| Вид документа | Технічний бюлетень |
|---|---|
| Виробник | JCI |
| Код документа | fx15-controller-technical-bulletin |
| Група обладнання | FX15 Field Controller |
| Сторінок | 58 |
| Мова документа | англійська |
| Розмір файлу | 2.2 МБ |
Текст документа
Technical Bulletin FX15 Controller
Issue Date June 9, 2014
FX15 Controller
Introduction to FX15 Controller ............................................................ 3
Key Concepts ...................................................................................................... 4
FX15 Controller ................................................................................................................. 4
Installation .............................................................................................. 5
North American Emissions Compliance............................................................................ 6
Detailed Procedures ........................................................................................... 7
Mounting Instructions ........................................................................................................ 7
Assembling the Integrated MUI......................................................................................... 8
Connection Details .......................................................................................................... 10
Connection Details for I/O Expansion (XT-XP Modules) on Local Extension Bus .......... 13
Connection Details for the N2 Open Card ...................................................................... 13
Connection Details for the LONWORKS Card................................................................... 17
Connection Details for the Remote User Interface ......................................................... 19
Connection Details for the FX Programming Key ........................................................... 22
Inputs and Outputs .............................................................................. 26
Introduction ....................................................................................................... 26
Key Concepts .................................................................................................... 27
Detailed Procedures ......................................................................................... 28
Isolation Diagram ............................................................................................................ 28
FX15 Controller I/Os Powered at 24 VAC....................................................................... 29
Analog Inputs .................................................................................................................. 30
Digital Inputs ................................................................................................................... 36
Analog Outputs ............................................................................................................... 37
Digital Outputs ................................................................................................................ 39
Extension Modules ......................................................................................................... 42
Troubleshooting ................................................................................................ 44
Reading 9999 or Invalid from the Analog Inputs ............................................................. 44
Cannot Properly Read Current Sensors ......................................................................... 44
© 2014 Johnson Controls, Inc. 1
Code No. LIT-12011107 www.johnsoncontrols.com
2 FX15 Controller Technical Bulletin
Operation .............................................................................................. 45
Introduction ....................................................................................................... 45
Key Concepts .................................................................................................... 45
Software Programming and Application Configuration ................................................... 45
Alarm and Event Management ....................................................................................... 46
Time Scheduling ............................................................................................................. 46
User Interfaces ............................................................................................................... 46
Security ........................................................................................................................... 46
Supervisory Option ......................................................................................................... 46
Application Upload/Download ......................................................................................... 46
User Interface ................................................................................................................. 47
Security ........................................................................................................................... 49
Specifications and Technical Data ..................................................... 50
Ordering Codes ................................................................................................. 50
Technical Specifications .................................................................................. 53
I/O Technical Details ....................................................................................................... 53
N2 Open Card ................................................................................................................. 55
LONWORKS Connection................................................................................................... 55
Programming Key ........................................................................................................... 56
FX15 Controller ............................................................................................................... 56
FX15 Extended Range Controller ................................................................................... 57
FX15 Controller Technical Bulletin 3
Introduction to FX15 Controller
Figure 1: FX15 Classic Controller
The FX15 controller is a high performance field controller of the
Facility Explorer system, specifically designed for commercial Heating,
Ventilating, Air Conditioning, and Refrigeration (HVACR) applications
such as chillers and rooftops, indoor packaged air conditioning units, air
handling units, and close control units.
The FX15 controller has 27 physical inputs and outputs and supports a
wide range of temperature sensors and actuating devices. Additional
physical inputs and outputs may be achieved by adding the XT/XP
expansion modules on the local Extension bus.
The FX15 controller is fully programmable or configurable, using the
FX Tools Pro software package, for a wide range of commercial
environmental control applications.
The FX15 controller is also available with a serial communication card
for integration into a Building Automation System with a LONWORKS®
or N2 Open bus network.
For stand-alone applications an onboard, real-time clock circuit is also
included to support the start-stop scheduling of equipment and real-time
based control sequences.
The FX15 controller can be integrated, as a slave device, in a distributed
control application managed by a master controller (FX16 Master
Controller or Master Display).
