Terminal Unit Controller (TUC), models RS-1180 and LP-RSM003

Вид документаІнструкція
ВиробникJCI
МоделіRS-1180, LP-RSM003, GUARDE-OS
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.8 МБ

Про документ

The TUC is a terminal unit controller for fan coil units, heat pumps and similar HVAC terminal equipment, providing control of valves, thermal actuators, fans and electric heaters with room sensor module inputs. Configuration is set via jumpers and DIP switches (S1 for the room module type, S2 for configuration, S4 for network). The document covers compatible room sensor modules including TM-21xx, RS-1180 series, LP-RSM003 series, and other room sensor modules.

Ключові дані

Device power supply230 VAC ±10%, 50/60 Hz, 12 VA (including 24VAC (7VA))
Maximum current input15A (including I/Os)
Output for actuators24 VAC ±15%, 50/60 Hz, 7 VA
Room / return air sensor input (T1)NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%
Space temperature input (S)NTC10K (10K @ 25 °C) 0 ÷ 40 °C ±0,2 °C
Analog outputs Y/W/VSF0 ÷ 10 VDC, 5 mA - Not Isolated ±0,1 VDC
NetworkRS485, N2 / BACnet protocol
Terminals rating1 x 2.5 mm 24 - 12 AWG, 10 A cables; up to 250 VAC

Застосування

  • Fan coil / terminal unit control: on/off cooling and heating actuators, proportional thermal actuators (DAT) for 4-pipe or 2-pipe systems
  • Electric heater output, first or second stage
  • Fan speed control: 1, 2 or 3 speeds (default) or variable speed fan signal (VSF, proportional 0 - 10 V)
  • Occupancy indication via temporary occupancy button and occupancy LED
  • Inputs for condensation sensing, presence detection, window open / unit disable, change-over sensor, soft-start coil sensor, discharge air sensor

Особливості

  • Selectable BACnet protocol or N2 Open protocol over RS485 networking (2-wire or 3-wire)
  • End-of-network termination resistor (120 Ω) via DIP switch S4.2; signal reference terminal via S4.1
  • Automatic binding and instance numbering options
  • Fused outputs: F1 (6.3 A main fuse for unit and relay outputs), F2 (0.4 A for TA outputs)
  • Absolute set-point scale (12-28 °C) or dial set-point scale (+/- 3 °C)
  • DIN rail mounting or mounting using 2 x 4 mm screws

Технічні дані

Parameter Value
Device power supply (L-N) 230 VAC ±10%, 50/60 Hz, 12 VA (including 24VAC (7VA)) (power supply for actuators)
Maximum current input 15A (including I/Os)
Output for actuators 24 VAC ±15%, 50/60 Hz, 7 VA
Output for room sensor modules 5V: 5 VDC ±10%, 10mA / 15 VDC ±5%, 30mA
Output for active sensors 15 VDC ±5%, 20mA
Digital inputs DI1–DI4 Unit Disable / Window Open; Condensing Sensor; Presence Detector; Auxiliary General Purpose (voltage free contact n.o.)
Occ Temporary occupancy button of room sensor module
T1 analog input NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3% — Room / Return Air Sensor
T2 analog input NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3% — Change-over Sensor / Contact or voltage-free contact (n.o.)
T3 analog input NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3% — Soft-Start Coil Sensor
T4 analog input NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3% — Discharge Air Sensor
FAN analog input 0 ÷ 10 VDC ±0,5 °C (RS Series) — fan speed override
SP analog input 0 ÷ 5 VDC ±0,05 V (TM Series) — set-point
S analog input (RS Series) 0 ÷ 10 VDC (Linear) 0 ÷ 40 ±0,5 °C
S analog input (TM Series) NTC10K (10K @ 25 °C) 0 ÷ 40 °C ±0,2 °C
Clg digital output SPST 6(3)A 230 VAC relay (fused F1, max 6A) — On/Off cooling actuator
Htg digital output SPST 10A max 230 VAC relay (not fused) — heating actuator or electrical heater
Fan speeds output SPST 6(3)A 230 VAC relay (fused F1, max 6A)
TAc output (fused F2) Triac 230 VAC, 0,29 A max (fused, max 0.4 A) — proportional cooling thermal actuator (DAT)
TAh output (fused F2) Triac 24 VAC, 0,3 A max (fused, max 0.4 A) — proportional heating thermal actuator (DAT)
TA outputs jumper J3 Ta outputs 230 VAC or 24 VAC
Analog outputs Y, W, VSF 0 ÷ 10 VDC, 5 mA - Not Isolated ±0,1 VDC
LED output Open collector, 5 V — occupancy LED
Ambient conditions 0 … +50 °C, 10 … 90% RH
Terminals 1 x 2.5 mm 24 - 12 AWG, 10 A cables; voltages up to 250 VAC
Network wiring Shielded, twisted 22 AWG cable for N2 / BACnet protocol
SELV / Class 2 wiring separation minimum 30 cm recommended; not parallel to power line cables longer than 3 m
Dimensions (height) 57 mm

DIP switch configuration summary

S1 – Room Module

Switch Function Position
S1.1 TM-21xx, RS-1180 Series / LP-RSM003 Series On / Off
S1.2 Other Room Sensor Modules / RS-1180 Series On / Off
S1.3 Other Room Sensor Modules / RS-1180 Series On / Off
S1.4 Absolute Set-point Scale (12-28 °C) / Dial Set-point Scale (+/- 3 °C) On / Off

S2 – Configuration (selected settings)

Switch Function Position
S2.1 HTG El. Heater output 1st stage / 2nd stage On / Off
S2.2 BACnet Protocol / N2 Open Protocol On / Off
S2.3 4-Pipe / 2-Pipe (1 valve output - "Cool" terminal) On / Off
S2.4 Output Valves On/Off / Proportional On / Off
S2.5 & S2.6 1, 2 or 3 fan speeds (3 speeds default) per combination table
S2.7 Instance number through software / automatic On / Off
S2.8 Automatic Binding ON / OFF On / Off
S2.9 HTG relay general purpose (via protocol) / standard logic (Heat) On / Off

S4 – Network

Switch Function Position
S4.1 Terminal connected to "Signal Reference" / NOT connected On / Off
S4.2 End of Network (120 Ω) / Not end of network On / Off

