TC-8900 is a family of analogue controllers for fan coil control in 2 pipe, 2 pipe with change-over, 2 pipe with electrical coil, or 4 pipe configurations. The family includes All-in-one Controller Units (TC-8900 series), Built-in Controller Units (TC-8930) and the ES-8930 Remote Setpoint Module. The controller integrates sensor, direct/reverse input, window input, PI control, up to two valve outputs, mode push button and setpoint readjustment potentiometer in one package.
Ключові дані
| Supply | 24 VAC ±15% 50/60Hz (TC-89x0); 15 VDC from TC-893x (ES-8930) |
|---|---|
| Outputs | TC-89x1: 0…10 V, 10 mA max; TC-89x3/4/6: triac 24 VAC, 0.5 A max |
| Ambient operating temperature | 0…50 °C |
| Humidity range | 0 to 95 % not condensing (specifications page); 10…95 % not condensing (installation instructions) |
| Storage temperature | -20 +70 °C |
| Protection | IP30 (IEC529) |
| Housing material | ABS + polycarbonate, self-extinguishing VO UL94 |
| Dimensions (H x W x D) | 80 mm x 80 mm x 33 mm |
Застосування
- Control of fan coils with 2 pipe configuration
- 2 pipe with change-over configuration
- 2 pipe with electrical coil configuration
- 4 pipe configuration
- Wall mount or fan coil mount operation
Особливості
- All-in-one condensed package: sensor, direct/reverse input, window input, PI control, up to two valve outputs, mode (comfort/stand-by) push button and setpoint readjustment potentiometer
- Option to limit the setpoint adjustment range or cancel setpoint adjustment
- Active or passive input flexibility (temperature, humidity, differential pressure etc.)
- Modern and discreet cover which snaps onto a plug-in mounting base
- Electric terminals located on mounting base for easier wiring and commissioning
- Standard range of mounting kits for mounting flexibility
Технічні дані
| Parameter | Value |
|---|---|
| Supply (TC-89x0) | 24 VAC ±15%, 50/60 Hz |
| Supply (ES-8930) | 15 VDC from TC-893x |
| Power consumption | 1.5 VA with no load |
| Output TC-89x1 | 0…10 V, 10 mA max |
| Output TC-89x3/4/6 | Triac output 24 VAC, 0.5 A max |
| Output ES-8930 (remote setpoint) | 1…9 V, 0.1 mA max |
| Output TC-8907 | 0…13 V, 0.1 mA max |
| Sensor recalibration | CW +0.8 °C / CCW –0.8 °C |
| Remote sensor NTC | NTC K10 10 kΩ at 25 °C (TE-9100-8502 or TS-9104 sensor series) |
| Remote sensor 0…10V | Input impedance >50 kΩ (TS-9101, HT-9000, PS-910x, PT-910x sensor series) |
| Proportional band (NTC models) | TC-8901: 1…4 K; TC-8903: 2…8 K; TC-8904: 1…4 K |
| Dead band (NTC models) | TC-8901: 0 to 2 K; TC-8904: 0 to 2 K; TC-8906: 0 to 2 K |
| Differential (on/off) | 0.2 to 2 K (TC-8906) |
| Time base | 120 seconds (TC-8903); 5…15 minutes (TC-8904) |
| Integral time | Off or 4 minutes |
| Standby offset BSB / Window offset BOF | BSB 2 K, BOF 5 K (NTC models); BSB 10 %, BOF 25 % (0…10V models) |
| Proportional band (0…10V models) | TC-8901-2183-WK: 5 to 20 %; TC-8903-1183-WK: 10 to 40 % |
| Dead band (0…10V models) | 0 to 10 % (TC-8901-2183-WK) |
| Mode indicator | Red LED: comfort (ON), standby (blinking), window open (off) — not available on TC-8930 |
| Ambient operating temperature | 0…50 °C |
| Humidity range | 0 to 95 % not condensing |
| Storage temperature | -20 +70 °C |
