YLCS 0350SA/HA/AA to 1120SA/HA/AA (models 0350 — Water cooled liquid chiller / remote air cooled chiller, York YLCS SA, HA & AA

Вид документаІнструкція
ВиробникJCI
МоделіYLCS 0350SA/HA/AA to 1120SA/HA/AA (models 0350, 269, 0480, 344, 381, 400, 0660/0670, 0725/0750
Група обладнанняother
Мова документаанглійська
Розмір файлу3.1 МБ

Про документ

York YLCS screw chillers cool water or glycol solutions for air conditioning installations. Models are available in three versions: standard units (SA), units for high condensing temperatures (HA) and units with remote air-cooled condensers (AA). All models consist of 2 screw compressors with integral oil separators in separate refrigerant circuits, a dual circuit shell and tube DX evaporator, and — on SA & HA models — single circuit water cooled condensers.

Ключові дані

RefrigerantR134a
Power supply400 V, 3 Ø, 50 Hz nominal (360 to 440 V)
Chilled liquid outlet temperature (water)4.5 to 15 °C
Liquid outlet temperature (glycol)-12 to 15 °C
Air temperature surrounding unit4 to 46 °C
Cooler waterside maximum working pressure10 barg
Compressor typeTwin helical semi-hermetic rotary screw, 2950 rpm (50 Hz)
Capacity control rangeapproximately 30% to 100% per compressor (steps 15, 27, 39, 51, 63, 75, 87, 100 %)

Застосування

  • Cooling of water or glycol solutions for all types of air conditioning installations
  • Heat pump applications (with Heat Pump Sensor Kit, YLCS HA only)

Особливості

  • Microprocessor controls: 40 character LCD display, colour coded 35 button sealed keypad, Imperial or Metric units display
  • Motor current protection: high current trip at 115% FLA (9 s) or above 105% FLA for 30 s; low motor current protection below 15% FLA
  • Motor protector module with thermistors in motor windings (opens above 110°C, re-closes at 75°C); phase rotation relay per power section
  • Panel enclosures designed to IP42, powder painted galvanised steel; IP54 available as option
  • Options include: closed transition star/delta starter, power factor correction to 0.95, flow switch, suction shut-off valves, low temperature evaporator kits, pressure relief serviceable valve kits, sequence controller, printer, mechanical gauge kit, anti-vibration mounts, E-Link gateway (BACnet, MODBUS, LON, N2), BAS interface (4–20 mA, 0–10 Vdc, dry contact; YORK ISN via RS485 PWM)
  • Emergency stop device (QCSD/ESD) removing the 230 Vac supply to the control system

Технічні дані

Parameter Value
Refrigerant R134a
Compressor oil York Grade "L" Oil (York Grade L)
Compressor type Twin helical semi-hermetic rotary twin screw, direct drive, integral oil separator
Compressor motor speed 2950 rpm (50 Hz)
Compressor design working pressure 28 kg/cm²
Compressor immersion heater 300 watt (230 V 1 Ø 50 Hz), temperature activated
Motor starting star/delta open transition (standard) or star/delta closed transition (optional); inrush limited to approximately 33% LRA
Condenser type (SA & HA) Cleanable shell and tube, seamless external finned 19 mm OD copper tubes; removable steel water heads
Condenser design working pressures 10 bar g waterside / 30 bar g refrigerant side (SA & HA)
Evaporator type 2 pass dual circuit shell and tube DX; insulated with flexible closed-cell foam
Evaporator waterside design working pressure 10 bar g
Evaporator refrigerant side design working pressure 20 bar g (models 0350 to 0670 and 1120), 24 bar g (models 0750 to 0980)
Remote condenser system Design Working Pressure (AA) at least 27.6 barg
Remote condenser discharge pressure requirement at least 4.0 bar above suction pressure
Liquid subcooling required on arrival at unit (AA) 4 °C to 10 °C
Panel enclosure ingress protection IP42 standard, IP54 option
Power supply 400 V, 3 Ø, 50 Hz nominal; min 360 V, max 440 V
Voltage-free contact rating 125 VA (max voltage 254 Vac, 28 Vdc)
Control supply load (multi point) 3 A at 400 V; internal fuse class aM 10; max customer fuse 16 A
Fouling factor basis 0.044 m² °C/kW (0.00025 ft²hr°F/Btu)
Recommended chilled water pH between 7 and 8.5
Glycol operation leaving cooler temperatures below 4.5 °C; HA/AA models only
Operating weights (SA-HA) 3420 kg (0350) … 6610 kg (1120)
Operating weights (AA) 3090 kg (0350) … 5710 kg (1120)
Dimensions length × height 3225 × 2100 mm (0350) to 4000 × 2145 mm (1120)
Sound power level SWL 93 dB(A) (0350–0480), 95 dB(A) (0530–0750), 101 dB(A) (0860–1120)
Warranty period eighteen months from delivery
Storage temperature limits not below 4 °C nor above 46 °C
Lifting lug set part number 026L00261-000
Anti-vibration mount kit kit 362L18081 (models 0350 to 0670); kit 362L18733 (models 0750 to 1120); 25 mm deflection spring mounts
Flow switch 1 inch BSP thread, suitable for 10 barg DWP, gold contacts
Electrical data highlights
Parameter Value
Nominal running amps, unit, SA model 1120 @ 380 V 379 A (without PFC) / 351 A (with PFC)
Nominal running amps, unit, HA/AA model 1120 @ 380 V 460 A (without PFC) / 426 A (with PFC)
System power per compressor (e.g. YTS M-A-H, economised) 108 kW nominal / 120 kW max running power (SA); 130 kW nominal / 210 kW max (HA/AA)
Locked rotor conditions, YTS M-A-H (Star for Star/Delta table): Star AMPS 467 A (380 V) / 492 A (400 V)
Locked rotor conditions, YTS M-A-H (Star for Star/Delta table): Star/Delta AMPS 1400 A (380 V) / 1475 A (400 V)
Standard non-fused disconnect switch rating (SA) Ie 500 A, M10 lug (YLCS 0350–0980); Ie 630 A, M12 (YLCS 1120)
Max IEC 269-2-1 gG fuse (SA, standard) 125–355 A depending on model/system
Conditional short-circuit current of fused disconnect switch 50 kA
Circuit breaker short-circuit trip 4× In within 60 ms
Physical data examples
Model Compressors (circ. 1 / circ. 2) Evaporator type Condenser type Victaulic evaporator conn.
0350 YTS FAD / YTS FAD DED315 CDEW240 (×2) 5"
0480 YTS HAE / YTS HAE DED535 CDEW300 (×2) 6"
0620 YTS JAG / YTS IAF DED585 CDEW450 (×2) 6"
0750 YTS JAF / YTS JAF DED715 CDEW550 (×2) 8"
0980 YTS MAH / YTS LAG M200 CDEW550X (×2) 10"
1120 YTS MAH / YTS MAH M240 CDEW550X (×2) 10"

