Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1922510
fmoaps less 1922510 9thcc:2-144A Electric Transducers Rev:
07/18/97
logo:
FM-OAP Series JCI
left ft:
elec
Output Analog Pneumatic Function Module right ft:
standard
Sect# = 0
seQ# = 101
oapfm.eps
Each field device requires the FM-OAP-102 • the pressure output is held below low
(manual module) and either the FM-OAP101 setpoint during power outage or pressure
or the FM-OAP103 (auto modules). Together loss, creating controlled condition for
these modules provide automatic or manual resumption of power or pressure
control of pneumatic field devices. • adjustable output range enhances the
ability to customize calibration to field a
Features device or other application requirements
• plug-in capability with Johnson Controls
products speeds installation and ensures Applications
secure wiring connections, saving time and The OAP Function Module is typically used to
money control pneumatic valve or damper actuators.
• the auto/manual switch provides added The FM-OAP101/102 is designed for use with
flexibility during installation, the Metasys Network Controllers; the FM-
FM-OAP101/102/103 commissioning, troubleshooting, or OAP103/102 is designed for use with
electrical power outage Application Specific Controllers.
Description • the output pressure test port allows
accurate pressure reading of the OAP’s To Order
The Output Analog Pneumatic (OAP)
Function Module converts an electrical control output, to speed installation, calibration, Specify the code number from the following
signal into a proportional pressure output and troubleshooting selection chart.
signal to control a pneumatic field device.
Selection Chart
Code Number Description
FM-OAP101-0 OAP Automatic Function Module used with DCM Controllers
FM-OAP102-0 OAP Manual Function Module used with both the OAP101 and OAP103
FM-OAP103-0 OAP Automatic Function Module used with Application Specific Controllers
Note: Modules must be ordered together for application; however, both
can be ordered separately for replacement.
Accessories
Code Number Description
A-4000-137 Replacement Pneumatic Coalescing Oil Filter for OAP102
A-4000-1037 Replacement Pneumatic Coalescing Oil Filter for OAP102 (5/pkg.)
AS-FMK102-0 Function Module Kit
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 08/00 Johnson Controls, Inc
1/2
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1922510
FM-OAP Series Output Analog Pneumatic Function Module (Continued)
Specifications
FM-AOP Output Analog Pneumatic Function Module
FM-OAP101 Automatic Module used with DCMs
Module FM-OAP102 Manual Module used with OAP101 and OAP103
FM-OAP103 Automatic Module used with AHU and LCP Controllers
Output Range <1 to >19 psig (<7 to >131 kPa) at 20 psig supply pressure
Output Limits Minimum Output Flow 400 SCIM at 3 to 15 psig (R-2080 equivalent) (107 mI/second at 21 to 103 kPa)
Air Consumption Maximum 50 SCIMs at 3 to 15 psig (13 mI/second at 21 to 103 kPa)
Input-Output Characteristics Linear pressure output proportional to input value
Supply Pressure Air Supply Pressure 20 psig (nominal) to 25 psig (maximum) (138 to 172 kPa)
FM-OAP101 0 to 100% of adjusted zero and span
Input Range
FM-OAP103 0 to 20 mA from an ASC controller
Resolution 0.1% of full range
Maximum Linearity Error 2.5% of full scale in the 3 to 15 psig (21 to 103 kPa) range
Accuracy Maximum Hysteresis Error 2.5% in the 3 to 15 psig (21 to 103 kPa) range
Supply Pressure Sensitivity 0.1 psig per 1 psig supply variation (typical) (0.1 kPa per 1 kPa supply variation)
Auto Mode 0.015 psig per °F (0.19 kPa per °C)
Thermal Effects
Manual Mode 0.03 psig per °F (0.37 kPa per °C)
FM-OAP101 Non-Interactive Zero / Offset can be adjusted up to 14 psig (97 kPa)
Calibration Adjustments Span can be adjusted from 6 psig (41 kPa) to 14 psig (96 kPa)
FM-OAP103 Adjustment Midpoint can be adjusted from 3 to 15 psig
Output pressure set to 0 psig (0 kPa) on loss of supply pressure
Default Condition
Output pressure set to less than minimum operating range pressure on electrical power outage
FM-OAP101 Power is from the NCU/NEU
Source Power Power is from a 2-wire current loop; control signal = 0 to 20 mA; maximum resistance = 375 ohms;
FM-OAP103
input impedance = 340 ohms ±10%
Operating Environmental Requirements 40 to 122°F (4.4 to 50°C); 10 to 90% non-condensing relative humidity; 86°F (30°C) maximum dew point
-20 to 140°F (-29 to 60°C)
Storage/Shipping Environmental Requirements 5 to 95% non-condensing relative humidity
86°F (30°C) maximum dew point
Dimensions (H x W x D) 1.7 x 2.6 x 7.0 in. (43 x 66 x 178 mm)
Shipping Weight 1.25 lb. (0.56 kg)
Agency Compliance FCC Part 15 Subpart J - Class A, UL 916, UL864, CSA C22.2 No. 205
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 08/00 Johnson Controls, Inc