FX16 Master Controller Product Bulletin
                                                                                           Issued May 8 2007

                                    FX16 Master Controller

The FX16 Master Controller is a high performance             The FX16 Master Controller is fully configurable or
field controller in the Facility Explorer platform. The      programmable, using the FX Tools software package,
FX16 is designed for commercial Heating, Ventilating,        for a wide range of commercial HVAC and
Air Conditioning, and Refrigeration (HVACR)                  refrigeration applications.
applications, such as chillers, rooftop units, packaged
air conditioning units, Air Handling Units (AHUs), and       N2 Open or LONWORKS® communication cards are
close control units, as well as small distributed control    available with the FX16 Master Controller for the
systems with terminal units.                                 integration of the controller into a compatible Building
                                                             Automation System (BAS).
The FX16 has 27 physical inputs and outputs and
supports a wide range of temperature sensors and
actuator devices. Up to 64 additional physical inputs
and outputs can be added using XT/XP expansion
modules. The FX16 can manage a distributed control
application with up to 16 slave FX controllers (FX05,
FX06, FX07, FX14, or FX15). The FX16 can also
monitor and control a number of N2 Open compatible
devices through its gateway feature. Parameters in a
distributed control application can be displayed and
modified from optional integral or remote user
interfaces.

The FX16 also features communications services to
transmit event notification text messages via Short                    Figure 1: FX16 Master Controller
Messaging Service (SMS) or by e-mail. With its
onboard Web server, you can browse and make
adjustments to the application from a remote location.
                                               Features and Benefits
      Optional Integral or Remote User         Provide a clear presentation of control system data on a
      Interfaces (UIs)                         menu-driven, scrolling, 4 line by 26 character Liquid Crystal
                                               Display (LCD) with backlight.

      Distributed Control Application          Provides the ability to control complex systems by coordinating the
                                               activities of multiple controllers in a single application.

      Embedded Web Server                      Allows remote access to the data in the control system via a Web
                                               browser and modem connection to the FX16 Master Controller.

      Communication Services                   Provide automatic reporting of events and alarms by e-mail or by
                                               Short Message Service (SMS) with optional acknowledgement.

      Network Communications                   Provide a cost effective method for stand-alone or networked
      Options – N2 Open and                    operation.
      LONWORKS Protocol
 Continued on next page . . .

© 2007 Johnson Controls, Inc.                                                                                           1
  Code No. LIT-12011084
                                        Features and Benefits (Cont.)
     Freely Programmable or                   Is suitable for a wide range of applications for environmental and
     Configurable Using FX Tools              refrigeration control using the extensive programming features of
                                              the FX Tools software package.

     Onboard Trend and Event                  Provide the necessary information for analyzing the control system
     Logging                                  performance and diagnosing fault conditions.

     Analog Input Types Selected in           Allows choice of temperature and other sensors according to the
     Software                                 control range and application.

2   FX16 Master Controller Product Bulletin
                                                         The FX16 Master Controller provides the formatted
Onboard Inputs and Outputs (I/Os)                        data for the requested pages starting with a home
Up to 27 physical inputs and outputs can be              page from which other pages can be requested. Each
connected to the FX16 Master Controller, including:      page may contain graphic images, links to the other
                                                         pages, and data windows for the display of live data
•   6 Analog Inputs (AIs) – software configurable        from the control system.
•   8 Digital (Binary) Inputs (DIs) – for voltage free   The active values are transmitted by the embedded
    contacts                                             Web server in the FX16 Master Controller to the
                                                         screen of the computer. Typically up to 16 values can
•   9 Digital (Binary) Outputs (DOs)
                                                         be continuously updated on one page and the user
    −   9 relays with 230 VAC contacts or                may adjust or override values on the screen. Access
                                                         to the Web pages is protected by a password system
    −   4 relays and 5 opto-isolated Triacs for 24 VAC   to prevent unauthorized data access and control
•   4 Analog Outputs (AOs) – 0 to10 VDC                  actions.
                                                         In summary, the Web server interface provides the
Scalable I/O Expansions                                  following features from any computer directly
The input/output capacity of the FX16 Master             connected to the FX16 Master Controller or has
Controller may be extended by connecting up to four      access to the telephone system. The Web server
XT extension modules via the Local Link Bus.             interface:

Expansion Modules (XPs) provide input and output         •   displays live variables in the monitored control
capabilities for the XT extension modules, as follows:       system

•   XT91D00      Processor/Communication Module          •   adjusts and commands variables in the control
                                                             system
•   XP91D02      6 universal AIs + 2 AOs
                                                         •   displays and acknowledges active alarms
•   XP91D03      8 DOs (triacs)
                                                         •   displays the event history log
•   XP91D04      4 DIs + 4 DOs (triacs)
                                                         •   displays trended data values and copy/paste to
•   XP91D05      8 DIs                                       Microsoft Excel spreadsheet for storage and
                                                             further processing
•   XP91D06      4 DOs (relays) 230 VAC (Europe only)
                                                         •   enables and disables trend logs
•   XP91D07 4 DOs (relays) 24 VAC
    (North America only)                                 •   reads and modifies communication parameters
                                                             including e-mail addresses, telephone numbers,
Embedded Web Server and Web                                  and others

Page Access
The FX16 Master Controller features an embedded
Web server that enables a local or remote user to
establish communication with the FX16 Master
Controller from a computer and to browse live control
data, active alarms and events, trend data, and
configuration parameters. This feature provides an
effective, low-cost monitoring system without the need
for any special or proprietary supervisory software.
The Web pages are accessed using a direct serial line
or telephone modem connection and the Point-to-Point
Protocol (PPP) from any computer with Microsoft®
Internet Explorer software that serves as a Web
browser.                                                         Figure 2: Web Page with Trend Data

                                                                    FX16 Master Controller Product Bulletin      3
Communication Services                                    Alternatively, if the user has access to a computer with
                                                          Web browser and modem connection, the control
The FX16 Master Controller can be programmed to           system can be viewed on the Web pages that have
send out e-mail and/or Short Message Service (SMS)        been generated in the FX16 Master Controller.
text messages when connected to a modem and
telephone line or to a GSM modem with an                  You can also use the e-mail service to periodically
appropriate transmitter and antenna. E-mail messages      send trend log data to a remote e-mail receiver for
are directed to an Internet Service Provider (ISP) that   electronic storage and to prevent the loss of data in
offers an e-mail forwarding service. SMS messages         the FX16 Master Controller when the trend buffer
can be sent to a service center or directly to a mobile   is full.
telephone. Messages are sent when an event goes
into the active or alarm state and can be directed to a
prioritized list of destinations.

                                      Figure 3: Communication Services

4   FX16 Master Controller Product Bulletin
                                                           Another benefit of a distributed application is the ability
Distributed Application                                    to combine FX controllers to achieve the inputs and
A distributed application is a control strategy managed    outputs required for the physical equipment interface.
by the FX16 Master Controller but is executed              The application is automatically distributed and
concurrently in the FX16 Master Controller and in up to    executed in the individual controllers forming a single
16 FX slave controllers connected to the Local Link        control system.
Bus. The communication between the controllers is
defined by network variables in the distributed            Gateway Feature
application and the FX16 Master Controller executes
                                                           The latest versions of the FX16X Master Controller
the communication in the most effective way to
                                                           feature a Gateway object. The Gateway object allows
maintain the performance of the entire control system.
                                                           the FX16 to monitor up to 16 N2 Open devices (that
Distributed applications are used for the coordinated      are not slaves in a Distributed Application) on the
control of a central plant and the remote equipment        Local Link Bus. These devices can be FX controllers
that it serves. For example, a distributed application     fitted with an N2 Open communication card, Metasys®
could be applied to an FX16 Master Controller              Application Specific Controllers (ASCs) (UNT, VAV,
controlling an air handling unit, an FX14 controller       AHU), Metasys compatible N2 Open Vendor (VND)
controlling a chiller unit, and a number of FX07           devices, or System 91 N2 devices (DX-9100 and
controllers controlling zone terminal units or fan coil    TC-910x).
units.