Варіанти замовлення

Nomenclature example: YLCS0350SA50YAA — base product (Y: York, L: Liquid, C: Chiller, S: Screw); unit designator (S: Standard Unit, H: High Condensing Temperature, A: Remote Condenser); refrigerant (A: R-134a); voltage/starter (5 0: 380-415 / 3 / 50, Y: Star Delta); design series (A: Design Series A).

Power connection variants:

  • Single Point – System Fused Disconnect Switches (standard)
  • Single Point – System Circuit Breakers (option; input terminal block, not available on YLCS0955, 1050, 110 HA & AA)
  • Multi Point – System Circuit Breakers (option)

Other options as listed under Special features.

Допуски та стандарти

  • ISO 9001 accredited design and manufacturing organisation
  • Machinery Directive (2006/42/EC)
  • EMC Directive (2004/108/EC)
  • Safety Code for Mechanical Refrigeration EN378-2 (2008)
  • Pressure Equipment Directive 97/23/EC, CE marking
  • NES713 Issue 3 (1991): thermal/acoustic materials toxicity index <10, non-hazardous, non-toxic
  • BS 476 pt 7 Class 1 flammability rating (thermal/acoustic materials)
  • Optional ISO EN1092-1 type 01.A welded flanges; EN1092-1 Type 01.A welded/companion flange kits
  • Relief pipework sizing reference: EN13136
  • Overcurrent protection per EN 60204; contactor co-ordination TYPE 1 to EN 60947-1:1992; fuses to IEC 269-2-1 gG
  • Sound pressure values to ISO 3744; sound data per EN 292-1991

Текст документа

                      YLCS - SA, HA & AA MODELS

INSTALLATION, OPERATION & MAINTENANCE   Revision 5   035L02630-100 (0410)




               WATER COOLED LIQUID CHILLER AND
                 REMOTE AIR COOLED CHILLER




                                                                    R134a
                                                                                 035L02630-100 Rev.5 (0410)




                                          Contents


1    SUPPLIER INFORMATION                    5   4   INSTALLATION                                        22

     1.1   Introduction                      5       4.1   Location Requirements                        22

     1.2   Warranty                          5       4.2   Installation of Vibration Isolators          22

     1.3   Safety                            5       4.3   Pipework Connection                          22

     1.4   Responsibility for Safety         5       4.4   Water Treatment                               23

     1.5   About this Manual                 6       4.5   Pipework Arrangement                         24

     1.6   Misuse of Equipment               6       4.6   Connection Types & Sizes                      24

     1.7   Emergency Shutdown                7       4.7   Refrigerant Relief Valve Piping              24

     1.8   Safety Labels                     7       4.8   Condenser Cooling Liquid Systems             25

     1.9   Material Safety Data              8       4.9   Remote Refrigerant Condenser Systems         25

2    PRODUCT DESCRIPTION                    11       4.10 Electrical Connection                         26

     2.1   Introduction                     11       4.11 Power Wiring                                   27

     2.2   Compressor                       11       4.12 Output Signals                                 28

     2.3   Refrigerant Circuits             13       4.13 System Inputs                                  28

     2.4   Condenser (SA and HA Models)     13       4.14 Power Supply Connections                      30

     2.5   Cooler                           13       4.15 Connection Diagram                            32

     2.6   Power and Control Panels         13   5   COMMISSIONING                                       33

     2.7   Microprocessor Controls          14       5.1   Preparation                                   33

     2.8   Motor Current Protection         14       5.2   First Time Start-up                           35

     2.9   Keypad Controls                  14   6   UNIT OPERATION                                      36

     2.10 Accessories and Options           15       6.1   General Description                          36

     2.11 Nomenclature                      17       6.2   Start-up                                      36

     2.12 Functional Description            17       6.3   Normal Running and Cycling                   36

3    TRANSPORTATION, HANDLING AND STORAGE   20       6.4   Shutdown                                      36

     3.1   Delivery and Storage             20   7   MAINTENANCE                                        37

     3.2   Inspection                       20       7.1   General Requirements                         37

     3.3   Moving the Unit                  20       7.2   Daily Maintenance                            37

     3.4   Lifting Weights                  21       7.3   Scheduled Maintenance                        37

                                                     7.4   Pressure Vessel In-Service Inspection        38


    GB                                                                                                   3
035L02630-100 Rev.5 (0410)


8   TROUBLE SHOOTING                                   39

    8.1   Competent Persons Trouble Shooting Guide     39

    8.2   Sensor Calibration Charts                    41

9   TECHNICAL DATA                                     42

    9.1   Flow Rate and Pressure Drop Graphs           42

    9.2   Operating Limitations                        44

    9.3   Physical Data                                45

    9.4   Electrical Data - YLCS SA Models             46

    9.5   Electrical Data - YLCS HA & AA Models        50

    9.6   Sound Data                                   53

    9.7   Clearances                                   54

    9.8   Dimensions                                   55

    9.9   Weight Distribution and Isolator Positions   61

    9.10 Process and Instrumentation Diagram
         (Models 0350SA/HA/AA to 0620SA/HA/AA)         63

    9.11 Process and Instrumentation Diagram
         (Models 0670SA/HA/AA to 1120SA/HA/AA)         64

    9.12 Component Layout
         (Models 0350SA/HA/AA to 0980SA/HA/AA)         65

    9.13 Component Layout (Models 1120SA/HA/AA)        65

10 SPARE PARTS                                         66

    10.1 Recommended Spares                            66

    10.2 Recommended Compressor Oils                   66

    10.3 Associated Drawings                           67

11 DECOMMISSIONING. DISMANTLING
   AND DISPOSAL                                        68

    11.1 General                                       68




4                                                           GB
                                                                                         035L02630-100 Rev.5 (0410)