4 FX15 Controller Technical Bulletin
Optional accessories make the FX15 controller the state of the art
solution for the HVACR market:
• N2 Open plug-in communication card
• LONWORKS plug-in communication card
• user interface: Medium User Interface (MUI) and Large User
Interface (LUI)
Key Concepts
FX15 Controller
Features
• fully programmable using FX Tools package
• interchangeable RS-485, N2 Open, or LONWORKS FTT10
communication cards for supervisory system
• DIN rail mounting
• female connector option: screw or spring clamp connectors
• Input/Output (I/O) expansion modules
• optional user interfaces: integrated, local, or remote
• events displayed on user interface (up to 12 events)
• easy commissioning via proprietary commissioning tool
• Programming Key for easy application uploading and downloading
FX15 Controller Technical Bulletin 5
Installation
This chapter describes the process of installing an FX15 controller.
179 (7.05) 66 (2.6)
49 (1.93)
142 (5.59)
75 (2.95)
44 (1.73) 122 (4.8) 35 (1.38)
B B
215 (8.46)
Figure 2: Mounting Dimensions for FX15 Controller, mm (in.)
(Shown with Integral User Interface and Screw Connectors)
180.5 (7.11)
46.5 (1.83)
Panel cut-out
Figure 3: Panel Cut-Out Dimensions for User Interfaces, mm (in.)
Two different types of terminal connectors are available: spring clamp
or screw connectors. The screw connectors are included, whereas the
spring clamp connectors must be ordered separately. For details, see
Ordering Codes.
6 FX15 Controller Technical Bulletin
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for
a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy, and if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is
likely to cause harmful interference, in which case the user will be
required to correct the interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the
Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du
Règlement sur le matériel brouilleur du Canada.
FX15 Controller Technical Bulletin 7
Detailed Procedures
Follow these instructions to properly install and connect the FX15
controller.
! WARNING: Risk of Electric Shock. Disconnect or isolate all power
supplies before making electrical connections. More than one disconnect or
isolation may be required to completely de-energize equipment. Contact with
components carrying hazardous voltage can cause electric shock and may
result in severe personal injury or death.
AVERTISSEMENT: Risque de décharge électrique. Débrancher ou isoler
toute alimentation avant de réaliser un branchement électrique. Plusieurs
isolations et débranchements sont peut-être nécessaires pour-couper
entièrement l'alimentation de l'équipement. Tout contact avec des composants
conducteurs de tensions dangereuses risque d'entraîner une décharge
électrique et de provoquer des blessures graves, voire mortelles.
Mounting Instructions
To mount an FX15 controller:
1. Snap the controller onto the 35 mm (1.38 in.) rail for DIN rail
mounting. To release the controller, insert a screwdriver in Slots B
and lift the retaining clip. Since the retaining clip is spring-loaded,
you can also remove the controller without a screwdriver by
carefully pushing the controller up against the clip and then tilting
the top forward to release the top lug from the DIN rail.
2. Make wiring terminations with detachable connectors, which accept
1 x 1.5 mm2 (0.002 in.2)/14 AWG cable. Two types are available:
screw and cage clamp connectors. For details, see Ordering Codes.
Make terminations of the Supervisor Link, Expansion Bus, and
Remote Display via the connectors provided with the controller.
3. Verify that the wiring has been correctly installed and that voltage
levels are appropriate for the various input signals according to the
application.
4. Set the jumpers and address switches of the controller as required.
For more information, see Jumper Details.
8 FX15 Controller Technical Bulletin
Assembling the Integrated MUI
To assemble the integrated MUI:
1. Remove the FX15 controller front cover screws.
Figure 4: Open the FX15 Controller
2. Hook the display to the top of the FX15 controller cover.
Figure 5: Display Installation
3. Push the display down until it locks into the FX15 controller.
PUSH
Figure 6: Display Locking
FX15 Controller Technical Bulletin 9
4. Open the FX15 controller.
Figure 7: Open the FX15 Controller
5. Install the ribbon cable. Do not twist the ribbon cable; keep the
ribbon cable flat.
!
NO
Figure 8: Ribbon Cable Installation
6. Close the FX15 controller and secure the two front cover screws.
10 FX15 Controller Technical Bulletin
Connection Details
LP-FX15D2x and LP-FX15D7x Wiring Diagram
Figure 9: Connection Details for the FX15 Controller (9 Relays)
FX15 Controller Technical Bulletin 11
LP-FX15D1x and LP-FX15D6x Wiring Diagram
Figure 10: Connection Details for the FX15 Controller
(5 Triacs and 4 Relays)
Consider the following information when working with the connection
details for the FX15 controller:
• All commons are electrically dependent.
