SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

YCSE040 — Water and remote air cooled screw chillers, York YCSE / YCRE

Вид документаІнструкція
ВиробникJCI
МоделіYCSE040, YCSE050, YCSE060, YCSE080, YCSE100, YCRE040, YCRE050, YCRE060
Група обладнанняother
Мова документаанглійська
Розмір файлу3.6 МБ

Про документ

YORK YCSE/YCRE R407C chillers are designed for water or water-glycol cooling, intended for indoor installation in a plant room. Units have one or two independent refrigerant circuits with a single evaporator and, on YCSE models, a single water-cooled condenser; YCRE models use a field-supplied remote air-cooled condenser. They are factory assembled, pressure tested, evacuated and fully charged with refrigerant R407C and oil.

Ключові дані

Cooling capacity range YCSE134–320 kW
Cooling capacity range YCRE127–307 kW
RefrigerantR407C (GWP 1520)
Power supply400 V, 3 ~, 50 Hz (nominal); allowable 360 to 440 V
Compressor typeSemi-hermetic Screw, capacity control 15-100 %
Evaporator design working pressure (water side)10 barg
Maximum refrigerant side pressure30 bar
Ambient air temperature range5 °C min to 46 °C max

Застосування

  • Cooling water or glycol solutions for air conditioning installations
  • Glycol cooling options for water outlet temperatures below 5 °C (Category 1: 0 to 4 °C; Category 2: -1 to -5 °C; Category 3: -6 to -10 °C)
  • Heat pump operation on YCSE units (option)

Особливості

  • Suction-cooled semi-hermetic twin-screw compressors with continuous slide valve capacity control (15% to 100% per compressor; 7.5, 15-100 % on two-circuit models)
  • Stainless steel brazed plate heat exchangers with victaulic-grooved connections (flange connections optional)
  • Electronic expansion valve, filter dryer, sight glass with moisture indicator
  • IP2X power/control cabinet with non-fused disconnect switch
  • Options: Modbus or Lonworks BMS interface (HARC), CSC-5S multi unit sequencer (up to 8 units), compressor circuit breakers, differential water pressure switches, flow switches, PN16 flanges, spring isolators or resilient pads, heat pump kit (YCSE only)
  • Factory operational test performed before dispatch

Технічні дані

Parameter Value
Refrigerant R407C
Refrigerant GWP 1520
Compressor type Semi-hermetic Screw
Capacity control 15-100 % per compressor
Evaporator type Brazed PHE
Evaporator waterside design working pressure 10 barg
Evaporator refrigerant side design working pressure 18 bar g
Condenser (YCSE) refrigerant side design working pressure 30 bar g
Condenser (YCSE) waterside design working pressure 10 barg
Number of refrigerant circuits 1 (040-080) / 2 (100)
Refrigerant charge per circuit 12 / 14 / 16 / 18 kg; 14 / 14 kg (model 100)
Oil charge per circuit 6 litre
Power supply 400V, 3 ~, 50 Hz (nominal); allowable 360 to 440 V
Control terminals voltage AC220-240V (terminals 1~21/57), DC24V (terminals A~D), H-link low signal (E~F)
Cabinet ingress protection IP2X
Liquid outlet temperature (water) 5 to 15 °C
Liquid outlet temperature (glycol) -10 to 15 °C
Minimum / maximum ambient air temperature 5 °C / 46 °C
Recommended minimum system water volume 420 / 510 / 610 / 730 / 1010 litres (by model size)
Fouling factor (design basis) 0.044 m² °C/kW
Required water pH 7 to 8.5
YCSE dimensions (L × W × H) 850 × 1105 × 1520 mm (040-080); 1465 × 1105 × 1700 mm (100)
YCSE operating weight 780 / 800 / 875 / 1000 / 1655 kg
YCRE dimensions (L × W × H) 885 × 1045 × 1562 mm (040/050); 885 × 1104 × 1562 mm (060); 1471 × 1104 × 1720 mm (080/100)
YCRE operating weight 650 / 710 / 760 / 1250 / 1370 kg
Remote condenser system Design Working Pressure (min.) at least 27.6 barg
YCRE refrigerant gas connection pipe Outer Diameter 41.3 mm, Thickness 2.0 mm
YCRE refrigerant liquid connection pipe Outer Diameter 28.6 mm, Thickness 1.6 mm
Max. piping length to remote condenser 30.0 m
Max. height difference (unit below remote condenser) 25.0 m
Max. height difference (unit above remote condenser) 5.0 m
Nominal running amps YCSE (at 400 V, kW by model) 34 A (040), 40 A (050), 49 A (060), 55 A (080), 80 A (100)
Nominal running amps YCRE 34 A (040), 42 A (050), 52 A (060), 68 A (080), 84 A (100)
Sound power LWA (EN 292-1991 SPL) YCSE/YCRE: 68 / 69 / 71 / 71 / 72 dB(A) by model size
Compressor HP switch cut-out 2.74 MPa (manual reset, non-adjustable)
Compressor LP switch (pressure sensor) cut-out 0.05 MPa
Compressor internal thermostat Cut-out 115 °C, Cut-in 93 °C
Discharge gas cut-out 140 °C
Refrigerant circuit pressure relief valve setting 3.0 MPa
Freeze protection thermostat cut-out 2.0 °C
Oil heater rating 150 W

Варіанти замовлення

Nomenclature example: YCSE100SB50B — Y = York, C = Chiller, S = Screw, E = European; capacity :040 :050 :060 :080 :100; S = Standard Unit; B = R407C Refrigerant; 50 = 380-415 / 3 / 50 + N; B = Design Level. Accessories/options referenced in the document: Modbus (HARC-MODBUS), Lonworks (HARC-LONWORKS), Multi Unit Sequencer CSC-5S, compressor circuit breakers, differential water pressure switches, flow switches, glycol cooling categories 1–3, discharge/suction stop valves, compressor safety valve(s), dual pressure relief valves, suction pressure relief valves, PN16 flanges, AVM resilient pads, AVM spring isolators, water filter, wooden crate, heat pump kit (YCSE only).