| Mounting | Direct surface mount, plastic surface mount base with wiring conduits, recessed wall box and panel mounting kits |
| Housing material | ABS + polycarbonate, self-extinguishing VO UL94 |
| Protection | IP30 (IEC529) |
| Colour | RAL-9010 pure white |
| Dimensions (H x W x D) | 80 mm x 80 mm x 33 mm |
| Shipping weight | 0.15 kg |
Варіанти замовлення
All-in-one Controller Units:
| Order code | Output | Sensor input | Setpoint range |
|---|---|---|---|
| TC-8903-1131-WK | 1xPAT | Built-in NTC | 12…28°C |
| TC-8901-2131-WK | 2x0…10V | Built-in NTC | 12…28°C |
| TC-8904-2131-WK | 2xDAT | Built-in NTC | 12…28°C |
| TC-8906-2131-WK | 2xOn/Off | Built-in NTC | 12…28°C |
| TC-8903-1132-WK | 1xPAT | Remote NTC | 12…28°C |
| TC-8901-2132-WK | 2x0…10V | Remote NTC | 12…28°C |
| TC-8904-2132-WK | 2xDAT | Remote NTC | 12…28°C |
| TC-8906-2132-WK | 2xOn/Off | Remote NTC | 12…28°C |
| TC-8903-1151-WK | 1xPAT | Built-in NTC | 0…40° |
| TC-8903-1152-WK | 1xPAT | Remote NTC | 0…40° |
| TC-8903-1183-WK | 1xPAT | Remote 0…10V | 0…100% |
| TC-8901-2183-WK | 2x0…10V | Remote 0…10V | 0…100% |
Built-in Controller Units (setpoint range: remote, see ES-8900):
| Order code | Output | Sensor input |
|---|---|---|
| TC-8933-1112-W | 1xPAT | From ES |
| TC-8931-2112-W | 2x0…10V | From ES |
| TC-8934-2112-W | 2xDAT | From ES |
| TC-8936-2112-W | 2xOn/Off | From ES |
Remote Setpoint Module:
| Order code | Sensor input |
|---|---|
| ES-8930-3031-WK | Built-in NTC |
Accessories (order separately):
| Order code | Description |
|---|---|
| TM-9100-8900 | Opening tool for sensor case |
| TM-9100-8901 | Dial stop screws kit (bag of 100 self tapping screws) |
| TM-9100-8931-W | Plastic surface mounting kit |
| TM-9100-8941-W | Wall box mounting kit |
| TM-9100-8951-W | Panel mounting kit |
Допуски та стандарти
- UL94 (housing material rating)
- IP30 per IEC529
- EMC (89/336 EEC) according to EN 50081-1 and EN 50082-1
Позиції каталогу з цим документом
Текст документа
European Electronic Controls Catalogue
Catalogue Section F
Product Bulletin TC-8900
Issue date 06 2000
TC-8900 All-in-one Controller Units
and ES-8930 Remote Setpoint Module
Introduction
TC-8900 is a family of analogue controllers,
designed for the control of fan coils with 2 pipe, 2
pipe with change-over, 2 pipe with electrical coil, or
4 pipe configurations.
The family includes All-in-one Controller Units (TC-
8900), a Remote Set point Module (ES-8930) and
Built-in Controller Units (TC-8930).
The TC-8900 has been designed to be easy to
use, while integrating the most common room air
conditioning control functions. TC-8900 All-in-one Controller Unit
ES-8930 Remote Setpoint Module with TC-8930
Built-in Controller Unit
Features and Benefits
G All in one condensed package: sensor, Provides better value for money in the smallest
direct/reverse input, window input, PI package
control, up to two valve outputs, mode
(comfort/stand-by) push button and
setpoint readjustment potentiometer
G Option to limit the setpoint adjustment Usability in critical environments where limited
range or to cancel the setpoint adjustability is preferred
adjustment
G Active or passive input Flexibility on the input: temperature, humidity,
differential pressure etc.
