YORK YLPA units are factory-assembled air-to-liquid reversible scroll heat pumps for cooling and heating water or glycol solutions, in Style B with 60 Hz supply and HFC-410A refrigerant. Each unit has two independent refrigerant circuits, fully charged and operationally tested at the factory. Capacity ranges from 115 to 170 tons cooling (400–600 kW), delivered by hermetic suction-cooled scroll compressors switched by a microprocessor controller.
Ключові дані
| Cooling capacities | 400 kW to 600 kW (115 Tons to 170 Tons) |
|---|---|
| Heating capacities | 400 kW to 600 kW (1390 MBH to 2040 MBh) |
| Refrigerant | R-410A (GWP 2088) |
| Power supply | 460 - 3 - 60 V-Ø-Hz (also 200/230/380/575V options per nomenclature) |
| Number of refrigerant circuits | 2 |
| Heat exchanger waterside design working pressure | 150 psig |
| Heat exchanger refrigerant side design working pressure | 650 psig |
| Sound power | 98–100 dB(A) base unit; 97–99 dB(A) with acoustic blankets |
| Operating weight | 10472 lb (0115SE) / 11904 lb (0145SE) / 13447 lb (0170SE) |
Застосування
- Cooling and heating water or glycol solutions in air conditioning installations
- Outdoor installations at ground level on suitable foundation or rooftop locations
- Not suitable for purposes other than those specified in the manual
Особливості
- Two independent refrigerant circuits with electronic expansion valves, four-way reversing valves, accumulators, liquid receivers and removable core filter-driers
- Hermetic scroll compressors with integral overload protection that automatically resets; soft start available as option
- Shell-and-tube direct expansion heat exchanger with frost protection heater to -4°F and victaulic grooved water connections
- IP55 power/controls cabinet with non-fused lockable disconnect switch usable as emergency stop
- Microprocessor control: automatic lead/lag, anti-recycle and anti-coincident timers, daily/holiday scheduling, load limiting, remote temperature reset via analogue or EMS-PWM input
- Native communications: Modbus RTU, BACnet MS/TP and N2 via standard RS485 port; RS-232 printer port
- Adaptive defrost control, one circuit at a time, balanced so heat is not removed from the hot water system during defrost
- Options: Chicago Code relief valves, neoprene pad isolators, 1" or 2" spring isolators, single-point supply terminal block or circuit breaker, flange kit (PN10), York Hydro Kit (single or dual pump), acoustic blankets
Технічні дані
| Parameter | Value |
|---|---|
| Refrigerant | R-410A |
| Refrigerant charge (System 1/System 2) | 126/139 lb (0115SE), 177/130 lb (0145SE), 177/177 lb (0170SE) |
| Oil charge (System 1/System 2) | 29.5/29.5 lb (0115SE), 44.2/29.5 lb (0145SE), 44.2/44.2 lb (0170SE) |
| Recommended compressor oil | York grade V |
| Number of compressors (Sys 1/Sys 2) | 2/2 (0115SE), 3/2 (0145SE), 3/3 (0170SE) |
| Compressor type | Scroll |
| Heat exchanger type | Shell and tube, direct expansion, 2-pass dual circuit |
| Water volume (heat exchanger) | 250 l (0115SE), 300 l (0145SE, 0170SE) |
| Water connections | 8 inch, Victaulic groove type |
| Waterside design working pressure | 150 psig |
| Refrigerant side design working pressure | 650 psig |
| Fouling factor basis of performance | 0.0001 ft²·hr·°F/Btu |
| Liquid outlet temp., cooling (water) | 39 to 59 °F |
| Liquid outlet temp., heating (water) | 95 to 131 °F |
| Liquid outlet temperature range (∆T), both modes | 6 to 15 °F |
| Air temperature – standard unit, cooling mode | 32 to 115 °F |
| Air temperature – standard unit, heating mode | 14 to 95 °F |
| Heat exchanger flow rate | 181–700 gpm (0115SE), 200–850 gpm (0145SE, 0170SE) |
| Heat exchanger pressure drop | 3.4 to 58.1 ftH2O |
| Maximum water side pressure | 150 psi / psig |
| Maximum refrigerant side pressure | 650 psi / psig |
| Power supply voltage | 200/230/380/460/575 V, 3Ø, 60 Hz (nominal); tolerance ±10% |
| Unit power supply (electrical data table) | 460 - 3 - 60 V-Ø-Hz; voltage limits 414 - 506 V |
| Min. Circuit Ampacity | 264 A (0115SE), 326 A (0145SE), 487 A (0170SE) |
| Max. Dual Element Fuse Size / Circuit Breaker Size | 300 A (0115SE), 350 A (0145SE), 600 A (0170SE) |
| Compressor RLA (each) | 54.5 A |
| Compressor LRA (each) | 310 A |
| Fan FLA (each fan) | 4 A |
| Number of fans (Sys 1/Sys 2) | 4/4 (0115SE), 6/4 (0145SE), 6/6 (0170SE) |
| Total air flow – standard models | 47 m³/s (0115SE), 58 m³/s (0145SE), 70 m³/s (0170SE) |
| Dimensions L×W×H | 194.4×88.4×94.1 in (0115SE), 230.5×88.4×94.1 in (0145SE), 274.4×88.4×94.1 in (0170SE) |
