The TE-7000 Room Command Module is a room-mounted user interface designed for use with the VMA1400 series VAV Modular Assembly, which controls a variable air volume (VAV) terminal unit. It provides an NTC temperature sensor, a setpoint adjustment dial (12 to 28°C or -3 to +3K), an occupancy button with LED indicator, and a built-in service tool socket for PC-based commissioning of the VMA1400 and air supply system.
Ключові дані
| Setpoint dial range | 12 to 28°C or -3 to +3K |
|---|---|
| Temperature sensor | NTC Thermistor 0 to 40°C, 2252 Ω at 25°C |
| Supply voltage | Power from VMA1400 VAV Modular Assembly |
| Ambient operating conditions | 0 to 50°C, 10 to 90% RH noncondensing |
| Ambient storage conditions | -20 to 70°C, 10 to 90% RH noncondensing |
| Housing protection | IP30 (IEC529) |
| Dimensions (HxWxD) | 80 x 80 x 33 mm |
| Remote set point | 2.0 KΩ potentiometer (with 4.99 KΩ parallel resistor) |
Застосування
- Room command module for VMA1400 series VAV Modular Assembly in variable air volume terminal units
- Occupant comfort control: occupancy button commands occupied mode for a set period of time (default one hour)
- Commissioning and balancing of the VAV system at the room module location via service tool connection
Особливості
- Modern attractive cover, white or off-white, snaps onto plug-in mounting base — easy to install and service
- Terminals located on mounting base — easy to wire and test
- Service tool socket for commissioning via RS485/RS232 converter (IU-9100) with cable TE-7000-8900
- Range of standard mounting kits: surface mount, wall box mount, panel mount
- Dial-stop screws allow mechanical limitation of dial travel between ±3 K and ±0.3 K or between 12/28°C and 19.3/20.7°C
- Optional serrated dial knob (add "-K" to ordering code)
- Powered by the VMA over an 8-wire cable; no other power source required
Технічні дані
| Parameter | Value |
|---|---|
| Supply Voltage | Power from VMA1400 VAV Modular Assembly |
| Ambient Operating Conditions | 0 to 50°C, 10 to 90% RH noncondensing |
| Ambient Storage Conditions | -20 to 70°C, 10 to 90% RH noncondensing |
| Terminations | Terminal block in base for 1 x 1.5mm² (16 AWG) (maximum) cable |
| Temperature Sensor | NTC Thermistor 0 to 40°C, 2252 Ω at 25°C |
| Remote Set Point | 2.0 KΩ potentiometer (with 4.99 KΩ parallel resistor), marked for 12 to 28°C or -3 to +3 K; mechanical dial-stop screws available |
| Occupancy Button and Mode Indicator | Momentary contact and LED in series circuit (steady on: occupied; blinking: standby; off: unoccupied) |
| Mounting | Direct surface mount, plastic base for surface mount with wiring conduit, recessed wall box and panel mounting kits |
| Housing Material | ABS + polycarbonate, self extinguishing VO UL94 |
| Protection | IP30 (IEC529) |
| Dimensions (HxWxD) | 80 x 80 x 33 mm |
| Shipping Weight | 0.15 kg |
| Agency Compliance | CE Directive 89 / 336 / EEC EN50081-1, EN 50082-1 |
Варіанти замовлення
European Models (with System 91 Type Service Tool Connector):
| Ordering Code | Color | Setpoint Dial Range |
|---|---|---|
| TE-7000-8002 | Off-White/Gray Base | 12 to 28°C |
| TE-7000-8002-W | White/White Base | 12 to 28°C |
| TE-7000-8003 | Off-White/Gray Base | -3 to +3 K |
| TE-7000-8003-W | White/White Base | -3 to +3 K |
Note: Add "-K" to code for setpoint dial with serrated edge, e.g. TE-7000-8002-K, TE-7000-8002-WK.