1 SUPPLIER INFORMATION
1.1 Introduction                                             For warranty purposes, the following conditions must
                                                             be satisfied:
York YLCS chillers are manufactured to the highest
design and construction standards to ensure high             The initial start of the unit must be carried out by trained
performance, reliability and adaptability to all types of    personnel from an Authorised York Service Centre.
air conditioning installations.
                                                             Only genuine York approved spare parts, oils and
The units are intended for cooling water or glycol           refrigerants must be used.
solutions and are not suitable for purposes other than
those specified in this manual.                              All the scheduled maintenance operations detailed in
                                                             this manual must be performed at the specified times
This manual and the Microprocessor Based Control             by suitably trained and qualified personnel.
System Operating Instructions contain all the information
required for correct installation and commissioning          Failure to satisfy any of these conditions will automatically
of the unit, together with operating and maintenance         void the warranty.
instructions. The manuals should be read thoroughly
before attempting to operate or service the unit.            1.3 Safety
All procedures detailed in the manuals, including            Standards for Safety
installation, commissioning and maintenance tasks
must only be performed by suitably trained and qualified     YLCS chillers are designed and built within an EN
personnel.                                                   ISO 9001 accredited design and manufacturing
                                                             organisation and, within the limits specified in this
The manufacturer will not be liable for any injury or        manual, are in conformity with the essential health and
damage caused by incorrect installation, commissioning,      safety requirements of the following European Union
operation or maintenance resulting from a failure to         Directives:
follow the procedures and instructions detailed in the
manuals.                                                     Machinery Directive (2006/42/EC)

1.2 Warranty                                                 EMC Directive (2004/108/EC)

Johnson Controls warrants all equipment and materials        Safety Code for Mechanical Refrigeration
against defects in workmanship and materials for             (EN378-2 (2008))
eighteen months from delivery unless extended warranty
has been agreed as part of the contract.                     Refrigeration equipment built at Johnson Controls
                                                             Nantes conforms to the applicable and essential safety
The warranty is limited to free replacement and shipping     requirements of Pressure Equipment Directive 97/23/EC
of any faulty part, or sub-assembly which has failed due     and bear CE marking.
to poor quality or manufacturing errors. All claims must
be supported by evidence that the failure has occurred       1.4 Responsibility for Safety
within the warranty period, and that the unit has been
operated within the designed parameters specified.           Every care has been taken in the design and manufacture
                                                             of the units to ensure that they meet the safety
All warranty claims must specify the unit model, serial      requirements listed in the previous paragraph. However,
number and order number. These details are printed on        the individual operating or working on any machinery is
the unit identification plate, fitted on the outer edge of   primarily responsible for:
the options panel.
                                                             Personal safety, safety of other personnel, and the
The unit warranty will be void if any modification to the    machinery.
unit is carried out without prior written approval from
Johnson Controls.                                            Correct utilisation of the machinery in accordance with
                                                             the procedures detailed in the manuals.




 GB                                                                                                                     5
035L02630-100 Rev.5 (0410)


1.5 About this Manual                                           Mechanical Strength

The following symbols are used in this document to alert        The unit is not designed to withstand loads or stresses
the reader to areas of potential hazard.                        from adjacent equipment, pipework or structures.
                                                                Additional components must not be mounted on the unit.
           A Warning is given in this document to               Any such extraneous loads may cause structural failure
           identify a hazard which could lead to                and may result in injury to the operator, or damage to
           personal injury. Usually an instruction will         the equipment.
WARNING    be given, together with a brief explanation
           and the possible result of ignoring the              General Access
           instruction.
                                                                There are a number of areas and features which may
           A Caution identifies a hazard which could lead       be a hazard and potentially cause injury when working
           to damage to the machine, damage to other            with the unit unless suitable safety precautions are taken.
           equipment and/or environmental pollution.            It is important to ensure access to the unit is restricted
 CAUTION   Usually an instruction will be given, together       to suitably qualified persons who are familiar with the
           with a brief explanation and the possible result     potential hazards and precautions necessary for safe
           of ignoring the instruction.                         operation and maintenance of equipment containing
                                                                high temperatures, pressures and voltages.
           A Note is used to highlight additional information
           which may be helpful to you but where there          Pressure Systems
           are no special safety implications.
    NOTE                                                        The unit contains refrigerant vapour and liquid under
                                                                pressure, release of which can be a danger and cause
                                                                injury. The user should ensure that care is taken during
The contents of this manual include suggested best
                                                                installation, operation and maintenance to avoid damage
working practices and procedures. These are issued
                                                                to the pressure system. No attempt should be made
for guidance only, they do not take precedence over
                                                                to gain access to the component parts of the pressure
the above stated individual responsibility and/or local
                                                                system other than by suitably trained and qualified
safety regulations.
                                                                personnel.
This manual and any other document supplied with the
                                                                Electrical
unit, are the property of YORK which reserves all rights.
They may not be reproduced, in whole or in part, without
                                                                The unit must be earthed. No installation or maintenance
prior written authorisation from an Authorised YORK
                                                                work should be attempted on electrical equipment
representative.
                                                                without first switching off, isolating and locking-off the
                                                                power supplies. Work on live equipment must only be
1.6 Misuse of Equipment                                         carried-out by suitably trained and qualified personnel.
                                                                No attempt should be made to gain access to inside of
Suitability for Application                                     the control panel, wiring or other electrical enclosures
                                                                during normal operation of the unit.
The unit is intended for cooling water or glycol solutions
and is not suitable for purposes other than those               Refrigerants and Oils
specified in these instructions. Any use of the equipment
other than its intended use, or operation of the equipment      Refrigerants and oils used in the unit are generally
contrary to the relevant procedures may result in injury        non-toxic, non-flammable and non-corrosive, and pose
to the operator, or damage to the equipment.                    no special safety hazards. Use of gloves and safety
                                                                glasses are, however, recommended when working on
The unit must not be operated outside the design limits         the unit. Build up of refrigerant vapour, from a leak for
specified in this manual.                                       example, does pose a risk of asphyxiation in confined or
                                                                enclosed spaces and attention should be given to good
Structural Support                                              ventilation. For more comprehensive information on
                                                                safety precautions for use of refrigerants and oils, refer
Structural support of the unit must be provided as              to the Materials Safety Data tables provided.
indicated in these instructions. Failure to provide proper
support may result in injury to the operator, or damage
to the equipment.