Допуски та стандарти

  • EMC Directive 2004/108/EC
  • Low Voltage Directive 2006/95/EC

Текст документа

TUC - Terminal Unit Controller
       Installation Instructions                    Istruzioni d’installazione per                Installationsguide                      Инструкция по установке для
       for the technician /fitter                   il personale specializzato                    för installatör / montör                техника/монтажника
       Manuel d’installation                        Guía de instalación                           Pokyny k instalaci pro                  Instruções de Instalação
       pour le specialiste / monteur                para el specialista del ramo                  techniky a montéry                      para o técnico/instalador
       Installationsanleitung                       Installatiehandleiding                        Instrukcja instalacji dla               适用于技术人员与安装人员的
       für die Fachkraft / Monteur                  voor de vakman / monteur                      technika/montera                        安装说明书




                                                                                                                                                                     9




                                                      57 mm




    • Dimensions • Dimensions • Abmessungen
  • Dimensioni • Dimensiones • Afmetingen • Mått
• Rozměry • Wymiary • Размеры • Dimensões • 尺寸
                          [mm]                                                                     Figure 1: Connection Details


• Compliance • Conformité • Konformität • Conformità • Conforme con • Voorschriften en normen • Överensstämmelse
• Shoda s požadavky norem a směrnic • Dane dotyczące zgodności • Соответствие стандартам • Conformidade
                Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of the
                EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.
                Johnson Controls, Inc., déclare que ces produits sont conformes aux exigences essentielles et autres dispositions pertinentes de la
   Europe       Directive 2004/108/CE (CEM) et de la Directive 2006/95/CE (basse tension).
                Johnson Controls, Inc. erklärt, dass diese Produkte konform sind mit den wesentlichen Anforderungen und sonstigen anwendbaren Bestimmungen
                der EMV-Richtlinie 2004/108/EG und der Niederspannungsrichtlinie 2006/95/EG.
                Johnson Controls, Inc. dichiara che questi prodotti sono conformi ai requisiti fondamentali ed altre relative disposizioni della Direttiva
                EMC 2004/108/CE e della Direttiva bassa tensione 2006/95/CE.
                Johnson Controls, Inc., declara que estos productos cumplen los requisitos esenciales y demás disposiciones aplicables de la directiva
                EMC 2004/108/EC y la directiva europea de baja tensión 2006/95/EC.
                Johnson Controls, Inc. verklaart dat deze producten voldoen aan de essentiële vereisten en andere relevante bepalingen van de
                EMC-richtlijn 2004/108/EC en de richtlijn 2006/95/EC voor laagspanning.
                Johnson Controls, Inc. uppger att dessa produkter överensstämmer med kraven och andra relevanta bestämmelser i EMC-direktiv 2004/108/EC
                och lågspänningsdirektiv 2006/95/EC.
                Johnson Controls, Inc., prohlašuje, že tyto výrobky jsou v souladu se základními požadavky a ostatními odpovídajícími ustanoveními směrnice
                EMC 2004/108/ES a směrnice o nízkonapěťových zařízeních 2006/95/ES.
                Firma Johnson Controls, Inc. zapewnia, że te produkty spełniają podstawowe wymagania i inne istotne warunki dyrektywy dotyczącej zgodności
                elektromagnetycznej 2004/108 oraz dyrektywy dotyczącej niskich napięć 2006/95/WE.
                Johnson Controls, Inc, заявляет, что данные изделия соответствуют основным требованиям и другим положениям Директивы по
                электромагнитной совместимости EMC 2004/108/EC и Директивы по безопасности низковольтного оборудования 2006/95/EC.
                Johnson Controls, Inc., declara que estes produtos estão em conformidade com os requisitos essenciais e outras disposições relevantes da directiva
                EMC 2004/108/EC e baixa tensão 2006/95/EC



P/N 24-85737-1404 Rev. - Issue Date 01 2012
• This document is subject to change without notice • Ce document peut être sujet à des modifications sans préavis • Änderungen ohne Ankündigung vorbehalten
• Questo documento è soggetto a modifiche senza preavviso • Este documento está sujeto a cambios sin previo aviso • Dit document kan zonder kennisgeving worden gewijzigd
• Det här dokumentet kan ändras utan föregående meddelande • Tento dokument podléhá změnám bez předchozího upozornění
• Informacje zawarte w tym dokumencie mogą ulec zmianie bez powiadomienia • Настоящий документ может быть изменен без уведомления
 • Este documento está sujeito a alterações, sem aviso prévio • 本文档如有变化,恕不另行通知
 TUC

                                                                                  (a).           (b).       (c).         (d).
                                                                                 Green         Yellow     Yellow        Power
                                                                                  Vert         Jaune      Jaune        Marche
                                                                                 Grün            Gel        Gel          Netz
                                                                                 Verde         Giallo     Giallo    Alimentazione
                                                                                  Verde       Amarillo   Amarillo    Alimentación
                                                                                 Groen          Geel       Geel         Voeding
                                                                                  Grön           Gul        Gul          Ström
                                                                                 Zelený         Žlutý      Žlutý       Napájení
                                                                                 Zielona        Żółta      Żółta       Zasilanie
                                                                                Зеленый       Желтый     Желтый        Питание
                                                                                  Verde       Amarelo    Amarelo       Potência
                                                                                     绿色        黄色         黄色            电源

                                                                                     Leds
                                                   • Ambient     • Omgivning         50 °C
                                                   • Ambiante    • Prostředí   MAX                          MAX     90% RH
                                                   • Umgebung    • Otoczenia         122 °F
                                                   • Ambiente    • Среда
                                                   • Ambiente    • Ambiente          0 °C
                                                   • Atmosfeer
                                                                               MIN                          MIN     10% RH
                                                                 • 环境                32 °F
Figure 2: 2 Pipe Output   Figure 3: Fan Speeds




               Figure 4: RS485 Networking 2-wire                               Figure 5: RS485 Networking 3-wire




                     Mounting on a DIN Rail                                    Mounting using 2 x 4 mm screws