| Shipping weight | 9811 lb (0115SE), 11243 lb (0145SE), 12124 lb (0170SE) |
| Operating weight | 10472 lb (0115SE), 11904 lb (0145SE), 13447 lb (0170SE) |
| Sound power (base unit) | 98 dB(A) (YLPA0115SE), 99 dB(A) (YLPA0145SE), 100 dB(A) (YLPA0170SE) |
| Sound power incl. acoustic blankets | 97 dB(A) (YLPA0115SE), 98 dB(A) (YLPA0145SE), 99 dB(A) (YLPA0170SE) |
| Control supply | 115 V - 1 Ø - 60 Hz |
| Evaporator heater supply / load | 115 - 1 - 60 V-Ø-Hz; 280 W (all models) |
| Cabinet ingress protection | IP 55 (power/controls); fan motors IP54 |
| Flow switch (accessory) | F61MG-1C vapor-proof SPDT, NEMA 3R, 150 PSIG (10.5 bar) DWP, -20°F to 250°F (-29°C to 121°C), 1” NPT connection |
| Voltage free contacts rating | 125 VA |
| Remote emergency stop device rating | 20 amps, 115 V, AC-15 |
| Control terminal block voltage | nominal 30 VDC |
| Parameter | Low Limit | High Limit | Default |
|---|---|---|---|
| Cooling liquid setpoint (water) | 40°F | 70°F | 44°F |
| Suction pressure cutout (cooling, water) | 80 psig | 120 psig | 87 psig (factory setting 81 psig) |
| Discharge pressure cutout | 325 psig | 575 psig | 560 psig (factory setting 575 psig) |
| Anti-recycle timer | 240 s | 600 s | 600 s |
| Defrost initiation time | 15 min | 90 min | 60 min (factory 30/25 min) |
| Defrost termination time | 1 min | 6 min | 3 min |
| Mechanical HP cut-out auto reset | — | — | 585 psig |
| Model | Shipping | Operating | Point weights R1–R4 / L1–L4 |
|---|---|---|---|
| 0115SE | 9811 | 10472 | 1864 / 1026 / 1414 / 2178 / 1822 / 2168 |
| 0145SE | 11243 | 11904 | 1021 / 1471 / 1024 / 1356 / 1595 / 2191 / 1541 / 1705 |
| 0170SE | 12124 | 13447 | 1068 / 1545 / 1642 / 1279 / 1595 / 2257 / 2479 / 1582 |
Dim A = 47 (all models), Dim B = 32 or 47 depending on arrangement, Dim C = 32 (0115SE), 39 (0145SE), 47 (0170SE) for most arrangements, Dim D up to 106/126 (solid walls, arrangement A2), Dim E = 55–83 depending on arrangement.
Варіанти замовлення
Nomenclature example: YLPA0115SE40XBB — base product Y (York) L (scroll) P (heat pump) A (all regions); nominal capacity 0115/0145/0170 kW; unit designation S (standard unit); refrigerant E (R-410A); voltage/starter codes: 4x (460/3/60), 1x (200/3/60), 2x (230/3/60), 8x (380/3/60), 5x (575/3/60); design series B.
Options/accessories listed: flow switch F61MG-1C; Chicago code relief valves; neoprene pads isolators; 1" spring isolators (CP1-1D series, rated capacity 85–1785 lb); 2" spring isolators (CP2-1D series, 1020–3570 lb); Y2RSI-2D restrained vibration isolators (150–3740 lb); RD-style duralene isolators (RD1-WR to RD4-WR); flange kit (PN10 flanges); single-point supply terminal block; single-point circuit breaker; lifting lug sets (part numbers 026L00261-000 — 4 lug set, 026-45594-000 — 6 lug set).
Допуски та стандарти
Designed and manufactured within an EN ISO 9001 accredited organization (products produced at an ISO9001 certified facility). Conforms to:
- ANSI/ASHRAE Standard 15, Safety Code for Mechanical Refrigeration
- ANSI/NFPA Standard 70, National Electrical Code (N.E.C.)
- ASME Boiler and Pressure Vessel Code, Section VIII Division 1
- ARI Standard 550/590-98, Water Chilling Packages Using the Vapor Compression Cycle
- ASHRAE 90.1 Energy Standard for Building Except Low-Rise Residential Buildings
- ARI 370 Sound Rating of Large Outdoor Refrigeration and Air Conditioning Equipment
- U.L./cU.L. Listing Label for construction of chillers
- Relief valve piping sizing per EN13136 for critical or complex installations
Текст документа
YLPA 0115SE, 0145SE, 0170SE
INSTALLATION, OPERATION AND
Supersedes: 150.68-ICOM1 (1217) FORM 150.68-ICOM1 (1020)
MAINTENANCE
035-23346-100
MODEL YLPA AIR TO LIQUID
REVERSIBLE SCROLL HEAT PUMPS
STYLE B
Cooling Capacities: 115 Tons to 170 Tons
Cooling Capacities: 400 kW to 600 kW
Heating Capacities:1390 MBH to 2040 MBH
Heating Capacities: 400 kW to 600 kW
60Hz
HFC-410A
Issue Date:
October 15, 2020 Products are produced at a
facility whose quality-
management systems are
ISO9001 certified.
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
IMPORTANT!
Read BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-product labels,
recognize these inherent hazards, protect themselves, this document and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
DANGER indicates an imminently CAUTION identifies a hazard which could
hazardous situation which, if not avoided, lead to damage to the machine, damage
will result in death or serious injury. to other equipment and/or environmental
pollution. Usually an instruction will be
given, together with a brief explanation.