                                         Figure 4: Distributed Application

Supervisory Options                                        LONWORKS Network
                                                           When fitted with a LONWORKS Communication Card,
You can integrate the FX16 Master Controller into a
                                                           the FX16 can communicate peer-to-peer with other
supervisory Building Automation System (BAS) for
                                                           LONWORKS compatible devices and provide data
continuous monitoring of the control system. The FX16
                                                           access to a supervisory system.
Master Controller supports two methods of integration:
N2 Open and LONWORKS network.

N2 Open Network
When fitted with an N2 Open Communication Card,
the FX16 can connect to an N2 Open compatible BAS,
providing access to control system variables and
parameters.
                                                                       FX16 Master Controller Product Bulletin       5
Time Scheduling                                             When an event goes into the active state, it is entered
                                                            into the table of active events and the event history log
The FX16 Master Controller has an embedded
                                                            with the time and date of occurrence, and a message
real-time clock that supports all real-time functions
                                                            window appears on the display screen. The event can
including the time and date display on the integral and
                                                            also be configured to send a text message to one or
remote displays, the time stamping of events, and
                                                            more of the following:
trend data. The real-time clock also enables the time
scheduling of start, stop, and occupancy commands           •   E-mail Message Server
for the plant being monitored and controlled.               •   Mobile Telephone with Short Message Service
Scheduled commands may be configured to execute                 (SMS)
on one or more days of the week, and an exception
day calendar allows for alternative time schedules on       The system only removes the events from the table of
holidays or during special periods in the year.             active events when you acknowledge the event and
                                                            the event returns to an inactive or normal state. You
Time schedules may be displayed and edited on the           can acknowledge events from any of the connected
available user interfaces or in a Web page on a Web         user interfaces. Displays and the Web page have
browser screen. The real-time clock is battery backed       password protection. You can view the table of active
with an average battery life of more than 2 years.          events and the event history log on the integral or
                                                            remote displays or on the Web browser screen.

                                                            Data Trend Logging
                                                            The FX16 Master Controller can be configured to
                                                            record data samples at a defined interval for up to
                                                            40 variables within the control application. The sample
                                                            interval is defined for each variable and can be set
                                                            from every minute to once per day. In the latest
                                                            LP-FX16X Rev. A version, the onboard memory can
                                                            store trend log samples from 40 variables at 15 minute
     Figure 5: Occupancy Schedule Definition
                                                            intervals for up to 100 days.
Alarm and Event Management                                  You can view trend data for each variable within a
                                                            specified time period in text format on the connected
The FX16 Master Controller manages and records
                                                            user displays. You can also view trend log data from a
events or errors that are generated by the operating
                                                            Web browser; this allows you to copy and paste trend
system and events or alarms that are associated with
                                                            information into a spreadsheet application, such as
data points or variables in the control application.
                                                            Excel for further processing and electronic storage.
System events indicate to the user that the control
                                                            You can transmit trend logs at regular intervals, from
system requires some attention and include events
                                                            1 hour to every day via the telephone modem
such as:
                                                            connection to an e-mail server. You can also upload
•   system power up                                         Trend data with FX CommPro. FX CommPro then
•   trend buffer full                                       converts the data into a standard format for transfer to
                                                            a computer.
•   communication message failure (E-mail, SMS)
                                                            A system event message is generated if the trend
•   device communication error
                                                            buffer is not configured in the circular recording mode
•   application or display diagnostic error                 and the buffer becomes full.
Application events or alarms indicate to the user that
the controlled equipment requires attention or that the     User Interfaces
controlled conditions are not within the expected limits.   The FX16 Master Controller supports two user
For example:                                                interfaces, which can be integral and remote. These
•   Analog value is outside of a desired range.             user interfaces feature a 4 line by 26 character Liquid
                                                            Crystal Display (LCD), 6 push buttons, and 10 discrete
•   Status value represents a condition that is not         status Light-Emitting Diodes (LEDs). The display and
    normal.                                                 navigation menus are fully programmable within the
                                                            control application using FX Builder.