  P/N 24-85737-1404 Rev. - Issue Date 01 2012
TUC
       WARNING
      • Risk of Electric Shock and Property Damage.
      • Disconnect each of multiple power supplies before making electrical connections.
      • Disconnect power supply before making electrical connections, jumper or DIP-Switch setting.
      • More than one disconnect may be required to completely de-energize equipment.
      • Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
      • Use this controller only as an operating control.
      • Where failure or malfunction of the TUC could lead to personal injury or damage to the controlled equipment or other property, additional
        precautions must be designed into the control system.
      • Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls that are intended to warn of, or protect
        against, failure or malfunction of the controller.
      • The integrated circuits in the controller are sensitive to static currents. Take suitable precautions.
       ATTENTION
      • Risque d'électrocution et d’accidents matériels.
      • Débranchez chacune des alimentations électriques avant de procéder aux connexions.
      • Débranchez l’alimentation avant de procéder aux connexions électriques et au réglage des cavaliers ou des commutateurs DIP.
      • Il faudra peut-être en déconnecter plusieurs avant que l’équipement soit totalement hors tension. Le contact avec des composants porteurs d’une
        tension dangereuse peut provoquer une électrocution, ainsi que des lésions graves ou fatales.
      • Utilisez uniquement ce régulateur pour commander le fonctionnement.
      • Si une panne ou une défaillance de l’appareil risque d’entraîner des lésions corporelles, d'endommager l'équipement régulé ou de provoquer
        d’autres dégâts matériels, il faut intégrer des précautions supplémentaires au système de régulation.
      • Incorporez d'autres dispositifs tels que des systèmes de supervision ou d'alarme ou bien des contrôles de sécurité ou de limites pour avertir
        l’opérateur et protéger le matériel en cas de panne ou de défaillance du régulateur.
      • Débranchez chacune des alimentations électriques avant de procéder aux connexions. Il faudra peut-être en déconnecter plusieurs avant que
        l’équipement soit totalement hors tension.
      • Le contact avec des composants porteurs d’une tension dangereuse peut provoquer une électrocution, ainsi que des lésions graves ou fatales.
       ACHTUNG
      • Gefahr von Stromschlägen und Sachschäden.
      • Entfernen Sie alle Stromversorgungen, bevor Sie elektrische Verbindungen herstellen.
      • Trennen Sie die Stromversorgung, bevor Sie elektrische Verbindungen herstellen oder Jumper oder DIP-Schalter einstellen.
      • Um die Anlage völlig stromlos zu machen, müssen möglicherweise mehrere Versorgungen entfernt werden.
      • Eine Berührung von Komponenten, die unter gefährlicher Spannung stehen, kann einen elektrischen Schlag verursachen und zu schweren
        Verletzungen oder zum Tod von Menschen führen.
      • Verwenden Sie diesen TUC-Regler nur als Steuerelement für die Bedienung.
      • Wenn der Ausfall oder eine Fehlfunktion des TUC zu Personenschäden oder Beschädigungen der gesteuerten Anlage oder anderer Gegenstände
        führen könnte, müssen in dem Regelungssystem zusätzliche Vorsichtsmaßnahmen vorgesehen werden.
      • Bauen Sie andere Geräte ein und achten Sie auf ihren fehlerfreien Betrieb, wie beispielsweise Überwachungs- oder Alarmsysteme oder
        Sicherheits- oder Begrenzerelemente, um vor Ausfall oder Fehlfunktionen des TUC-Reglers zu schützen.
      • Die integrierten Schaltkreise im Regler reagieren empfindlich auf elektrostatische Entladungen. Ergreifen Sie entsprechende Vorsichtsmaßnahmen.
       AVVERTENZA
      • Rischio di scosse elettriche e danni materiali.
      • Prima di eseguire connessioni elettriche, scollegare tutte le sorgenti di alimentazione.
      • Scollegare l'alimentazione prima di effettuare connessioni elettriche o impostare jumper e interruttori dip-switch.
      • Per togliere tensione all'apparecchiatura, potrebbero essere necessarie più operazioni di disconnessione.
      • Il contatto con componenti sottoposti a tensioni pericolose può causare scosse elettriche con conseguenti lesioni personali gravi o morte.
      • Utilizzare questo controller solo come controllo operativo.
      • Qualora un guasto o un malfunzionamento del controller possa provocare lesioni personali o danni all'apparecchiatura controllata o altri danni
        materiali, è necessario adottare precauzioni aggiuntive nel sistema di controllo.
      • Includere e gestire altri dispositivi, ad esempio sistemi di supervisione o di allarme oppure controlli di limitazione o sicurezza che hanno lo scopo di
        avvisare o proteggere da guasti o malfunzionamenti del controller.
      • I circuiti integrati nel controller sono sensibili alla corrente statica. Adottare le precauzioni del caso.
       ADVERTENCIA
      • Riesgo de descarga eléctrica y daños materiales.
      • Desconecte todas las fuentes de alimentación antes de realizar conexiones eléctricas.
      • Desconecte el suministro eléctrico antes de realizar las conexiones eléctricas o configurar los puentes o los interruptores PLD.
      • Es posible que se necesite más de una desconexión para desactivar por completo el equipo.
      • El contacto con componentes que conduzcan voltaje peligroso puede causar descargas eléctricas y dar lugar a lesiones graves o incluso a la
        muerte.
      • Utilice este controlador TUC sólo como control de funcionamiento.
      • En el caso de que un fallo o un funcionamiento defectuoso del TUC provoque lesiones personales o daños en el equipo controlado o en otros
        objetos, se deben diseñar precauciones adicionales en el sistema de control.
      • Incorpore y realice el mantenimiento de otros dispositivos, como sistemas de alarma o supervisión, o controles de límites o de seguridad, con el fin
        de advertir de fallos o de funcionamientos defectuosos del controlador TUC y proteger de ellos.
      • La electricidad estática afecta a los circuitos integrados del controlador. Adopte las debidas precauciones.
       WAARSCHUWING
      • Risico van elektrische schokken en beschadiging van eigendommen.
      • Schakel voordat u elektrische verbindingen maakt de instellingen van de jumpers of DIP-switches uit.
      • Schakel alle meervoudige stroombronnen uit voordat u elektrische verbindingen maakt.
      • Mogelijk moet u meerdere voedingen uitschakelen om de apparatuur geheel van elektriciteit te ontdoen.
      • Contact met onderdelen met een gevaarlijke spanning kan elektrische schokken veroorzaken en ernstig persoonlijk letsel of de dood tot gevolg
        hebben.
      • Gebruik deze TUC-regelaar uitsluitend als regelaar.
      • Wanneer de TUC niet goed of helemaal niet werkt en dit persoonlijk letsel of beschadigingen van de apparatuur of andere eigendommen tot gevolg
        kan hebben, moeten aanvullende voorzorgsmaatregelen in het regelsysteem worden ingebouwd.
      • Zorg voor andere apparaten zoals bewakings- of alarmeringssystemen of beveiligings- of begrenzingsmechanismen die waarschuwen bij, of
        bescherming bieden tegen, het uitvallen van de TUC-regelaar.
      • De ingebouwde circuits van de regelaar zijn gevoelig voor statische elektriciteit. Neem afdoende voorzorgsmaatregelen.