WARNING indicates a potentially hazardous NOTE is used to highlight additional
situation which, if not avoided, could result information which may be helpful to you.
in death or serious injury.
External wiring, unless specified as an optional connection in the manufacturer’s product line, is
not to be connected inside the micro panel cabinet. Devices such as relays, switches, transducers
and controls may not be installed inside the panel. No external wiring is allowed to be run through
the micro panel. All wiring must be in accordance with YORK’s published specifications and must
be performed only by qualified YORK personnel. YORK will not be responsible for damages/
problems resulting from improper connections to the controls or application of improper control
signals. Failure to follow this will void the manufacturer’s warranty and cause serious damage to
property or injury to persons.
2 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls’ policy for con- It is the responsibility of rigging, lifting, and operating/
tinuous product improvement, the information con- service personnel to verify the applicability of these
tained in this document is subject to change without documents to the equipment. If there is any question
notice. Johnson Controls makes no commitment to regarding the applicability of these documents, rig-
update or provide current information automatically ging, lifting, and operating/service personnel should
to the manual or product owner. Updated manuals, if verify whether the equipment has been modified and
applicable, can be obtained by contacting the nearest if current literature is available from the owner of the
Johnson Controls Service office or accessing the John- equipment prior to performing any work on the chiller.
son Controls Knowledge Exchange website at https://
docs.johnsoncontrols.com/chillers/.
REVISION NOTES
Revisions made to this document are indicated in the following table. These revisions are to technical information,
and any other changes in spelling, grammar, or formatting are not included.
AFFECTED PAGES DESCRIPTION
3 Conditioned Based Maintenance program information added
CONDITIONED BASED MAINTENANCE
Traditional chiller maintenance is based upon assumed Planned Service Agreement that leverages real time
and generalized conditions. In lieu of the traditional and historical data, delivering performance reporting,
maintenance program, a Johnson Controls YORK corrective actions required and data enabled guidance
Conditioned Based Maintenance (CBM) program can for optimal operation and lifecycle assurance. The pro-
be substituted. This CBM service plan is built around gram will include fault detection diagnostics, operation
the specific needs for the chiller, operating conditions, code statistics, performance based algorithms and ad-
and annualized impact realized by the chiller. Your lo- vance rules based rationale delivered by the Johnson
cal Johnson Controls Branch can propose a customized Controls Connected Equipment Portal.
WARNING!
The Control Cabinet contains lethal AC and DC voltages. Before performing service inside
the cabinet, remove the AC supply feeding the chiller.
The DC Voltage on the DC Bus will take 5 minutes to bleed off, after
AC power is removed. Always check the DC Bus Voltage with a
Voltmeter to assure the capacitor charge has bled off before working
on the system.
NEVER short out the DC Bus to discharge the filter capacitors.
NEVER place loose tools, debris, or any objects inside the Control Panel Cabinet.
NEVER allow the Control Panel Cabinet doors to remain open if there is a potential for rain
to enter the panel. Keep doors closed and assure all latches are engaged on each door
unless the unit is being serviced.
JOHNSON CONTROLS 3
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
Page Left Intentionally Blank
4 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
TABLE OF CONTENTS
GENERAL INFORMATION & SAFETY SINGLE POINT POWER SUPPLY
WIRING. ........................................................... 23
INTRODUCTION.............................................. 7 CONTROL CIRCUIT TRANSFORMER. ..... 23
WARRANTY. ..................................................... 7 REMOTE EMERGENCY STOP DEVICE.... 23
SAFETY. ............................................................. 7 CONTROL WIRING - VOLTAGE FREE
FLUORINATED GREENHOUSE GASES. .... 7 CONTACT. ....................................................... 23
RESPONSIBILITY FOR SAFETY. ................. 8 CHILLED LIQUID PUMP STARTER........... 23
ABOUT THIS MANUAL.................................. 8 RUN CONTACTS. ........................................... 24
MISUSE OF EQUIPMENT............................... 8 ALARM CONTACTS...................................... 24
CONTROL WIRING - SYSTEM INPUTS.... 24
PRODUCT DESCRIPTION FLOW SWITCH............................................... 24
REMOTE START/STOP.................................. 24
INTRODUCTION............................................ 11 REMOTE MODE SELECTION. .................... 24
COMPRESSORS.............................................. 11 REMOTE RESET OF CHILLED LIQUID
REFRIGERANT CIRCUITS........................... 11 SETPOINT........................................................ 24
REFRIGERANT TO WATER HEAT REMOTE LOAD LIMITING.......................... 24
EXCHANGER.................................................. 11 FAN FULL SPEED INHIBIT.......................... 24
AMBIENT COILS............................................ 11 EMS ANALOGUE INPUT.............................. 24
POWER AND CONTROLS PANELS............ 12 MODBUS, BACNET MS/TP AND N2. ......... 24
MICROPROCESSOR CONTROLS............... 12 CONNECTION DIAGRAM. .......................... 25
ACCESSORIES AND OPTIONS................... 13
REFRIGERANT FLOW BLOCK COMMISSIONING
DIAGRAMS. .................................................... 14
COMPONENT LOCATION DIAGRAM....... 15 PREPARATION................................................ 27
NOMENCLATURE.......................................... 15 PREPARATION - POWER OFF..................... 27