Допуски та стандарти

  • EN ISO 9001 accredited design and manufacturing organisation
  • Machinery Directive (98/37/EC)
  • Low Voltage Directive (2006/95/EC)
  • EMC Directive (2004/108/EC)
  • Pressure Equipment Directive 97/23/EC, CE marking
  • EN13136 (relief pipework sizing reference)
  • EN 60204 (overcurrent protection responsibility)
  • NES713 Issue 3 (1991) toxicity index of thermal/acoustic materials
  • BS 476 pt 7 Class 1 flammability rating (thermal/acoustic materials)
  • Sound data per Eurovent specification and EN 292-1991

Текст документа

Библиотека СОК 




                          YCSE040-YCSE100 & YCRE040-YCRE100
            INSTALLATION, COMMISSIONING,
              OPERATION & MAINTENANCE
                                             Revision 1   Form 035-21786-100 (0909)




                                  WATER AND REMOTE AIR
                                 COOLED LIQUID CHILLERS
                                WITH SCREW COMPRESSORS
                                         STYLE B
                                     (YCSE 134-320KW)
                                     (YCRE 127-307KW)


                                           Aspak




                                                                   R407C
                                                                          035-21786-100 Rev. 1 (0909)



                                         TABLE OF CONTENTS

1   SUPPLIER INFORMATION                          4   INSTALLATION

    1.1   Introduction                      1.1       4.1   Location Requirements                 4.1

    1.2   Warranty                          1.1       4.2   Installation of Vibration Isolators   4.1

    1.3   Safety                            1.1       4.3   Pipework Connection                   4.1

    1.4   Responsibility for Safety         1.2       4.4   Water Treatment                       4.2

    1.5   About this Manual                 1.2       4.5   Pipework Arrangement                  4.3

    1.6   Misuse of Equipment               1.2       4.6   Connection Types & Sizes              4.3

    1.7   Emergency Shutdown                1.3       4.7   Condenser Cooling Liquid Systems 4.4

    1.8   Safety Labels                     1.3       4.8   Electrical Connection                 4.5

    1.9   Material Safety Data              1.4       4.9   Remote Refrigerant Condenser
                                                            Systems (YCRE models only)            4.5
2   PRODUCT DESCRIPTION
                                                      4.10 Power Wiring                           4.8
    2.1   Introduction                      2.1
                                                      4.11 Control Wiring                         4.8
    2.2   Compressor                        2.1
                                                      4.12 Connection Diagram                     4.9
    2.3   Refrigerant Circuits              2.1
                                                  5   COMMISSIONING
    2.4   Evaporator                        2.1
                                                      5.1   Preparation                           5.1
    2.5   Condenser                         2.1
                                                      5.2   First Time Start-up                   5.2
    2.6   Power and Control Panels          2.2
                                                  6   UNIT OPERATION
    2.7   Accessories and Options           2.2
                                                      6.1   General Description                   6.1
    2.8   Nomenclature                      2.3
                                                      6.2   Operation                             6.1
    2.9   Refrigerant Flow Diagram          2.4
                                                      6.3   Normal Running and Cycling            6.1
3   TRANSPORTATION, HANDLING AND
    STORAGE                                           6.4   Shutdown                              6.1

    3.1   Delivery and Storage              3.1       6.5   Control System                        6.1

    3.2   Inspection                        3.1   7   MAINTENANCE

    3.3   Moving the Unit                   3.1       7.1   General Requirements                  7.1

    3.4   Lifting Weights                   3.2       7.2   Daily Maintenance                     7.1

    3.5   Weight Distribution & Centre                7.3   Scheduled Maintenance                 7.1
          of Gravity                        3.2
                                                      7.4   Pressure Vessel In-Service
                                                            Inspection                            7.2




                                                                                                        I-i
035-21786-100 Rev. 1 (0909)



8      TROUBLE SHOOTING

       8.1   Competent Persons Trouble
             Shooting Guide                 8.1

9      TECHNICAL DATA

       9.1   Flow Rate and Pressure Drop
             Graphs                         9.1

       9.2   Performance Graphs             9.2

       9.3   Operating Limitations          9.4

       9.4   Physical Data                  9.5

       9.5   Electrical Data                9.6

       9.6   Sound Data                     9.7

       9.7   Clearances and Foundations     9.8

       9.8   Dimensions                     9.9

10 SPARE PARTS

       10.1 Renewal Parts List             10.1

       10.2 Recommended Compressor Oils    10.1

       10.3 Associated Drawings            10.1

11 DECOMMISSIONING. DISMANTLING AND
   DISPOSAL

       11.1 General                        11.1




I-ii
                                                                                            035-21786-100 Rev. 1 (0909)




1     SUPPLIER INFORMATION                                       For warranty purposes, the following conditions must be
                                                                 satisfied:
1.1   Introduction
                                                                 The initial start of the unit must be carried out by trained
York YCSE/YCRE chillers are manufactured to the                  personnel from an Authorised York Service Centre.
highest design and construction standards to ensure
high performance, reliability and adaptability to all types      Only genuine York approved spare parts, oils and
of air conditioning installations.                               refrigerants must be used.

The units are intended for cooling water or glycol               All the scheduled maintenance operations detailed in
solutions and are not suitable for purposes other than           this manual must be performed at the specified times by
those specified in this manual.                                  suitably trained and qualified personnel.

