Product/Technical F61
                                                                                                   Issue Date July 30, 2002

                                  F61 Series Flow Switches

The F61 Series Flow Switches respond to fluid flow in
lines carrying water, ethylene glycol, or other
nonhazardous fluids. Two subseries are available.

F61 Series Sensitive Flow Switches respond to low
fluid flow rates in applications with pipe sizes under
1-inch trade size. (See Figure 1.)                                     Figure 1: F61MD (Left) and F61KD (Right)
                                                                               Sensitive Flow Switches
F61 Series Standard Flow Switches use a variety of
paddle sizes to respond to fluid flow rates in
applications with pipe sizes greater than 1-inch trade
size. (See Figure 2.)

Single-Pole, Double-Throw (SPDT) and Single-Pole,
Single-Throw (SPST) open-low versions of these flow
switches are available.

                                                                        Figure 2: F61KB Standard Flow Switch
                                               Features and Benefits
              NEMA 3 or NEMA 3R                         Allows use in indoor or outdoor applications
                  Enclosure on Selected Models

              Stainless Steel Bellows on                Allow use in fluid lines carrying chlorinated water,
                  Selected Models                        treated water, or other nonhazardous fluids

                                                         Actuates switch with less than 1.0 GPM (3.8 L/min)
              Low-Flow Operation on                     flow for water applications or 9.0 GPM (34.1 L/min)
                  Selected (Sensitive) Models
                                                         flow for steam applications

              Gold-Plated Contacts on                   Reduces intermittent contact problems in
                  MG Models                              low-voltage and low-current circuits

              Maximum Fluid Pressure                    Permits use in a wide range of pressure flow
                  of 150 psig (1034 kPa)                 conditions

© 2002 Johnson Controls, Inc.                                                                                               1
  Code No. LIT-125225                                                                                  www.johnsoncontrols.com
Application                                                Standard Flow Switches
                                                           Use F61 Series Standard Flow Switches in
IMPORTANT: All F61 Series Flow Switches are                applications with fluid pressures up to 150 psig
intended to control equipment under normal                 (1034 kPa). A typical application for a standard
operating conditions. Where failure or malfunction of      F61 flow switch is to shut down the refrigeration
an F61 Flow Switch could lead to an abnormal               compressor on a fluid chiller system if flow stops,
operating condition that could cause personal injury       reducing chances of chiller freeze-ups.
or damage to the equipment or other property, other
devices (limit or safety controls) or systems (alarm or
                                                           NEMA 1 Enclosures
supervisory) intended to warn of, or protect against,
failure or malfunction of the F61 Flow Switch must         Use models with NEMA 1 enclosures for indoor
be incorporated into and maintained as part of the         applications where they are protected from weather
control system.                                            and splashing water. Use these models with pipes
                                                           carrying fluids at temperatures in the range of
                                                           32 to 250F (0 to 121C) where fluid temperatures are
                                                           above ambient dew point.
    !
        CAUTION: Risk of Equipment Damage.                 NEMA 3/NEMA 3R Enclosures
Do not use F61 Series Flow Switches with                   Use models with NEMA 3/NEMA 3R (rain-tight)
hazardous fluids or in hazardous atmospheres. Use          enclosures for indoor or outdoor applications in
in these conditions may cause malfunction or               high-humidity environments. Use these models in
improper operation.                                        applications with pipes carrying fluids at temperatures
                                                           below dew point temperature or below 32F (0C) but
                                                           above -20F (-29C). Do not use these models in
                                                           applications or environments where the temperature
IMPORTANT: F61 Series Flow Switches must not               may cause the fluid to freeze.
be used where the fluid in the pipes drops below the
fluid’s freezing point, causing an internal freeze-up.     Gold Contacts
                                                           Models with gold-plated contacts provide improved
Sensitive Flow Switches                                    electrical performance in low-voltage, low-current
The F61 Series Sensitive Flow Switches have                circuits. Use these models for low-energy loads to
1/2 in. Female NPTF or 3/4 in. Female NPTF inlet and       operate small relays, solenoid valves, and electronic
outlet connections.                                        control circuits.
Use F61 Sensitive Flow Switches in applications
where flow rates are low, such as:
                                                           Operation
                                                           The flow switch responds to pressure exerted on the
   water purification and treatment systems               fluid paddle by the flowing fluid. A range adjustment
   booster pumps                                          screw adjusts the rate of flow required to actuate the
                                                           switch.
   cooling systems for electronic tubes, bearings, and
    compressors                                            Table 1: SPDT Switch Wiring
   rapid recovery water heaters (starting the water                 Types                    Switch Wiring
    heater when water is withdrawn)                           F61KB, F61KD, F61LB          color-coded terminals
   control of food waste disposal units (starting motor     F61MB, F61MD, F61MG         four color-coded wire leads
    when a predetermined amount of water is flowing
    through the unit and stops when the flow
                                                           The red terminal or wire is the Common. The green
    decreases to a predetermined rate)
                                                           wire is Ground. Red to Yellow closes on flow increase.
   switch to shut down the refrigeration compressor       Red to Blue closes on flow decrease. See Table 4
    on a fluid chiller system if flow stops, reducing      through Table 8 for flow rates.
    chances of chiller freeze-ups

