Water-cooled scroll chiller, YORK YCWL (R410A)

Вид документаІнструкція
ВиробникJCI
МоделіYCWL0240SE, YCWL0290SE, YCWL0345SE, YCWL0395SE, YCWL0200HE, YCWL0230HE, YCWL0260HE, YCWL0300HE
Група обладнанняother
Мова документаанглійська
Розмір файлу1.2 МБ

Про документ

Factory-assembled indoor water-cooled liquid chillers for cooling water or glycol solutions in air conditioning installations. Each unit uses two independent refrigerant circuits with suction-cooled hermetic scroll compressors, shell-and-tube evaporator and condenser, factory charged with R410A and oil. Available in Standard Efficiency (SE) and High Efficiency (HE) designators.

Ключові дані

Cooling capacity range188 kW TO 580 kW
RefrigerantR410A
Power supply400V, 3 ~, 50 Hz (nominal), V 360 to 440
Evaporator waterside design working pressure10.3 bar g
Condenser waterside design working pressure10 bar g
Maximum refrigerant side pressurebar 38.6
Liquid outlet temperature (water)°C 4.5 to 15
Ambient air temperaturemin 4.5 °C / max 46 °C

Застосування

  • Cooling water or water-glycol solutions in air conditioning installations
  • Indoor installation in a plant room
  • Non-reversible heat pump option for controlling leaving condenser liquid temperature

Особливості

  • Microprocessor control with automatic start/stop, anti-recycle and anti-coincidence timers, pumpdown on shutdown, automatic reset after power failure
  • Remote chilled liquid setpoint reset via PWM input or EMS analogue input (4 to 20 mA, 0 to 20 mA, 0 to 10 Vdc, 2–10 Vdc)
  • BACnet communications via RS485 port
  • Options: soft starters, power factor correction (target 0.9), acoustic compressor blankets, dual pressure relief valves, Victaulic flange kits, neoprene pad and 25 mm spring isolators
  • LCD/keypad available in English, French, German, Italian, Spanish

Технічні дані

Parameter Value
Refrigerant R410A
Number of refrigerant circuits 2
Compressor type Suction-cooled, hermetic scroll
Compressor quantity 4 (6 on YCWL0385HE, YCWL0445HE, YCWL0530HE, YCWL0610HE)
Evaporator type Shell and tube, direct expansion (DX)
Evaporator waterside design working pressure 10.3 bar g
Evaporator refrigerant side design working pressure 27.58 bar g
Condenser type Shell and tubes, cleanable
Condenser waterside design working pressure 10 bar g
Condenser refrigerant side design working pressure 38.61 bar g
Power supply voltage 400V, 3 ~, 50 Hz (nominal), V 360 to 440
Liquid Outlet Temperature (Water) 4.5 to 15 °C
Liquid Outlet Temperature Range 3 to 8 °C (chilled) / 3 to 10 °C (cooling liquid)
Minimum Ambient Air Temperature 4.5 °C
Maximum Ambient Air Temperature 46 °C
Maximum Refrigerant Side Pressure 38.6 bar
Control panel enclosure IP32 cabinet
Voltage-free contacts rating 125 VA
Remote emergency stop device rating 16 amps, 110 V, AC-15
Recommended fouling factor 0.044 m² °C/kW
Water pH range between 7 and 8.5
Warranty period eighteen months from date of shipment
Physical data (selection)
Parameter Value
Dimensions SE 0240–0395 (L × W × H) e.g. 3192 × 861 × 1750 mm (YCWL0240SE)
Operating weight range (SE) 1895 – 2366 kg
Operating weight range (HE) 1967 – 3492 kg
Evaporator water connections 6" – 8"
Condenser water connections 4" – 5"
Refrigerant charge per circuit (range across models) 27 – 88.5 kg

Варіанти замовлення

Model number nomenclature: Y C W L - XXXX - H/S - E - 50 - X - AA — WATER COOLED SCROLL COMPRESSOR; REFRIGERANT R410A; UNIT DESIGNATOR S = Standard Efficiency, H = High Efficiency; DOL STARTING VOLTAGE CODE 50 = 380/415-3-50.

Допуски та стандарти

  • EN ISO 9002 accredited manufacturing organisation
  • Machinery Directive (98/37/EC)
  • Low Voltage Directive (73/23/EEC, EN 60204)
  • EMC Directive (89/336/EEC)
  • Pressure Equipment Directive (97/23/EC)
  • ANSI/ASHRAE Standard 15
  • ASHRAE 90.1
  • ANSI/NFPA Standard 70 (N.E.C.)
  • ASME Boiler and Pressure Vessel Code, Section VIII Division 1
  • ASHRAE 34
  • ARI Standard 550/590
  • UL code 1995, ETL/cETL listing label
  • OSHA
  • ARI 370

Текст документа

                                             WATER COOLED LIQUID CHILLERS

INSTALLATION, OPERATION & MAINTENANCE   Revision 0              Form 201.26-NM2 (1007)

                                                                  (035-21965-110)




                                        Zafiro
                          WATER COOLED CHILLERS
                         WITH SCROLL COMPRESSORS




                                                                               R410A
STYLE A
COOLING CAPACITIES: 188 kW TO 580 kW
           FORM 201.26-NM2 (1007)



                                      IMPORTANT!
                          Read BEFORE PROCEEDING!
                                    GENERAL SAFETY GUIDELINES