• Analog outputs are opto-isolated and are externally powered at
24 VAC. To maintain the opto-isolation, use a separate power
supply (3 VA) for the analog outputs.
• Digital inputs are opto-isolated and are externally powered at
24 VAC. To maintain the opto-isolation, use a separate power
supply (3 VA) for the digital inputs.
12 FX15 Controller Technical Bulletin
Jumper Details
b
a AI1 AI2 AI3 AI4 AI5 AI6
123
e
f
d
Battery
c
Figure 11: Jumper Connections
Table 1: Jumper Connections
Analog Input (AI) 0-20/4-20 mA Resistive, 0-10 V or Ratiometric
AI1-AI6 Jumpers Closed Jumpers Open
a (Default configuration)
Sensors Power Supply AVPS +5 V EXT VDC +16 V
Terminal Number 13 Pins closed between Pins closed between 2 and 3
b 1 and 2 (Default configuration)
Battery Type CR2032, average life time: 3 years.
c Note: Batteries removed from this device must be recycled or disposed of in accordance
with local, national, and regional regulations. Only certified technicians or qualified building
maintenance personnel should service Johnson Controls® products.
Pin strip closed: battery backup enabled
d Pin strip open: battery excluded (to preserve charge)
Jumper d is set to ON at the factory and should only be set to OFF if the controllers are to
be kept in storage without power for an extended period of time. Set the jumper to ON before
the controllers are installed and powered up; otherwise, back-up RAM and the Real-Time
Clock (RTC) are not enabled.
e Plug-in connector for the optional communication card.
Plug-in connector for the optional display ribbon cable.
f
FX15 Controller Technical Bulletin 13
Connection Details for I/O Expansion (XT-XP Modules) on Local
Extension Bus
Figure 12: Connection Details for the XT/XP Modules
Consider the following information when working with the connection
details for the XT/XP Modules:
• maximum XT modules: four XT91D00s
• maximum bus length: 1,200 m (4,000 ft)
• Install a repeater (for example, RP-9100-810x) to regenerate the
RS-485 signal if more than 31 N2 devices are connected on the
same N2 bus trunk and/or the N2 bus trunk length is more than
1,200 m (4,000 ft).
• Install 220 ohm end-of-line resistors at each end of the XT-Bus line
when the bus length is greater than 100 m (330 ft). When the bus
length is less than 100 m (330 ft), insert only one 220-ohm resistor
at the FX15 controller end only.
Connection Details for the N2 Open Card
The FX15 controller comes with the N2 Open card either installed or
not installed. If the N2 Open card is not installed, you can install the N2
Open card at a later time in the field. For details, see Ordering Codes.
14 FX15 Controller Technical Bulletin
The N2 Open plug-in serial card allows you to connect the FX15
controller to an N2 Open serial network through the RS-485 standard.
LED
Address
Selection
Figure 13: N2 Open Plug-in Communication Card
Figure 14: N2 Open Card Connection
Assembling the N2 Communication Card
To install the N2 communication card:
1. Power off the controller (hot plug-in not allowed).
2. Open the controller. See Figure 15.
FX15 Controller Technical Bulletin 15
Figure 15: Open the Controller
3. Insert the card. See Figure 16.
Align the pins as shown in figure.
Figure 16: Insertion of the N2 Open Card
4. Set the address DIP switches.
5. Replace and close the lid.
IMPORTANT: The Complementary Metal Oxide Semiconductor (CMOS)
integrated circuit in the controller and on the communication card are sensitive
to static current discharges. Take suitable precautions.
16 FX15 Controller Technical Bulletin
Address Selection
Use the DIP switches (see Figure 13) to select the serial address of the
FX15 controller in the N2 Open network. The address selection occurs
in binary mode.
Examples:
• 1st ON, all others open
address = 20 + 01 + … = 1
• 1st ON, 4th ON, all others open
address = 20 + 01 + 02 + 23 = 9
The address zero is not allowed. The factory default address
configuration is 1.
IMPORTANT: Cycle the controller power to activate the new serial address.
Network Layout
Refer to the N2 Communication Bus Technical Bulletin (LIT-636018).