6   FX16 Master Controller Product Bulletin
The integral Medium User Interface (MUI) is built into    FX Tools Software
the front face of the FX16, allowing direct access to
the control system’s points. FX16 models are available    The FX Tools software suite is used to program,
with and without the Integral MUI.                        download, test, and commission the FX devices,
                                                          including the FX16. FX Tools is available on CD in two
Two versions of the remote Medium User Interface are      versions: FX Tools Pro and FX Tools Express
available for panel or wall mounting:                     (North America only).
•   LP-DIS60P20-0C: You can mount this MUI within
                                                          FX Tools Pro CD includes:
    a panel up to 3 m (10 ft) from the FX16. This user
    interface is powered by the FX16. The LP-KIT007-      •   FX Builder – used to fully program an FX16.
    000C is a flat telephone cable needed to connect          FX Builder provides complete flexibility in
    a power supply and data communications to the             programming the FX16.
    FX16.
                                                          •   FX CommPro N2 – used to download, test, and
•   LP-DIS60P21-0C: You can mount this MUI within             commission an FX16 on an N2 Open network
    a panel or on a wall surface up to 300 m (1,000 ft)
    from the FX16. This user interface must be            •   FX CommPro LON – used to download, test, and
    independently powered. The data communication             commission an FX16 on a LONWORKS network
    requires a 3-wire shielded cable (not provided)       •   FX Builder Express – used to select an FX16
    connected to the FX16’s Remote Display                    application and configure it using graphical
    connection.                                               plug-ins (North America only).
                                                          The FX Builder Express CD does not include
                                                          FX Builder (North America only).

                                                          Application Upload/Download
                                                          With the FX16, you can download and upload a full
                                                          application file to and from the latest LP-FX16X Rev. A
                                                          version using a computer with the FX CommPro N2
           Figure 6: Medium User Interface                tool software. This way, the controller contains all the
                                                          information for you to retrieve, view, and modify the
                                                          application in FX Builder if the archived version of the
Multi-language Database                                   file is not available. You can only download earlier
All the text on the available User Interfaces is fully    versions of the controller with the application operating
programmable and can be entered in up to five             code using FX CommPro, and the full application file
different languages.                                      remains in the FX Builder archive.
The user is then able to select the preferred language
from the display menu when logging into the system.
This feature has been designed for systems intended
for installation in many countries in the world or for
areas where more than one language is spoken.

                                                                     FX16 Master Controller Product Bulletin     7
Dimensions in mm (in.)
                                           215 (8.46)                             49 (1.93)

                                                                                              For Omega Rail DIN/EN 50022 Mounting
       142 (5.59)   122 (4.8)                                                     DIN RAIL

                                B                                 B
       FX16-003_09 2003

                                    Figure 7: FX16 Master Controller Dimensions

8   FX16 Master Controller Product Bulletin
Ordering Codes
Table 1: FX16 Master Controller - Standard Temperature Range Ordering Information
 Product Code      Description
 LP-FX16D00-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), no communications card
 LP-FX16D01-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), N2 Open communications card
 LP-FX16D02-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), LON communications card
 LP-FX16D03-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), RS-232 communications card
 LP-FX16D10-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), no communications card
 LP-FX16D11-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), N2 Open communications card
 LP-FX16D12-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), LON communications card
 LP-FX16D13-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), RS-232 communications card

Table 2: FX16 Master Controller - Extended Temperature Range Controllers (Rev. A) Ordering Information
 Product Code      Description
 LP-FX16X00-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), no communications card
 LP-FX16X01-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), N2 Open communications card
 LP-FX16X02-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), LON communications card
 LP-FX16X03-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), RS-232 communications card
 LP-FX16X50-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), no communications card
 LP-FX16X51-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), N2 Open communications card
 LP-FX16X52-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), LON communications card
 LP-FX16X53-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), RS-232 communications card
 LP-FX16X10-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), no communications card
 LP-FX16X11-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), N2 Open communications card
 LP-FX16X12-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), LON communications card
 LP-FX16X13-000C   FX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), RS-232 communications card
 LP-FX16X60-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), no communications card
 LP-FX16X61-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), N2 Open communications card
 LP-FX16X62-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), LON communications card
 LP-FX16X63-000C   FX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), RS-232 communications card