This equipment is a relatively complicated apparatus.            as well as severe personal injury or death to themselves
During installation, operation, maintenance or service,          and people at the site.
individuals may be exposed to certain components or
                                                                 This document is intended for use by owner-authorized
conditions including, but not limited to: refrigerants,
                                                                 operating/service personnel. It is expected that this
oils, materials under pressure, rotating components, and
                                                                 individual possesses independent training that will
lethal voltage. Each of these items has the potential, if
                                                                 enable them to perform their assigned tasks properly
misused or handled improperly, to cause bodily injury
                                                                 and safely. It is essential that, prior to performing any
or death. It is the obligation and responsibility of
                                                                 task on this equipment, this individual shall have read
operating/service personnel to identify and recognize
                                                                 and understood this document and any referenced
these inherent hazards, protect themselves, and proceed
                                                                 materials. This individual shall also be familiar with and
safely in completing their tasks. Failure to comply with
                                                                 comply with all applicable governmental standards and
any of these requirements could result in serious damage
                                                                 regulations pertaining to the task in question.
to the equipment and the property in which it is situated,



                                              SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:


          DANGER indicates an imminently                                  CAUTION identi es a hazard which could
          hazardous situation which, if not avoided,                      lead to damage to the machine, damage
          will result in death or serious injury.                         to other equipment and/or environmental
DANGER                                                                    pollution. Usually an instruction will be
                                                                          given, together with a brief explanation.




          WARNING indicates a potentially hazardous                       NOTE is used to highlight ad di tion al
          situation which, if not avoided, could result                   information which may be helpful to you.
          in death or serious injury.




          External wiring, unless speci ed as an optional connection in the manufacturer’s product line, is
          not to be connected inside the micro panel cabinet. Devices such as relays, switches, transducers
          and controls may not be installed inside the panel. No external wiring is allowed to be run through
          the micro panel. All wiring must be in accordance with Johnson Controls published speci cations
          and must be performed only by quali ed Johnson Controls personnel. Johnson Controls will not
          be responsible for damages/problems resulting from improper connections to the controls or
          application of improper control signals. Failure to follow this will void the manufacturer’s warranty
          and cause serious damage to property or injury to persons.




                                                             2                                          035-21965-110 Rev. 0
                                                                                 FORM 201.26-NM2 (1007)


                               CHANGEABILITY OF THIS DOCUMENT

In complying with Johnson Controls policy for continuous product improvement, the information contained in this
document is subject to change without notice. While Johnson Controls makes no commitment to update or provide
current information automatically to the manual owner, that information, if applicable, can be obtained by contacting
the nearest Johnson Controls Service Centre.
It is the responsibility of operating/service personnel to verify the applicability of these documents to the equipment in
question. If there is any question in the mind of operating/service personnel as to the applicability of these documents,
then prior to working on the equipment, they should verify with the owner whether the equipment has been modified
and if current literature is available.




035-21965-110 Rev. 0                                        3
              FORM 201.26-NM2 (1007)


                                                            TABLE OF CONTENTS

GENERAL SAFETY GUIDELINES ....................... 2                                    Suction Service Valves....................................... 18
SAFETY SYMBOLS ................................................ 2                      Victaulic Flange Kit ........................................... 18
CHANGEABILITY OF THIS DOCUMENT .......... 3                                            Compressor Acoustic Blankets .......................... 18
TABLE OF CONTENTS .......................................... 4                         Final overspray .................................................. 18
                                                                                       Flow switch ........................................................ 18
1 GENERAL CHILLER INFORMATION &                                                        Differential Pressure Switch .............................. 18
  SAFETY                                                                               Neoprene Pad Isolators ...................................... 18
                                                                                       25 mm Spring Isolators ...................................... 18
   INTRODUCTION ............................................... 6                      UNIT MODEL NUMBER NOMENCLATURE
   WARRANTY ....................................................... 6                  NOMENCLATURE ........................................... 20
   SAFETY .............................................................. 6
   Standards for Safety ............................................. 6              3 HANDLING AND STORAGE
   FLUORINATED GREENHOUSE GASES ........ 7
   RESPONSIBILITY FOR SAFETY..................... 7                                    DELIVERY AND STORAGE ........................... 21
   ABOUT THIS MANUAL ................................... 7                             INSPECTION .................................................... 21
   MISUSE OF EQUIPMENT................................. 8                              MOVING THE CHILLER ................................ 21
   Suitability for Application ................................... 8                   Lifting by Crane/Hoist ....................................... 21
   Structural Support ................................................ 8               Lifting by Fork lift ............................................. 21
   Mechanical Strength ........................................... 8                   LIFTING WEIGHTS ......................................... 21
   General Access..................................................... 8
   Pressure Systems ................................................. 8              4 INSTALLATION
   Electrical .............................................................. 8
   Refrigerants and Oils ........................................... 8                 Location Requirements ...................................... 23
   High Temperature and Pressure Cleaning............ 8                                Installation of Vibration Isolators ...................... 23
   Emergency Shutdown .......................................... 8                     Pipework Connection......................................... 23
   Safety Labels........................................................ 9             Water Treatment ................................................. 24
   MATERIAL SAFETY DATA ............................ 10                                Chilled Liquid System ....................................... 24
                                                                                       Connection Types & Sizes ................................. 25
2 PRODUCT DESCRIPTION                                                                  Refrigerant Relief Valve Piping ......................... 25
                                                                                       Condenser Cooling Liquid Systems .................. 26
   Introduction........................................................ 15             Inlet Temperature Control (by others) ............... 26
   Compressors ...................................................... 15               ELECTRICAL CONNECTION ........................ 27
   Refrigerant Circuits ........................................... 16                 Power Wiring ..................................................... 27
   Evaporator.......................................................... 16             Single Point Power Supply Wiring .................... 27
   Condenser .......................................................... 16             Remote Emergency Stop Device ....................... 27
   Power and Control Panels .................................. 16                      Control Wiring - Voltage Free Contacts............. 27
   OPTIONS AND ACCESSORIES                                                             Chilled Liquid Pump Starter .............................. 27
   Alarm Contacts: ................................................ 17                 Run Contacts ...................................................... 28
   Soft Starters ....................................................... 18            Alarm Contacts .................................................. 28
   Power Factor Correction .................................... 18                     Control Wiring - System Inputs ......................... 28
   Language LCD and Keypad .............................. 18                           Flow Switch ....................................................... 28
   Non-reversible Heat Pump................................. 18                        Remote Start/Stop .............................................. 28
   38 mm Evaporator Insulation ............................ 18                         Remote Reset of Chilled Liquid Setpoint .......... 28
   Pressure Relief (CE/PED) Service Valve Kit .... 18                                  Remote Load Limiting ....................................... 28
   Dual Pressure Relief Valves ............................... 18                      Heat Pump Kit ................................................... 28
                                                                                       EMS Analogue Input ......................................... 28
                                                                                       BACnet ............................................................. 28
                                                                                       CONNECTION DIAGRAM ............................. 29