FX15 Controller Technical Bulletin 17
Connection Details for the LONWORKS Card
The FX15 controller comes with the LONWORKS card either installed or
not installed. If the LONWORKS card is not installed, you can install the
LONWORKS card at a later time in the field. For details, see Ordering
Codes.
The LONWORKS plug-in serial card allows you to connect the FX15
controller to a LONWORKS network.
Service PIN
Reachable from the
controller top lid
Figure 17: LONWORKS Plug-in Communication Card
Figure 18: LONWORKS Card Connection
Assembling the LONWORKS Communication Card
To assemble the LONWORKS communications card:
1. Power off the controller (hot plug-in not allowed).
2. Open the controller. See Figure 19.
18 FX15 Controller Technical Bulletin
Figure 19: Open the Controller
3. Insert the card. See Figure 20.
Align the pins as shown in figure.
Figure 20: Insertion of the LONWORKS Card
4. Replace and close the lid.
IMPORTANT: The CMOS integrated circuit in the controller and on the
communication card are sensitive to static current discharges.
Take suitable precautions.
Refer to the LONWORKS FTT-10A Free Topology User’s Guide
(078-0156-01F) for technical guidelines associated with free topology
restrictions. Refer to the Junction Box and Wiring Guidelines for
Twisted Pair LONWORKS Networks (005-0023-01) for more detailed
information on wiring specification. These documents are available on
the Echelon® Web site (www.echelon.com).
FX15 Controller Technical Bulletin 19
Connection Details for the Remote User Interface
The FX15 controller can support up to two Medium User Interfaces
(MUIs) at the same time.
The MUI is available in two models: panel mount (up to 3 m [9.8 ft])
and wall mount (up to 1 km [0.6 mi]). The FX15 controller can support
one panel mount MUI plus one wall mount MUI, or two wall mount
MUIs (see Figure 21 and Figure 22).
For the panel mount connection, use the cable connection kit
(LP-KIT007-000C), which is 3 m (9.8 ft) long, with a phone jack on the
MUI side and a screw connector on the FX15 controller side.
Figure 21: Installation for One Local and One Remote MUI
20 FX15 Controller Technical Bulletin
MUI-008_10 2002
Max 1 Km, total length
MUI 1 MUI 2
1 5 1 5
2 6 2 6
3 7 3 7
4 8 4 8
FX15
To Power Supply
9 ÷ 48 VDC To Power Supply
12 ÷ 24 VAC 9 ÷ 48 VDC
12 ÷ 24 VAC
FX15 "Universal"
LL+ LL- +9V Com
(not used)
To MUI 1
To FX15
To MUI 2
FX15 "Classic"
V Com (-)
V /~ (+)
RT Com
Com +16V LL- LL+ RT-
(not used) RT+
Figure 22: Installation for Two Wall Mount MUIs
FX15 Controller Technical Bulletin 21
Assigning the Medium User Interface’s N2 Address in Case
of Multiple Connections
At powerup, the MUI automatically has a default N2 address equal to 1.
If you connect multiple MUIs, change the second MUI N2 Address to
avoid communication conflicts.
When the second MUI displays Device Offline, as shown in Figure 23,
press the and keys simultaneously to switch the N2 Address
to 2. See Figure 24.
Figure 23: MUI N2 Address Selection
Figure 24: MUI N2 Address Changed
22 FX15 Controller Technical Bulletin
Connection Details for the FX Programming Key
Use the FX Programming Key to upload an application from a computer
or from a preprogrammed FX15 controller, then download that
application to other FX15 controllers.
Upload Download
LED Download / Upload
LEDs Download / Upload failed
<1 sec to select
>3 sec to confirm
>15 sec for MEMORY ERASE
LP-KIT100-001_09 2002
Figure 25: FX Programming Key
FX15 Controller Technical Bulletin 23
Connecting the Programming Key to an FX15 Controller
To connect the Programming Key to an FX15 controller:
1. Power off the controller.
2. Remove any connected user interfaces from the Remote Display
Port (JP2).
3. Plug the Programming Key into the Display Port (JP2)
(see Figure 26).