This manual contains all the information required for            Failure to satisfy any of these conditions will
correct installation and commissioning of the unit,              automatically void the warranty.
together with operating and maintenance instructions.
The manuals should be read thoroughly before                     1.3    Safety
attempting to operate or service the unit.
                                                                 Standards for Safety
All procedures detailed in the manuals, including
installation, commissioning and maintenance tasks                YCSE/YCRE chillers are designed and built within an
must only be performed by suitably trained and qualified         EN ISO 9001 accredited design and manufacturing
personnel.                                                       organisation and, within the limits specified in this
                                                                 manual, are in conformity with the essential health and
The manufacturer will not be liable for any injury or            safety requirements of the following European Union
damage caused by incorrect installation,                         Directives:
commissioning, operation or maintenance resulting
from a failure to follow the procedures and instructions         Machinery Directive (98/37/EC)
detailed in the manuals..
                                                                 Low Voltage Directive (2006/95/EC)
1.2   Warranty
                                                                 EMC Directive (2004/108/EC)
Johnson Controls warrants all equipment and materials
against defects in workmanship and materials for one             They conform to the applicable and essential safety
year from initial start-up, or eighteen months from              requirements of Pressure Equipment Directive
delivery (whichever occurs first) unless extended                97/23/EC and bear CE marking.
warranty has been agreed as part of the contract.
                                                                 Fluorinated Greenhouse Gases
The warranty is limited to free replacement and shipping
of any faulty part, or sub-assembly which has failed due         n     This equipment contains fluorinated greenhouse
to poor quality or manufacturing errors. All claims must               gases covered by the Kyoto Protocol.
be supported by evidence that the failure has occurred
within the warranty period, and that the unit has been           n     The global warming potential of the refrigerant
operated within the designed parameters specified.                     (R407C) used in this unit is 1520.

All warranty claims must specify the unit model, serial          n     The refrigerant quantity is stated in the Physical
number and order number. These details are printed on                  Data table in Section 9 of this document.
the unit identification plate, fitted on the outer edge of the
options panel.                                                   n     The fluorinated greenhouse gases in this
                                                                       equipment may not be vented to the atmosphere.
The unit warranty will be void if any modification to the
unit is carried out without prior written approval from          n     This equipment should only be serviced by
Johnson Controls.                                                      qualified technicians.




                                                                                                                       1-1
035-21786-100 Rev. 1 (0909)



1.4   Responsibility for Safety                                    1.6   Misuse of Equipment

Every care has been taken in the design and                        Suitability for Application
manufacture of the units to ensure that they meet the
safety requirements listed in the previous paragraph.              The unit is intended for cooling water or glycol solutions
However, the individual operating or working on any                and is not suitable for purposes other than those
machinery is primarily responsible for:                            specified in these instructions. Any use of the equipment
                                                                   other than its intended use, or operation of the
Personal safety, safety of other personnel, and the                equipment contrary to the relevant procedures may
machinery.                                                         result in injury to the operator, or damage to the
                                                                   equipment.
Correct utilisation of the machinery in accordance with
the procedures detailed in the manuals.                            The unit must not be operated outside the design limits
                                                                   specified in this manual.
1.5   About this Manual
                                                                   Structural Support
The following symbols are used in this document to alert
the reader to areas of potential hazard.                           Structural support of the unit must be provided as
                                                                   indicated in these instructions. Failure to provide proper
          A Warning is given in this document to                   support may result in injury to the operator, or damage to
          identify a hazard which could lead to                    the equipment.
          personal injury. Usually an instruction will
          be given, together with a brief explanation              Mechanical Strength
          and the possible result of ignoring the
          instruction.                                             The unit is not designed to withstand loads or stresses
                                                                   from adjacent equipment, pipework or structures.
          A Caution identifies a hazard which could                Additional components must not be mounted on the
          lead to damage to the machine, damage to                 unit. Any such extraneous loads may cause structural
          other equipment and/or environmental                     failure and may result in injury to the operator, or
          pollution. Usually an instruction will be given,         damage to the equipment.
          together with a brief explanation and the
          possible result of ignoring the instruction.             General Access

          A Note is used to highlight additional                   There are a number of areas and features which may be
          information which may be helpful to you but              a hazard and potentially cause injury when working with
          w h e r e th e r e a r e n o s p e c i a l s a f e t y   the unit unless suitable safety precautions are taken. It
          implications.                                            is important to ensure access to the unit is restricted to
                                                                   suitably qualified persons who are familiar with the
                                                                   potential hazards and precautions necessary for safe
The contents of this manual include suggested best                 operation and maintenance of equipment containing
working practices and procedures. These are issued for             high temperatures, pressures and voltages.
guidance only, they do not take precedence over the
above stated individual responsibility and/or local safety         Pressure Systems
regulations.
                                                                   The unit contains refrigerant vapour and liquid under
This manual and any other document supplied with the               pressure, release of which can be a danger and cause
unit, are the property of Johnson Controls which                   injury. The user should ensure that care is taken during
reserves all rights. They may not be reproduced, in                installation, operation and maintenance to avoid
whole or in part, without prior written authorisation from         damage to the pressure system. No attempt should be
an Authorised Johnson Controls representative.                     made to gain access to the component parts of the
                                                                   pressure system other than by suitably trained and
                                                                   qualified personnel.




1-2
                                                                                     035-21786-100 Rev. 1 (0909)



Electrical                                                   1.8   Safety Labels

The unit must be earthed. No installation or                 The following labels are fixed to each unit to give
maintenance work should be attempted on electrical           instruction, or to indicate potential hazards which may
equipment without first switching off, isolating and         exist.
locking-off the power supplies. Work on live equipment
must only be carried-out by suitably trained and                              White symbol on blue background
qualified personnel. No attempt should be made to gain                        For safe operation, read the
access to inside of the control panel, wiring or other                        Instructions first
electrical enclosures during normal operation of the unit.