                                                                                 4                                                    035-21965-110 Rev. 0
                                                                                                     FORM 201.26-NM2 (1007)




5 COMMISSIONING                                                                  10 SPARE PARTS

   PREPARATION................................................. 31                 RECOMMENDED SPARES ............................. 57
   Preparation - Power Off ..................................... 31                RECOMMENDED COMPRESSOR OIL ......... 57
   Soft Start (Option) ............................................. 32            ASSOCIATED DRAWINGS ............................. 57
   FIRST TIME START-UP ................................... 33
                                                                                 11 DECOMMISSIONING. DISMANTLING AND
6 TECHNICAL DATA                                                                    DISPOSAL 55

   EVAPORATOR WATER PRESSURE DROP .......                                          GENERAL ......................................................... 59
   OPERATING LIMITATIONS ........................... 36
   PHYSICAL DATA............................................. 37
   ELECTRICAL DATA - YCWL/SE MODELS .. 38
   COMPRESSOR DATA...................................... 38
   ELECTRICAL DATA - YCWL/HE MODELS . 39
   COMPRESSOR DATA...................................... 39
   DIMENSIONS - YCWL0240SE, YCWL0290SE,
   YCWL0345SE, YCWL0395SE,YCWL0200HE,
   YCWL0230HE, YCWL0260HE, YCWL0300HE,
   YCWL0345HE YCWL0425HE ........................ 40
   DIMENSIONS - YCWL0385HE, YCWL0445HE,
   YCWL0530HE AND YCWL0610HE ............... 42
   WEIGHT DISTRIBUTION & VIBRATION
   ISOLATOR DATA ............................................. 44

7 UNIT OPERATION

   GENERAL DESCRIPTION .............................. 49
   START-UP ......................................................... 49
   NORMAL RUNNING AND CYCLING........... 49
   SHUTDOWN .................................................... 49

8 MAINTENANCE

   GENERAL REQUIREMENTS ......................... 51
   DAILY MAINTENANCE ................................. 51
   SCHEDULED MAINTENANCE ..................... 51
   Evaporator/Condenser In-Service Inspection .... 52

9 TROUBLE SHOOTING

   COMPETENT PERSONS TROUBLE SHOOT-
   ING GUIDE ....................................................... 53
   SENSOR CALIBRATION CHARTS ................ 55
   Leaving Liquid Temperature (-BLLT) ............... 55
   Discharge Pressure (-BDP) and Suction (-BSP)
   Transducers ........................................................ 55




035-21965-110 Rev. 0                                                         5
           FORM 201.26-NM2 (1007)


                        GENERAL CHILLER INFORMATION & SAFETY

INTRODUCTION                                                      For warranty purposes, the following conditions must
                                                                  be satisfied:
YORK YCWL chillers are manufactured to the highest
design and construction standards to ensure high                  • The initial start of the unit must be carried out by
performance, reliability and adaptability to all types of           trained personnel from an Authorized Johnson Controls
air conditioning installations.                                     Service Centre. See Section 5, Commissioning.
The unit is intended for cooling water or glycol solutions        • Only genuine Johnson Controls approved spare
and is not suitable for purposes other than those specified         parts, oils, coolants, and refrigerants must be used.
in this manual.                                                     Recommendations on spare parts stocking can be
                                                                    found in Section 7, Maintenance.
This manual contains all the information required for
correct installation and commissioning of the unit,               • All the scheduled maintenance operations detailed
together with operating and maintenance instructions.               in this manual must be performed at the specified
The manuals should be read thoroughly before                        times by suitably trained and qualified personnel. See
attempting to operate or service the unit.                          Section 7, Maintenance,
All procedures detailed in the manuals, including                 Failure to satisfy any of these conditions will
installation, commissioning and maintenance tasks must            automatically void the warranty. See Warranty Policy
only be performed by suitably trained and qualified               (Section 7, Maintenance).
personnel.
                                                                  SAFETY
The manufacturer will not be liable for any injury or
                                                                  Standards for Safety
damage caused by incorrect installation, commissioning,
operation or maintenance resulting from a failure to              YCWL chillers are designed and built within an
follow the procedures and instructions detailed in the            EN ISO 9002 accredited manufacturing organisation.
manuals.
                                                                  Chillers conform with the following European
WARRANTY                                                          Directives:
Johnson Controls warrants all equipment and materials             • Machinery Directive (98/37/EC)
against defects in workmanship and materials for a
period of eighteen months from date of shipment, unless           • Low Voltage Directive (73/23/EEC, EN 60204)
labor or extended warranty has been purchased as part             • EMC Directive (89/336/EEC)
of the contract.
                                                                  • Pressure Equipment Directive (97/23/EC)
The warranty is limited to parts only replacement and
shipping of any faulty part, or sub-assembly, which has           Or conversely comply with the applicable sections of
failed due to poor quality or manufacturing errors. All           the following Standards and Codes:
claims must be supported by evidence that the failure             • ANSI/ASHRAE Standard 15 - Safety Code for
has occurred within the warranty period, and that the               Mechanical Refrigeration.
unit has been operated within the designed parameters
specified.                                                        • ASHRAE 90.1 - Energy Efficiency Compliance.