230 VAC 24 VAC
Remote Display Port
(JP2)
>15 sec for MEMORY ERASE
Download / Upload failed
Download
Download / Upload
<1 sec to select
>3 sec to confirm
Upload LED
LEDs
FX16-018_09 2003
Figure 26: Programming Key Connection to FX15 Controller
4. Power up the controller and download/upload the application.
24 FX15 Controller Technical Bulletin
Connecting the Programming Key to a Computer
Figure 27: Programming Key Connection to a Computer
To connect the Programming Key to a computer:
1. Connect the terminal adapter (included in the Programming Key kit)
to the RS-232/485 converter connected to the computer.
Table 2: Terminal Adapter
Adapter RS-232/485 Converter
1 Com
2 Not used
3 RT-
4 RT+
2. Power the Programming Key via AC/DC adapter.
3. Launch FX Loader.
4. Upload the application.
FX15 Controller Technical Bulletin 25
Performing a Programming Key Memory Erase
If an application is loaded on the Programming Key, and you want to
use a different application, you have to erase the Programming Key
memory.
The Programming Key memory is erased automatically when you use
FX Loader. However, when an application is loaded from a computer,
or when the application is loaded from another FX15 controller, you
must manually perform erase the Programming Key memory.
To erase the Programming Key memory:
1. Power up the Programming Key, either by hot-plugging it to an
FX15 controller (already on) or with an AC/DC adapter.
2. Press the Programming Key button for 15 seconds to initiate the
memory erase.
During the memory erase, the green Light-Emitting Diode (LED)
blinks slowly. Then the green and the yellow LEDs blink twice
alternately, and then the green LED remains on indicating the
memory is erased.
If the green and the yellow LEDs blink simultaneously, it means that the
erase process has failed. Retry. When the memory is completely erased,
the LEDs stop blinking. The Programming Key is now ready for a new
upload. The memory erase is also necessary if the previous upload from
the FX15 controller fails (communication has been interrupted).
Error Codes
You can view the error codes only when an integrated MUI display
(LP-DIS60U10-C) is mounted to the FX15 controller.
Table 3: Error Codes
Error Meaning Possible Cause Action
Code
51 Private ID Controller and Save the application with
mismatch application in the key the proper ID (if available)
have different protection and retry the download.
IDs.
52 Memory full Attempting to upload an Proceed with the memory
application to a key erase and retry uploading.
already loaded.
52 Memory empty Attempting to download Upload the key with the
an application from an target application.
empty key.
26 FX15 Controller Technical Bulletin
Inputs and Outputs
Introduction
The FX15 controller features the following I/O Channels:
• six high resolution Analog Inputs (AIs) (13 bit, A/D Converter)
• eight opto-isolated Digital Inputs (DIs) from potential free contacts,
each with transition counter
• nine Digital Outputs (DOs) (four relays, and five optional relays or
triacs)
• four opto-isolated Analog Outputs (AOs)
Figure 28: FX15 Controller I/Os
FX15 Controller Technical Bulletin 27
Key Concepts
Analog Inputs
The FX15 controller accepts six high resolution, universal analog
inputs; each of the inputs can be configured as active or passive by
application software and jumper configurations.
Digital Inputs
The FX15 controller accepts eight opto-isolated digital inputs from
voltage-free contacts.
Analog Outputs
The FX15 controller provides up to four 0-10 VDC opto-isolated analog
outputs.
Digital Outputs
The FX15 controller provides nine digital outputs, available in two
hardware configurations with nine relays, or four relays and five triacs.
28 FX15 Controller Technical Bulletin
Detailed Procedures
Isolation Diagram
Figure 29: Insulation Diagram
(*) Opto-isolated (maximum 500 V) if an additional separated power
supply is used
(**) Not isolated
(***) DC/DC converted with dielectric strength up to 1000 V
FX15 Controller Technical Bulletin 29
FX15 Controller I/Os Powered at 24 VAC
15 VA
Figure 30: Powering FX15 Controller I/Os
To maintain the insulation between the FX15 controller power supply
and the I/Os, run the power supply cable while respecting the polarity as
shown in Figure 30, and add an External Protection fuse (2 A) to avoid
incorrect wiring.
IMPORTANT: Maintain proper polarity and voltage or current ratings.
Improper polarity or exceeding the voltage or current ratings will void the
warranty.
30 FX15 Controller Technical Bulletin
Analog Inputs
You can configure the six high-resolution analog inputs to accept a wide
range of voltage, current, and resistive input signals.
See I/O Technical Details for the complete FX15 controller I/O table.