6                                                                                                                    GB
                                                                                    035L02630-100 Rev.5 (0410)


High Temperature and Pressure Cleaning                     1.8 Safety Labels

High temperature and pressure cleaning methods (e.g.       The following labels are fixed to each unit to give
steam cleaning) should not be used on any part of the      instruction, or to indicate potential hazards which may
pressure system as this may cause operation of the         exist.
pressure relief device(s). Detergents and solvents which
may cause corrosion should also be avoided.                             White symbol on blue background
                                                                        For safe operation, read the Instructions
1.7 Emergency Shutdown                                                  first

In case of emergency the common input section of the
control panel is fitted with an emergency stop device                   Black symbol on yellow background
(QCSD/ESD), this can be identified as red in colour and                 Warning: This machine may start
sited on a yellow back plate. When operated, it removes                 automatically without prior warning
the 230 Vac supply to the control system. The device can
be locked in the 0 (OFF) position using a padlock.
                                                                        Black symbol on yellow background
                                                                        Warning: Hot surface




                                                                        Black symbol on yellow background
                                                                        Warning: Safety relief valve may discharge
                                                                        gas or liquid without prior warning


                                                                        Black symbol on yellow background
                                                                        Warning: Isolate all electrical sources of
                                                                        supply before opening or removing the
                                                                        cover, as lethal voltages may exist

                                                                        Black symbol on yellow background
                                                                        General attention symbol




 GB                                                                                                             7
035L02630-100 Rev.5 (0410)


1.9 Material Safety Data

Refrigerant Data:
Safety Data              R134a
Toxicity                 Low.
In contact with skin     Liquid splashes or spray may cause freeze burns. Unlikely to be hazardous by skin absorption.
                         Thaw affected areas with water. Remove contaminated clothing carefully — may adhere to skin in
                         case of freeze burns. Wash affected areas with plenty of warm water. If symptoms occur (irritation
                         or blistering) obtain medical attention.
In contact with eyes     Vapour has no effect. Liquid splashes or spray may cause freeze burns. Immediately irrigate with
                         eyewash solution or clean water for at least 10 minutes. Obtain immediate medical attention.
Ingested                 Highly unlikely to occur — but should this occur freeze burn will occur. Do not induce vomiting.
                         Provided patient is conscious, wash mouth with water and give about 250 ml (0.5 pint) to drink.
                         Obtain immediate medical attention.
Inhalation               High atmospheric concentrations may have an anaesthetic effect, including loss of
                         consciousness.
                         Very high exposures may cause an abnormal heart rhythm and prove suddenly fatal.
                         At higher concentration there is a danger from asphyxiation due to reduced oxygen content of
                         atmosphere. Remove patient to fresh air, keep warm and at rest. Administer oxygen if necessary.
                         Apply artificial respiration if breathing has ceased or shows signs of failing. In event of cardiac
                         arrest apply external cardiac massage. Obtain immediate medical attention.
Further medical advice Symptomatic and supportive therapy is indicated. Cardiac sensitisation has been described
                       which may, in the presence of circulating catecholamines such as adrenalin, give rise to cardiac
                       arrhythmia’s and subsequent arrest following exposure to high concentrations.
Long term exposure       A lifetime inhalation study in rats has shown that exposure to 50,000 ppm resulted in benign
                         tumours of the testis. This is not considered to be of relevance to humans exposed to
                         concentrations at or below the occupational exposure limit.
Occupational             Recommended limit: 1000 ppm v/v - 8 hr TWA.
exposure limits
Stability                Not specified.
Conditions to avoid      Use in presence of naked flames, red hot surfaces and high moisture levels.
Hazardous reactions      May react violently with sodium, potassium, barium and other alkali and alkaline earth metals.
                         Incompatible materials: Magnesium and alloys containing more then 2% magnesium.
Hazardous                Halogen acids by thermal decomposition and hydrolysis.
decomposition
products
General precautions      Avoid inhalation of high concentrations of vapours. Atmospheric concentrations should be
                         minimised and kept as low as reasonably practicable below the occupational exposure limit. The
                         vapour is heavier than air and collects at low level and in confined areas. Ventilate by extraction
                         at lowest levels.
Respiratory protection   Where doubt exists on atmospheric concentration, HSE approved breathing apparatus should be
                         worn. This should be self contained or of the long breather type.
Storage                  Keep containers dry and in a cool place away from fire risk, direct sunlight, and all sources of
                         heat such as radiators. Keep at temperatures not exceeding 45 °C.
Protective clothing      Wear overalls, impervious gloves and goggles/face protection.