All warranty claims must specify the unit model, serial           • ANSI/NFPA Standard 70 - National Electrical Code
number, order number and run hours/starts. Model                    (N.E.C.).
and serial number information is printed on the unit              • ASME Boiler and Pressure Vessel Code, Section VIII
identification plate.                                               Division 1.
The unit warranty will be void if any modification to the         • ASHRAE 34 - Number Designation and Safety
unit is carried out without prior written approval from             Classification of Refrigerants.
Johnson Controls.
                                                                  •




                                                              6                                        035-21965-110 Rev. 0
                                                                                 FORM 201.26-NM2 (1007)

• ARI Standard 550/590 - Positive Displacement                  ABOUT THIS MANUAL
  Compressors and Water Cooled Rotary Sdrew Water
  Chilling Packages.
                                                                The following terms are used in this document to alert     1
                                                                the reader to areas of potential hazard.
• Conform to UL code 1995 for construction of chillers
                                                                         A WARNING is given in this document to
  and provide ETL/cETL listing label.                                    identify a hazard, which could lead to
• OSHA - Occupied Safety and Health Act.                                 personal injury. Usually an instruction will
                                                                         be given, together with a brief explanation
• ARI 370 Sound Rating of Large Outdoor Refrigeration                    and the possible result of ignoring the
  and Air Conditioning Equipment.                                        instruction.
FLUORINATED GREENHOUSE GASES                                             A CAUTION identi es a hazard which could
                                                                         lead to damage to the machine, damage
• This equipment contains fluorinated greenhouse gases                   to other equipment and/or environmental
  covered by the Kyoto Protocol.                                         pollution. Usually an instruction will be
                                                                         given, together with a brief explanation
• The global warming potential of the refrigerant
                                                                         and the possible result of ignoring the
  (R410A) used in this unit is 1720.
                                                                         instruction.
• The refrigerant quantity is stated in the Physical Data                A NOTE is used to highlight additional
  table in Section 9 of this document.                                   information, which may be helpful to you
• The fluorinated greenhouse gases in this equipment                     but where there are no special safety
  may not be vented to the atmosphere.                                   implications.

• This equipment should only be serviced by qualified           The contents of this manual include suggested best
  technicians.                                                  working practices and procedures. These are issued for
                                                                guidance only, and they do not take precedence over
RESPONSIBILITY FOR SAFETY                                       the above stated individual responsibility and/or local
Every care has been taken in the design and manufacture         safety regulations.
of the unit to ensure compliance with the safety                This manual and any other document supplied with the
requirements listed above. However, the individual              unit are the property of Johnson Controls which reserves
operating or working on any machinery is primarily              all rights. They may not be reproduced, in whole or
responsible for:                                                in part, without prior written authorization from an
• Personal safety, safety of other personnel, and the           authorized Johnson Controls representative.
  machinery.
• Correct utilization of the machinery in accordance with
  the procedures detailed in the manuals.
•




035-21965-110 Rev. 0                                        7
           FORM 201.26-NM2 (1007)

MISUSE OF EQUIPMENT                                               Electrical
Suitability for Application                                       The unit must be earthed. No installation or maintenance
                                                                  work should be attempted on the electrical equipment
The unit is intended for cooling water or glycol solutions
                                                                  without first switching power OFF, isolating and locking-
and is not suitable for purposes other than those specified
                                                                  off the power supply. Servicing and maintenance on live
in these instructions. Any use of the equipment other
                                                                  equipment must only be performed by suitably trained
than its intended use, or operation of the equipment
                                                                  and qualified personnel. No attempt should be made to
contrary to the relevant procedures may result in injury
                                                                  gain access to the control panel or electrical enclosures
to the operator, or damage to the equipment.
                                                                  during normal operation of the unit.
The unit must not be operated outside the design
                                                                  Refrigerants and Oils
parameters specified in this manual.
                                                                  Refrigerants and oils used in the unit are generally
Structural Support
                                                                  nontoxic, non-flammable and non-corrosive, and pose
Structural support of the unit must be provided as                no special safety hazards. Use of gloves and safety
indicated in these instructions. Failure to provide proper        glasses is, however, recommended when working on the
support may result in injury to the operator, or damage           unit. The build up of refrigerant vapor, from a leak for
to the equipment and/or building.                                 example, does pose a risk of asphyxiation in confined or
                                                                  enclosed spaces and attention should be given to good
Mechanical Strength
                                                                  ventilation.
The unit is not designed to withstand loads or stresses
                                                                  High Temperature and Pressure Cleaning
from adjacent equipment, pipework or structures.
Additional components must not be mounted on the unit.            High temperature and pressure cleaning methods (e.g.
Any such extraneous loads may cause structural failure            steam cleaning) should not be used on any part of the
and may result in injury to the operator, or damage to            pressure system as this may cause operation of the
the equipment.                                                    pressure relief device(s). Detergents and solvents, which
                                                                  may cause corrosion, should also be avoided.
General Access
                                                                  Emergency Shutdown
There are a number of areas and features, which may
be a hazard and potentially cause injury when working             In case of emergency, the control panel is fitted with a
on the unit unless suitable safety precautions are taken.         incoming supply non-fused disconnect switch which can
It is important to ensure access to the unit is restricted        be used as the emergency stop device. When operated it
to suitably qualified persons who are familiar with the           removes the electrical supply to the control circuit thus
potential hazards and precautions necessary for safe              shutting down the unit.
operation and maintenance of equipment containing
high temperatures, pressures and voltages.
Pressure Systems

The unit contains refrigerant vapor and liquid under
pressure, release of which can be a danger and cause
injury. The user should ensure that care is taken during
installation, operation and maintenance to avoid damage
to the pressure system. No attempt should be made
to gain access to the component parts of the pressure
system other than by suitably trained and qualified
personnel.