A dedicated jumper is available for each analog input.
• Install this jumper in its closed position if the connected sensor
provides a current signal (0-20/4-20 mA).
• Install this jumper in its open position if the connected sensor
provides a resistive, ratiometric, or voltage (0-2/0-10 V) input
signal.
AI1
AGND EXT V AGND AGND EXT V AGND AGND AGND
AI2 AI3 AI4 AI5 AI6
AI1 AI2 AI3 AI4 AI5 AI6
aFX16-025_10 2003
Figure 31: Analog Input Jumpers
The active sensor (voltage or current) inputs have programmable range
parameters within the application software. These parameters,
HighRange and LowRange, define the equivalent values for reading at
High (10 V and 20 mA) and Low (0 V, 4 mA, and 0 mA) signal input.
Voltage and current inputs from differential pressure transducers can be
linearized by a square root function (SQRT), which operates over the
complete range of the input.
The passive sensors (resistance) have preprogrammed linearization
curves within the application software. For these sensors, the
measurement range is fixed. You can set the reliability range via
software.
The read signal is converted by the FX15 controller according to the
related Analog Input object setup. Available setups are:
• Linear 0-10 V
• SQRT 0-10 V
• Linear 0-10 V, 20% suppression (2-10 V)
• Linear 0-2 V
• SQRT 0-2 V
• Linear 0-2 V, 20% suppression (0.4-2 V)
• Linear 0-20 mA
• SQRT 0-20 mA
FX15 Controller Technical Bulletin 31
• Linear 0-20 mA, 20% suppression (0.4-2 mA)
• Resistance 2k ohm
• A99
• NTC 2k2 ohm
• Ni1000 Johnson Controls
• Ni1000 Johnson Controls Extended
• Ni1000 Landis and Gyr®
• Ni1000 DIN
• Pt1000
• Ratiometric
The measurement unit is also configurable, enabling the controller to
propagate the measured value according to the appropriate scale unit via
the network. Available configurable units are:
• Temperature
• Percentage
• Air Pressure
• Liquid Pressure
• Flow
• Concentration
• Ampere
• Voltage
A configurable filter constant in seconds is performed by the FX15
controller on its Analog Inputs for the reduction of signal instability.
You can configure an additional Anti-Spike filter to limit the rate of
change of the input values to the value indicated by this attribute.
The FX15 controller provides a configurable jumper for (Terminal 13)
+5 V Analog Voltage Power Supply (AVPS), or a +16 V External VDC
supply, for active analog input sensors (see Jumper Details.)
The EXT VDC can supply up to 80 mA for a maximum of four 0/4-20
mA active sensors. The AVPS can supply up to 10 mA for ratiometric
sensors.
Connecting Active 0-10 V Sensors
The FX15 controller can accept all the active temperature, pressure,
flow, and humidity sensors providing 0-10 VDC signals.
Figure 32 shows the connection between an FX15 controller and an
HT-9001 probe.
32 FX15 Controller Technical Bulletin
HT-9001-UDx
Active Humidity and Temperature Sensor
C A B - - Bt
1 2 3 4 5 6 7 8
AI1 AI2 AI3
AGND AGND AGND
EXT V EXT V
FX15
FX16
Figure 32: Active 0-10 V Probe, Connection Diagram
The inputs must be configured to accept 0-10 V signals by the
application software in the FX15 controller. The AI Jumpers must be
opened (factory default setting) to accept voltage inputs.
Table 4: Active 0-10 V Sensors
FX15 Terminals HT-9001 Terminals Description
AGND (1) A Common Reference
EXT V (3) C Sensor Power Supply 16 V, 80 mA
AI1 (2) B Humidity Output 0-10 V
AI2 (5) Bt Temperature Output 0-10 V
N ote: The numbers inside the parentheses are the FX15 controller
terminal numbers.
FX15 Controller Technical Bulletin 33
Connecting Passive Resistive Sensors
The FX15 controller analog inputs accept linear resistive signals as the
Resistive 2k ohm. The Analog Input software can also linearize signals
provided by the most common sensors as Ni1000, A99, Pt1000, and
NTC 2k2.
The inputs must be configured to accept A99 resistive signals by the
application software in the FX15 controller. The AI Jumpers must be
opened to accept resistance input (Factory default setting). Figure 33
shows an A99 wiring diagram. Connect the resistive sensors in the same
way.