North American Models (off-white with gray USA wall plate accessory, serrated knob and telephone jack Service Tool connector):
| Ordering Code | Setpoint Dial Range |
|---|---|
| TE-7000-0001 | 65 to 85°F |
| TE-7000-0002 | 12 to 28°C |
| TE-7000-0003 | - to + (no units) |
Accessories:
| Ordering Code | Description |
|---|---|
| TE-7000-8900 | Service Tool Connector Cable (1.5m) (for use with IU-9100 converter) |
| TM-9100-8900 | Special Tool (to open module) |
| TM-9100-8901 | Dial-Stop Screws Kit (bag of 100 self-tapping screws) |
| TM-9100-8902 | Serrated Knob Kit (bag of 10 knobs) - Off-white |
| TM-9100-8902-W | Serrated Knob Kit (bag of 10 knobs) - White |
| TM-9100-8930 | Surface Mounting Kit - Gray |
| TM-9100-8931 | Surface Mounting Kit - Off-white |
| TM-9100-8931-W | Surface Mounting Kit - White |
| TM-9100-8941-W | Wall Box Mounting Kit - White |
| TM-9100-8951-W | Panel Mounting Kit - White |
Допуски та стандарти
- CE Directive 89 / 336 / EEC, EN50081-1, EN 50082-1
- IP30 (IEC529)
- Housing material self-extinguishing VO UL94
Позиції каталогу з цим документом
Текст документа
European Electronic Controls Catalog
Catalog Section A
Product Bulletin TE-7000
Issue Date 1198
TE-7000 Room Command Module
I ntroduction
The TE-7000 Room Command Module is
designed for use with the VMA1400 series VAV
Modular Assembly. The VMA1400 is a control
device for a variable air volume (VAV) terminal
unit that provides conditioned air to the room in
which the TE-7000 is installed.
The module has an NTC temperature sensor, a
dial for setpoint adjustment within the range of 12
to 28°C or -3 to +3K, and an occupancy button
with an LED indicator. If the VAV controller is not
already in occupied mode, as shown by the LED
indicator, the occupant may press the occupancy
button to obtain comfort control for a set period of
time, normally defaulted to one hour.
The module also has a built-in connector for a PC
Figure 1: TE-7000 Room Command Module
with the software to test and commission the
VMA1400 series VAV Modular Assembly and the
air supply system.
Features and Benefits
Modern attractive cover, in white or off-white, Blends with room décor.
which snaps onto a plug-in mounting base. Easy to install and service.
Terminals located on mounting base. Easy to wire and test.
Service tool connection. Variable Air Volume system can be commissioned
and balanced at the room module location.
Range of standard mounting kits. Flexibility in mounting possibilities.
© 1998 Johnson Controls, Inc. A5.1
Order No. DS 24.130 E
2 TE-7000
A pplication Overview O rdering Codes
The TE-7000 Room Command Module is used European Models
specifically with the VMA1400 series VAV (With System 91 Type Service Tool Connector)
Modular Assembly and includes:
Ordering Code Color Setpoint Dial
• an NTC “K2” temperature sensor (see the Range
NTC K2 Resistance Table on page 10) TE-7000-8002 Off-White/ 12 to 28°C
Gray Base
• a setpoint dial and potentiometer for remote
setpoint adjustment of 12 to 28°C or TE-7000-8002-W White/ 12 to 28°C
White Base
-3 to +3K
TE-7000-8003 Off-White/ -3 to +3 K
• an LED to indicate the occupancy mode as Gray Base
follows: TE-7000-8003-W White/ -3 to +3 K
White Base
steady on: occupied (comfort) mode
Note: Add “-K” to code for setpoint dial with
blinking: standby mode serrated edge, e.g. TE-7000-8002-K,
off: unoccupied (or off) mode TE-7000-8002-WK
• an occupancy button (switch) in a series Accessories
circuit with an LED to either:
Ordering Code Description
1. command the occupied mode from the TE-7000-8900 Service Tool Connector Cable
standby or unoccupied mode for a set (1.5m) (for use with IU-9100
period of time, or converter)
2. change the occupancy mode to TM-9100-8900 Special Tool (to open module)
occupied, standby or unoccupied for a TM-9100-8901 Dial-Stop Screws Kit (bag of 100
set period of time, self-tapping screws)
TM-9100-8902 Serrated Knob Kit (bag of 10
as defined in the configuration data base of knobs) - Off-white
the VMA device.
TM-9100-8902-W Serrated Knob Kit (bag of 10
• a socket for the connection of a PC with knobs) - White
testing and commissioning software via an TM-9100-8930 Surface Mounting Kit - Gray
RS485/RS232 converter. A cable is TM-9100-8931 Surface Mounting Kit - Off-white
available for use with the IU-9100 converter TM-9100-8931-W Surface Mounting Kit - White
(see ordering codes). TM-9100-8941-W Wall Box Mounting Kit - White
The Room Command Module is connected by TM-9100-8951-W Panel Mounting Kit - White
an 8-wire cable to the VMA and requires no
other source of power.