                                                              8                                         035-21965-110 Rev. 0
                                                               FORM 201.26-NM2 (1007)

Safety Labels

The following labels are fixed to each unit to give                                     1
instruction, or to indicate potential hazards which may
exist.
              White symbol on blue background
              For safe operation, read the Instructions
              first


              Black symbol on yellow background
              Warning: This machine may start
              automatically without prior warning


              Black symbol on yellow background
              Warning: Hot surface


              Black symbol on yellow background
              Warning: Safety relief valve may discharge
              gas or liquid without prior warning


              Black symbol on yellow background
              Warning: Isolate all electrical sources of
              supply before opening or removing the
              cover, as lethal voltages may exist
              Black symbol on yellow background
              General attention symbol


              Black symbol on yellow background
              Power Factor Correction fitted
              Warning: On isolating the supply it may
              take up to 60 seconds for the capacitor
              voltage to fall below 60 volts




035-21965-110 Rev. 0                                       9
           FORM 201.26-NM2 (1007)

MATERIAL SAFETY DATA
Refrigerant Safety Data R410A:
COMPOSITION/INFORMATION ON INGREDIENTS
Components Material         PENTAFLUOROETHANE (HFC-125)                     DIFLUOROMETHANE (HFC-32)
CAS Number                  354-33-6                                        75-10-5
%                           50                                               50
HAZARDS IDENTIFICATION
Potential Health Effects    Inhalation of high concentrations of vapour is harmful and may cause heart irregularities,
                            unconsciousness, or death. Intentional misuse or deliberate inhalation may cause death
                            without warning. Vapour reduces oxygen available for breathing and is heavier than air. Liquid
                            contact can cause frostbite.
                            At flame temperatures, this material can decompose to hydrogen fluoride which can be lethal
                            at much lower concentrations.
Human Health Effects        Overexposure to the vapours by inhalation may include temporary nervous system
                            depression with anaesthetic effects such as dizziness, headache, confusion, incoordination,
                            and loss of consciousness. Higher exposures to the vapours may cause temporary alteration
                            of the heart's electrical activity with irregular pulse, palpitations, or inadequate circulation.
                            Gross overexposure may be fatal. Skin contact with the liquid may cause frostbite.

                               Individuals with preexisting diseases of the central nervous or cardiovascular system may
                               have increased susceptibility to the toxicity of increased exposures.
Carcinogenicity Information    None of the components present in this material at concentrations equal to or greater than
                               0.1% are listed by IARC, NTP, OSHA or ACGIH as a carcinogen.
FIRST AID MEASURES
Inhalation                     If inhaled, immediately remove to fresh air. Keep person calm.
                               If not breathing, give artificial respiration. If breathing is difficult, give oxygen. Call a physician.

Skin Contact                   Flush area with lukewarm water. Do not use hot water. If frostbite has occurred, call a
                               physician.
Eye Contact                    In case of contact, immediately flush eyes with plenty of water for at least 15 minutes. Call a
                               physician.
Ingestion                      Do not induce vomiting. Give plenty of water in sips
Notes to Physicians            THIS MATERIAL MAY MAKE THE HEART MORE SUSCEPTIBLE TO ARRHYTHMIAS.
                               Catecholamines such as adrenaline, and other compounds having similar effects, should be
                               reserved for emergencies and then used only with special caution.
FIRE FIGHTING MEASURES
Flammable Properties       Flash Point : No flash point
                           Flammable Limits in Air, % by Volume:
                           LEL : None per ASTM E681
                           UEL : None per ASTM E681
                           Autoignition: Not determined
Fire and Explosion Hazards Cylinders may rupture under fire conditions. Decomposition may occur.
                           Contact of welding or soldering torch flame with high concentrations of refrigerant can result
                           in visible changes in the size and colour of torch flames. This flame effect will only occur in
                           concentrations of product well above the recommended exposure limit, therefore stop all work
                           and ventilate to disperse refrigerant vapours from the work area before using any open
                           flames.
                           R-410A is not flammable in air at temperatures up to 100 deg C (212 deg F) at atmospheric
                           pressure. However, mixtures of R-410A with high concentrations of air at elevated pressure
                           and/or temperature can become combustible in the presence of an ignition source. R-410A
                           can also become combustible in an oxygen enriched environment (oxygen concentrations
                           greater than that in air). Whether a mixture containing R-410A and air, or R-410A in an
                           oxygen enriched atmosphere becomes combustible depends on the inter-relationship of 1)
                           the temperature 2) the pressure, and 3) the proportion of oxygen in the mixture. In general, R-
                           410A should not be allowed to exist with air above atmospheric pressure or at high
                           temperatures; or in an oxygen enriched environment. For example: R-410A should NOT be
                           mixed with air under pressure for leak testing or other purposes.



                                                               10                                                035-21965-110 Rev. 0
                                                                                    FORM 201.26-NM2 (1007)


Refrigerant Safety Data R410A:
Extinguishing Media         As appropriate for combustibles in area.
Fire Fighting Instructions  Cool cylinder with water spray or fog. Self-contained breathing apparatus (SCBA) is required        1
                            if cylinders rupture and contents are released under fire conditions. Water runoff should be
                            contained and neutralized prior to release.
ACCIDENTAL RELEASE MEASURES
Safeguards (Personnel)      NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL)
                            sections before proceeding with clean-up. Use appropriate PERSONAL PROTECTIVE
                            EQUIPMENT during clean-up.
Accidental Release Measures Ventilate area, especially low or enclosed places where heavy vapours might collect.
                            Extinguish open flames. Use self-contained breathing apparatus (SCBA) for large spills or
                            releases. Eliminate electrical sources.
HANDLING AND STORAGE
Handling (Personnel)        Avoid breathing vapour. Avoid liquid contact with eyes and skin. Use with sufficient ventilation
                            to keep employee exposure below recommended limits. See Fire and Explosion Data section.