                                                                         FX16 Master Controller Product Bulletin      9
Table 3: FX16 Communications Cards (for Upgrade or Replacement) Ordering Information
 Product Code        Description
 LP-NET151-010C      N2 Open communication card for LP-FX16D and LP-FX16X (not Rev. A) controllers
 LP-NET161-000C      N2 Open communication card for LP-FX16X Rev. A controllers
 LP-NET152-010C      LON communication card for LP-FX16 controllers
 LP-NET163-000C      RS-232 communication card for LP-FX16 controllers

Table 4: User Interfaces Ordering Information
 Product Code        Description
 LP-DIS60P20-0C      Medium User Interface for FX16 (non-isolated version); Can be mounted up to 3 m (10 ft) from the
                     FX16 and includes panel mounting hardware.
 LP-DIS60P21-0C      Medium User Interface for FX16 (isolated version); Can be mounted up to 300 m (1,000 ft) from the
                     FX16 and includes panel and wall mounting hardware.

Table 5: Accessories Ordering Information
 Product Code        Description
 LP-KIT007-000C      Interface cable 3 m (9.8 ft) for Medium User Interface (LP-DIS60P20-0C) to FX16
 LP-KIT007-001C      Interface cable for standard modem to FX16
 LP-KIT007-013C      Null modem cable, 3 m (9.8 ft)
 LP-KIT007-014C      Null modem cable, 15 m (49 ft)

Table 6: FX16 Accessories - Only Available in Europe Ordering Information
 Product Code         Description
 LP-KIT007-002C       Interface Cable (1.5 m/4.9 ft) for GSM modem to FX16 and Master Display
 LP-KIT090-000C       GSM 900/1800 FastTrack Modem
 LP-KIT090-001C       GSM Modem Plug-in Antenna
 LP-KIT090-003C       GSM Modem Magnetic Mount Antenna with 2.5 m Cable
 LP-KIT090-004C       GSM Modem Panel Mount Antenna with 5 m Cable
 LP-KIT090-005C       GSM Modem Power Adapter, 230 VAC/12 VDC, Wall Plug
 LP-KIT015-001C       Kit of Female Cage Clamp Connectors

Table 7: FX16 Demonstration Cases Ordering Information
 Product Code         Description
 LP-FX16DEM-051C      Demo Case with FX16 Master Controller, display, 9 relays, N2 Open card – 230 VAC power
 LP-FX16DEM-052C      Demo Case with FX16 Master Controller, display, 9 relays, LON card – 230 VAC power
 LP-FX16DEM-053C      Demo Case with FX16 Master Controller, display, 9 relays, RS-232 card – 230 VAC power
 LP-FX16DEM-061C      Demo Case with FX16 Master Controller, display, 9 relays, N2 Open card – 120 VAC power
 LP-FX16DEM-062C      Demo Case with FX16 Master Controller, display, 9 relays, LON card – 120 VAC power
 LP-FX16DEM-063C      Demo Case with FX16 Master Controller, display, 9 relays, RS-232 card – 120 VAC power

10   FX16 Master Controller Product Bulletin
Table 8: Expansion I/O Modules Ordering Information
 Product Code       Description
 LP-XT91D00-000C    Facility Explorer Extension Module
 LP-XP91D02-000C    Facility Explorer Expansion Module - 6 AI, 2 AO
 LP-XP91D03-000C    Facility Explorer Expansion Module - 8 DO (triacs)
 LP-XP91D04-000C    Facility Explorer Expansion Module - 4 DI, 4 DO (triacs)
 LP-XP91D05-000C    Facility Explorer Expansion Module - 8 DI
 LP-XP91D06-000C    Facility Explorer Expansion Module - 4 relays, 230 VAC 3 A (Europe Only)
 LP-XP91D07-000C    Facility Explorer Expansion Module - 4 relays, 24 V 3 A (North America Only)

Table 9: Software Tools Ordering Information
 Product Code       Description
 LP-FXTPRO-0        FX Tools Pro CD (FX Builder, FX Builder Express, FX CommPro N2, LON) - New User
 LP-FXTPRO-6        FX Tools Pro CD (FX Builder, FX Builder Express, FX CommPro N2, LON) - Upgrade
 LP-FXTEXP-0        FX Tools Express CD (FX Builder Express, FX CommPro N2) (North America only)