2   F61 Series Flow Switches Product/Technical Bulletin
Dimensions
NEMA1 Enclosures
                                                        7/8
                                                             Diameter Hole for 1/2 in. Trade Size Conduit
                                                       (22)
                                                      1-1/16 Diameter Knockout Ring for 3/4 in. Trade Size Conduit
                                  4                    (27)
                                (102)                                               2-3/4
                                             2                            1-3/8      (71)
                                           (51)                           (35)

                                                                                                             Dimension by
                                                          2-11/16
                                                                                                            Liquid Line Size
                                                            (68)
                                                                 1-3/4                                               A     B
                                                                  (44)                                        1 1-7/16 1
                                                                                                             (25) (37) (25)

                                            1-1/4                                             Grounding      2     2-1/2 1-1/8
                                                     4-3/4                                      Screw       (51)   (64) (29)
                                            (33)                 1-1/8
                                                     (121)                                       Hole
                                                                 (29)                                        3     3-1/2 1-1/8
             Use these                                                                                      (76)   (89) (29)
            wrench flats
              to tighten                                                                                      4   6-5/8 1-1/8
          the flow switch                                                                                   (101) (168) (29)
           at installation.                1 in.
                                        11-1/2 NPT    A                   B                                   5   6-5/8 1-1/8
                     Paddle                                                                                 (152) (168) (29)
                     Screw

                                Figure 3: Standard Flow Switch (F61KB Type), in./mm
                          4                                                           2-3/4
                        (102)                                                         (71)
                                     2                                        1-3/8                  7/8
                                                                              (35)                          Diameter Hole for
                                    (51)                                                            (22)
                                                                                                            1/2 in. Trade Size
                                                                                                                 Conduit

                                                    2-11/16
                                                      (68)                                          1-1/8
                                                                                                             Diameter Knockout
                                                              1-3/4                                  29
                                                                                                               Ring for 3/4 in.
                                                              (44)                                               Trade Size
                                                                                                                  Conduit

                                                                                              Grounding
                                                              1-1/2
                                                                                               Screw
                                                     2-3/8    (38)                              Hole
                                                     (60)

                                                                                               1-1/2 Hex,
                  1-3/16                                                                        38 Both
                                                                                  7/8                Ends
                   (30)                     1/2 in.-14 Dryseal Thread
                           2-5/16                                                (22)
                                                        OR
                            (59)                                                    1-3/4
                                            3/4 in.-14 Dryseal Thread
                                            As Specified (Both Ends)                 (44)

                                Figure 4: Sensitive Flow Switch (F61KD Type), in./mm

                                                                         F61 Series Flow Switches Product/Technical Bulletin      3
NEMA 3/NEMA 3R Enclosures
                                                       1-1/8 On MB and MG Types
                                                       (29)
                                                                        1/2-14 NPSM Thread
                                 3-11/16                5/8
                                                             On LB Types
                                   (94)                (15)                           2-3/4
                                        1-13/16                                1-3/8  (71)
                                          (47)                                                                Dimension by
                                                                                (35)                         Liquid Line Size
                                                                                                                     A      B
                                                                                                               1 1-7/16 1
                                                                    2-7/8                                     (25) (37) (25)
                                                                    (73)
                                                                            1-9/16                            2     2-1/2 1-1/8
                                                                             (40)                            (51)   (64) (29)
                                                                                                              3     3-1/2 1-1/8
                                                                                                             (76)   (89) (29)
                                               1-1/4          4-3/4
                                               (33)           (121) 1-1/16                                     4   6-5/8 1-1/8
                                                                     (27)                                    (101) (168) (29)
                Use these
               wrench flats                                                                                    5   6-5/8 1-1/8
                 to tighten                                                                                  (152) (168) (29)
             the flow switch
              at installation.
                                           1 in. 11-1/2 NPT                          B
                                                                A
                       Paddle
                       Screw

                    Figure 5: Standard Flow Switch (F61LB, F61MB, F61MG Types), in./mm
                                 3-11/16                1-1/8       1/2 in.-14 NPSM                  2-3/4
                                   (94)                 (29)             Thread                      (71)
                                           1-13/16                    on MD Types            1-3/8
                                             (47)                                            (35)

