Code No. LIT-1922410
Issued February 1, 2009
S351
Humidity Stage Module
Description Features
The S351 Stage Module is used in conjunction • humidification or dehumidification mode,
with the W351 Humidity Control to add field selectable
multiple staging capability. Using a Y350R, up • adjustable differential and offset
to five S351s can be added to the W351 via • 5-pin connectors eliminate wiring between
the 5-pin, plug-together connector. Using a modules
24 VAC or greater external transformer, up to
nine S351s can be added. The S351 has an Applications
SPDT output relay and three adjustments
Use for multiple staging for humidification/
including offset (de-energize stage action from
dehumidification of clean rooms, computer
setpoint), humidification or dehumidification
rooms, or space humidity control.
mode, and differential.
.
Offset Differential
Potentiometer Potentiometer
Module S351
Connector
Module Jumper Block
Connector Position
Humidification Selection Chart
Relay Energized
Dehumidification Code Number Output Differential Offset
LED Indicator
Relay S351AA-1C SPDT Relay 2 to 10% RH 2 to 30% RH
N.C. COM N.O. s3511.eps 0.145 Mounting Slot
Relay Output Terminals 3.68 For #6 Screws
Interior of S351 0 .5
13
2.94
Technical Specifications 75
DIN 5.00 S351
S351 Humidity Stage Module with Percent RH Scale Rail 127 ON
Case and Cover Material NEMA 1, high-impact thermoplastic
Supply Voltage 24 volt power supply provided by Y350R or
external 24 VAC transformer
Power Consumption 1 VA max.
Ambient Operating -30 to 150°F (-34 to 66°C)
Temperature Shipping -40 to 185°F (-40 to 85°C) 1.56 0.42 2.40
40 11 61
Ambient Operating 10 to 90% RH non-condensing 1.20
Humidity Shipping 0 to 95% RH non-condensing 31
Relay SPDT enclosed relays, contacts rated at
10 amp non-inductive, 1/2 hp, 120/240 VAC
Mounting Surface or DIN rail
2.40
Relay Contact Ratings 61
Voltage, AC 120 208/240 0.85
Full Load Amp 9.8 4.9 22
s3512.eps
Locked Rotor Amp 58.8 29.4 0 .8 7 5 Conduit
Non-Inductive Amp 10 at 24/240 VAC 22 Hole
Pilot Duty – 125 VA at 24/240 VAC S351 Dimensions, in. (mm)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc. www.johnsoncontrols.com