Storage              Clean, dry area. Do not heat above 52 deg C (125 deg F).
EXPOSURE CONTROLS/PERSONAL PROTECTION
Engineering Controls Avoid breathing vapours. Avoid contact with skin or eyes. Use with sufficient ventilation to
                     keep employee exposure below the recommended exposure limit. Local exhaust should be
                     used if large amounts are released. Mechanical ventilation should be used in low or enclosed
                     places.
Personal Protective  Impervious gloves should be used to avoid prolonged or repeated exposure. Chemical splash
Equipment            goggles should be available for use as needed to prevent eye contact. Under normal
                     manufacturing conditions, no respiratory protection is required when using this product
                     provided exposure is maintained at or below occupational limits. Self-contained breathing
                     apparatus (SCBA) is required if a large release occurs.

Exposure Guidelines            Applicable Exposure Limits
                               PENTAFLUOROETHANE (HFC-125)
                               PEL (OSHA) : None Established
                               TLV (ACGIH) : None Established
                               AEL * (DuPont) : 1000 ppm, 8 & 12 Hr. TWA
                               WEEL (AIHA) : 1000 ppm, 4900 mg/m3, 8 Hr. TWA
                               DIFLUOROMETHANE (HFC-32)
                               AEL * (DuPont) : 1000 ppm, 8 & 12 Hr. TWA
                               WEEL (AIHA) : 1000 ppm, 8 Hr. TWA
                               * AEL is DuPont's Acceptable Exposure Limit. Where governmentally imposed occupational
                               exposure limits which are lower than the AEL are in effect, such limits shall take precedence.

PHYSICAL AND CHEMICAL PROPERTIES
Physical Data              Boiling Point : - 60.8 F (-51.6 C) @ 1 atm
                           Vapour Pressure : 239.7 psia 25 C (77 F)
                           % Volatiles : 100 WT%
                           Evaporation Rate : (Cl4 = 1) Greater than 1
                           Solubility in Water : Not determined
                           Odour : Slight ethereal
                           Form : Liquefied gas
                           Colour : Clear, colourless
                           Specific Gravity : 1.066 @ 25 C (77 F)
STABILITY AND REACTIVITY
Chemical Stability         Material is stable. However, avoid open flames and high temperatures.
Incompatibility with Other Incompatible with active metals, alkali or alkaline earth metals--powdered Al, Zn, Be, etc.
Materials
Decomposition              Decomposition products are hazardous. This material can be decomposed by high
                           temperatures (open flames, glowing metal surfaces, etc.) forming hydrofluoric acid and
                           possibly carbonyl fluoride. These materials are toxic and irritating. Contact should be avoided.



035-21965-110 Rev. 0                                         11
           FORM 201.26-NM2 (1007)


Refrigerant Safety Data R410A:
Polymerization              Polymerization will not occur.
Other Hazards               Decomposition : Decomposition products are hazardous. This material can be decomposed
                            by high temperatures (open flames, glowing metal surfaces, etc.) forming hydrofluoric acid,
                            and possibly carbonyl halides.
TOXICOLOGICAL INFORMATION
Animal Data                 The blend is untested.
                            HFC-125
                            Inhalation 4-hour ALC: >709,000 ppm in rats
                            Single exposure to high doses caused: Lethargy. Laboured breathing. Weak cardiac
                            sensitization, a potentially fatal disturbance of heart rhythm caused by a heightened
                            sensitivity to the action of epinephrine. Lowest-Observed-Adverse-Effect-Level for cardiac
                            sensitization: 100,000 ppm.
                            Repeated exposure caused: No significant toxicological effects. No-Observed-Adverse-Effect-
                            Level(NOAEL): 50,000 ppm
                            ADDITIONAL TOXICOLOGICAL EFFECTS:
                            No animal data are available to define the following effects of this material: carcinogenicity,
                            reproductive toxicity. In animal testing this material has not caused developmental toxicity.
                            Tests have shown that this material does not cause genetic damage in bacterial or
                            mammalian cell cultures, or in animals. This material has not been tested for its ability to
                            cause permanent genetic damage in reproductive cells of mammals (not tested for heritable
                            genetic damage).
                            HFC-32
                            Inhalation 4 hour-ALC: > 520,000 ppm in rats
                            Single exposure caused: Lethargy. Spasms. Loss of mobility in the hind limbs. Other effects
                            include weak cardiac sensitization, a potentially fatal disturbance of heart rhythm caused by a
                            heightened sensitivity to the action of epinephrine. 250,000 ppm.
                            Repeated exposure caused pathological changes of the lungs, liver, spleen, kidneys. In more
                            recent studies repeated exposure caused: No significant toxicological effects.

                              No-Observed-Effect-Level (NOEL): 49,100 ppm.
                              No animal data are available to define the following effects of this material: carcinogenicity,
                              reproductive toxicity. Animal data show slight fetotoxicity but only at exposure levels
                              producing other toxic effects in the adult animal. Tests have shown that this material does not
                              cause genetic damage in bacterial or mammalian cell cultures, or in animals. This material
                              has not been tested for its ability to cause permanent genetic damage in reproductive cells of
                              mammals (not tested for heritable genetic damage).