For information purposes only:
North American Models from Customer
Service in Milwaukee (all in off-white with gray
USA wall plate accessory, serrated knob and
telephone jack Service Tool connector)
Ordering Code Setpoint Dial Range
TE-7000-0001 65 to 85°F
TE-7000-0002 12 to 28°C
TE-7000-0003 - to + (no units)
A5.1
TE-7000 3
M ounting and Wiring Instructions The TM-9100-8941-W Wall Box Mounting Kit
• Adjust height “D” turning screws “A” to match
The TE-7000 module is designed for wall the depth of the wall box.
mounting in the room to be controlled, using at
least two of the four screw holes on the base.
The module may be mounted directly on the
wall, or one of the three mounting kits may be
used. The wiring enters from the back through Max. Ø 62 mm
the base. Min. Ø 55 mm
Choose an appropriate place where the
temperature is representative of the general
room conditions. Avoid cold or warm draughts
from doors or windows, and exposure to radiant
heat from lamps, radiators or direct sunlight.
However, sufficient air circulation over the
module is required for a satisfactory response to
room temperature changes. Min. 45 mm
Place insulation material in the wiring conduit or
any open space behind the wall to prevent air • Insert the kit into the wall box in the position
entering the module through the base. shown below.
Remove the base from the cover by inserting the
point of the special tool (TM-9100-8900) into the
small hole at the center top of the cover. While
pressing down gently, prise the base away from
the cover. As the two parts separate, remove the
tool and continue to pull the cover away from the
base until the cover is free. To reassemble the
module, place the cover over the lower edge of
the base and push the upper part of the cover
until it “clicks” firmly in place.
The TM-9100-893x(-W) Surface Mounting Kit
Screw the kit directly on the wall using holes “A”
• Tighten screws “B” until the prongs clamp
and mount the base of the module on the kit,
properly on the box.
using the two screws included and inserting
them in the two opposite holes “B”, as indicated • Mount the base of the module on the kit as
below: shown below, using the two screws included
and inserting them in two opposite holes of
UP OB EN
the four marked “C”.
A
B
A5.1
4 TE-7000
The TM-9100-8951-W Panel Mounting Kit Wiring Instructions
• Cut a circular hole in the panel with a The installation of electrical wiring must conform
diameter dimension as shown below: to local codes and should be carried out by
authorized personnel only. Users should ensure
that all Johnson Controls products are used
safely and without risk to health or property.
Max. Ø 60 mm Before connecting or disconnecting any wires,
Min. Ø 57 mm ensure that all power supplies have been
switched off and all wires are potential free to
prevent equipment damage and electrical shock.
Terminations are made on the terminal blocks in
Max. 12 mm
the base of the module which accept 1.5 mm2
• Turn prongs “A” as shown below. Insert the (16 AWG) wires. All wiring to the module is at
kit into the panel in the position shown below. extra low (safe voltage) and must be separated
from power line voltage wiring. Do not run wiring
close to transformers or high frequency
generating equipment. Complete and verify all
wiring connections before applying power to the
VMA1400 to which the module is connected.
Do not attempt field repairs. If the module does
not operate properly when correctly wired, it
should be replaced.
• Turn prongs “A” as shown below. Turn
screws “B” until the kit is fixed on the panel.
• Mount the base of the module on the kit as
shown below, using the two screws included
Figure 2: Wiring Diagram
and inserting them in two opposite holes of
the four marked “C”.
A5.1
TE-7000 5
4. To limit travel of the dial, choose the desired
D ial-Stop Screws range, and insert screws
corresponding holes. For example, for a
in the
A pair of self-tapping screws can be installed to limitation of ± 2.5 K, insert one screw each in
mechanically limit the range of the TM-9100 set the holes marked (A) in Figure 4.
point dial between ±3 K and ±0.3 K or between
12/28°C and 19.3/20.7°C.
1. Remove the base of the module from the
cover by inserting the point of the special
tool (TM-9100-8900) into the small hole at
the center top of the cover. While pressing
down gently, prise the base away from the
cover. As the two parts separate, remove
the tool and continue to pull the cover away
from the base until the cover is free.