G Modern and discreet cover which snaps Blends in with room décor. Easier installation
onto a plug-in mounting base
G Electric terminals located on mounting Easier wiring and commissioning
base
G Standard range of mounting kits Mounting flexibility
©2000 Johnson Controls, Inc. F30
Order Nr.24.245E
2 TC-8900
O rdering data
All-in-one Output Sensor input* Built-in Controller Output Sensor input*
Controller Units Units
TC-8903-1131-WK 1xPAT Built-in NTC TC-8933-1112-W 1xPAT From ES
TC-8901-2131-WK 2x0…10V Built-in NTC TC-8931-2112-W 2x0…10V From ES
TC-8904-2131-WK 2xDAT Built-in NTC TC-8934-2112-W 2xDAT From ES
TC-8906-2131-WK 2xOn/Off Built-in NTC TC-8936-2112-W 2xOn/Off From ES
• Setpoint range: remote, see ES-8900
TC-8903-1132-WK 1xPAT Remote NTC
TC-8901-2132-WK 2x0…10V Remote NTC
Remote Setpoint Output Sensor input*
TC-8904-2132-WK 2xDAT Remote NTC Module
TC-8906-2132-WK 2xOn/Off Remote NTC ES-8930-3031-WK - Built-in NTC
• Setpoint range: 12…28° • Setpoint range: 12…28°C
All-in-one
Controller Units
Output Sensor input*
Accessories
Accessories (order separately)
TC-8903-1151-WK 1xPAT Built-in NTC
TC-8903-1152-WK 1xPAT Remote NTC Order code Description
• Setpoint range: 0…40° TM-9100-8900 Opening tool for sensor case
TM-9100-8901 Dial stop screws kit (bag of
All-in-one Output Sensor input* 100 self tapping screws)
Controller Units TM-9100-8931-W Plastic surface mounting kit
TC-8903-1183-WK 1xPAT Remote TM-9100-8941-W Wall box mounting kit
0…10V TM-9100-8951-W Panel mounting kit
TC-8901-2183-WK 2x0…10V Remote
0…10V See “RS-9100 product bulletin” for details
on accessories.
• Setpoint range: 0…100%
*Remote sensor input: see “Specifications”
last page of this document
Technical characteristics - models with NTC sensor input
Models TC-8901 series TC-8903 series TC-8904 series TC-8906 series
Dead Band 0 to 2 K - 0 to 2 K 0 to 2 K
Differential - - - 0.2 to 2 K
Proportional Band 1…4 K 2…8 K 1…4 K -
Time base - 120 seconds 5…15 minutes -
Integral Time - Off or 4 minutes - -
Standby Offset BSB 2K 2K 2K 2K
Window Offset BOF 5K 5K 5K 5K
Technical characteristics - models with 0…10V sensor input
Models TC-8901-2183-WK TC-8903-1183-WK
Dead Band 0 to 10% -
Proportional Band 5 to 20% 10 to 40%
Integral Time - Off or 4 minutes
Standby Offset BSB 10% 10%
Window Offset BOF 25% 25%
F30
TC-8900 3
Application
The TC-89x0 Controllers operate either wall mount or fan coil mount, optionally receiving the set point
from the Remote Setpoint Module.
TC-8900 ES-8930-3031-WK
TC-8930
FAN COIL FAN COIL
“All-in-one Controller Unit”, wall mount Unit mount “Built-in Controller Unit“,
with “Remote Setpoint Module”
Adjustment
Front description
• TC-8900 and ES-8930 (sliding cover open)
Sensor recalibration
Dir/Rev switch
Factory set in
RA position
RA
DA
Set point adjustment Mode status LED
Stand-by/comfort
push button
LED status Mode Status
on comfort
blinking stand-by
off Window open
• TC-8930
No front adjustment
F30
4 TC-8900
Back description
TC-8900 and TC-8930
PB: Proportional band
DB: Dead band
Tn: Integral time for PAT
Time: Time base for DAT
Diff: Differential for on/off control
RA DA
RA DA PB PB
PB PB 2 3 2 3
2 3 2 3
1 K 4 1 K 4
1 K 4 1 K 4 DB
1 TIME
DB 10
1
I
0 K 2 5 I 15
Min.