P/N 24-85737-1404 Rev. - Issue Date 01 2012
TUC
       VARNING
      • Risk för elektriska stötar och skador på egendom.
      • Koppla från all spänningsmatning innan de elektriska anslutningarna görs.
      • Koppla från strömkällan innan du gör de elektriska anslutningarna och bygel- eller DIP-brytarinställningarna.
      • Fler än en spänningsmatning kan behöva kopplas bort innan utrustningen är helt strömlös.
      • Kontakt med komponenter med farlig spänning kan ge elektriska stötar som kan orsaka allvarliga eller livshotande personskador.
      • Använd styrenheten endast som en manöverkontroll.
      • Om felaktiga funktioner hos styrenheten kan leda till skador på person, den styrda utrustningen eller annan egendom, måste ytterligare
        säkerhetsfunktioner integreras i styrsystemet.
      • Installera och underhåll andra enheter, till exempel övervaknings- eller larmsystem eller säkerhets- eller begränsningskontroller som är avsedda att
        varna för, eller skydda mot, fel hos styrenheten.
      • De integrerade kretsarna i styrenheten är känsliga för statisk ström. Vidta lämpliga åtgärder.
       UPOZORNĚNÍ
      • Nebezpečí zásahu elektrickým proudem a poškození majetku.
      • Před zapojením elektrických přívodů odpojte veškeré zdroje napájení.
      • Před zapojením elektrických přívodů či nastavením můstků a přepínačů DIP odpojte zdroj napájení.
      • Aby bylo zařízení úplně vypnuto, bude pravděpodobně nutné odpojit více připojení.
      • Dotyk s komponenty pod nebezpečným napětím může způsobit zasažení elektrickým proudem a může vést k vážnému poranění či úmrtí.
      • Zařízení TUC používejte pouze jako provozní regulátor.
      • Pokud by selhání nebo nesprávná činnost regulátoru TUC mohly vést k poranění osob nebo poškození ovládaného zařízení či jiného majetku, musí
        být v regulačním sytému zavedena další preventivní opatření.
      • Do systému je vhodné začlenit a udržovat v něm další zařízení, jako například dohlížecí nebo výstražné systémy a ovládací prvky limitních hodnot
        nebo zabezpečení určené k varování či ochraně v případě závady nebo chybné funkce regulátoru TUC.
      • Integrované obvody v regulátoru jsou citlivé na statický proud. Učiňte proto příslušná opatření.
       OSTRZEŻENIE
      • Niebezpieczeństwo porażenia prądem elektrycznym i uszkodzenia mienia.
      • Przed wykonaniem podłączenia elektrycznego należy odłączyć wszystkie źródła zasilania.
      • Przed wykonaniem połączeń elektrycznych i ustawień zworek lub przełączników DIP należy odłączyć zasilanie sterownika.
      • W celu całkowitego odłączenia urządzenia od zasilania może być konieczne wykonanie odłączenia w kilku miejscach.
      • Dotknięcie elementów będących pod niebezpiecznym napięciem może spowodować porażenie i poważne obrażenia lub nawet śmierć.
      • Sterownika TUC należy używać wyłącznie jako regulatora sterowania.
      • Jeśli awaria lub wadliwe działanie sterownika TUC mogłyby doprowadzić do obrażeń ciała lub uszkodzenia urządzenia sterowanego względnie
        innego wyposażenia, w systemie sterowania należy zastosować dodatkowe środki ostrożności.
      • W takim wypadku należy zainstalować i utrzymywać inne urządzenia, na przykład systemy nadzorcze lub alarmowe albo regulatory zabezpieczające lub ograniczające,
        które mają na celu ostrzeganie lub zabezpieczenie przed awarią albo wadliwym działaniem sterownika TUC.
      • Układy scalone sterownika są wrażliwe na elektryczność statyczną. Należy zachować odpowiednie środki ostrożności.
       ВНИМАНИЕ
      • Возможно поражение электрическим током и причинение материального ущерба.
      • Перед выполнением электрических соединений отключите все имеющиеся источники электропитания.
      • Перед выполнением электрических соединений и изменением положений перемычек или DIP-переключателей отключите источник
        электропитания.
      • Для полного обесточивания оборудования отключение, возможно, потребуется произвести в нескольких местах.
      • Прикосновение к частям и элементам, находящимся под опасным напряжением,
        может привести к серьезной травме или смерти в результате поражения электротоком.
      • Данный контроллер должен использоваться только в качестве средства управления.
      • В тех случаях, когда неисправность или сбой в работе контроллера могут стать причиной несчастного случая либо повреждения
        управляемого оборудования или другого имущества, в системе управления должны быть предусмотрены дополнительные меры защиты.
      • В тех случаях, когда неисправность или сбой в работе контроллера могут стать причиной несчастного случая либо повреждения
        управляемого оборудования или другого имущества, в системе управления должны быть предусмотрены дополнительные меры защиты.
      • Внутренняя электрическая схема контроллера чувствительна к статическому электричеству. Соблюдайте надлежащие меры
        предосторожности.
       AVISO
      • Risco de Choque Eléctrico e Danos em Bens.
      • Desligue todas as fontes de alimentação, antes de efectuar ligações eléctricas.
      • Desligue a fonte de alimentação, antes de efectuar ligações eléctricas ou ajustes de ligações em ponte ou comutadores DIP.
      • Pode ser necessário desligar mais do que uma fonte de alimentação para cortar totalmente a alimentação de energia do equipamento.
      • O contacto com componentes alimentados com tensões perigosas pode provocar danos pessoais graves ou morte.
      • Este controlador apenas deve ser utilizado como controlo de operações.
      • Se avarias ou mau funcionamento do TUC puderem provocar danos pessoais ou danos no equipamento controlado ou noutros bens, o projecto
        do sistema de controlo deve incluir dispositivos de protecção adicionais.
      • Devem ser incluídos e utilizados outros dispositivos, tais como sistemas de alarme ou supervisão ou controlos limitadores ou de segurança
        destinados a avisar ou a proteger em caso de avaria ou mau funcionamento do controlador.
      • Os circuitos integrados do controlador são sensíveis a electricidade estática. Devem ser tomadas as devidas precauções.
       警告
      • 存在导致触电或财产损失的风险。
      • 请在连接电路前断开各个电源。
      • 请在连接电路、进行跳线或 DIP 开关设置前断开电源。
      • 可能需要断开多个电源以完全切断设备电源。
      • 接触携带危险电压的组件可能导致触电,并可能造成严重的人身伤害或死亡。
      • 仅将此控制器用作操作控制装置。
      • TUC 的任何失效或故障都可能导致人身伤害,或造成受控设备损坏或其他财产损失,控制系统中必须设计有额外的预防措施。
      • 在系统中添加其他设备并进行维护,例如用于警告或预防控制器失效或出现故障的监督或警报系统,以及安全或极限控制装置。
      • 控制器中的集成电路对静态电流十分敏感。请采取适当的预防措施。