2. Set the dial to the center top position, with
the pointer (indentation) at the 0 K or 20°C
mark.
3. Then insert the special TM tool (Ordering tmtbhole
Code TM-9100-8900) through the hole in
the back of the cover (1) and push gently Note: For an asymmetrical range, you may
until the dial knob becomes free (2). insert screws into differently lettered
holes on each side.
12-28°C ±3K
2 A 13.3 / 26.7 ± 2.5
1
B 14.3 / 25.7 ± 2.1
C 15.3 / 24.7 ± 1.8
D 16.3 / 23.7 ± 1.4
E 17.3 / 22.7 ±1
F 18.3 / 21.7 ± 0.7
G 19.3 / 20.7 ± 0.3
tmtbremd
5. Press the dial knob back in place on the
Figure 3: Removing the Dial Knob cover, making sure the pointer (indentation)
is aligned with the 0 K or 20°C mark at the
3. On the front of the module cover you will see top of the circle. Then place the cover over
a series of seven holes on either side of the the lower edge of the TM-9100 base and
set point dial pivot, which had been hidden push the upper part of the cover until it
by the knob. “clicks” firmly into place.
G G
F F
E E
D D
C C
B B
A A
Figure 4: Dial-Stop Screws
A5.1
6 TE-7000
S errated Dial Knob S ervice Tool Socket
To replace a smooth dial knob with a serrated The service tool socket is accessed by sliding
knob, follow steps 1, 2, 3 and 5 under Dial-Stop the panel upwards as shown in Figure 6 below.
Screws, substituting a serrated knob for the
smooth knob in Step 5.
Sliding panel
Service Tool Socket
set esc
Figure 6: Service Tool Socket
Figure 5: Module with Serrated Dial Knob
A5.1
TE-7000 7
D imensions (in mm.)
80 33 Ø 4.2
TB1 TB2
20
1 2 3 4 5 6 7 8
16 24
Setpoint 60
UP
adjustment
80 Ø 4.2 6.2
12 28 Mode-
°C
4.2
LED 6.2
4.2
Mode
selector
60
Figure 7: Basic Model TE-7000-800x Figure 8: Plug-in Mounting Base
Max. Ø 60 mm
78 Min. Ø 57 mm 78
12 78 12 78
Figure 9: Wall Box Mounting Kit Figure 10: Panel Mounting Kit
TM-9100-8941-W TM9100-8951-W
UP OB EN
58
60
Ø5 78
Ø 3.5
25 78
11 17
13
20
Figure 11: Surface Mounting Kit TM-9100-893x(-W)
A5.1
8 TE-7000
NTC K2 Resistance Table
Temperature in °C Resistance in Ω
0 7352,8
5 5717,8
10 4481,5
15 3537,9
20 2812,8
25 2252,0
30 1814,4
35 1470,6
40 1199,6
S pecifications
Supply Voltage Power from VMA1400 VAV Modular Assembly
Ambient Operating 0 to 50°C
Conditions 10 to 90% RH noncondensing
Ambient Storage -20 to 70°C
Conditions 10 to 90% RH noncondensing
Terminations Terminal block in base for 1 x 1.5mm² (16 AWG) (maximum) cable
Temperature Sensor NTC Thermistor 0 to 40°C, 2252 Ω at 25°C
Remote Set Point 2.0 KΩ potentiometer (with 4.99 KΩ parallel resistor) marked for 12 to 28°C or -3 to +3 K.
Mechanical limitation of travel available with dial-stop screws.
(See ordering codes.)
Occupancy Button and Momentary contact and LED in series circuit.
Mode Indicator
Mounting Direct surface mount, plastic base for surface mount with wiring conduit, and recessed
wall box and panel mounting kits. (See ordering codes.)
Housing Material: ABS + polycarbonate, self extinguishing VO UL94
Protection: IP30 (IEC529)
Dimensions (HxWxD) 80 x 80 x 33 mm
Shipping Weight 0.15 kg
Agency Compliance CE Directive 89 / 336 / EEC EN50081-1, EN 50082-1
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.
Johnson Controls International
Westendhof 8 Rev. Level 1198
45143 Essen European Electronic Controls Catalog
Germany Printed in Germany
A5.1
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.