0 K 2
TC-89X4 (DAT)
TC-89X1 (0…10 V)
RA DA
DIFF DIFF
PB 0.8 1.4 0.8 1.4
I
0.2 K 2 0.2 K 2
2
I I 8
K
DB
1
Tn (TI)
5 Min.
0 2
K
TC-89X3 (PAT) (factory default – jumper closed TC-89X6 (ON/OFF)
TI= 4 min)
Factory settings: All trimmers are set at middle value.
ES-8930
No back adjustment
F30
TC-8900 5
Operation
SP: Setpoint
PB: Proportional band
DB: Dead band
BSB: Standby offset
BOF: “Window open” offset
2x0…10V Outputs (e.g. 4-pipe system)
BOF BOF
Output
BSB RA PB DA PB BSB
100 %
Process
0%
Variable
Off DB DB Off
Standby Standby
Comfort Comfort
SP
1x0…10V DA or RA Output (2-pipe system with change-over, use the “RA” output of the controller)
Output BOF Output BOF
BSB RA PB RA PB BSB
100 % 100 %
DB DB
0% Process Process
0%
Variable Variable
Off SP SP Off
Standby Standby
Comfort Comfort
RA (Reverse acting) DA (Direct acting)
F30
6 TC-8900
2XDAT Outputs (e.g. 4-pipe system)
Output BOF
BOF
BSB RA PB DA PB BSB
100 %
0% Process
Variable
DB DB
Off Off
Standby Standby
SP
Comfort Comfort
1XDAT DA or RA Output (2-pipe system with change-over, use the “RA” output of the controller)
Output BOF
Output BOF
BSB RA PB RA PB BSB
100 % 100 %
DB DB
Process Process
0% 0%
Variable Variable
Off SP Off
Standby Standby
SP
Comfort Comfort
RA (Reverse acting) DA (Direct acting)
F30
TC-8900 7
2xOn/Off Outputs (e.g. 4-pipe system)
Output BOF BOF
BSB RA DIF DA DIF BSB
100 %
Process
0%
DB DB Variable
Off Off
Standby Standby
Comfort SP Comfort
1xOn/Off DA or RA Output (2-pipe system with change-over, use the “RA” output of the controller)
Output Output
BOF BOF
RA DIF RA DIF
BSB BSB
100 % 100 %
DB DB
Process Process
0% 0%
Variable Variable
Comfort SP SP Comfort
Standby Standby
Off Off
RA (Reverse acting) DA (Direct acting)
F30
8 TC-8900
Wiring Diagram
The following drawings indicate the connection diagrams of the different stand alone models and Remote
Setpoint Module.
The contacts have the following functions:
Window contact ( ): Window closed = contact closed
Dir /Reverse contact ( ): Direct (summer) = contact closed
Reverse (winter) = contact open
A change-over thermostat can be connected to terminals 7 and 8. In that case the internal contact must
be fixed at winter (open).
Models Diagram n° Models Diagram n°
TC-8903-1131-WK 1 TC-8903-1151-WK 1
TC-8901-2131-WK 2 TC-8903-1152-WK 1
TC-8904-2131-WK 1
TC-8906-2131-WK 1 TC-8903-1183-WK 3
TC-8901-1283-WK 4
TC-8903-1132-WK 1
TC-8901-2132-WK 2 TC-8933-1112-W 5
TC-8904-2132-WK 1 TC-8931-2112-W 5
TC-8906-2132-WK 1 TC-8934-2112-W 5
TC-8936-2112-W 5
ES-8930-3131-WK 5
Diagram 1 Note:
On TC-890X Window Jumper factory set. 8 9
Remove when window input is used.