P/N 24-85737-1404 Rev. - Issue Date 01 2012
           READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS CAREFULLY BEFORE INSTALLING AND SAVE IT FOR FUTURE USE

                                                                                             Table 4: Dip Switch S4 Network
IMPORTANT: Cables and wiring at Safety Extra Low Voltage (SELV) and Class 2 wiring
(North America) must be separated from power line voltage wiring. A minimum                                   Function                                           Position
separation distance of 30 cm is recommended. Do not run extra low voltage cables                                  Terminal connected to “Signal Reference”       On
parallel to power line voltage cables for long distances greater than 3 m. Do not run        S4.1
                                                                                                                  Terminal NOT connected                         Off
extra low voltage wiring close to transformers or high frequency generating equipment.
                                                                                                              End of Network (120)                              On
                                                                                             S4.2
Wirings and Configurations                                                                                    Not end of network                                 Off
Figure 1: Connection Details
(a). Fuse for TA outputs (T-Series) (b). Main Fuse for unit and Relay outputs (T-Series)     RS485 Networking
                                                                                             Figure 4: 2-wire (see Table 4)
(c). Circuit Breaker 16 A (d). Jumper for fan selection (e). Voltage Jumper for TA Outputs
                                                                                             (a). S4.1 Off,   Terminal NOT connected (b). Shield
FUSES                                                        LEDs                            (c). N2 / BACnet Protocol Shielded, twisted 22 AWG (d). Shield after last unit connected
F1      6.3 A - Main fuse for unit and relay outputs         Power    The unit is powered                                                            to ground
F2      0.4 A - Ta outputs                                   TX       Transmit               Figure 5: 3-wire (see Table 4)
                                                             RX       Receive                (a). S4.1 On,    Terminal Connected to “Signal Reference” (b). RS485 Signal Reference

• Set the jumpers DIP switches and address switches of the controller.                       (c). N2 / BACnet Protocol Shielded, twisted 22 AWG (d). Shield after last unit connected
                                                                                                                                                     to ground
  For more information, see Jumpers and DIP switch Settings for TUC Controller.
• Make wiring terminations with the screw connectors.                                        Table 5: Input and Output
  All terminals can accept 1 x 2.5 mm 24 - 12 AWG, 10 A cables.                              Terminals         Type                                       Description
  Note: These terminals may carry voltages up to 250 VAC.
• Verify that the wiring is correctly installed and that voltage levels are appropriate      Digital Inputs
  for the various input signals according to the application.                                                                                             Unit Disable / Window
                                                                                             DI1
• Keep all cables as short as possible and tie in position.                                                                                               Open
• All wiring should conform to local codes and must be carried out by authorized             DI2                                                          Condensing Sensor
  personnel only.
                                                                                             DI3                                                          Presence Detector
Table 1: Jumpers Settings                                                                                      Voltage Free Contact (n.o.)
                                                                                             DI4                                                          Auxiliary General Purpose
Jumpers                                                Function
                                                                                                                                                          Room Sensor Module
JMP1 - Fan configuration                               Fan VSF (Proportional 0 - 10 V)       Occ                                                          Temporary Occupancy
(Jumper block on left under DI3 terminal)              Fan On/Off (Relay)                                                                                 Button
J3 Voltage Jumper for TA outputs                       Ta outputs 230 VAC                    Anolog Inputs
(Jumper block above TAc,TAh terminals)                 Ta outputs 24 VAC                     T1                NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%       Room / Return Air Sensor