DISPOSAL CONSIDERATIONS
Waste Disposal        Comply with Federal, State, and local regulations. Reclaim by distillation or remove to a
                      permitted waste disposal facility.
TRANSPORTATION INFORMATION
Shipping Information  DOT/IMO/IATA
                      Proper Shipping Name : Liquefied Gas, N.O.S. (Pentafluoroethane and Difluoromethane)

                              Hazard Class : 2.2
                              UN No. : 3163
                              Label(s) : Nonflammable Gas
                              Shipping Containers : Tank Cars. Cylinders. Ton Tanks




                                                            12                                            035-21965-110 Rev. 0
                                                                                       FORM 201.26-NM2 (1007)


Oil Safety Data YORK 'V' Oil:
Section 1 Substance Product Information                                                                                     1
Product Trade Name: YORK "V" Oil.
Chemical Name: Carboxylic Ester.
Section 2 Components and Hazard Statement
This product is non-hazardous. This material has no known hazards under applicable laws.
Section 3 Safe Handling and Storage
Handling: Keep containers closed when not in use. Wash thoroughly after handling. Empty container contains product
Storage: No special storage precautions required.
Section 4 Physical Data
Appearance: Clear liquid.
Boiling Point: Not Determined.
Vapour Pressure: Not Determined.
Specific Gravity (water=1): 0.97 @ 15.6°C.
Volatiles, Percent by Volume: Unknown.
Odour: Mild.
Solubility in Water: Insoluble.
Evaporation Rate: Not Determined.
Section 5 Fire and Explosion Hazards
Flash Point: > 232°C, 450°F COC (Minimum).
Flammable Limits: not established.
Autoignition Temperature: no data.
Extinguishing Media: CO2, dry chemical or foam. Water can be used to cool and protect exposed material.
Unusual Fire and Explosion Hazards: Toxic fumes, gases or vapours may evolve on burning.
Special Fire Fighting Techniques: Firefighters should use approved self-contained breathing apparatus. Water may cause
Section 6 Reactivity Data
Stability: Material is normally stable at moderately elevated temperatures and pressures.
Hazardous Polymerization: Will not occur.
Incompatible Materials: Strong acids. Strong bases. Strong oxidizing agents.
Decomposition Temperature: Not Determined.
Thermal Decomposition: Smoke, carbon monoxide, carbon dioxide, aldehydes and other products of incomplete combustion.
Section 7 Health Hazard Data
First Aid Procedures
Ingestion: DO NOT INDUCE VOMITING. If conscious, give 2 glasses of water. Get immediate medical attention.
Eyes: Flush with water at least 15 minutes. Get medical attention if eye irritation develops or persists.
Skin: Wash with soap and water. Get medical attention if irritation develops. Launder contaminated clothing before reuse.
Inhalation: Remove exposed person to fresh air if adverse effects are observed.
Additional Information: Note to physician: Treat symptomatically.
Section 8 Personal Protection Information
Respiratory Protection: Use respirator with an organic vapour cartridge if exposure limit is exceeded.
Ventilation: Use with adequate ventilation.
Protective Gloves: Neoprene.
Eye/Face Protection: Safety glasses.
Clothing: Long sleeve shirt is recommended.
Section 9 Spill or Leak Procedures
Spill Procedures: Personal Protective Equipment must be worn, see Personal Protection Information (Section 8). Ventilate
Section 10 Waste Disposal Methods
This material, if discarded, should be disposed of in a licensed facility in accordance with local regulations.




035-21965-110 Rev. 0                                           13
          FORM 201.26-NM2 (1007)


Thermal & Acoustic Materials Data
Health Hazard & First Aid   Toxicity Index <10 to NES713 Issue 3 (1991): Non-hazardous, non-toxic. No first aid
                            necessary.
Stability / Reactivity      Stable.
Handling / Use / Disposal   No special handling precautions required. Dispose of according to local laws and regulations
                            governing non-biodegradable non-hazardous solid wastes.
Fire & Explosion            Flammability rating Class 1 to BS 476 pt 7: Non-flammable. If forced to burn, combustion
                            products are typically over 95% carbon dioxide and carbon monoxide.




                                                         14                                          035-21965-110 Rev. 0
                                                                                     FORM 201.26-NM2 (1007)


                                         PRODUCT DESCRIPTION


                                                                                                                                  2




INTRODUCTION                                                       Compressors

YORK YCWL chillers are designed for water or water-                The unit has suction-cooled, hermetic scroll compressors.
glycol cooling.                                                    High efficiency is achieved through a controlled orbit and
                                                                   the use of advanced scroll geometry. The compressors
All units are designed for indoor installation in a plant
                                                                   incorporate a compliant scroll design in both the axial
room.
                                                                   and radial directions. All rotating parts are statically and
The unit is completely factory assembled with all                  dynamically balanced. The compressor motors have
interconnecting refrigerant piping and wiring ready for            integral protection against overloads. The overload
field installation. The unit is pressure tested, evacuated,        protection that will automatically reset. Starting is direct
and fully factory charged with refrigerant R410A and               on line, but soft start is available as an option.
oil in each of the independent refrigerant circuits. After
                                                                   The compressors are switched On and Off by the unit
assembly, an operational test is performed with water
                                                                   microprocessor to provide capacity control. Each
flowing through the evaporator and condenser to ensure
                                                                   compressor is fitted with a crankcase strap heater. All
that each refrigerant circuit operates correctly.
                                                                   compressors are mounted on isolator pads to reduce
The unit structure is manufactured from heavy-gauge,               transmission of vibration to the rest of the unit.
galvanised steel coated with baked-on ‘Caribbean Blue‘
powder paint.