Refrigerants and Oils
                                                                              Black symbol on yellow background
Refrigerants and oils used in the unit are generally                          Warning: This machine may start
non-toxic, non-flammable and non-corrosive, and pose                          automatically without prior warning
no special safety hazards. Use of gloves and safety
glasses are, however, recommended when working on
the unit. Build up of refrigerant vapour, from a leak for                     Black symbol on yellow background
example, does pose a risk of asphyxiation in confined or                      Warning: Hot surface
enclosed spaces and attention should be given to good
ventilation. For more comprehensive information on
safety precautions for use of refrigerants and oils, refer
to the Materials Safety Data tables provided.
                                                                              Black symbol on yellow background
High Temperature and Pressure Cleaning                                        Warning: Safety relief valve may
                                                                              discharge gas or liquid without prior
High temperature and pressure cleaning methods (e.g.                          warning
steam cleaning) should not be used on any part of the
pressure system as this may cause operation of the                            Black symbol on yellow background
pressure relief device(s). Detergents and solvents                            Warning: Isolate all electrical sources
which may cause corrosion should also be avoided.                             of supply before opening or removing
                                                                              the cover, as lethal voltages may exist
1.7   Emergency Shutdown

In case of emergency the unit can be shut down by                             Black symbol on yellow background
operating the main power switch on the control panel.                         General attention symbol




                                                                                                                1-3
035-21786-100 Rev. 1 (0909)



1.9   Material Safety Data

Refrigerant Data:

Safety Data               R407C
Toxicity                 Low.
In contact with skin     Liquid splashes or spray may cause freeze burns. Unlikely to be hazardous by skin absorption.
                         Thaw affected areas with water. Remove contaminated clothing carefully — may adhere to skin in
                         case of freeze burns. Wash affected areas with plenty of warm water. If symptoms occur (irritation
                         or blistering) obtain medical attention.
In contact with eyes     Vapour has no effect. Liquid splashes or spray may cause freeze burns. Immediately irrigate with
                         eyewash solution or clean water for at least 10 minutes. Obtain immediate medical attention.
Ingested                 Highly unlikely to occur — but should this occur freeze burn will occur. Do not induce vomiting.
                         Provided patient is conscious, wash mouth with water and give about 250 ml (0.5 pint) to drink.
                         Obtain immediate medical attention.
Inhalation               High atmospheric concentrations may have an anaesthetic effect, including loss of consciousness.
                         Very high exposures may cause an abnormal heart rhythm and prove suddenly fatal.
                         At higher concentration there is a danger from asphyxiation due to reduced oxygen content of
                         atmosphere. Remove patient to fresh air, keep warm and at rest. Administer oxygen if necessary.
                         Apply artificial respiration if breathing has ceased or shows signs of failing. In event of cardiac
                         arrest apply external cardiac massage. Obtain immediate medical attention.
Further medical advice Symptomatic and supportive therapy is indicated. Cardiac sensitisation has been described which
                         may, in the presence of circulating catecholamines such as adrenalin, give rise to cardiac
                         arrhythmia’s and subsequent arrest following exposure to high concentrations.
Long term exposure       A lifetime inhalation study in rats has shown that exposure to 50,000 ppm resulted in benign
                         tumours of the testis. This is not considered to be of relevance to humans exposed to
                         concentrations at or below the occupational exposure limit.
Occupational exposure Recommended limit: 1000 ppm v/v - 8 hr TWA.
limits
Stability                Not specified.
Conditions to avoid      Use in presence of naked flames, red hot surfaces and high moisture levels.
Hazardous reactions      May react violently with sodium, potassium, barium and other alkali and alkaline earth metals.
                         Incompatible materials: Magnesium and alloys containing more then 2% magnesium.
Hazardous                Halogen acids by thermal decomposition and hydrolysis.
decomposition
products
General precautions      Avoid inhalation of high concentrations of vapours. Atmospheric concentrations should be
                         minimised and kept as low as reasonably practicable below the occupational exposure limit. The
                         vapour is heavier than air and collects at low level and in confined areas. Ventilate by extraction at
                         lowest levels.
Respiratory protection Where doubt exists on atmospheric concentration, HSE approved breathing apparatus should be
                         worn. This should be self contained or of the long breather type.
Storage                  Keep containers dry and in a cool place away from fire risk, direct sunlight, and all sources of heat
                         such as radiators. Keep at temperatures not exceeding 45 °C.
Protective clothing      Wear overalls, impervious gloves and goggles/face protection.
Spill/leak procedure     Ensure suitable personal protective clothing and respiratory protection is worn. Provided it is safe
                         to do so, isolate the source of the leak. Allow small spillage’s to evaporate provided there is
                         suitable ventilation.
                         Large spillage’s: Ventilate area. Contain spillage’s with sand, earth or any suitable absorbent
                         material. Prevent liquid from entering drains, sewers, basements and work pits since vapour may
                         create a suffocating atmosphere.
Disposal                 Best to recover and recycle. If this is not possible, destruction is to be in an approved facility which
                         is equipped to absorb and neutralise acids and other toxic processing products.
Fire extinguishing data Non-flammable at atmospheric conditions.
Containers               Fire exposed containers should be kept cool with water sprays. Containers may burst if
                         overheated.
Fire fighting protective Self contained breathing apparatus and protective clothing must be worn in fire conditions.
equipment




1-4
                                                                                            035-21786-100 Rev. 1 (0909)




Thermal and Acoustic Materials Data
Health Hazard & First      Toxicity Index <10 to NES713 Issue 3 (1991): Non-hazardous, non-toxic. No first aid necessary.
Aid
Stability / Reactivity     Stable.
Handling / Use /           No special handling precautions required. Dispose of according to local laws and regulations
Disposal                   governing non-biodegradable non-hazardous solid wastes.
Fire & Explosion           Flammability rating Class 1 to BS 476 pt 7: Non-flammable. If forced to burn, combustion products
                           are typically over 95% carbon dioxide and carbon monoxide.