Table 2: DIP Switch S1 - Room Module                                                                           NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%       Change-over Sensor /
                                                                                             T2
                                                                                                               or Voltage-Free Contact (n.o.)             Contact
                  Function                                             Position
                                                                                             T3                                                           Soft-Start Coil Sensor
                  TM-21xx, RS-1180 Series                              On                                      NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%
S1.1                                                                                         T4                                                           Discharge Air Sensor
                  LP-RSM003 Series                                     Off
                                                                                             FAN               0 ÷ 10 VDC ±0,5 °C (RS Series)             Fan Speed Override
                  Other Room Sensor Modules                            On
S1.2                                                                                         SP                0 ÷ 5 VDC ±0,05 V (TM Series)              Set-Point
                  RS-1180 Series                                       Off
                                                                                                               0 ÷ 10 VDC (Linear) 0 ÷ 40 ±0,5 °C
                  Other Room Sensor Modules                            On                                      (RS Series)
S1.3                                                                                         S                                                            Room / Space Temperature
                  RS-1180 Series                                       Off                                     NTC10K (10K @ 25 °C) 0 ÷ 40 °C ±0,2 °C
                                                                                                               (TM Series)
                  Absolute Set-point Scale (12-28 °C)                  On
S1.4                                                                                         Digital Outputs
                  Dail Set-point Scale (+/- 3 °C)                      Off
                                                                                             Clg (Fused F1) SPST 6(3)A 230 VAC Relay (Fused, Max 6A) On/Off Cooling Actuator
Table 3: DIP Switch S2 - Configuration
                                                                                                                                                          On/Off Heating Actuator or
                 Function                                               Position             Htg               SPST 10A Max 230 VAC Relay (Not Fused)
                                                                                                                                                          Electrical Heater
                 HTG El. Heater output - 1st Stage                      On
S2.1
                 HTG El. Heater output - 2nd Stage                      Off                  (Fused F1)        SPST 6(3)A 230 VAC Relay (Fused, Max 6A) On/Off Fan Speeds
                                                                                             (Fan Speeds)
                 BACnet Protocol                                        On
S2.2                                                                                         TAc                                                          Cooling Proportional
                 N2 Open Protocol                                       Off                  (Fused F2)        230 VAC:                                   Thermal Actuator (DAT)
                 4-Pipe                                                 On                                     230 VAC, 0,29A Max Triac (Fused, Max 0.4A)
S2.3*                                                                                        TAh               24 VAC, 0,3A Max Triac (Fused, Max 0.4A) Heating Proportional
                 2-Pipe (1 valve output - "Cool" terminal)              Off                  (Fused F2)                                                   Thermal Actuator (DAT)
                 Output Valves - On/Off                                 On                   LED               Open Collector, 5 V                        Occupancy LED
S2.4
                 Output Valves - Proportional                           Off                  Analog Output
                 1 Fan speed (Low speed output)                         S2.5 On, S2.6 On                                                                  Modulating Cooling
                                                                                             Y
                 2 Fan speeds (Low & High speed outputs)                S2.5 On, S2.6 Off                                                                 Actuator
S2.5 & S2.6**                                                                                                  0 ÷ 10 VDC, 5 mA - Not Isolated ±0,1 VDC Modulating Heating
                                                                        S2.5 Off, S2.6 Off   W
                 3 Fan speeds (default)                                                                                                                 Actuator
                                                                        S2.5 Off, S2.6 On
                                                                                             VSF                                                          Variable Speed Fan Signal
                 Instance number through software                       On
S2.7                                                                                         Power Supply
                 Automatic Instance Number                              Off
                                                                                                               230 VAC ±10%, 50/60 Hz, 12 VA (Including
                 Automatic Binding ON                                   On                   L-N               24VAC (7VA) (Power Supply for Actuators). Device Power Supply
S2.8
                 Automatic Binding OFF                                  Off                                    Maximum current input 15A (Including I/Os)
                 HTG relay - general purpose - work through                                  24 V              24 VAC ±15%, 50/60 Hz, 7 VA                Output for Actuators
                                                                        On
S2.9             protocol                                                                                                                                 Output for Room Sensor
                 HTG relay - standard logic (Heat)                      Off
                                                                                             5V                5 VDC ±10%, 10mA / 15 VDC ±5%, 30mA
                                                                                                                                                          Modules
* see Figure 2: 2 Pipe Output         ** see Figure 3: Fan Speeds                            15 V              15 VDC ±5%, 20mA                           Output for Active Sensors