FIRST TIME START-UP. ................................ 28
HANDLING AND STORAGE
OPERATION
DELIVERY AND STORAGE......................... 17
INSPECTION. .................................................. 17 CONTROL PANEL KEYS. ............................. 31
MOVING THE UNIT. ..................................... 17 STATUS KEY. .................................................. 31
LIFTING WEIGHTS. ...................................... 18 DISPLAY/PRINT KEYS. ................................ 36
ENTRY KEYS. ................................................. 42
INSTALLATION SETPOINTS KEYS.......................................... 42
UNIT KEYS...................................................... 48
LOCATION REQUIREMENTS. .................... 19 OPTIONAL PRINTER INSTALLATION. .... 51
OUTDOOR INSTALLATIONS...................... 19 BAS/EMS TEMPERATURE RESET............. 51
LOCATION CLEARANCES. ......................... 19 BACNET, MODBUS AND YORKTALK 2
INSTALLATION OF VIBRATION COMMUNICATIONS. .................................... 55
ISOLATORS. .................................................... 21
PIPEWORK CONNECTION.......................... 21 MAINTENANCE
PIPEWORK ARRANGEMENT. .................... 21
CHILLED LIQUID SYSTEM......................... 22 GENERAL REQUIREMENTS....................... 67
CONNECTION TYPES AND SIZES. ........... 22 DAILY MAINTENANCE. .............................. 67
WATER TREATMENT.................................... 22 SCHEDULED MAINTENANCE................... 68
WATER QUALITY REQUIREMENTS......... 22 HEAT EXCHANGER IN-SERVICE
REFRIGERANT RELIEF VALVE PIPING. . 22 INSPECTION. .................................................. 68
ELECTRICAL CONNECTION...................... 23 COMPETENT PERSONS TROUBLE
POWER WIRING............................................. 23 SHOOTING GUIDE. ....................................... 69
SENSOR CALIBRATION CHARTS. ............ 71
JOHNSON CONTROLS 5
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
TECHNICAL DATA
WATERSIDE PRESSURE DROP GRAPH
OF EVAPORATORS........................................ 73
OPERATING LIMITATIONS......................... 74
PHYSICAL DATA............................................ 74
ELECTRICAL DATA....................................... 75
SOUND DATA.................................................. 75
ISOLATOR DATA............................................ 80
ONE INCH DEFLECTION SPRING
ISOLATORS CROSS REFERENCE.............. 80
ONE INCH DEFLECTION SPRING
ISOLATORS INSTALLATION
INSTRUCTIONS. ............................................ 81
TWO INCH DEFLECTION SPRING
ISOLATORS CROSS REFERENCE.............. 82
TWO INCH DEFLECTION SPRING
ISOLATORS INSTALLATION AND
ADJUSTMENT. ............................................... 83
DURALENE ISOLATOR CROSS
REFERENCE.................................................... 84
DURULENE ISOLATORS
INSTALLATION.............................................. 85
SPARE PARTS
RECOMMENDED SPARES........................... 87
RECOMMENDED COMPRESSOR OIL. ..... 87
ASSOCIATED DRAWINGS........................... 87
DECOMMISSIONING, DISMANTLING AND
DISPOSAL
6 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
GENERAL INFORMATION & SAFETY
INTRODUCTION For warranty purposes, the following conditions must
be satisfied:
YORK YLPA units are manufactured to the highest
design and construction standards to ensure high • The initial start of the unit must be carried out by
performance, reliability and adaptability to all types of trained personnel from an Authorized Johnson
air conditioning installations. Controls Service Center.
The unit is intended for cooling and heating water or • Only genuine Johnson Controls approved spare
glycol solutions and is not suitable for purposes other parts, oils, coolants, and refrigerants must be used.
than those specified in this manual. • All the scheduled maintenance operations detailed
This manual contains all the information required for in this manual must be performed at the specified
correct installation and commissioning of the unit, times by suitably trained and qualified personnel.
together with operating and maintenance instructions. • Failure to satisfy any of these conditions will au-
The manuals should be read thoroughly before tomatically void the warranty.
attempting to operate or service the unit.
SAFETY
All procedures detailed in this manual, including
installation, commissioning and maintenance tasks must Standards for Safety
only be performed by suitably trained and qualified YLPA units are designed and manufactured within an
personnel. EN ISO 9001 accredited organization and in conformity
The manufacturer will not be liable for any injury or with the following Standards and Codes:
damage caused by incorrect installation, commissioning, • ANSI/ASHRAE Standard 15, Safety Code for
operation or maintenance resulting from a failure to Mechanical Refrigeration.
follow the procedures and instructions detailed in the
manuals. • ANSI/NFPA Standard 70, National Electrical Code
(N.E.C.).
WARRANTY
• ASME Boiler and Pressure Vessel Code, Section VIII
Johnson Controls warrants all equipment and materials Division 1.
against defects in workmanship and materials for a
period of eighteen months from date of shipment, unless • ARI Standard 550/590-98, Water Chilling Packages
labor or extended warranty has been purchased as part Using the Vapor Compression Cycle.
of the contract. • ASHRAE 90.1 Energy Standard for Building Except
Low-Rise Residential Buildings.
The warranty is limited to parts only replacement and
shipping of any faulty part, or sub-assembly, which has • ARI 370 Sound Rating of Large Outdoor Refrigeration
failed due to poor quality or manufacturing errors. All and Air Conditioning Equipment.
claims must be supported by evidence that the failure has
In addition, the chillers conform to Underwriters
occurred within the warranty period, and that the unit has
Laboratories (U.L.) for construction of chillers and
been operated within the designed parameters specified.
provide U.L./cU.L. Listing Label.