035-21965-110 Rev. 0                                          15
           FORM 201.26-NM2 (1007)

Refrigerant Circuits                                               Condenser

Two independent refrigerant circuits are provided on               The twin-refrigerant circuit water-cooled condenser is
each unit. Each circuit uses copper refrigerant pipe               cleanable shell and tubes type with seamless externally
formed on computer controlled bending machines to                  finned copper tubes rolled into tubes sheets, removable
reduce the number of brazed joints resulting in a reliable         water heads and built-in subcooler. The waterside (tubes)
and leak resistant system.                                         design working pressure is 10 bar g. The refrigerant
                                                                   side (shell) design working pressure is 38.61 bar g.
Liquid line components include: a service valve with
                                                                   The refrigerant side is protected by pressure relief
charging port, a high absorption removable core filter-
                                                                   valve(s).
drier, a solenoid valve, a sight glass with moisture
indicator and a thermal expansion valve. Liquid lines              Water Connection to the condenser is via victaulic-
between the expansion valve and the cooler are covered             grooved connections. Flange connections are available
with flexible, closed-cell insulation.                             as an option.
Suction line components include: a pressure relief valve,          Power and Control Panels
a pressure transducer and a service valve. Optional
                                                                   All power and controls are contained in a IP32 cabinet
isolation ball valves are available. Suction lines are
                                                                   with hinged, latched and gasket sealed outer doors.
covered with flexible, closed-cell insulation.
                                                                   The power panel includes:
Discharge lines include service and isolation (ball)
valves, two high-pressure cutout switches, a pressure              • A factory mounted non-fused disconnect switch with
transducer and a pressure relief valve.                              external, lockable handle to enable connection of the
                                                                     unit power supply. The disconnect switch can be used
Evaporator
                                                                     to isolate the power for servicing.
The 2-pass dual circuit shell and tube type direct
                                                                   • Factory mounted compressor contactors and manual
expansion (DX) evaporator has refrigerant in the tubes
                                                                     motor starters to provide overload and short circuit
and chilled liquid flowing through the baffled shell. The
                                                                     protection.
waterside (shell) design working pressure of the cooler
is 10.3 bar g. The refrigerant side (tubes) design working         • Factory mounted control transformer to convert the
pressure is 27.58 bar g. The refrigerant side is protected           unit supply voltage to 110 V - 1 Ø - 50 Hz for the
by pressure relief valve(s).                                         control system.
The evaporator shall have water pass baffles fabricated            • Control supply fuses and connections for a remote
from galvanised steel to resist corrosion. Removable                 emergency stop device.
heads are provided for access to internally enhanced,
                                                                   The control panel includes:
seamless, copper tubes. Water vent and drain connections
are included. The cooler is insulated with flexible closed-        • A Liquid Crystal Display (two display lines of twenty
cell foam.                                                           characters per line) with Light Emitting Diode
                                                                     backlighting for easy viewing.
Water Connection to the evaporator is via victaulic-
grooved connections. Flange connections are available              • A Colour coded 12-button keypad.
as an option.
                                                                   • Customer terminal block for control inputs and liquid
                                                                     flow switch.




                                                              16                                         035-21965-110 Rev. 0
                                                                                     FORM 201.26-NM2 (1007)

The microprocessor control includes:                              • Day, date and time
• Automatic control of compressor start/stop, anti-               • Daily start/stop times
  coincidence and anti-recycle timers, automatic
                                                                  • Holiday status
  pumpdown on shutdown, evaporator pump and unit                                                                             2
  alarm contacts. Automatic reset to normal chiller               • Automatic or manual system lead/lag control
  operation after power failure.
                                                                  • Lead system definition
• Remote water temperature reset via a pulse width
  modulated (PWM) input signal or up to two steps of              • Compressor starts & operating hours (each
  demand (load) limiting                                            compressor)

• Software stored in non-volatile memory (EPROM),                 • Run permissive status
  with programmed setpoints retained in a lithium                 • Number of compressors running
  battery backed real time clock (RTC) memory for a
  minimum of five years.                                          • Liquid solenoid valve status

• Forty character liquid crystal display, with description        • Load & unload timer status
  available in five languages (English, French, German,           • Water pump status
  Spanish or Italian)
                                                                  System Safeties:
Programmable setpoints:
                                                                  Cause individual compressors to perform auto shut
• Chilled liquid temperature setpoint and range                   down and require manual reset in the event of 3 trips in
                                                                  a 90-minute time period:
• Remote reset temperature range
                                                                  • High discharge pressure
• Set daily schedule/holiday for start/stop
                                                                  • Low suction pressure
• Manual override for servicing
                                                                  • High pressure switches
• Low liquid temperature cutout
                                                                  • Motor protector
• Low suction pressure cutout
                                                                  • Unit Safeties:
• High discharge pressure cutout
                                                                  • Are automatic reset and cause compressor to shut
• Anti-recycle timer (compressor start cycle time)                  down
• Anti-coincident timer (delay compressor starts)                 • Low leaving chilled liquid temperature
Displayed Data:
                                                                  • Under voltage
• Return and leaving liquid temperature
                                                                  • Loss of liquid flow (through flow switch)
• Low leaving liquid temperature cutout setting                   Alarm Contacts:
• Metric or Imperial data                                         • Low leaving chilled liquid temperature
• Discharge and suction pressure cutout settings                  • Low voltage
• System discharge and suction pressures                          • Low battery
• Anti-recycle timer status for each compressor                   • High discharge pressure (per system)
• Anti-coincident system start timer condition                    • Low suction pressure (per system)
• Compressor run status
• No cooling load condition




035-21965-110 Rev. 0                                         17
           FORM 201.26-NM2 (1007)

ACCESSORIES AND OPTIONS                                           Suction Service Valves

                                                                  A ball valve is added to each suction line pipework for
Soft Starters
                                                                  isolation.
Factory mounted soft starters reduce the inrush current
                                                                  Victaulic Flange Kit
to the last compressor on each refrigerant circuit. They
are preset so that no field adjustment is required.               Victaulic PN10 Flange joint kit supplied loose for field
                                                                  installation. Includes flange and companion flange and
Power Factor Correction
                                                                  all necessary nuts, bolts and gaskets.
Factory mounted passive (static) power factor correction
                                                                  Compressor Acoustic Blankets
capacitors to correct unit compressor power factors to
a target of 0.9 (depending on operating conditions).              Each compressor is individually enclosed in an acoustic
This option is Special Quotation only, contact YORK /             sound blanket. The sound blankets are made with one
Johnson Controls for details.                                     layer of acoustical absorbent textile fibre of 15 mm
              