Refrigerant Oil Data:

Safety Data                                      York "Y" Oil

Hazardous Ingredients / Identity Information
Hazardous Components (Specific Chemical         No hazardous materials present.
Identity, Common Name)                          CHEMICAL NAME:           Polyole ester and Lubricating oil additive
                                                COMPONENT :              Polyole ester >99mass%
                                                Lubricating oil additive <1mass%
                                                OSHA PEL                 ACGIH TLV

Physical Characteristics
Boiling Point                                   Not applicable
Vapor Pressure (mmHg)                           Not applicable
Vapor Density (AIR=1)                           Not applicable
Appearance and Odor                             Light yellow, clear mobile liquid
Specific Gravity (H.0=1)                        1.0230g/cm³(15)
Melting Point (Pour point)                      -27.5
Evaporation Rate                                Not applicable

Fire and Explosion Hazard Data
Flash Point (Method Used)                       250 (COC)
Flammable limits                                No information    LEL      UEL
Extinguishing Media                             Foam, dry chemical, carbon dioxide
Special Fire Fighting Procedures                No
Unusual Fire and Explosion Hazards              Not in particular. Normal protective measures for organic chemical products
                                                with flash points of above 100

Reactivity Data
Stability                                       Stable
Incompatibility (Materials to Avoid)            No
Hazardous Decomposition or By-products          No
Hazardous Polymerization                        Will not occur




                                                                                                                        1-5
035-21786-100 Rev. 1 (0909)




 Health Hazard Data
 Route(s) of Entry                             No significant health hazards are identified. Prolonged repeated skin
                                               contact may cause irritation and dermatitis
 Health Hazards (Acute and Chronic)            No significant health hazards are identified. Prolonged repeated skin
                                               contact may cause irritation and dermatitis
 Carcinogenicity                               NTP: No           IARC Monographs: No         OSHA Regulated: No
 Signs and Symptoms of Exposure                No information is available
 Medical Conditions Generally Aggravated       No information is available
 by Exposure
 Skin Contact                                  Wash material off the skin with copious amounts of water and soap
 Eyes Contact                                  Immediately flush with plenty of water for at least 15 minutes
 Inhalation                                    Remove exposed person to fresh air
 Ingestion                                     Do not induce vomiting. Call a physician immediately

 Precautions for Safe Handling and Use
 Steps to be Taken In Case Material is         Prevent spillage from spreading by using sand and absorb the liquid
 Released or Spilled                           substance using a suitable inert material. Transfer to a suitably labelled
                                               sealable container. Do not allow liquid to enter open waters or ground
                                               water.
 Waste Disposal Method                         Waste material may be incinerated under conditions which meet all Federal,
                                               state and local environmental control regulations.
 Precautions to be Taken in Handling and       Store in cool, dark and low humidity place.
 Storing
 Other Precautions                             Avoid repeated skin contact and breathing of mist or vapour.

 Control Measures
 Respiratory Protection                        Under normal conditions, respirator is not usually required.
 Ventilation                                   Local Exhaust              Not required
                                               Mechanical (General)       Not required
                                               Special                    Adequate ventilation should be maintained
                                                                          when handling heated products
 Protective Gloves                             Rubber gloves
 Eye Protection                                Glasses or goggles
 Other Protective Clothing or Equipment        Not required
 Work/Hygienic Practices                       Not required

 Additional Information
 The information contained herein has been compiled from data published in the literature. This data is believed to be
 reliable, but certain values may vary from source to source.
 This data is not to be construed as absolutely complete. It is the responsibility of the user to determine the best
 precautions necessary for his/her application.
 This data only refers to the specific material designated and not to any combinations.




1-6
                                                                                       035-21786-100 Rev. 1 (0909)




                                                                                                       4

                                                5
                                                                                                           1




                                                                                                               2



    1   Compressor
    2   Evaporator
    3   Condenser (YCSE only)
    4   Power Section
                                                        3
    5   Control Panel



                                                             2.3   Refrigerant Circuits
2       PRODUCT DESCRIPTION
                                                             Depending on model size, one or two independent
2.1     Introduction                                         refrigerant circuits are provided on each unit. Each
                                                             circuit uses copper refrigerant pipe formed on computer
YORK YCSE/YCRE R407C chillers are designed for               controlled bending machines to reduce the number of
water or water-glycol cooling. It is designed for indoor     brazed joints resulting in a reliable and leak resistant
installation in a plant room. Units are available with one   system.
or two independent refrigerant circuits with a single
evaporator and, on YCSE models, a single condenser.          Liquid line components include a service valve, a high
Units are completely factory assembled with all              absorption filter dryer, a sight glass with moisture
interconnecting refrigerant piping and wiring ready for      indicator and an electronic expansion valve.
field installation. The units are pressure tested,
evacuated, and fully factory charged with refrigerant        Suction line components include an optional service
R407C and oil in each of the independent refrigerant         and isolation valve.
circuits. After assembly, an operational test is
performed with water flowing through the evaporator          Discharge line components include a check valve, an
and condenser (YCSE) to ensure that each refrigerant         optional service and isolation valve and a pressure relief
circuit operates correctly.                                  valve.

2.2     Compressor                                           2.4   Evaporator

The unit has suction cooled, semi-hermetic screw             The evaporator is a stainless steel brazed type plate
compressors. The compressors incorporate twin-screw          heat exchanger. The waterside design working
rotors and solenoid valves for continuous capacity           pressure is 10 barg. The refrigerant side design working
control. The compressors are equipped with a built-in oil    pressure is 18 bar g. The cooler is thermally insulated
separator, an oil sight glass, a crankcase oil heater and    with flexible closed cell foam. Water connection to the
a suction filter. The compressors have a 2-pole motor        evaporator is via victaulic-grooved connections. Flange
with over current and thermostat protection. Start / Delta   connections are available as an option.
starting is provided as standard. All compressors are
mounted on isolator pads to reduce transmission of           2.5    Condenser (YCSE Only)
vibration to the rest of the unit.
                                                             The condenser is a stainless steel brazed type plate
Capacity Control                                             heat exchanger. The waterside design working
                                                             pressure is 10 barg. The refrigerant side design working
For YCSE/YCRE units, the compressors will start at the       pressure is 30 bar g. Water connection to the condenser
minimum load position and provide a capacity control         is via victaulic-grooved connections. Flange
range from 15% to 100 % per compressor using a               connections are available as an option.
continuous function slide valve.