8                                                                                                                           GB
                                                                                                  035L02630-100 Rev.5 (0410)



Spill/leak procedure       Ensure suitable personal protective clothing and respiratory protection is worn. Provided it is
                           safe to do so, isolate the source of the leak. Allow small spillage’s to evaporate provided there is
                           suitable ventilation.
                           Large spillage’s: Ventilate area. Contain spillage’s with sand, earth or any suitable absorbent
                           material. Prevent liquid from entering drains, sewers, basements and work pits since vapour may
                           create a suffocating atmosphere.
Disposal                   Best to recover and recycle. If this is not possible, destruction is to be in an approved facility
                           which is equipped to absorb and neutralise acids and other toxic processing products.
Fire extinguishing data Non-flammable at atmospheric conditions.
Containers                 Fire exposed containers should be kept cool with water sprays. Containers may burst if
                           overheated.
Fire fighting protective   Self contained breathing apparatus and protective clothing must be worn in fire conditions.
equipment




Refrigerant Oil Data
Safety Data                York "L" Oil
Classification             Non-hazardous
In contact with skin       Minimally irritating. No first aid necessary. Exercise reasonable personal cleanliness including
                           cleansing exposed skin areas several times daily with soap and water. Launder soiled work
                           clothes at least weekly.
In contact with eyes       Flush eyes with eyewash solution or clean water for 15 minutes and consult a physician.
Ingested                   May cause nausea and diahorrhea. Obtain immediate medical attention.
Inhalation                 If oil mist is inhaled, remove to fresh air and consult a physician.
Occupational               Not determined.
exposure limits
Stability                  Stable but hygroscopic - store in sealed containers.
Conditions to avoid        Strong oxidisers, caustic or acid solutions, excessive heat. May degrade some paints and rubber
                           materials.
Hazardous                  Not fully, Analogous compounds evolve carbon monoxide, carbon dioxide and other unidentified
decomposition              fragments when burned. Burning may evolve irritating/noxious fumes.
Respiratory protection     Use in well ventilated areas - ventilate locally.
Protective clothing        Goggles or face shield should be worn. Gloves not necessary, but recommended, especially for
                           prolonged exposure.
Spill / Leak procedure     Wear suitable protective equipment. Especially goggles. Stop source of spill. Use absorbent
                           materials to soak up fluid (i.e. sand, sawdust and commercially available materials).
Disposal                   Incinerate the oil and all associated wastes in an approved facility in accordance with local laws
                           and regulations governing oily wastes.
Fire extinguishing data Flash point over 300°C. Use dry chemical, carbon dioxide or foam. Spraying water on hot or
                        burning liquid may cause frothing or splashing.
                           If a leak or spill has not ignited use water spray to disperse the vapours and to provided
                           protection for persons attempting to stop the leak.
Containers                 Fire exposed containers should be kept cool with water sprays.
Fire fighting protective   Self contained breathing apparatus should be worn in fire conditions.
equipment




GB                                                                                                                                9
035L02630-100 Rev.5 (0410)



Thermal & Acoustic Materials Data
Health Hazard & First Aid    Toxicity Index <10 to NES713 Issue 3 (1991): Non-hazardous, non-toxic. No first aid
                             necessary.
Stability / Reactivity       Stable.
Handling / Use / Disposal    No special handling precautions required. Dispose of according to local laws and
                             regulations governing non-biodegradable non-hazardous solid wastes.
Fire & Explosion             Flammability rating Class 1 to BS 476 pt 7: Non-flammable. If forced to burn,
                             combustion products are typically over 95% carbon dioxide and carbon monoxide.




10                                                                                                                 GB
                                                                                             035L02630-100 Rev.5 (0410)


                                                                                        5

                                       5                                                          6
                                6                                                                         4
                                                                                                               3
                    4                                                                                                  7

           7
  3




                                                         1
                                                               1




                                                                           2
                                           2


  1                           1 Compressor                               5 Common Input Section                    1
                              2 Condenser                                6 Power Section - System 2
                              3 Cooler                                   7 Control section
                              4 Power Section - System 1

2 PRODUCT DESCRIPTION
2.1 Introduction                                                   2.2 Compressor

York YLCS chillers are designed for water or water-                Twin helical semi-hermetic screw compressors, are
glycol cooling. Models are available in three versions:            provided to ensure high operational efficiencies and
standard units (SA), units for applications requiring high         reliable performance. A microprocessor controlled output
condensing temperatures (HA) and units for applications            pressure regulating capacity control valve commands
where remote condensers are necessary (AA).                        compressor capacity independent of control valve input
                                                                   pressure and balances the compressor capacity with the
All models are designed for indoor installation. The               cooling load. The compressor is a positive displacement
units are completely assembled with all interconnecting            type characterised by two helically grooved rotors which
refrigerant piping and internal wiring, ready for field            are manufactured from forged steel. The 50 Hz motor
installation.                                                      operates at 2950 rpm to direct drive the male rotor which
                                                                   in turn drives the female rotor on a light film of oil.
The unit consists of 2 screw compressors with integral
oil separators in separate refrigerant circuits, each with a       Each compressor is direct drive, semi-hermetic, rotary
single circuit water cooled condenser (SA & HA models),            twin screw type with integral oil separator and includes
and a dual circuit shell and tube DX evaporator.                   the following items:

Before delivery, the SA & HA unit is pressure tested,              Two screw rotors, with asymmetric profiles, manufactured
evacuated, and fully charged with refrigerant and oil              from forged steel.
in each of the independent refrigerant circuits. After
assembly, an operational test is performed with water              A cast iron compressor housing precision machined to
flowing through the cooler to ensure that each refrigerant         provide optimal clearance for the rotors.
circuit operates correctly. For AA units, the unit shall
be pressure tested, evacuated, and filled with 0.35 bar            An integral discharge check valve to prevent rotor
g pressure of nitrogen per independant circuit. After              backspin during shutdown.
assembly, a simulated functional test is performed on
the unit.                                                          Discharge shut-off service valves.

The unit framework is fabricated using heavy-gauge                 A reliable suction gas cooled high efficiency, accessible
galvanised steel which is zinc phosphate pre-treated               hermetic motor with overload protection using both
and powder coated to minimise corrosion.                           thermistor and over current protection.