2 x DAT (TC-8904-21xx-WK)
2 x ON/OFF (TC-8906-21xx-WK)
Com
1 x PAT (TC-8903-11xx-WK)
M 15 VDC
24 VAC Com
24 VAC Remote Sensor
Com (TC-8903/4/6-x1x2-WK)
1 2 3 4 5 6 7 8 9 10 11 12 OR
Built-in Sensor
(TC-8903/4/6-x1x1-WK)
PAT models (TC-8903) : terminals 3 & 5 functions
Jumper Action Position Temperature (*) Terminal Energised
3 5
ON OFF
RA Set point OFF OFF
OFF ON
OFF ON
DA Set point OFF OFF
ON OFF
(*) Temperature increase Temperature decrease
F30
TC-8900 9
Diagram 2
15 VDC
RA DA
0...10 V 0...10 V
24 VAC Com
Com Remote Sensor
24 VAC
(TC-8901-21x2-WK)
OR
1 2 3 4 5 6 7 8 9 10 11 12
Built-in sensor
(TC-8901-21x1-WK)
Diagram3
1 x PAT
0...10 VDC
input
M
15 VDC Com
Com
24 VAC Com
24 VAC
1 2 3 4 5 6 7 8 9 10 11 12
Diagram4
0...10 VDC
input
15 VDC
RA DA
0...10 V 0...10 V Com
24 VAC Com
24 VAC
Com
1 2 3 4 5 6 7 8 9 10 11 12
Note:
On TC-890X Window Jumper factory set. 8 9
Remove when window input is used.
F30
10 TC-8900
Diagram 5
ES-8930-3131-WK
SetPoint
Com
1 2 3 18 19 6 7 8 9 10 11 12
Stand-by/Window Status
Signal common Signal common Temperature
15 VDC Dir/Rev Setpoint
See all in one models
connection diagram
1 2 3 4 5 6 7 8 9 10 11 12
TC-8930
Note:
On ES-8930 Window Jumper factory set.
18 19
Remove when window input is used.
F30
TC-8900 11
Dimensions (in mm)
80 33
20
16 24
Set Point
Dial
80 28
12
°C
Mode
LED
Occupancy
Button
tmtbdim
TC-8900 series stand alone and ES-8930
TC-8930 series has the same external dimensions as TC-8900, without setpoint dial, push button,
LED and sliding cover.
F30
12 TC-8900
Specifications
Models TC-89x0 ES-8930
Supply 24VAC ±15% Supplied by TC-8930
Power consumption 1.5 VA with no load ---
Output TC-89x1: 0…10V 10mA max ---
TC-89x3/4/6: triac 0,5A max
24VAC
Sensor ricalibration CW + 0.8 °C ---
CCW – 0.8 °C
Remote sensor • NTC K10 10kΏ at 25°C (TE-9100-8502 or TS-9104 Sensor
series)
• 0…10V (input impedance >50kΩ) (TS-9101, HT-9000, PS-910x
PT-910x Sensor series)
Ambient operating 0…50°C
temperature
Humidity range 0 to 95% not condensing
Storage temperature -20 +70°C
Mode indicator Red LED to indicate comfort (ON), standby (blinking), off (OFF), not
available on TC-8930
Mounting Direct surface mount, plastic base for surface mount with wiring
conduits, and recessed wall box and panel mounting kits. (See
Ordering Codes.)
Housing Material: ABS + polycarbonate, self-extinguishing VO UL94.
Protection: IP30 (IEC529)
Color: RAL-9010 pure white
Dimensions (H x W x D) 80 mm x 80 mm x 33 mm
Shipping Weight 0.15 kg
Compliance: EMC (89/336 EEC) according to the standard EN 50081-1
and EN 50082-1
* Note: other technical characteristics can be found in page 2
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these
specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages resulting from
misapplication or misuse of its products.
Johnson Controls International, Inc.
Headquarters: Milwaukee, WI, USA
European Headquarters: Westendhof 8, 45143 Essen, Germany
European Factories: Lomagna (Italy), Leeuwarden (The Netherlands), Essen (Germany)
Branch Offices: principal European Cities
This document is subject to change without notice Printed in Europe
F30
TC-8901/3/4/6 All-in-one Controller Unit
INSTALLATION INSTRUCTIONS
Mounting 80
1. Remove the base of the module from the cover by 33
inserting a pointed tool (a special tool, Ordering
Code TM-9100-8900, is available from Johnson
Controls) into the small hole at the center top of the
cover .
2. While pressing down gently, prise the base away 80
from the cover.