                                                                                                                   2-1
035-21786-100 Rev. 1 (0909)



                                                            2.7   Accessories and Options

                                                            Modbus
       1       2-Pole Motor
       2       Built-in Oil Separator                       To integrate the unit into the building management
       3       Twin Screw Rotors                            system. The interface permits the connection of up to 8
       4       Oil Sight Glass                              units using the Modbus communications protocol. Refer
       5       Oil Heater
                                                            to HARC Modbus data sheet (035-22384-000).
       6       Suction Filter

                                                            Lonworks
                                        2

                                                            To integrate the unit into the building management
                                                            system. The interface permits the connection of up to 8
                                                            units using the Lon communications protocol. Refer to
           1
                                                            HARC Lonworks data sheet (035-22383-000).

                                                            Multi Unit Sequencer - CSC-5S

                                                            Provides individual control and monitoring for up to 8
                                                        3
                                                            units within the air conditioning system. This allows the
                                                            units to be managed remotely from the plant room.
                                                    4
           6
                                                   5        Compressor Circuit Breakers

                                                            Circuit breakers to replace the standard fuses for
                                                            protection against over current. The breakers provide
                                                            more precise monitoring than fuses and easy reset after
                                                            fault.
2.6   Power and Control Panels
                                                            Differential Water Pressure Switch (es)
All power and controls are contained in an IP2X cabinet
with hinged and gasket sealed outer doors.                  Differential pressure switches between the water inlet
                                                            and outlets to ensure liquid flow during operation.
The power section includes
                                                            Flow Switch (es)
A factory mounted non-fused disconnect switch with
external handle to enable connection of the unit power      Field installed flow switches to ensure liquid flow during
supply. The disconnect switch can be used to isolate the    operation.
power for servicing.
                                                            Glycol Cooling
Factory mounted compressor contactors, fuses and
over current relays to provide overload and short circuit   Factory set-up for applications requiring water outlet
protection.                                                 temperatures below 5°C: Category 1: Outlet
                                                            temperature 0 to 4°C; Category 2: Outlet temperature -1
The control section includes                                to - 5°C and Category 3: Outlet temperature - 6 to - 10°C.
                                                            The system must have the correct percentage of glycol
Four 7-segment LED display                                  added. (Refer to glycol application factors)

Four push button switches                                   Discharge and/or Suction Stop Valves

LED indicators for power, operation and alarm status        Factory fitted valve(s) to allow refrigerant isolation
                                                            during servicing.
Customer terminal block for control inputs and liquid
flow switch connection                                      Compressor Safety Valve(s)

Microprocessor boards to provide automatic operation        Factory fitted single or dual compressor safety valve(s).
and accurate temperature control.




2-2
                                                                                                    035-21786-100 Rev. 1 (0909)



Dual Pressure Relief Valves                                             AVM (Spring Isolators)

Two safety valves in parallel of which one is operational               Spring and cage type isolators for mounting under the
to assist in valve replacement during maintenance.                      unit base rails to avoid transmission of vibration to the
                                                                        plant room structure (supplied loose with unit for field
Suction Pressure Relief Valves                                          assembly)

Additional pressure relief valve on suction side of                     Water Filter
compressor when required.
                                                                        Field installed water filter at the cooler inlet to protect the
PN16 Flanges                                                            exchanger from excessive fouling.Wooden Crate

Welded PN16 flanges and companion flanges on the                        Special packing in a wooden crate to protect the chiller
water connections with gasket seals.                                    from damages during transportation

AVM (Resilient Pads)                                                    Heat Pump Kit (YCSE only)

Rubber anti-vibration pads underneath the unit to avoid                 Capability to control the chiller based on the condenser
transmission of vibration to the plant room structure.                  leaving water temperature.

2.8    Nomenclature




           YCSE100SB50B
   1   2   3   4                           5     6      7          7   8                            9   10 11
 BASE PRODUCT TYPE                        NOMINAL CAPACITY        UNIT DESIGNATOR / REFRIGERANT    VOLTAGE   DESIGN SERIES


   Y                 : York                 #     #     #    kW    S        : Standard Unit         5    0        : 380-415 / 3 / 50 + N
       C             : Chiller            Standard Units                B   : R407C Refrigerant               B   : Design Level
           S         : S = Screw          :040   :050 :060
                     : R = Remote Air     :080   :100
                           Cooled Screw
               E     : European




Refigerant Flow Diagram

YCSE

Low-pressure liquid refrigerant enters the cooler and is evaporated and superheated by the heat energy absorbed
from the chilled liquid passing through the cooler plates. Low-pressure vapour enters the compressors where
pressure and superheat are increased. High pressure superheated refrigerant enters the condenser where heat is
rejected to the condenser water passing through the plates. The fully condensed and subcooled liquid leaves the
condenser and enters the expansion valve, where pressure reduction and further cooling takes place. The
low-pressure liquid refrigerant then returns to the cooler.

YCRE

Low pressure liquid refrigerant enters the cooler and is evaporated and superheated by the heat energy absorbed
from the chilled water passing through the cooler plates. Low pressure vapour enters the compressor where
pressure and superheat are increased. Heat is rejected by the remote condenser. The fully condensed and
subcooled liquid refrigerant then enters the expansion valve where pressure reduction and further cooling takes
place before returning to the cooler.