A99BB
Resistive Temperature Sensor
1 2 3 4 5 6 7 8
AI1 AI2 AI3
AGND AGND AGND
EXT V EXT V
FX15
FX16
Figure 33: A99 Resistive Sensor Connection Diagram
IMPORTANT: The two resistive probe leads are the same, in that they have
no polarity; therefore, it is not necessary to respect any specific order when
connecting to the terminal block.
34 FX15 Controller Technical Bulletin
Connecting Active Current Sensors
The FX15 controller analog inputs can accept a maximum of four active
current sensors, powered by the FX15 controller itself, in the range 0-20
mA or 4-20 mA. The AI has to be configured via software (and
hardware jumpers) to accept current signals. If a 4-20 mA sensor is
connected, the specific hardware jumpers must be closed
(see Figure 31) and the application can be configured through the FX
Builder, setting 0-20 mA, 20% suppression.
The FX15 controller can be connected to the P299xAx Series of
Johnson Controls pressure sensors which generate a 4-20 mA signal.
P299xAx
Active Pressure Sensor
1 2 3 4 5 6 7 8
AI1 AI2 AI3
AGND AGND AGND
EXT V EXT V
FX15
FX16
Figure 34: Pressure Sensor Connection Diagram
Table 5: Active Current Sensors
FX15 Terminals P299xAx Cable Description
AGND (1) Green Common Reference
EXT V (3) Brown Sensor Power Supply 16 V, 80 mA
AI1 (2) White Pressure Output 4-20 mA
N ote: The numbers inside the parentheses are the FX15 controller
terminal numbers.
FX15 Controller Technical Bulletin 35
Connecting Active Sensors Powered by 24 VAC
The FX15 can accept active temperature, pressure, flow, and humidity
sensors providing 0-10 V or current signals powered by 24 VAC.
A second transformer (24 VAC/24 VAC, 3 VA maximum) powering
only the Analog Input is required to maintain the insulation from the
microprocessor.
Active Sensor powered at 24 V
3 VA max
24 Vac 24 Vac
1 2 3 4 5 6 7 8 32 33 34 35
AI1 AI2 AI3
AGND AGND AGND
EXT V EXT V
24V V ~ Com
FX15
24V V ~ Hot
FX16
Earth
91 92 93
15 VA
220
24 Vac
Vac
Figure 35: Active Sensor powered at 24 VAC Connection Diagram
Table 6: Active Sensors Powered by 24 VAC
FX15 Terminals Sensor Cable Description
AGND (1) Green Common Reference
AI1 (2) White Signal Output
N ote: The numbers inside the parentheses are the FX15 controller
terminal numbers.
IMPORTANT: Not powering the Analog Input with a second transformer, or
powering the AI with the power supply on another FX controller, results in a
short circuit causing the failure of the FX15 controller.
36 FX15 Controller Technical Bulletin
Digital Inputs
The FX15 controller features eight opto-isolated digital inputs from
potential-free contacts. A digital input is active depending on its polarity
setting. The default setting is Direct, meaning it is active (true) when
closed.
See I/O Technical Details for the complete FX15 controller I/O table.
Digital Inputs Powered by 24 VAC
The eight FX15 controller Digital Inputs must be 24 V powered
(through terminals 34 and 35). Both AC or DC voltage can be used. If
DC is used, then the power supply of the DIs must be independent from
the controller power supply (FX15 controller is compatible with VAC
power only). The digital inputs can use the same FX15 controller
voltage supply, or they can be separately powered in order to maintain
the microprocessor opto-isolation from the controller voltage supply.
24 Vac 220Vac
3 VA max
21 22 23 24 32 33 34 35
DI V ~ Com
DI8
DICom DICom DICom
DI V ~ Hot
DI1 DI2
FX15
FX16
V ~ Com
24V
Earth V ~ Hot
91 92 93
15 VA
24 Vac 220Vac
Figure 36: Powering Digital Inputs Maintaining Opto-Isolation
FX15 Controller Technical Bulletin 37
Table 7: Digital Inputs Powered by 24 VAC
FX15 Terminals Description
DI V ~ Hot (35) 24 VAC, Digital Inputs Power Supply
DI V ~ Com (34) Digital Inputs Power Supply Common
DI8 (33) Digital Input 8, Voltage-Free contact
DICom (32) Common Reference, Voltage-Free contact
N ote: The numbers inside the parentheses are the FX15 controller
terminal numbers.