All warranty claims must specify the unit model, serial
FLUORINATED GREENHOUSE GASES
number, order number and run hours/starts. Model
and serial number information is printed on the unit • This equipment contains fluorinated greenhouse gases
identification plate. covered by the Kyoto Protocol.
The unit warranty will be void if any modification to • The global warming potential of the refrigerant
the unit are carried out without prior written approval (R-410A) used in this unit is 2088.
from Johnson Controls. • The refrigerant quantity is stated in the Physical Data
table.
• The fluorinated greenhouse gases in this equipment
may not be vented to the atmosphere.
• This equipment should only be serviced by qualified
technicians.
JOHNSON CONTROLS 7
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
RESPONSIBILITY FOR SAFETY The unit must not be operated outside the design
parameters specified in this manual.
Every care has been taken in the design and manufacture
of the unit to ensure compliance with the safety Structural Support
requirements listed above. However, the individual
Structural support of the unit must be provided as
operating or working on any machinery is primarily
indicated in these instructions. Failure to provide proper
responsible for:
support may result in injury to the operator, or damage
• Personal safety, safety of other personnel, and the to the equipment and/or building.
machinery. Mechanical Strength
• Correct utilization of the machinery in accordance with The unit is not designed to withstand loads or stresses
the procedures detailed in the manuals. from adjacent equipment, pipework or structures.
ABOUT THIS MANUAL Additional components must not be mounted on the unit.
Any such extraneous loads may cause structural failure
The following terms are used in this document to alert and may result in injury to the operator, or damage to
the reader to areas of potential hazard. the equipment.
A WARNING is given in this document to General Access
identify a hazard, which could lead to
personal injury. Usually an instruction will There are a number of areas and features, which may
be given, together with a brief explanation be a hazard and potentially cause injury when working
and the possible result of ignoring the on the unit unless suitable safety precautions are taken.
instruction. It is important to ensure access to the unit is restricted
A CAUTION identifies a hazard which could to suitably qualified persons who are familiar with the
lead to damage to the machine, damage to potential hazards and precautions necessary for safe
other equipment and/or environmental operation and maintenance of equipment containing
pollution. Usually an instruction will be high temperatures, pressures and voltages.
given, together with a brief explanation and
the possible result of ignoring the Pressure Systems
instruction. The unit contains refrigerant vapor and liquid under
A NOTE is used to highlight additional pressure, release of which can be a danger and cause
information, which may be helpful to you injury. The user should ensure that care is taken during
but where there are no special safety installation, operation and maintenance to avoid damage
implications. to the pressure system. No attempt should be made
to gain access to the component parts of the pressure
The contents of this manual include suggested best system other than by suitably trained and qualified
working practices and procedures. These are issued for personnel.
guidance only, and they do not take precedence over
the above stated individual responsibility and/or local Electrical
safety regulations. The unit must be earthed. No installation or maintenance
This manual and any other document supplied with the work should be attempted on the electrical equipment
unit are the property of YORK which reserves all rights. without first switching power OFF, isolating and locking-
They may not be reproduced, in whole or in part, without off the power supply. Servicing and maintenance on live
prior written authorization from an authorized YORK equipment must only be performed by suitably trained
representative. and qualified personnel. No attempt should be made to
gain access to the Control Panel or electrical enclosures
MISUSE OF EQUIPMENT
during normal operation of the unit.
Suitability for Application
Rotating Parts
The unit is intended for cooling water or glycol solutions Fan guards must be fitted at all times and not removed
and is not suitable for purposes other than those specified unless the power supply has been isolated. If ductwork is
in these instructions. Any use of the equipment other to be fitted, requiring the wire fan guards to be removed,
than its intended use, or operation of the equipment alternative safety measures must be taken to protect
contrary to the relevant procedures may result in injury against the risk of injury from rotating fans.
to the operator, or damage to the equipment.
8 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
Sharp Edges Safety Labels
The fins on the air-cooled condenser coils have sharp The following labels are fixed to each unit to give
metal edges. Reasonable care should be taken when instruction, or to indicate potential hazards which may
working in contact with the coils to avoid the risk of exist.
minor abrasions and lacerations. The use of gloves is
White symbol on blue background
recommended.
For safe operation, read the instructions
Frame rails, braces, and other components may also first.
have sharp edges. Reasonable care should be taken when
working in contact with any components to avoid risk
of minor abrasions and lacerations. Black symbol on yellow background.
Refrigerants and Oils Warning: This machine may start
automatically without prior warning.
Refrigerants and oils used in the unit are generally
nontoxic, non-flammable and non-corrosive, and pose
no special safety hazards. However, the use of gloves Black symbol on yellow background
and safety glasses are recommended when working on Warning: Hot surface.
the unit. The build up of refrigerant vapor, from a leak
for example, does pose a risk of asphyxiation in confined
or enclosed spaces and attention should be given to good Black symbol on yellow background
ventilation. Warning: Safety relief valve may discharge
High Temperature and Pressure Cleaning gas or liquid without prior warning.
High temperature and pressure cleaning methods (e.g.
steam cleaning) should not be used on any part of the Black symbol on yellow background
pressure system as this may cause operation of the Warning: Isolate all electrical sources of
pressure relief device(s). Detergents and solvents, which supply before opening or removing the
may cause corrosion, should also be avoided. cover, as lethal voltages may exist.