   P/N 24-85737-1404 Rev. - Issue Date 01 2012
          LISEZ ATTENTIVEMENT LES PRÉSENTES INSTRUCTIONS ET LES CONSIGNES DE SÉCURITÉ AVANT DE PROCÉDER À L’INSTALLATION
          ET CONSERVEZ-LES AUX FINS D’UTILISATION ULTÉRIEURE
                                                                                                  Tableau 4: Commutateur DIP S4 - Réseau
IMPORTANT: Les câbles et le câblage SELV (Safety Extra Low Voltage), ainsi que le
câblage de classe 2 (Amérique du Nord), doivent être séparés du câblage de tension                             Fonction                                                          Position
de la ligne électrique. Il est conseillé de les espacer d’au moins 30 cm. Ne tirez pas de                           Terminal connecté à “Signal Reference” (référence de signal) Marche
câbles basse tension supplémentaires parallèlement aux câbles de tension de la ligne               S4.1
                                                                                                                    Terminal NON connecté                                        Arrêt
électrique sur plus de 3 m. Ne tirez pas de câblage basse tension supplémentaire à
proximité des transformateurs ou d’équipements générant de la haute fréquence.                                 Fin du réseau (120)                                              Marche
                                                                                                   S4.2
Câblage et configurations                                                                                      Pas fin du réseau                                                 Arrêt
Figure 1: Détails de la connexion                                                                 Réseau RS485
(a). Fusible pour sorties TA (série T)                                                            Figure 4: Bifilaire (Tableau 4)
(b). Fusible principal des sorties de l’unité et des relais (série T) (c). Disjoncteur 16 A       (a). S4.1 arrêt,     Terminal NON connecté (b). Blindage
(d). Cavalier de sélection du mode de ventilation (e). Cavalier de tension pour sorties TA        (c). Protocole N2/BACnet, câble blindé et  (d). Blindé après connexion à la masse du
                                                                                                       torsadé 22 AWG                             dernier appareil
FUSIBLES                                                  Voyants
                                                                                                  Figure 5: Trifilaire (Tableau 4)
F1 6,3 A - Fusible principal des sorties de l'unité et    Marche L’appareil est sous tension
                                                                                                  (a). S4.1 marche,       Terminal connecté à (b). Signal de référence RS485
   des relais                                             TX        Transmission                      “Signal Reference” (référence de signal)
F2 0,4 A - Sorties TA                                     RX        Réception                     (c). Protocole N2/BACnet, câble blindé et     (d). Blindé après connexion à la masse du
                                                                                                       torsadé 22 AWG                                dernier appareil
• Réglez les cavaliers, les commutateurs DIP et les commutateurs d’adresse du
  régulateur.                                                                                     Tableau 5: Entrée et sortie
  Pour en savoir plus, reportez-vous aux réglages des cavaliers et des commutateurs                Bornes             Type                                        Description
  DIP du régulateur TUC.                                                                           Entrées numériques
• Terminez le câblage avec les connecteurs à vis.                                                                                                                 Désactivation de l’appareil /
  Toutes les bornes acceptent des câbles de 2,5 mm, 24 - 12 AWB, 10 A.                             DI1
                                                                                                                                                                  Fenêtre ouverte
  Remarque: ces bornes peuvent supporter des tensions allant jusqu’à 250 VAC.
                                                                                                   DI2                                                            Détecteur de condensation
• Vérifiez que l’installation du câblage est correcte et que les niveaux de tension sont
  adaptés aux divers signaux d’entrée de l’application.                                            DI3                                                            Détection de présence
• Les câbles doivent être les plus courts possible et attachés.                                    DI4                Contact sans tension (non ouvert)           Auxiliaire, polyvalent
• Le câblage doit respecter les codes locaux et n’être confié qu’à du personnel agréé.                                                                            Bouton d’occupation
                                                                                                                                                                  temporaire du module de
Tableau 1: Réglages des cavaliers                                                                  Occ
                                                                                                                                                                  détection des conditions
Cavaliers                                                  Fonction                                                                                               ambiantes
                                                           Ventilateur VSF                         Entrées analogiques
JMP1 - Configuration du ventilateur                        (proportionnel 0-10 V)                                                                                 Détecteur d’air ambiant /
(bloc de cavaliers à gauche sous la borne DI3)                                                     T1                 NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%
                                                           Marche/arrêt du ventilateur (relais)                                                                   de retour
                                                                                                                      NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3% Détecteur/contact de
Cavalier de tension J3 pour sorties TA              Sorties TA 230 VAC                             T2
                                                                                                                      ou Contact sans tension (non ouvert)        changement de mode
(bloc de cavaliers au-dessus des bornes Tac et TAh) Sorties TA 24 VAC
                                                                                                                                                                  Détecteur de serpentin
                                                                                                   T3
Tableau 2: Commutateur DIP S1 - Module température ambiante                                                                                                       Soft-Start
                                                                                                                      NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%
                                                                                                                                                                  Détecteur d’air de
                 Fonction                                                          Position        T4
                                                                                                                                                                  refoulement
                 TM-21xx, série RS-1180                                            Marche                                                                         Priorité de la vitesse de
S1.1                                                                                               FAN                0 ÷ 10 VDC ±0,5 °C (série RS)
                 Série LP-RSM003                                                   Arrêt                                                                          ventilation
                                                                                                                      0 ÷ 5 VDC ±0,05 V (série TM)
                 Autres modules de détection des conditions ambiantes              Marche          SP                                                             Point de consigne
S1.2                                                                                                                  0 ÷ 10 VDC (Linear) 0 ÷ 40 ±0,5 °C
                 Série RS-1180                                                     Arrêt
                                                                                                                      (série RS)                                  Température ambiante
                 Autres modules de détection des conditions ambiantes              Marche          S
                                                                                                                      NTC10K (10K @ 25 °C) 0 ÷ 40 °C ±0,2 °C (pièce/espace)
S1.3                                                                                                                  (série TM)
                 Série RS-1180                                                     Arrêt
                                                                                                   Sorties numériques
                 Échelle de point de consigne absolu (12-28 °C)                    Marche
S1.4                                                                                               Clg                Relais SPST 6(3)A 230 VAC                   Actionneur de marche/arrêt
                 Échelle du cadran du point de consigne (+/- 3 °C)                 Arrêt           (fusible F1)       (à fusible, 6 A maxi.)                      du refroidissement
Tableau 3: Commutateur DIP S2 - Configuration                                                                                                                     Actionneur de marche/arrêt
                                                                                                                      Relais SPST 10 A maxi. 230 VAC
              Fonction                                                          Position           Htg                                                            du chauffage ou chauffage
                                                                                                                      (sans fusible)
                                                                                                                                                                  électrique
              HTG Sortie de chauffage El. - 1er stade                           Marche
 S2.1
              HTG Sortie de chauffage El. - 2ème stade                          Arrêt             (fusible F1)       Relais SPST 6(3)A 230 VAC                    Marche/arrêt des vitesses
              Protocole BACnet                                                  Marche            (vitesses de       (à fusible, 6 A maxi.)                       de ventilation
 S2.2                                                                                             ventilation)
              Protocole N2 Open                                                 Arrêt
                                                                                                                                                                  Actionneur thermique
              4 tuyaux                                                          Marche
 S2.3*                                                                                            TAc (fusible F2) 230 VAC:                                       proportionnel de
              2 tuyaux (1 sortie clapet - terminal « Refroidissement »)         Arrêt                              230 VAC, 0,29A maxi. Triac                     refroidissement (DAT)
              Clapets de sortie - Marche/Arrêt                                  Marche                             (à fusible, 0,4 A maxi)
 S2.4                                                                                                              24 VAC, 0,3A maxi. Triac                       Actionneur thermique
              Clapets de sortie - Proportionnels                                Arrêt             TAh (fusible F2) (à fusible, 0,4 A maxi)                        proportionnel de chauffage
                                                                                S2.5 marche,                                                                      (DAT)
                 1 vitesse de ventilation (lente)                                                 Voyant          Collecteur ouvert, 5 V                          Voyant d'occupation
                                                                                S2.6 marche
                                                                                S2.5 marche,      Sortie analogique
                 2 vitesses de ventilation (lente et rapide)
                                                                                S2.6 arrêt                                                                        Actionneur de modulation
S2.5 et S2.6**                                                                                    Y
                                                                                S2.5 arrêt,                                                                       du refroidissement
                                                                                S2.6 arrêt                                                                        Actionneur de modulation
                 3 vitesses de ventilation (par défaut)                                           W                  0 ÷ 10 VDC, 5 mA - Non isolé ± 0,1 VDC
                                                                                S2.5 arrêt,                                                                       du chauffage
                                                                                S2.6 marche                                                                       Signal de vitesse de
                                                                                                  VSF
                 Nombre instance par le logiciel                                Marche                                                                            ventilation variable
S2.7                                                                                              Alimentation électrique
                 Nombre instance automatique                                    Arrêt
                                                                                                                  230 VAC ± 10 %, 50/60 Hz, 12 VA (dont 24
                 Binding automatique MARCHE                                     Marche
S2.8                                                                                              L-N             VAC (7 VA) (alimentation des actionneurs). Alimentation du dispositif
                 Binding automatique ARRÊT                                      Arrêt                             Entrée de courant maximale 15 A (dont E/S)
                 Relais HTG (chauffage) - Polyvalent - Fonctionne par                             24 V            24 VAC ±15%, 50/60 Hz, 7 VA                Sortie pour actionneurs
                                                                                Marche
S2.9             l’intermédiaire du protocole                                                                                                                Sortie pour modules
                 Relais HTG (chauffage) - Logique standard (chaleur)            Arrêt             5V              5 VDC ±10%, 10mA / 15 VDC ±5%, 30mA
                                                                                                                                                             capteurs de t° environnante
* Voir la Figure 2: Sortie 2 tuyaux       ** Voir la Figure 3: Vitesses de ventilation            15 V            15 VDC ±5%, 20mA                           Sortie pour capteurs actifs