Using Analog Inputs as Digital Inputs
If you need more than 8 digital inputs, the FX15 controller allows you
to use an analog input as a digital input.
FX15
Figure 37: Digital Input Connection Diagram
The Analog Input needs to be properly configured in FX Tools to read
the digital input.
Analog Outputs
The FX15 controller provides up to four, 0-10 VDC, 1.5 mA maximum,
opto-isolated analog outputs. The Analog Output objects provide the
interface between the four hardware Analog Output channels and the
control application. See I/O Technical Details for the complete FX15
controller I/O table.
Use the application software to configure the analog outputs for direct
acting or reverse acting.
Use the high limit (MaxOutput) and low limit (MinOutput) values to
limit the output signal.
Powering and Connecting the Analog Outputs
Power the analog outputs separately, through Terminals 79 and 80, to
ensure microprocessor isolation from the controller power supply
(see Figure 39).
38 FX15 Controller Technical Bulletin
The FX15 controller analog outputs are commonly used to drive
proportional devices and can be connected to all the Johnson Controls
Proportional Valve Actuators (Figure 38).
FX15
FX16
AO V ~ Com
AO Com AO Com AO Com AO Com V ~ Com
24V
AO1 AO2 AO3 AO4 AO V ~ Hot Earth V ~ Hot
71 72 73 74 75 76 77 78 79 80 91 92 93
15 VA
24 Vac 220Vac
Figure 38: Connecting the Analog Output without Opto-isolation
IMPORTANT: Maintain proper polarity and voltage or current ratings.
Improper polarity or exceeding the voltage or current ratings will void the
warranty.
FX15 Terminals Description
AO Com (77) Common Reference
AO4 (78) Analog Output 0-10 V
AO V~ Com (79) Common Reference
AO V~ Hot (80) Power Supply 24 VAC
N ote: The numbers inside the parentheses are the FX15 controller
terminal numbers.
To achieve insulation from the microprocessor, use different
24 VAC power supplies to power the controller, and to power the
analog outputs (through Terminals 79 and 80).
FX15 Controller Technical Bulletin 39
FX16
FX15 AO V ~ Com
AO Com AO Com AO Com AO Com V ~ Com
24V
AO1 AO2 AO3 AO4 AO V ~ Hot Earth V ~ Hot
71 72 73 74 75 76 77 78 79 80 91 92 93
3 VA
24 Vac 220Vac
24 Vac 220Vac
Figure 39: Separately Powering Analog Outputs
15 VA
FX15 Terminals Description
AO Com (77) Common Reference
AO4 (78) Analog Output 0-10 V
AO V~ Com (79) AO Common Reference
AO V~ Hot (80) AO Power Supply 24 VAC
V~ Hot (93) FX15 Power Supply 24 V
V~ Com (92) FX15 Common Reference
N ote: The numbers inside the parentheses are the FX15 controller
terminal numbers.
Digital Outputs
The FX15 controller features nine digital outputs, available in two
hardware configurations: all nine relays, or four relays and five triacs.
Use the application software to configure the Digital Outputs for direct
acting or reverse acting.
! WARNING: Risk of Electric Shock. Disconnect or isolate all power
supplies before making electrical connections. More than one disconnect or
isolation may be required to completely de-energize equipment. Contact with
components carrying hazardous voltage can cause electric shock and may
result in severe personal injury or death.
AVERTISSEMENT: Risque de décharge électrique. Débrancher ou isoler
toute alimentation avant de réaliser un branchement électrique. Plusieurs
isolations et débranchements sont peut-être nécessaires pour-couper
entièrement l'alimentation de l'équipement. Tout contact avec des composants
conducteurs de tensions dangereuses risque d'entraîner une décharge
électrique et de provoquer des blessures graves, voire mortelles.
40 FX15 Controller Technical Bulletin
Connecting the Relays
The FX15 controller features up to nine Digital Outputs with
electromechanical relays. To simplify assembly, the common terminals
of some relays have been grouped together. The relays are divided into
six groups, according to the distance of insulation.
Group #1 Group #2 Group #3 Group #4 Group #5 Group #6
Max
Показано початок документа. Повний текст — у PDF за посиланням вище.
Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.