Emergency Shutdown
Black symbol on yellow background
In case of emergency, the non-fused disconnect switch General attention symbol.
on the power panel should be used as the emergency stop
device. When operated it removes the electrical supply
to the unit thus shutting down the unit. Black symbol on yellow background
Warning: On isolating the supply it may
take up to 300 seconds for the capacitor
voltage to fall below 50 volts.
JOHNSON CONTROLS 9
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
Page Left Intentionally Blank
10 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
PRODUCT DESCRIPTION
INTRODUCTION compressors are mounted on isolator pads to reduce
YLPA air-to-liquid heat pumps are completely factory transmission of vibration to the rest of the unit.
assembled with all interconnecting refrigerant piping and The motor terminal boxes have IP54 weather protection.
wiring ready for field installation. The unit is pressure
tested, evacuated, and fully factory charged with REFRIGERANT CIRCUITS
refrigerant R-410A and oil in each of the independent Two independent refrigerant circuits are provided on
refrigerant circuits. After assembly, an operational each unit. Each circuit uses copper refrigerant pipe
test is performed with water flowing through the heat formed on computer controlled bending machines to
exchanger to ensure that each refrigerant circuit operates reduce the number of brazed joints resulting in a high
correctly. integrity and reliable system.
The unit structure is manufactured from heavy-gauge, Each circuit shall incorporate all components necessary
galvanized steel coated with baked-on powder paint for the designed operation including: a suction
(Champagne (RAL 7006, Munsell No. 9.8YR4.36/1.2)). accumulator, a liquid receiver, a four way reversing
YLPA units are designed and manufactured within an valve, service valves, isolation (ball/angle) valves,
EN ISO 9001 accredited organization and in conformity pressure relief valves, a high absorption removable
with the following Standards and Codes: core filter-drier, a sight glass with moisture indicator,
and an electronic expansion valve. Suction lines shall
• ANSI/ASHRAE Standard 15, Safety Code for be covered with closed-cell insulation.
Mechanical Refrigeration.
REFRIGERANT TO WATER HEAT EXCHANGER
• ANSI/NFPA Standard 70, National Electrical Code
(N.E.C.). The 2-pass dual circuit shell and tube type direct
expansion (DX) heat exchanger has refrigerant in the
• ASME Boiler and Pressure Vessel Code, Section VIII tubes and liquid flowing through the baffled shell. The
Division 1. waterside (shell) design working pressure is 150 psig.
The refrigerant side (tubes) design working pressure is
• ARI Standard 550/590-98, Water Chilling Packages
650 psig. The refrigerant side is protected by pressure
Using the Vapor Compression Cycle.
relief valve(s).
• ASHRAE 90.1 Energy Standard for Building Except
The heat exchanger is equipped with a heater for frost
Low-Rise Residential Buildings.
protection to -4°F (below this the ball valve in the
• ARI 370 Sound Rating of Large Outdoor Refrigeration discharge line must be closed) and insulated with flexible
and Air Conditioning Equipment. closed-cell foam.
In addition, the chillers conform to Underwriters Water connection to the heat exchanger is via victaulic
Laboratories (U.L.) for construction of chillers and grooved connections. Victaulic groove to flange
provide U.L./cU.L. Listing Label. converters are available as an option.
COMPRESSORS AMBIENT COILS
The YLPA unit has suction-cooled, hermetic scroll The ambient coils are seamless copper tubes, arranged
compressors. High efficiency is achieved through a in staggered rows, mechanically expanded into coated
controlled orbit and the use of advanced scroll geometry. aluminium fins. Integral sub-cooling is included.
The compressors incorporate a compliant scroll design
The ambient coil fans are designed for maximum
in both the axial and radial directions. All rotating parts
efficiency and statically and dynamically balanced
are statically and dynamically balanced. The compressor
for vibration free operation. They are directly driven
motors have integral protection against overloads that
by independent motors, and positioned for vertical air
will automatically reset. Starting is direct on line, and
discharge. The fan guards are constructed from heavy-
soft start is available as an option.
gauge, corrosion resistant, coated steel.
The compressors are switched On and Off by the unit
microprocessor to provide capacity control. Each
compressor is fitted with a crankcase strap heater. All
JOHNSON CONTROLS 11
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
The IP54 fan motors are the totally enclosed air-over • Software is loaded into the microprocessor controller
type with permanently lubricated double-sealed ball via a SD card, with programmed setpoints retained in a
bearings. lithium battery backed real time clock (RTC) memory.
POWER AND CONTROLS PANELS • Forty character liquid crystal display, with description
available in several languages.
All power and controls are contained in an IP 55 cabinet
with hinged and gasket sealed outer doors. Programmable setpoints:
The power panel includes: • Chilled liquid temperature setpoint and range
• A factory mounted non-fused disconnect switch • Hot liquid temperature setpoint and range
with external (red/yellow) lockable handle to enable
connection of the unit power supply. The disconnect • Remote reset temperature range
switch can be used to isolate the power for servicing • Set daily schedule/holiday for start/stop
and as a emergency stop.
• Manual override for servicing
• Factory mounted compressor contactors and
compressor fuses provide short circuit protection. • Low ambient cutout
Overload protection for each compressor is provided • High ambient cutout (heating only - fixed)
by inherent motor winding temperature sensing and
a trip module. • Low liquid temperature cutout
• Factory mounted fan contactors and fuses provide • Low suction pressure cutout
short circuit protection. Overload protection for • High discharge pressure cutout
each fan is provided by a inherent motor winding
temperature device. • Anti-recycle timer (compressor start cycle time)
• Factory mounted control transformer to convert the • Anti-coincident timer (delay compressor starts)
unit supply voltage to 115 V - 1 Ø - 60 Hz for the • Cooling suction superheat
control system.