                                                                         FX16 Master Controller Product Bulletin   11
Technical Specifications
Table 10: I/O Details
 Terminal Block       Channel          Type                   Remark/Application
 Analog Input (AI)
 TB1                  AI1, AI2, AI3,   See following table.   Software configurable
                      AI4, AI5, AI6    16 bit resolution      Application: temperature, humidity, and pressure
                      EXT-VDC          +16 V, 80 mA           0-10 V sensors or max. 4 0/4 - 20 mA sensors
                      AVPS/EXT-        AVPS = +5 V,           Directly power ratiometric sensors with AVPS, or
                      VDC              20 mA                  0-10 V, 0/4 - 20 mA sensors with EXT-VDC
                                       EXT-VDC = +16 V,       AVPS or EXT-VDC selected by jumpers.
                                       80 mA
 Digital Input (DI)
 TB2                  DI1, DI2, DI3,   Potential free         Transition counter at 50 Hz max.
                      DI4, DI5, DI6,   contacts               Minimum time ON: 10 ms. Minimum time OFF: 10 ms
                      DI7, DI8                                Prescaler function: max. division by 100
                      DI V~ Hot        24 VAC                 FX16 (not Rev. A): for isolation of DIs from the
                      DI V~ Com                               microprocessor, a separate 24 VAC power supply is required.

 Digital Output (DO)
 TB3                  DO1, DO2,        SPST 8(3)A power       Max. switching power (relays):
                      DO3              relays                 Motor: 240 W, 0.5 hp, 250 VAC
                                                              Rating (resistive): 8A 125 VAC
                                                                                  8A 30 VDC
                                                                                  8A 250 VAC
                                                              UL tested life (min. operations): 30,000 operations
                                                              (at 360 operations x hour)
                                                              Dielectric strength coil-contacts: 4000 V RMS for 1 minute
 TB4                  DO4, DO5         SPST 5(3)A power       Max. switching power (relays):
                                       relays or              Motor: 150 W, 0.25 hp, 250 VAC
                                       0.5 A/24 VAC triacs    Rating (resistive): 5 A 125 VAC
 TB5                  DO6, DO7,        SPST 5(3)A power                           5 A 30 VAC
                      DO8              relays or                                  5 A 250 VDC
                                       0.5 A/24 VAC triacs    UL tested life (min. operations): 30,000 operations
                                                              (at 360 operations x hour)
                                                              Dielectric strength coil-contacts: 4000 V RMS for 1 minute
 TB6                  DO9              SPDT NC 8(3)A          Same as TB3 relays
                                       250 V relay            Fail relay for enhanced security. The relay returns to its
                                                              Network Controller (NC) position not only at power fail but also
                                                              in case the microprocessor should fail: for example, watch-dog
                                                              or brown-out.
 Analog Output (AO)
 TB7                  AO1, AO2         0 -10 VDC              Used to drive analog actuators, frequency drives; 16 bit
                                       FX16D/FX16X:           resolution.
                                       1.5 mA
                                       FX16X Rev. A: 5 mA
 TB8                  AO3, AO4         0 -10 VDC              Used to drive analog actuators, frequency drives; 16 bit
                                       FX16D/FX16X:           resolution.
                                       1.5 mA
                                       FX16X Rev. A: 5 mA
                      AO V~ Hot        24 VAC                 FX16 (not Rev. A): for isolation of AOs from the
                                                              microprocessor a separate 24 VAC power supply is required.