3. As the two parts separate, remove the tool and
continue to pull the cover away from the base until
the cover is in free.
4. Mount the base on the wall to cover the electrical
output and secure with at least two screws.
Front description TC-8900 Controllers Units
Sensor recalibration
-1K +1K
Dir/Rev switch
Factory set in
RA position
RA
DA
Set point adjustment Mode status LED
Stand-by/comfort
push button
LED Status Mode Status
on occupied
blinking stand-by
off window open
Supply 24 VAC ± 15% 50/60Hz
TC-8901 Output 0…10V 10mA max.
TC-8903/4/6 Output Triac Output 24 VAC 0.5A max.
Ambient operating temp. 0…50°C
Humidity 10…95% not condensing
CE Compliance EMC(89/336 EEC) according to standard EM50081-1 EM50082-1
P/N 24-85784-70
2 TC-8901/3/4/6
TC-8900 Dimensions
TC-8930 All-in one Controller Unit
TC-8900 Separate Connectors
1 2 3 4 5 6 7 8 9 10 11 12
Back description
RA DA
DIFF DIFF RA DA
I PB PB
0.8 1.4
2 3 2 3
0.2 2
I
K
I
0.2 K 2
1 K 4 1 K 4
DB DB
1 1 TIME
10
I
0 2 5 15
I
0 K 2 K Min.
TC-8936 (ON/OFF) TC-8934 (DAT)
RA DA
PB PB PB
I 2 3 2 3
2
I I 8 1 K 4 1 K 4
K
DB
1
Tn (TI)
5 Min.
0 K 2
TC-8933 (PAT) TC-8931 (0…10V)
P/N 24-85784-70
TC-8900 3
Wiring
Models Diagram n° Models Diagram n°
TC-8903-1131-WK 1 TC-8903-1151-WK 1
TC-8901-2131-WK 2 TC-8903-1152-WK 1
TC-8904-2131-WK 1
TC-8906-2131-WK 1 TC-8903-1183-WK 1A
TC-8901-1283-WK 2A
TC-8903-1132-WK 1
TC-8901-2132-WK 2
TC-8904-2132-WK 1
TC-8906-2132-WK 1
Diagram1
2 x DAT (TC-8904-21xx-WK) Note:
2 x ON/OFF (TC-8906-21xx-WK)
Window Jumper factory set.
8 9
Remove when window input is used.
Com
1 x PAT (TC-8903-11xx-WK)
M 15 VDC
24 VAC Com
24 VAC Remote Sensor
Com (TC-8903/4/6-x1x2-WK)
1 2 3 4 5 6 7 8 9 10 11 12 OR
Built-in Sensor
(TC-8903/4/6-x1x1-WK)
Diagram1A
1 x PAT
0...10 VDC
input
M
15 VDC Com
Com
24 VAC Com
24 VAC
1 2 3 4 5 6 7 8 9 10 11 12
P/N 24-85784-70
4 TC-8901/3/4/6
Diagram 2
15 VDC
RA DA
0...10 V 0...10 V
24 VAC Com
Com Remote Sensor
24 VAC
(TC-8901-21x2-WK)
OR
1 2 3 4 5 6 7 8 9 10 11 12
Built-in sensor
(TC-8901-21x1-WK)
Diagram 2A
0...10 VDC
input
15 VDC
RA DA
0...10 V 0...10 V Com
24 VAC Com
24 VAC
Com
1 2 3 4 5 6 7 8 9 10 11 12
Note:
Window Jumper factory set.
8 9
Remove when window input is used.