• Heating suction superheat
• Control supply fuses and connections for a remote
emergency stop device. Displayed Data:
The control panel includes: • Leaving liquid temperature
• A Liquid Crystal Display (two display lines of twenty • Air coil defrost temperatures
characters per line) with Light Emitting Diode
• Low leaving liquid temperature cutout setting
backlighting for easy viewing.
• Low ambient temperature cutout setting
• A Color coded 12-button keypad.
• EEV output
• Customer terminal blocks for control inputs and liquid
flow switch. • Suction superheat
MICROPROCESSOR CONTROLS • Suction temperature
The microprocessor control includes: • Suction saturated temperature
• Automatic control of compressor start/stop, • Ambient air temperature
anticoincidence and anti-recycle timers, pump and
unit alarm contacts. Automatic reset to normal unit • Metric or Imperial data
operation after power failure. • Discharge and suction pressure cutout settings
• Remote water temperature setpoint reset via an analog • System discharge and suction pressures
input or a pulse width modulated (PWM) input signal,
or up to two steps of demand (load) limiting. • Anti-recycle timer status for each system
• Anti-coincident system start timer condition
12 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
• Compressor run status ACCESSORIES AND OPTIONS
• No load condition Flow Switch
• Day, date and time The flow switch or its equivalent must be furnished with
each unit. 150 psig (10.5 bar) DWP - For standard units.
• Daily start/stop times Johnson Controls model F61MG-1C Vapor-proof SPDT,
• Holiday status NEMA 3R switch (150 PSIG [10.5 bar] DWP), -20°F
to 250°F (-29°C to 121°C), with 1” NPT connection for
• Automatic or manual system lead/lag control upright mounting in horizontal pipe. (Field-mounted)
• Lead system definition Chicago Code Relief Valves
• Compressor starts & operating hours (each compressor) The unit will be provided with relief valves to meet
• Status of heat exchanger heater and fan operation Chicago code requirements. (Factory mounted)
Neoprene Pads Isolators
• Run permissive status
Recommended for normal installations (Field mounted)
• Number of compressors running
1" Spring Isolators
• Mode solenoid valve status
Level adjustable, spring and cage type isolators for
• Load & unload timer status
mounting under the unit base rails (Field mounted)
• Liquid pump status 2" Spring Isolators
System Safeties: Restrained Spring-Flex Mountings incorporating a
Cause individual compressors to perform auto shut rugged welded steel housing with vertical and horizontal
down and require manual reset in the event of 3 trips in limit stops. (Field mounted)
a 90-minute time period: Flange Kit
• High discharge pressure Provides contractor with the couplings best suited to
• Low suction pressure tie into the chilled water piping. All flanges are PN10.
• Low suction superheat Single-Point Supply Terminal Block
• High-pressure switches Includes enclosure, terminal-block and interconnecting
wiring to the compressors. Separate external protection
• Motor protector must be supplied, by others, in the incoming compressor-
power wiring. (Do not include this option if either the
Unit Safeties:
Single-Point Non-Fused Disconnect Switch or Single-
They are automatic reset and cause compressor to shut Point Circuit Breaker options have been included.)
down:
Single-Point Circuit Breaker
• Low leaving chilled liquid temperature
A unit mounted circuit breaker with external, lockable
• Under voltage handle (in compliance with N.E.C. Article 440-14), can
be supplied to isolate the power voltage for servicing.
• Loss of liquid flow (through flow switch) This option includes the Single-Point Power connection.
For each system a common alarm contact for:
• Low leaving chilled liquid temperature
• Low voltage
• Low battery
• High discharge pressure (per system)
• Low suction pressure (per system)
• Compressor motor protection
JOHNSON CONTROLS 13
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
REFRIGERANT FLOW BLOCK DIAGRAMS
Cooling and Defrost Modes
Low pressure liquid refrigerant enters the heat exchanger and is evaporated and superheated by the heat energy
absorbed from the chilled liquid. Low pressure vapor enters the compressor, via the four-way reversing valve and
accumulator, where pressure and superheat are increased. The high pressure vapor is fed to the ambient coils and
fans, via the four way reversing valve, where heat is removed. The fully condensed and subcooled liquid passes
through the electronic expansion valve where pressure is reduced and further cooling takes place before returning
to the heat exchanger.
Ambient Coils
(Condenser)
4-way valve
Refrigerant flow
EEV
Receiver
Compressors Heat Exchanger
Accumulator (Evaporator)
Heat Pump Mode
Liquid refrigerant enters the ambient coil, and is fully evaporated and superheated by the energy absorbed from the
ambient air. Low-pressure superheated refrigerant vapor passes through the four-way reversing valve and the
accumulator and enters the compressor, where pressure and superheat are increased. High-pressure superheated
refrigerant vapor enters the refrigerant to water plate heat exchanger where heat is rejected to the water. The high-
pressure liquid refrigerant, leaving the heat exchanger passes through the liquid receiver and enters the electronic
expansion valve where the refrigerant pressure is reduced and subsequently cooled before returning to the ambient
coil.