 GB                                                                                                                        11
035L02630-100 Rev.5 (0410)


               EVACUATION AND         DISCHARGE
                OIL FILL POINT         GAS OUT


                                                     LIFTING LUGS


                                                                          MOTOR TERMINALS




           OIL SIGHT GLASS


                                                                                                       SUCTION
                                                                                                        GAS IN




A suction gas screen and serviceable, 17 micron full flow       The compressor is lubricated by removing oil from
oil filter within the compressor housing.                       the discharged refrigerant gas within the integral oil
                                                                separator. For HA & AA units liquid injection is provided
Refrigerant gas is injected into the void created by the        into discharge rotor for discharge gas and oil cooling. The
unmeshing of the five lobed male and seven lobed                compressor design working pressure is 28kg/cm².
female rotor. Further meshing of the rotors closes the
rotor threads to the suction port and progressively             A 300 watt (230 V 1 Ø 50 Hz) immersion heater is located
compresses the gas in an axial direction to the discharge       in the compressor. The heater is temperature activated
port. The gas is compressed in volume and increased             to prevent refrigerant condensation.
in pressure before exiting at a designed volume at the
discharge end of the rotor casing. Since the intake and         Motor Starting
discharge cycles overlap, a resulting smooth flow of gas
is maintained.                                                  Two types of compressor motor starting are available:
                                                                star/delta open transition starter and optional star/delta
The rotors are housed in a cast iron compressor housing         closed transition starter.
precision machined to provide optimal clearances for
the rotors. Contact between the male and female rotor           The standard star/delta starter utilises 3 motor contactors
is primarily rolling on a contact band on each of the           and a transition delay relay. The optional closed Star/
rotor’s pitch circle. This results in virtually no rotor wear   Delta starter utilises 4 motor contactors, a set of transition
and increased reliability.                                      resistors and a transition delay relay. The star/delta start
                                                                allows inrush current to be limited to approximately
The compressor incorporates a complete anti-friction            33% LRA with the closed transition option reducing the
bearing design for reduced power input and increased            transient star to delta current.
reliability. Separated, cylindrical, roller bearings handle
radial loads. Angular-contact ball bearings handle axial        When the microprocessor initiates a start signal to run
loads. Together they maintain accurate rotor positioning        a compressor, it runs in Star for 4 seconds and then
at all pressure ratios, thereby minimising leakage and          transitions to Delta.
maintaining efficiency. A spring loaded check valve
is installed on the compressor discharge housing to             Capacity Control
prevent compressor rotor backspin due to system
refrigerant pressure gradients during shutdown.                 The loading control range is approximately 30% to 100%
                                                                per compressor via control steps. The micro controller
Motor cooling is provided by suction gas from the               will adjust compressor loading to balance the cooling
evaporator flowing across the motor.                            load. This will take account of the discharge pressure

12                                                                                                                      GB
                                                                                         035L02630-100 Rev.5 (0410)


and motor current should either approach their limiting       Models 0335 to 0750 have vertical water nozzles
value.                                                        (standard) with victualic couplings (shipped loose) for
                                                              field installation by contractor. Horizontal water nozzles
The automatic spring return of the capacity control valve     with victaulic couplings (shipped loose) are available
to the minimum load position will ensure compressor           as an option.
starting at minimum motor load.
                                                              Models 0860 and 1120 have horizontal water nozzles
2.3 Refrigerant Circuits                                      with victaulic grooves (victaulic couplings to be supplied
                                                              by others).
Each refrigerant circuit uses copper refrigerant pipe
formed on computer controlled bending machines to             Optional ISO EN1092-1 type 01.A welded flanges
reduce the number of brazed joints resulting in a reliable    and companion flanges, complete with nuts, bolts and
and leak resistant system.                                    gaskets are available on all models.

Liquid line components include: a manual shut-off valve       2.6 Power and Control Panels
with charging port, a high absorption removable core
filter-drier, a solenoid valve, a sight glass with moisture   All controls and motor starting equipment are factory
indicator, and a thermostatic expansion valve.                wired and function tested. The panel enclosures are
                                                              designed to IP42 and are manufactured from powder
Suction lines are covered with closed-cell insulation.        painted galvanised steel. Component mounting panels
                                                              are of non-painted galvanised steel to ensure effective
2.4 Condenser (SA and HA Models)                              earthing protection.

The two single refrigerant circuit water-cooled condensers    The panel is divided into power sections for each
are cleanable shell and tube type with seamless external      electrical system, a control section and a common
finned 19mmODcopper tubes rolled into tube sheets.            input section. Power entry is from the top of the control
The design working pressures are 10 bar g on the              panel common input section. Each section has separate
waterside and 30 bar g on the refrigerant side which is       hinged, latched, and gasket sealed doors.
protected by pressure relief valve(s).
                                                              Each power section contains:
The condenser has removable steel water heads. The
water connections have standard female threads (refer         Compressor fuses, compressor contactors, phase
to Section 9 - dimension drawings for details). Optional      rotation relay, compressor motor current transformer
extension or manifold kits are available with victualic       and a control circuit fuse.
couplings or flanges.
                                                              The control section contains:
For AA units water cooled condensers are factory
removed. Remote air-cooled condenser supplied by              On/Off switch, microcomputer keypad and display,
others (field installed).                                     microprocessor board (AMB), power supply board (APB)
                                                              and relay board (ARB).
2.5 Cooler                                                    The common input section contains:
The 2 pass dual circuit shell and tube type direct            An incoming non-fused disconnect switch for connection
expansion (DX) evaporator has chilled liquid circulating      of the customer provided single power supply. Internal
back and forth across the tubes from one end to the           factory wiring to two fused protected power sections. The
other. The waterside (shell) design working pressure          control supply is derived internally. (Refer to «Electrical
of the cooler is 10 bar g. The refrigerant side (tubes)       Connection Options» for details).
design working pressure is 20 bar g on models 0350 to
0670 and 1120 and 24 bar g on models 0750 to 0980.            The common input section also contains the control
The refrigerant side is protected by pressure relief          circuit switch disconnect/emergency stop device, a
valve(s).                                                     transformer (to provide the necessary 24 Vac supply for
                                                              the power supply board), control fuses, residual current
The evaporator shall have water pass baffles fabricated       circuit breaker, and terminals for a remote emergency
from non metalic composite materials (0335 to 0750)           stop device.
and corrosion resistant galvanised steel (0860 to 1120).
Removable heads are provided for access to internally
enhanced, seamless, copper tubes. Water vent and
drain connections are included. The cooler is insulated
with flexible closed-cell foam.