                                                                                                                                           2-3
035-21786-100 Rev. 1 (0909)



2.9   Refrigerant Flow Diagram

YCSE 040, 050, 060, 100 Models




       1   Compressor                              16   Compressor Safety Valve (Option)
       2   Check Valve                             17   Compressor Dual Safety Valve (Option)
       3   Pressure Relief Valve                   18   Thermistor - Suction
       4   Stop Valve (Option)                     19   Thermistor - Discharge
       5   Condenser                               20   Thermistor - Evaporator
       6   Stop Valve - Refrigerant Charge Point   21   Thermistor - Evaporator Water Inlet
       7   Stop Valve                              22   Thermistor - Evaporator Water Oulet
       8   Drier                                   23   Thermistor - Evaporator Water Oulet
       9   Sight Glass                             24   Thermistor - Condenser Water Inlet (Option)
      10   Electronic Expansion Valve              25   Thermistor - Condenser Water Outlet (Option)
      11   Evaporator                              26   Condenser Water Outlet
      12   Stop Valve (Option)                     27   Condenser Water Inlet
      13   Low Pressure Sensor                     28   Evaporator Water Inlet
      14   High Pressure Switch                    29   Evaporator Water Outlet
      15   High Pressure Sensor



2-4
                                                                              035-21786-100 Rev. 1 (0909)



YCSE 080 Models




       1    Compressor                              18   Pressure Switch
       2    Check Valve                             19   Solenoid Valve
       3    Pressure Relief Valve                   20   Capillary Tube
       4    Stop Valve (Option)                     21   Economiser
       5    Condenser                               22   Strainer
       6    Stop Valve - Refrigerant Charge Point   23   Thermistor - Suction
       7    Stop Valve                              24   Thermistor - Discharge
       8    Drier                                   25   Thermistor - Evaporator
       9    Sight Glass                             26   Thermistor - Evaporator Water Inlet
       10   Electronic Expansion Valve              27   Thermistor - Evaporator Water Oulet
       11   Evaporator                              28   Thermistor - Evaporator Water Oulet
       12   Stop Valve (Option)                     29   Thermistor - Condenser Water Inlet (Option)
       13   Low Pressure Sensor                     30   Thermistor - Condenser Water Outlet (Option)
       14   High Pressure Switch                    31   Condenser Water Outlet
       15   High Pressure Sensor                    32   Condenser Water Inlet
       16   Compressor Safety Valve (Option)        33   Evaporator Water Inlet
       17   Compressor Dual Safety Valve (Option)   34   Evaporator Water Outlet



                                                                                                        2-5
035-21786-100 Rev. 1 (0909)



YCRE 040, 050, 060, 080, 100 Models




       1   Compressor                               15   High Pressure Sensor
       2   Stop Valve                               16   Compressor Safety Valve (Option)
       3   Check Valve                              17   Compressor Dual Safety Valve (Option)
       4   Pressure Relief Valve (Field Supplied)   18   Thermistor - Suction
       5   Remote Condenser (Field Supplied)        19   Thermistor - Discharge
       6   Stop Valve                               20   Thermistor - Evaporator
       7   Drier                                    21   Thermistor - Evaporator Water Inlet
       8   Solenoid Valve                           22   Thermistor - Evaporator Water Oulet
       9   Sight Glass                              23   Thermistor - Evaporator Water Oulet
      10   Expansion Valve                          24   Evaporator Water Inlet
      11   Evaporator                               25   Evaporator Water Outlet
      12   Stop Valve (Option)                      26   YCRE
      13   Low Pressure Sensor                      27   Field Supplied
      14   High Pressure Switch




2-6
                                                                                             035-21786-100 Rev. 1 (0909)




3        TRANSPORTATION, HANDLING AND                             3.2   Inspection
         STORAGE
                                                                  Remove any transit packing and inspect the unit to
                                                                  ensure that all components have been delivered and
3.1      Delivery and Storage                                     that no damage has occurred during transit. If any
                                                                  damage is evident, it should be noted on the shipment
To ensure consistent quality and maximum reliability, all         documentation and a claim entered according to the
units are tested and inspected before leaving the                 instructions given.
factory. Units are shipped completely assembled and
containing refrigerant under pressure. Units are                  Major damage must be reported immediately to your
shipped without export crating unless this has been               local Johnson Controls representative.
specified on the Sales Order.
                                                                  3.3   Moving the Unit
If the unit is to be put into storage, before installation, the
following precautions should be observed:                         Before moving the unit, ensure that the installation site is
                                                                  suitable for installing the unit and is capable of
Ensure that all openings, such as water connections,              supporting the weight of the unit and all associated
are securely capped.                                              services.
Do not store where exposed to ambient air                         The units are designed to be moved using either lifting
temperatures exceeding 42°C.                                      chains or rollers .
The unit should be stored in a location where there is            Lifting by Crane/Hoist
minimal activity to limit the risk of accidental physical
damage.                                                           Attach the lifting chains to the lifting lugs on each corner
                                                                  of the unit framework. A spreader frame should be used
To prevent inadvertent operation of the pressure relief           to prevent damage to the unit from the lifting chains.
devices the unit must not be steam cleaned.
                                                                            The unit must only be lifted at the points
It is recommended that the unit is periodically inspected                   provided.
during storage.




    1   60° (or more)
    2   Power Section
    3   4 x Rigging Bolts
    4   Spreader Bars




                                                                                                                        3-1
035-21786-100 Rev. 1 (0909)



Moving the Unit with Rollers                               To prevent the unit tipping over do not tilt the
                                                           unit more than 15°.
Use at least 6 equal sized rollers under the base frame.
Each roller must support both outer frames. Ensure the
unit is balanced evenly on all the rollers.




                                                            <15°




3.4   Lifting Weights

For details of weights and weight distribution refer to
Section 9.

3.5   Weight Distribution & Centre of Gravity




3-2
                                                                                                              035-21786-100 Rev. 1 (0909)




4                   INSTALLATION                                                   transmitted vibration levels are required optional
                                                                                   anti-vibration isolators can be supplied loose for site
4.1                 Location Requirements                                          installation.

To achieve optimum performance and trouble-free                                    4.2    Installation of Vibration Isolators
service, it is essential that the proposed installation site
meets with the location and space requirements for the                             An optional set of spring and cage or rubber mat type
model being installed. For dimensions, weight and                                  vibration isolators can be supplied loose with each unit.
space requirements, including service access details,                              Installation drawings are attached inside the power and
refer to Section 9.                                                                control panel.

