a call for                       Press the YES key to set the
     heating or cooling in unoccupied states. This is the                       schedule for Monday or press the NO
                                                               Monday
     default setting.                                          set? Y/N         key to advance to Tuesday.
To select the fan mode while in the Main User Menu:
1. Press the NO key to all prompts until the fan mode                           Press the YES key to set the
   prompt appears on the display. Press the YES key                             occupied start time for Monday or
                                                               Occupied
   to set the fan mode.                                        day? Y/N         press the NO key to advance to
                                                                                Tuesday. Selecting NO will leave the
2. Press the UP/DOWN arrow keys to locate the                                   thermostat in the unoccupied state
   desired fan mode. Press the YES key to select the                            for the entire day.
   desired fan mode.                                                            Press the UP/DOWN arrow keys to
3. Press the YES key to return to the Status Display           Occupied         set the occupied start time. Press the
                                                               12:00 AM         YES key to enter the time.
   Menu or press the NO key to return to the fan
   mode selection menu.
Selecting Schedule (TEC2264-3 Only)                                             Press the UP/DOWN arrow keys to
Programming the Daily Schedule – Two-Event                     Unoccup          set the unoccupied start time. Press
                                                               12:00 AM         the YES key to enter the time.
The schedule-setting menu is used to enter the
occupied or unoccupied states for each day of the
week. The schedule-setting menu reflects either a
                                                                                Press the YES key to set the
two- or a four-event schedule per day, based on what
                                                               Tuesday          schedule for Tuesday or press the
was selected in the 2/4event parameter during the                               NO key to advance to Wednesday.
                                                               set? Y/N
configuration process. If the schedule-setting menu
does not reflect a two-event schedule, select two
events in the 2/4event parameter of the Installer
                                                                                Press the YES key to copy the
Configuration Menu.
                                                               Copy Y/N         schedule from the previous day.
When changing the time, press the UP/DOWN arrow                previous         Press the NO key to set a different
                                                                                schedule.
keys once to change the time in 1-minute increments;
press and hold down the keys to change the time in
30-minute increments.
Note: Programming one of the digital inputs to remote
NSB disables the menu.




12     TEC22x4-3 LONWORKS® Networked Multi-Stage Economizer Thermostats Installation Instructions
Table 4: Programming the Daily Schedule –                    Table 5: Programming the Daily Schedule –
         Two-Event (Part 2 of 2)                                      Four-Event (Part 2 of 2)
 Thermostat         Description                              Thermostat       Description
 Display                                                     Display
                    If the YES key was pressed, the next                      Press the YES key to set the
   Wednesda         prompt is for Wednesday. Repeat the         Monday        schedule for Monday or press the NO
   set? Y/N         procedure for the rest of the days of       set? Y/N      key to advance to Tuesday.
                    the week.


                    After setting the schedule for all the                    Press the YES key to set the
   Exit?            days of the week, following the last        Occupied      occupied start time for Monday or
           Y/N      entry for Sunday, press the YES key         day? Y/N      press the NO key to advance to
                    to return to the Status Display Menu                      Tuesday. Selectin