Ambient Coils
(Evaporator)
4-way valve
Refrigerant flow
EEV
Receiver
Compressors Heat Exchanger
Accumulator (Condenser)
Defrost
When ice builds up on the ambient coils defrost is initiated by operating the machine in a cooling mode. Each of
the refrigerant circuits will be defrosted one at a time. When defrost is operative the circuit operating in heat pump
mode is in balance with the circuit operating in defrost (cooling). Therefore, heat energy is not removed from the
hot water system.
14 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
COMPONENT LOCATION DIAGRAM
8
1
3
2
7
4
6 5
LD23120
1 Power Panel 5 Heat Exchanger
2 Non-Fused Disconnect Switch 6 Suction Accumulator
3 Control Panel 7 Ambient Coils
4 Compressors 8 Fans
NOMENCLATURE
YLPA0115SE40XBB
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATION REFRIGERANT VOLTAGE / STARTER DESIGN / DEVELOPMENT LEVELS
: York
Y : Scroll # # # # kW S : Standard Unit E : R-410A 4 6 x : 460/3/60 B : Design Series
L 0115 0145 0170 1 7 x : 200/3/60 B : Development Level
P : Heat Pump
A : All Regions 2
4
8
0
x : 230/3/60
x : 380/3/60
5 8 x : 575/3/60
JOHNSON CONTROLS 15
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
Page Left Intentionally Blank
16 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
HANDLING AND STORAGE
DELIVERY AND STORAGE MOVING THE UNIT
To ensure consistent quality and maximum reliability, Prior to moving the unit, ensure that the installation site
all units are tested and inspected before leaving the is suitable for installing the unit and is easily capable
factory. Units are shipped completely assembled and of supporting the weight of the unit and all associated
contain refrigerant under pressure. Units are shipped services.
without export crating unless crating has been specified
The unit should be lifted using lifting lugs and a spreader
on the Sales Order.
bar or frame of sufficient width to prevent damage to
If the unit is to be put into storage, prior to installation, the unit from the lifting chains.
the following precautions should be observed:
The unit must only be lifted by the base
• Ensure that all openings, such as water connec- frame at the points provided. Never move
tions are securely capped. the unit on rollers, or lift the unit using a
fork-lift truck.
• The unit should be stored in a location where there
is minimal activity in order to limit the risk of ac-
cidental physical damage. Care should be taken to avoid damaging
the ambient coil fins when moving the unit.
• To prevent inadvertent operation of the pressure
relief devices, the unit must not be steam cleaned.
• It is recommended that the unit is periodically in-
spected during storage.
Units are provided with lifting holes in the base frame
INSPECTION which accept the accessory lifting lug set (part number
Remove any transit packing and inspect the unit to 026L00261-000 - 4 lug set, 026-45594-000 - 6 lug set).
ensure that all components have been delivered and that The lugs should be inserted into the respective holes in
no damage has occurred during transit. If any damage the base frame and turned so that the spring loaded pin
is evident, it should be noted on the carrier’s freight bill engages into the hole and the flanges on the lug lock
and a claim entered in accordance with the instructions behind the hole. The lugs should be attached to the
given on the advice note. cables/chains using shackles or safety hooks.
Major damage must be reported immediately to your
local Johnson Controls representative.
JOHNSON CONTROLS 17
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
LIFTING WEIGHTS
The weights and weight distribution limits are given below.
Weight (lbs) Point Weight (lbs)
Model Shipping Operating R1 R2 R3 R4 L1 L2 L3 L4
0115SE 9811 10472 1864 1026 1414 2178 1822 2168
0145SE 11243 11904 1021 1471 1024 1356 1595 2191 1541 1705
0170SE 12124 13447 1068 1545 1642 1279 1595 2257 2479 1582
L1 L2 L3 L4
Control Panel
R1 R2 R3 R4
18 JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
INSTALLATION
LOCATION REQUIREMENTS LOCATION CLEARANCES
To achieve optimum performance and trouble-free Adequate clearances around the unit(s) are required
service, it is essential that the proposed installation site for the unrestricted air-flow for the ambient coils and
meet with the location and space requirements for the to prevent re-circulation of discharge air back onto the
model being installed. coils. If clearances given are not maintained, air-flow
The clearances recommended are nominal for the safe restriction or re-circulation will cause a loss of unit
and efficient operation and maintenance of the unit performance, an increase in power consumption, and
and power and control panels. Local health and safety may cause the unit to malfunction. Consideration should
regulations, or practical considerations for service also be given to the possibility of down drafts, caused
replacement of large components, may require larger by adjacent buildings, which may cause re-circulation
clearances than those given in this manual. or uneven unit air-flow.
OUTDOOR INSTALLATIONS For locations where significant cross winds are expected,
such as exposed roof tops, an enclosure of solid or
The units can be installed at ground level on a suitable louvre type is recommended to prevent wind turbulence
and level foundation easily capable of supporting the interfering with the unit air-flow.
weight of the unit, or on a suitable rooftop location. In
both cases an adequate supply of air is required. Avoid When units are installed in an enclosure, the enclosure
locations where the sound output and air discharge from height should not exceed the height of the unit on more
the unit may be objectionable. than one side. Where accumulation of snow is likely,
additional height must be provided under the unit to
The location should be selected for minimum sun ensure normal air-flow to the unit.
exposure and away from boiler flues and other sources
Dim. YLPA
of airborne chemicals that could attack the ambient coils
(in) 0115SE 0145SE 0170SE
and steel parts of the unit. A 47 47 47
Arrangement
B 32 32 32
If located in an area accessible to unauthorized persons, A1
C 32 39 47
steps must be taken to prevent access to the unit by Solid Walls