Code No. LIT-1922520
Issued February 1, 2009
F62 Series
Airflow Switch (SPDT – Contact Unit)
Description Series F62
This control detects air flow or the absence of
*
air flow in ducts, responding only to the
velocity of air movement. The one-piece
stainless steel paddle can be trimmed, if
necessary. The control is supplied with
;
mounting plate gasket. The range adjusting
screw permits field adjustment of flow rate
setting. 4
f62.eps
Action on Increase
Features of Flow
• rugged steel enclosure F62 Series Action Diagram
• easy access to wiring terminals
Applications F62AA-8
A typical application includes air flow sensing
in make-up air and exhaust systems.
Selection Chart
Technical Specifications Code Paddle Dimension Max Ambient Max. Air
Electrical Ratings Number Size in. Temp. °F (°C) Velocity
Motor Ratings VAC 120 208 240 277 F62AA-8C 1 2-1/8 in. x 10-3/8 in. H 100 (40) 2000 FPM
Nominal Horsepower 1 1 1 – 6-7/8 in. (including paddle), (10 m/sec.)
4 in. W, 2-13/16 in. D
AC Full Load A 16.0 8.8 8.0 –
F62AA-9C 3-1/8 in. x 10-3/8 in. H 100 (40) 2000 FPM
AC Locked Rotor A 96.0 52.8 48.0 – 6-7/8 in. (including paddle), (10 m/sec.)
Non-Inductive or Resistance 22.01 22.01 22.01 22.01 4 in. W, 2-13/16 in. D
Load A 1. Replaces McDonnell Miller AF-2
Pilot Duty – 125 VA, 120/277 VAC
1. SPST normally closed or normally open rating. SPDT rating is 16.0 amp
Note: See F61 and F62 Series Replacement Paddles Catalog Page,
LIT-1922525 for replacement paddles.
Air Velocity Required to Actuate Switch
Paddle Width Switch Actuation Minimum Air Velocity in FPM (m/sec) Required to Actuate Control 1
(in.) on Flow
Horizontal Flow Vertical Flow (Upward)
2 2 2
50 in (323 cm ) Less than 50 in. 50 in.2 (323 cm2 ) Less Than 50 in. 2
or Larger Duct Area (323 cm2 ) Duct Area or Larger Duct Area (323 cm2 ) Duct Area
2-1/8 Increase (R to Y Closes) 625 (3.2) 575 (2.9) 950 (4.8) 750 (3.8)
Decrease (R to B Closes) 325 (1.7) 220 (1.1) 850 (4.3) 575 (2.9)
3-1/8 Increase (R to Y Closes) 500 (2.5) 350 (1.8) 750 (3.8) 500 (2.5)
Decrease (R to B Closes) 250 (1.3) 100 (.5) 650 (3.3) 350 (1.8)
1. These are only approximations . Actual trip points are affected by air turbulence, humidity, air density, air temperature, and other factors.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc. www.johnsoncontrols.com