12   FX16 Master Controller Product Bulletin
                      AO V~ Com

Table 11: Analog Sensor Types
 Sensor Type                      Linearization Range                             Accuracy at 20°C (68° F)
                                                                                  Ambient
 Ni1000 JCI                       -45°C (-49°F) to 120°C (248°F)                  ±0.5°C (±1°F)
 Ni1000 JCI Extended Range        20°C (68°F) to 287°C (548.6°F)                  ±0.5°C (±1°F)
 Ni1000 Siemens® (L&G)            -50°C (-58°F) to 160°C (320°F)                  ±0.5°C (±1°F)
 Ni1000 DIN                       -60°C (-76°F) to 180°C (356°F)                  ±0.5°C (±1°F)
 Pt1000                           -50°C (-58°F) to 605°C (1,121°F)                ±0.5°C (±1°F)
 A99                              -50°C (-58°F) to 110°C (230°F)                  ±0.5°C (±1°F)
 NTC 2.25 k                       -40°C (-40°F) to 150°C (302°F)                  ±0.5°C (±1°F)
 NTC 10 k                         -40°C (-40°F) to 150°C (302°F)                  ±0.5°C (±1°F)
 0 to 5 VDC Ratiometric           10 to 90% of supply voltage (0.5 to 4.5 V       ±0.05 VDC
                                  nominal)
 Active 0 to 10 VDC               0 to 10 Volts                                   ±0.05 VDC
 Active 0 to 20 mA                0 to 20 mA                                      ±0.1 mA

                                                                          FX16 Master Controller Product Bulletin   13
FX16 Master Controller Standard and Extended Range Models
 Product                                      FX16D Master Controller
                                              FX16X Rev. A Master Controller Extended Temperature Range
 Power Supply Requirements                    24 VAC ±15%, 50/60 Hz - Class 2 Power Supply – Safety Extra-Low Voltage (SELV)
                                              in Europe
 Power Consumption                            15 VA at max. load
 Internal Fuse                                2 A, 250 V
 Protection Class                             IP 20
 Ambient Operating Conditions                 FX16D: -20°C (-4°F) to +50°C (122°F) ,10 to 95% RH (noncondensing)
                                              FX16X Extended Temperature Range: -40°C (-40°F) to +60°C (140°F) ,10 to 95%
                                              RH (noncondensing) (Integral Display may not operate below -20°C [-4°F])
 Ambient Storage Conditions                   -40°C (-40°F) to +70°C (158°F), 10 to 95% RH (noncondensing)
 Dimensions (H x W x D)                       142 x 215 x 49 mm (5.6 x 8.5 x 1.9 in.)
 Weight (with package)                        0.74 kg (1.6 lb)
 Connection Terminals for Signals             Screw terminals for max 1 x 1.5 mm2 (16 AWG) wires
 and Power Supply
                                                                                                    2
 N2 Open Bus Connection                       Screw terminals, cable size 0.5 mm to 1.5 mm , 24 AWG to 16 AWG, Belden cable,
 Terminals                                    4-core twisted pair with shield
                                                                                                    2
 LON Network Connection                       Screw terminals, cable size 0.5 mm to 1.5 mm , 24 AWG to 16 AWG, Belden cable,
 Terminals                                    2-core twisted pair with shield
                                                                                                    2
 Connection for Extension Bus                 Screw terminals, cable size 0.5 mm to 1.5 mm , 24 AWG to 16 AWG, Belden cable,
 and Remote Display                           4-core twisted pair with shield
 Compliance                                   Europe             – 89/336/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-1
                                                                 – 72/23/EEC, Low Voltage Directive: EN 60730
                                              Canada             – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
                                                                 – UL Recognized (XAPX8), CAN/CSA C22.2 No. 24, Temperature
                                                                   Indicating and Regulating Equipment
                                                                 – Industry Canada, ICES-003
                                              United             – UL Listed (PAZX), UL 916, Energy Management Equipment
                                              States             – UL Recognized (XAPX2), UL 873, Temperature Indicating and
                                                                   Regulating Equipment
                                                                 – FCC compliant to CFR 47, Part 15, Subpart B, Class A
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, contact a Facility Explorer technical support resource. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.
Federal Communications Commission (FCC) Statement
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC Rules. These limits
are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference, in which case the user will be required to correct the interference at his/her own expense.
Industry Canada (IC) Statement
This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Controls Group Global Headquarters
507 E. Michigan Street
P.O. Box 423                                                                                                  Published in U.S.A. and Europe
Milwaukee, WI 53201

14    FX16 Master Controller Product Bulletin

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.