P/N 24-85784-70
TC-8901/3/4/6 5
Operation
PB: Proportional band; DB: Dead band;
Tn: Integral time for PAT; Time: Time base for DAT
Diff: Differential for on/off control
2x0…10V Outputs (e.g. 4-pipe system) 1x0…10V DA or RA Output (2-pipe system with
change-over, use the “RA” output of the controller)
Output BOF BOF
BSB RA PB DA PB BSB Output BOF Output BOF
BSB RA PB RA PB BSB
100 % 100 % 100 %
DB DB
Process Process
0% 0%
Variable Variable
Off SP SP Off
Process
Standby Standby
0% Comfort Comfort
Variable
Off Off
Standby
DB DB
Standby
O O
Comfort Comfort RA (Reverse acting) DA (Direct acting
SP
2XDAT Outputs (e.g. 4-pipe system) 1XDAT DA or RA Output (2-pipe system with change-
over, use the “RA” output of the controller)
Output BOF BOF
BOF Output BOF Output
BSB RA PB DA PB BSB BSB RA PB RA PB BSB
100 % 100 % 100 %
DB DB
0% Process Process
0% 0%
Variable Variable
DB DB
Off Off Off Off
SP
Standby Standby Standby Standby
SP SP
Comfort Comfort Comfort Comfort
RA (Reverse acting) DA (Direct acting)
2xOn/Off Outputs (e.g. 4-pipe system) 1xOn/Off DA or RA Output (2-pipe system with
change-over, use the “RA” output of the controller)
Output Output
Output
BOF BOF
BOF BOF RA DIF RA DIF
BSB BSB
BSB RA DIF DA DIF BSB
100 % 100 %
100 %
DB DB
Process Process
0% 0 %
Variable Variable
Comfort SP SP Comfort
Process
0% Standby Standby
Variable Off Off
DB DB
Off Off
Standby
Standby
Comfort SP Comfort RA (Reverse acting) DA (Direct acting)
P/N 24-85784-70
6 TC-8901/3/4/6
Note:
P/N 24-85784-70
TC-8902 and TC-8907 Controllers Units
INSTALLATION INSTRUCTIONS
Mounting
1. Remove the base of the module from the cover by
inserting a pointed tool (a special tool, Ordering
Code TM-9100-8900, is available from Johnson
Controls) into the small hole at the center top of the
cover 80
33
2. While pressing down gently, prise the base away
from the cover.
3. As the two parts separate, remove the tool and
continue to pull the cover away from the base until 80
the cover is in free.
4. Mount the base on the wall to cover the electrical
output and secure with at least two screws.
Front description TC-8902/7 Controllers Units
Sensor recalibration
-1K +1K
Dir/Rev switch
Factory set in
RA position
Set point adjustment
RA
DA
Auto/OFF/3-Speed
TC-8902 Mode status LED
Fan Override Adjuster
Auto/OFF/ON Standby/Comfort
Fan Override Adjuster TC-8907 Push button
LED Status Mode Status
on occupied
blinking stand-by
off window open
Supply 24 VAC ± 15% 50/60Hz
TC-8902 Output 0…10V 10mA max.
TC-8907 Output 0…13V 0.1mA max.
Ambient operating temp. 0…50°C
Humidity 10…95% not condensing
CE Compliance EMC(89/336 EEC) according to standard EM50081-1 EM50082-1
P/N 24-85784-62
2 TC-8902/7
Back description TC-8902 and TC-8907
RA DA
RA DA DIFF DIFF
PB PB 0.8 1.4 0.8 1.4
2 3 2 3
0.2 K 2 0.2 2
K
1 K 4 1 K 4
DB DB
1 1
0 K 2 0 2
K
TC-8902-XXXX-WK TC-8907-XXXX-WK
PB: Proportional band DIFF: Differential On/Off control
DB: Dead band DB: Dead band
TC-8900 Dimensions
TC-8902/7 Separate Connectors
1 2 3 4 17 6 7 8 9 10 1112 1 2 3 4 5 6 17 8 9 10 1112
2-pipe system 4-pipe system
P/N 24-85784-62
TC-8902/7 3
Wiring diagrams: Note:
Window Jumper factory set.
8 9
Remove when window input is used.
TC-8902-1xxx-WK and TC-8907-1xxx-WK (2-pipe system)
3 4 5 6 17
Signal Com
RA Output FAN overriide
15VDC Remote Sensor
(TC-8907-1xx2-WK)
(TC-8902-1xx2-WK)
1 2 3 4 17 6 7 8 9 10 11 12 OR
Built-in sensor
(TC-8Показано початок документа. Повний текст — у PDF за посиланням вище.