 GB                                                                                                                   13
035L02630-100 Rev.5 (0410)


2.7 Microprocessor Controls                                  motor shuts down. Since the microprocessor is sending
                                                             a run signal to the contactor, it senses the low motor
The microprocessor has the following functions and           current below 15% FLA and shuts the system down.
displays:
                                                             Motor Protector Module
A liquid crystal 40 character display with text provided
on two lines and light emitting diode backlighting for       The motor protector module provides thermal overload
outdoor viewing.                                             protection.

A colour coded, 35 button, sealed keypad with sections       Three thermistors in the motor windings of each phase
for Display, Entry, Setpoints, Clock, Print, Program and     provide thermal protection. If the motor temperature rise
the unit Auto/Off switch.                                    above 110°C the motor protector module contact will
                                                             open. The contact will re-close at 75°C.
The standard functions include: water or glycol cooling,
automatic pump down after shutdown, run signal contact,      Phase Rotation relay (KPR)
demand load limiting from external building automation
system input, remote reset liquid temperature reset          Each power section is fitted with a phase rotating relay
input, unit alarm contacts, chilled liquid pump control,     to monitors the 3 phase voltage. Provided the phase
automatic or manual reset after power failure, automatic     rotation is correct the relay will close its contact in the
system optimisation to match operating conditions.           compressor contactor circuit.

The software is stored in non-volatile memory (EPROM)        2.9 Keypad Controls
to eliminate unit failure due to AC power failure. The
programmed setpoint is stored in a lithium battery           For a detailed description of the keypad controls refer
backed memory.                                               to the Microprocessor Based Control System Operating
                                                             Instructions.
2.8 Motor Current Protection
                                                             Status Key
The microprocessor motor protection provides high
current protection to assure that the motor is not           This key provides a display of the current operational
damaged due to voltage, excess refrigerant, or other         and/or fault status of the unit or the individual refrigerant
problems that could cause excessive motor current.           systems. The display will show the ‘highest priority"
                                                             information as determined by the microprocessor.
If the motor current exceeds the 115% FLA trip point
after 9 seconds of operation, or is above 105% for 30        The main categories of messages are: General Status
seconds, the microprocessor will shut the system down        Messages; Unit Warnings; Anticipation Control Status
and lock it out after three faults occur in 90 minutes. A    Messages; Chiller Fault Status Messages; System Fault
manual reset of the respective system switch is required     Status Messages.
to clear the fault and restart the system after a lockout.
A thorough check of the motor, wiring, and refrigerant       Display Keys
system should be carried out before restarting a system
that has faulted on high motor current.                      Each key provides a real-time display of commonly
                                                             required information about the chiller and individual
The microprocessor also provides low motor current           refrigerant system operating conditions and settings. This
protection when it senses a motor current less than 15%      is particularly useful during commissioning, monitoring
FLA. Low motor current protection is activated 9 seconds     the operation of the chiller, diagnosing potential future
after start. The microprocessor will shut the system down    problems and service troubleshooting. Parameters may
whenever low motor current is sensed and will lock out       be displayed in Imperial (°F and PSIG) or Metric (°C
a system if three faults occur in 90 minutes. Once a         and Bar) units.
system is locked out on Low Motor Current, it must be
manually reset with the system switch.                       Print Keys

The microprocessor also senses low motor current             These keys allow control panel display or remote printout
whenever a High Pressure Cut-out (HPCO) or Motor             of both current real-time operating and programmed data
Protector (MP) or Phase Rotation Relay (KPR) contact         as well as fault history data from the most recent three
opens. The MP, HPCO and KPR contacts are connected           safety shutdowns.
in series with the motor contactor. Whenever any of these
devices are open, the contactor de-energises and the         Printouts are via the RS232 port and a separate
                                                             printer.


14                                                                                                                  GB
                                                                                          035L02630-100 Rev.5 (0410)


Entry Keys                                                    Multi-Point - System Circuit Breakers

The numeric and associated keys are used for entering         Two door interlocked circuit breakers, mounted in
data required for programming the chiller. The ‘ENTER"        the power sections, for connection of the customer
key is also used for scrolling through information            provided power supplies. A non-fused disconnect switch
available after pressing other keys.                          / emergency stop device (QCSD/ESD) in the common
                                                              input section with termination for the customer (400 V,
Setpoints Keys                                                2 Ø, 50 Hz ) control supply.

These keys are used for display and programming of            Building Automation System (BAS) / EMS Interface
the local and remote offset chilled liquid temperature
setpoints.                                                    Provides a means to reset the leaving chilled liquid
                                                              temperature and from the BAS / EMS (Factory
Clock Keys                                                    Mounted):

These keys are used for display and programming of the        Printed circuit board to accept 4 to 20 mA, 0 to 10 Vdc,
clock and operating schedule for the chiller.                 or dry contact closure input from the BAS / EMS.

Temperature Offset                                                        A YORK ISN Building Automation System
                                                                          can provide a Pulse Width Modulated (PWM)
Pulse width modulating (PWM) input is provided to                         signal direct to the standard control panel via
remotely adjust the leaving chilled water temperature              NOTE   the standard on-board RS485 port.
setpoint to a higher value.
                                                              E-Link Gateway
Program Key
                                                              Interface to enable communication with building control
This key is used for display and programming of the           systems using BACnet, MODBUS, LON or N2 protocols.
chiller operational settings and limits.                      See separate York documentation.

2.10 Accessories and Options                                  Anti-Vibration Mounts

Power Supply Connection                                       Optional 25mm deflection, open spring, anti-vibration
                                                              mounts with levelling screw. Supplied loose for field
Units are available with either single point or multi point   installation.
power supply connections:
                                                              Optional floor mounting kit with 25 mm neoprene pads.
Single Point - System Fused Disconnect Switches               Supplied loose for field installation.