  P/N 24-85737-1404 Rév - Date de publication 01 2012
         LESEN SIE DIESE ANLEITUNG UND DIE SICHERHEITSHINWEISE VOR DER INSTALLATION SORGFÄLTIG DURCH
         UND BEWAHREN SIE SIE FÜR SPÄTERE REFERENZZWECKE AUF
                                                                                        Tabelle 4: DIP-Schalter S4 - Netzwerk
WICHTIG: Kabel und Verdrahtung mit Schutzkleinspannung (SELV, Safety Extra Low
Voltage) sowie Klasse-2-Verdrahtungen (Nordamerika) müssen von                                           Funktion                                             Position
Hochspannungskabeln getrennt verlegt werden.                                                                Klemme an “Signalreferenz” angeschlossen          Ein
Für die Trennung wird ein Mindestabstand von 30 cm empfohlen. Verlegen Sie              S4.1
Kleinspannungskabel nicht über weitere Distanzen als 3 m parallel zu                                        Klemme NICHT angeschlossen                        Aus
Hochspannungskabeln. Verlegen Sie Kleinspannungskabel nicht in der Nähe von                              Netzwerkende (120)                                  Ein
Transformatoren oder Geräten, die Hochfrequenzen erzeugen.                              S4.2
                                                                                                         Nicht Netzwerkende                                   Aus

Verdrahtungen und Konfigurationen                                                       RS485-Vernetzung
Abbildung 1: Details zum Anschluss                                                      Abbildung 4: 2-adrig (Tabelle 4)
(a). Sicherung für TA-Ausgänge (T-Serie)                                                (a). S4.1 Aus,     Klemme NICHT angeschlossen (b). Abgeschirmt
(b). Hauptsicherung für Gerät und Relaisausgänge (T-Serie) (c). Trennschalter 16 A      (c). N2/BACnet-Protokoll, abgeschirmt, (d). Abschirmung nach der letzten mit Masse
(d). Jumper für die Lüfterauswahl (e). Spannungsjumper für TA-Ausgäng                        verdrillt, 22 AWG                      verbundenen Einheit

SICHERUNGEN                                             LEDs                            Abbildung 5: 3-adrig (Tabelle 4)
F1 6,3 A - Hauptsicherung für Gerät und                 Netz Das Gerät ist              (a). S4.1 Ein,    Terminal an „Signalreferenz“ angeschlossen (b). RS485 Signalreferenz
   Relaisausgänge                                            eingeschaltet              (c). N2/BACnet-Protokoll, abgeschirmt, (d). Abschirmung nach der letzten mit Masse
F2 0,4 A -TA-Ausgänge                                   TX Übertragen                        verdrillt, 22 AWG                      verbundenen Einheit
                                                        RX Empfangen                    Tabelle 5: Eingang und Ausgang
• Stellen Sie die DIP-Schalter der Jumper und die Adressschalter des Reglers ein.        Klemmen           Typ                                         Beschreibung
  Weitere Informationen finden Sie in den Abschnitten über die Jumper- und DIP-          Digitale Eingänge
  Schalter-Einstellungen für den TUC-Regler.
• Verwenden Sie für die Verdrahtungsanschlüsse die Schraubverbindungen.                                                                                Gerät deaktivieren/Fenster
                                                                                        DI1
                                                                                                                                                       offen
  Alle Klemmen können Kabel mit 1 x 2,5 mm 24 - 12 AWG, 10 A aufnehmen.
  Hinweis: Diese Klemmen sind auf Spannungen von bis zu 250 VAC ausgelegt.              DI2                                                            Kondensationssensor
• Stellen Sie sicher, dass die Verdrahtung korrekt vorgenommen wird und dass            DI3                 Potentialfreier Kontakt (n.o.)             Präsenzmelder
  geeignete Spannungswerte für die verschiedenen Eingangssignale für die jeweilige      DI4                                                            Zusätzlich, Allgemein
  Anwendung vorliegen.
                                                                                                                                                       Taste Raumsensormodul
• Halten Sie alle Kabel so kurz wie möglich und befestigen Sie sie an der dafür         Occ
                                                                                                                                                       Vorübergehende Belegung
  vorgesehenen Position.
• Die gesamte Verdrahtung muss konform zu den örtlichen Vorgaben erfolgen und darf      Analogeingänge
  nur von qualifiziertem Personal durchgeführt werden.                                  T1                NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3% Raum/Rückluftsensor
Tabelle 1: Jumper-Einstellungen                                                                           NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%
                                                                                        T2                                                     Übergangssensor/Kontakt
 Jumper                                     Funktion                                                      oder Potentialfreier Kontakt (n.o.)
                                            Lüfter VSF (Proportional 0 - 10 V)          T3                                                     Soft-Start-Konvektorsensor
JMP1 - Lüfterkonfiguration                                                                                NTC50K (50K @ 25 °C) -10 ÷ 89 °C ±3%
(Jumper-Block links unter der DI3-Klemme)   Lüfter Ein/Aus (Relais)                     T4                                                     Abluftsensor
                                            TA-Ausgänge 230 VAC                                                                                Aufheben der
J3 Spannungsjumper für TA-Ausgänge                                                      FAN               0 ÷ 10 VDC ±0,5 °C (RS Series)       Lüftergeschwindigkeit
(Jumper-Block oberhalb der TAc/TAh-Klemmen) TA-Ausgänge 24 VAC                                            0 ÷ 5 VDC ±0,05 V (TM Series)
                                                                                        SP                                                     Sollwert
Tabelle 2: DIP-Schalter S1 - Raummodul                                                                    0 ÷ 10 VDC (Linear) 0 ÷ 40 ±0,5 °C
               Funktion                                              Position                             (RS Series)
                                                                                                                                               Raum- /
               Serie TM-21xx, RS-1180                                Ein                S                 NTC10K (10K @ 25 °C) 0 ÷ 40 °C ±0,2
                                                                                                                                               Umgebungstemperatur
 S1.1                                                                                                     °C
               Serie LP-RSM003                                       Aus                                  (TM Series)
               Andere Raumsensormodule                               Ein                Digitale Eingänge
 S1.2
               Serie RS-1180                                         Aus                Clg               SPST 6(3)A 230 VAC-Relais
               Andere Raumsensormodule                               Ein                                                                       Ein/Aus Kühlstellantrieb
                                                                                        (Abgesichert F1) (Abgesichert, max. 6 A)
 S1.3
               Serie RS-1180                                   