                            The clearances recommended are nominal                            Only spring and cage or rubber mat type
                            for the safe operation and maintenance of the                     vibration isolators can be installed. Do not
                            unit and power and control panels. Local                          install both types of vibration isolator together.
                            health and safety regulations, or practical
                            considerations for service replacement of
                            large components, may require larger                   4.3    Pipework Connection
                            clearances than those given in Section 9.
                                                                                   General Requirements
Units are designed for indoor installation and not
intended for wet, corrosive or explosive atmospheres.                              The following piping recommendations are intended to
Installation should allow for water drain, ventilation and                         ensure satisfactory operation of the unit. Failure to
sufficient clearance for service.                                                  follow these recommendations could cause damage to
                                                                                   the unit, or loss of performance, and may invalidate the
For installation in equipment rooms near noise-critical                            warranty.
areas, common walls should be of adequate sound
attenuating construction, all doors should be tightly                                         The maximum flow rate and pressure drop for
gasketed, and the unit should have vibration isolators                                        the cooler and condenser must not be
fitted.                                                                                       exceeded at any time.
                                                                                              Refer to Section 9 for details.


                                                                                   n     The water must enter the heat exchangers by the
                                                                                         inlet connection. Refer to Section 9 for details.

                                                                                   n     A flow switch must be installed in the customer
                                                                                         pipework at the outlet of the exchangers as shown
                                                                                         in the arrangement diagrams, and wired back to the
 150 - 200 mm                                                       150 - 200 mm
                                                                                         control panel using screened cable. For details
                                                                                         refer to “Electrical Connection”. This is to prevent
                                                                                         damage to the exchanges caused inadequate
                                                                                         liquid flow.
                3   4   5       2      1                       2    1
                                                                                   n     The flow switch used must have gold plated
The unit must be installed on a suitable flat and level                                  contacts for low voltage/current operation. Paddle
concrete base (2) that extends to fully support the unit                                 type flow switches suitable for 10 barg working
base frame.                                                                              pressure can be obtained from Johnson Controls
                                                                                         as an option for the unit.
On basement foundations remove a portion of the
basement floor (3) so that a concrete base can be                                  n     The liquid pump(s) installed in the pipework
poured resting on the ground (1) , with a corkboard (4)                                  system(s) should discharge directly into the unit
installed on both sides, and a waterproof sealing                                        heat exchanger section of the system. The
compound (5).                                                                            pump(s) require an auto-starter (by others) to be
                                                                                         wired to the control panel. For details refer to
The concrete base must capable of supporting 150% of                                     “Electrical Connection”.
the operating weight. In case of upper floors, the unit
and piping should be isolated from walls and ceiling. The
unit may be bolted to the foundation using 13 mm Ø
holes in the base of the framework. When lower



                                                                                                                                          4-1
035-21786-100 Rev. 1 (0909)



n     Pipework and fittings must be separately                         Any debris left in the water pipework between
      supported to prevent any loading on the heat                     the strainer and heat exchanger could cause
      exchanger(s). Flexible connections are                           serious damage to the plates in the heat
      recommended which will also minimise                             exchanger and must be avoided. The
      transmission of vibrations to the building. Flexible             installer/user must also ensure that the quality
      connections must be used if the unit is mounted on               of the water in circulation is adequate, without
      anti-vibration mounts as some movement of the                    any dissolved gasses which can cause
      unit can be expected in normal operation.                        oxidation of steel parts within the heat
                                                                       exchanger(s).
n     Pipework and fittings immediately next to the heat
      exchangers should be readily de-mountable to            4.4   Water Treatment
      enable cleaning prior to operation, and to facilitate
      visual inspection of the exchanger nozzles.                      The unit performance given in the Design
                                                                       Guide is based on a fouling factor of 0.044
n     Each heat exchanger must be protected by a 20                    m² °C/kW. Dirt, scale, grease and certain
      mesh strainer, available as an option, fitted as                 types of water treatment will adversely affect
      close as possible to the liquid inlet connection, and            the heat exchanger surfaces and therefore
      provided with a means of local isolation.                        unit performance. Foreign matter in the water
                                                                       system(s) can increase the heat exchanger
n     The heat exchanger(s) must not be exposed to                     pressure drop, reducing the flow rate and
      flushing velocities or debris released during                    causing potential damage to the heat
      flushing. It is recommended that a suitably sized                exchanger plates.
      by-pass and valve arrangement is installed to allow
      flushing of the pipework system. The by-pass can        Aerated, brackish or salt water is not recommended for
      be used during maintenance to isolate the heat          use in the water system(s). JCI recommend that a water
      exchanger without disrupting flow to other units. Do    treatment specialist is consulted to determine that the
      not exceed heat exchanger design pressures              proposed water composition will not affect the
      during water side pressure tests.                       evaporator materials of stainless steel. The pH value of
                                                              the water flowing through the heat exchangers must be
n     Thermometer and pressure gauge connections              kept between 7 and 8.5. The total installed sytem
      should be provided on the inlet and outlet              including pumps, cooling coils, pipework, couplings and
      connections of each heat exchanger.                     chiller should be assesed with regards to correct water
                                                              treatment. Poor or incorrect water treatment can lead to
n     Drain and air vent connections should be provided       warranty being avoided.
      at all low and high points in the pipework to permit
      drainage of the system, and to vent any air in the      Glycol Solutions
      pipes.
                                                              For unit operation with chilled liquid temperatures
n     Liquid systems at risk of freezing, due to low          leaving the cooler at below 5°C, glycol solutions should
      ambient temperatures, should be protected using         be used to help prevent freezing. Section 9, gives
      insulation and heater ta

Показано початок документа. Повний текст — у PDF за посиланням вище.

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.