A non-fused disconnect switch in the common input             Power Factor Correction:
section of the panel for connection of the customer
provided single power supply. Internal factory wiring to      Factory mounted passive (static) correction capacitors to
two door interlocked fused disconnect switches mounted        correct unit compressor power factors to 0.95 (depending
in the power sections. The control supply is derived          on operating conditions).
internally from the terminal block.
                                                              Flow Switch
Single Point - System Circuit Breakers
(Not available on the YLCS0955, 1050, 110 HA & AA)            Switch with 1 inch BSP thread suitable for 10 barg DWP
                                                              and having gold contacts for low voltage/current, to
A terminal block in the common input section of the panel     protect unit from loss of water flow. Supplied loose for
for connection of the customer provided single power          field installation,
supply. Internal factory wiring to two door interlocked
                                                              or
circuit breakers, mounted in the power sections. The
control supply is derived internally from the terminal        Factory fitted pressure differential switch on cooler.
block.
                                                              Suction Shut-off Valves

                                                              A ball valve in the low pressure (suction) pipework per
                                                              refrigerant circuit for isolation.




 GB                                                                                                                    15
035L02630-100 Rev.5 (0410)


Evaporator Kits                                               Double Thickness Insulation

Models 0350 to 0750, horizontal water nozzles with            The cooler is covered with 38 mm (1 ½ inch) flexible, UV-
victaulic couplings (shipped loose), vertical nozzle cooler   stable colour co-ordinated closed-cell, foam insulation
with EN1092-1 Type 01.A welded/companion flange kit,          to prevent sweating in humid environment.
or horizontal nozzle cooler with EN1092-1 Type 01.A
welded/companion flange kit. Models 0860 to 1120, ISO         Condenser extension / Manifold kits
EN1092-1 Type 01.A welded/companion flange kit for
standard horizontal nozzle cooler (Note: vertical nozzle      Condenser extension kit simplifies connections to
coolers are not available).                                   customer pipework. Both options come with either
                                                              Victaulic coupling or welded Flange/companion flange
Low temperature Evaporator Kits                               kit.

Low temperature evaporator configurations are identical       IP54
to the standard or options detailed above.
                                                              Panel enclosure designed to IP54.
Pressure Relief Valves Options
                                                              Language LCD and Keypad
• Pressure Relief (CE/PED) Serviceable Valve & Dual
  Kit.                                                        Standard display language and keypad is English.
  High & Low side vessels’ dual relief valves fitted with     French, German, Italian, Spanish, Portugese and
  3 way changeover valves and compressors’ single             Hungarian are available as options.
  relief valves fitted with ball valves, to assist valve
  replacement during maintenance without loss of              Sequence Controller:
  refrigerant charge.
                                                              Monitors mixed leaving chilled water or glycol temperature
• Pressure Relief (CE/PED) Serviceable Valve & Dual
                                                              from two to four units and controls to maintain required
  Kit & Burst.
                                                              mixed temperature whilst running the minimum number
  High & Low side vessels’ dual relief valves fitted with
                                                              of units.
  bursting disks and 3 way changeover valves and
  compressors’ single relief valves fitted with bursting
                                                              Printer
  disks and ball valves, to assist valve replacement during
  maintenance without loss of refrigerant charge.
                                                              Hand held printer for obtaining printout of unit operating
                                                              data and history data.
Dual Pressure Switch
                                                              Paint Overspray
Dual HP pressure cut-outs on both circuits.
                                                              Complete unit finish in Carribean Blue.
Heat Pump Sensor Kit:
                                                              Lifting Lug Kit
Capability of controlling condenser water off for heat
pump applications.
                                                              One set of ISO Mk5 cam locks to enable safe and easy
                                                              unit handling.
Closed Transition Star/Delta
                                                              Factory Witness Test:
With the addition of closed transition contactors and
resistors, the change over spike during starting can be
                                                              To perform a customer functional witness test of cooling
reduced to nearer the star inrush level thus reducing the
                                                              capacity only, test is carried out in factory test area.
risk of electrical interference during compressor start.

Mechanical Gauge Kit

Factory fitted mechanical gauges for display of suction
and discharge pressures, one complete set per
system.




16                                                                                                                GB
                                                                                                                                        035L02630-100 Rev.5 (0410)


2.11 Nomenclature



       YLCS0350SA50YAA
  1   2    3    4                    5        6   7    8               9                         10               11 12 13                           14 15
 BASE PRODUCT TYPE                  MODEL NUMBER                      UNIT DESIGNATOR            REFRIGERANT      VOLTAGE / STARTER                  DESIGN / DEVELOPMENT LEVEL


  Y                  : York           #       #   #    #      kW       S   : Standard Unit        A   : R-134a     5    0       : 380-415 / 3 / 50    A        : Design Series A
      L              : Liquid                                          H   : High Condensing                                Y   : Star Delta               A   : Engineering Change
            C        : Chiller      :0350 :0415 :0480 :0530   :0575         Temperature                                                                        or PIN Level
                S    : Screw        :0620 :0660 :0725 :0840   :0955    A   : Remote
                                    :1050 :1110                             Condensor




2.12 Functional Description

YLCS Models 0350 to 0620
                     Evaporator
                     PRV (2)

                                                                                               EVAPORATOR

                                                  TEV
                                                                SV                                                  T
      LLV           S


                                                                                   Condenser PRV (2)
                                                                                                                                                          Not fitted to
                                                                                                                                                          YLCS AA models
                                                                                             CONDENSER




                                                                                                Discharge
                                                                                               PRV (1) (2)


                                                                                          Compressor
                                                                                             PRV (2)
                          PT




      SV                                  s
                                                                                                                 NOTES:
                                                                       COMPRESSOR
                                                                                                                 1 - See Discharge Pressure Relief Valve Table
                                 Liquid Injection
                                                                                                                 2 - See Pressure Relief Valve Options Table
                                     Option
                                                                   Start Bypass Option




 GB                                                                                                                                                                                   17
035L02630-100 Rev.5 (0410)


YLCS Models 0670 to 1120
                  Evaporator
                  PRV (2)

                                                                  EVAPORATOR

                                          TEV
                    ECO