                                                                        2-7/8
                                                                        (73)
                                                                                 1-9/16
                                                                                  (40)

                                                                                     1-1/2
                                                                        2-3/8        (38)
                                                                        (60)

                                                                                                                1-1/2
                                                                                                                      Hex,
                            1-3/16                                                               7/8            (38)
                             (30)                                                                                     Both
                                  2-5/16                        1/2 in.-14 Dryseal Thread       (22)                  Ends
                                   (59)                                     OR                     1-3/4
                                                                3/4 in.-14 Dryseal Thread           (44)
                                                                As Specified (Both Ends)

                                 Figure 6: Sensitive Flow Switch (F61MD Type), in./mm

4   F61 Series Flow Switches Product/Technical Bulletin
Installation
F61 Series Sensitive Flow Switches do not require
adjustment or installation of paddles prior to mounting
the flow switch.
Some models of the F61 Series Standard Flow
Switches require installation or adjustment of paddles
prior to mounting. See Installing the Flow Paddles.

Parts Included
F61 Series Standard Flow Switches have a
three-piece flow paddle installed at the factory. Some
                                                                                                   1 in.
models also include a large flow paddle for large pipe
sizes.                                                                                             1-1/2 in.

Table 2: Replacement Parts                                                                         2 in.
  Kit Number                       Description
 KIT21A-600         Stainless Steel three-piece Paddle
                    (3 in., 2 in., and 1 in. Segments)                                             2-1/2 in.
 KIT21A-601         Stainless Steel 6 in. Paddle
 PLT52A-600R        Stainless Steel three-piece Paddle
                    (3 in., 2 in., and 1 in. Segments) and
                    6 in. Paddle                                                                   3 in.

 CVR62A-600R        Replacement Cover Assembly for LB,
                    MB, MD, and MG Types

Installing the Flow Paddles
                                                                                                    4 in.
 IMPORTANT: To allow the switch to detect changes
 in the fluid flow, the flow paddle must not touch the
 pipe or any restrictions in the pipe.

Adjust flow paddles to the size of the pipe used. Install                                           5 in.
the large flow paddle, if needed. Trim the flow paddle
at the arc corresponding to the pipe size (see Figure 7
and Figure 8).

                                                                        Original
                                                                        Length                      6 in.

                                                              Figure 8: Trimming Diagram for Large Flow Paddle

            Flow
           Paddle          Trim flow paddles to fit
                          pipe diameter or remove
           Screw
                            flow paddles that are
                        too large to fit pipe diameter.

           Figure 7: Installing the Paddles

                                                             F61 Series Flow Switches Product/Technical Bulletin   5
Mounting
                                                                      Tee or Welded
    !                                                                 Half-coupling
         CAUTION: Risk of Equipment Damage.
 To avoid damaging the switch, do not tighten the
 switch to the tee by grasping the switch enclosure.
 Use only the wrench flats provided.
                                                                                  A                        A

Mount the F61 Series Flow Switches using the                                       Dimension A must be at least
following guidelines:                                                          five pipe diameters from the nearest
                                                                               elbow, valve, or other pipe restriction.
   Install the switch so that the cover and interior are
    accessible.                                                           Figure 9: Required Piping Distance
   Mount the switch so that the flow of fluid is in the       Do not subject the flow switches to water hammer.
    direction of the arrow on the switch casing.               Use a suitable water hammer arrester if a fast-closing
                                                               valve is located downstream of the flow switch. See
   Use a pipe union on each side of the flow switch to        Figure 10.
    allow easy removal or replacement.
   Do not allow the pipe to extend too far into the flow
    switch casing.                                                                              F
                                                                                                l
                                                                                                o w

   Use pipe thread sealer on male threads only.                             F
                                                                             low              Wat
                                                                                                er
                                                                             S
                                                                             wi
                                                                              tch             H
                                                                                              ammer
   Do not remove the cover gasket or the wire                                                A
                                                                                              r
                                                                                              res
                                                                                                ter
    grommet from the conduit opening.                                                                            V
                                                                                                                 a
                                                                                                                 lv
                                                                                                                  e

For 1 in. pipe installation, mount the F61 flow switch in          Figure 10: Water Hammer Arrester Location
a standard 1 in. x 1 in. x 1 in. tee. For larger sizes of                          Schematic
pipe, use a reducing tee to keep the flow switch close
to the pipe and provide adequate paddle length in the          Wiring
flow stream.
                                                                  !
    Example: Use a 2 in. x 2 in. x 1 in. tee for a 2 in.
    pipe. If a standard 2 in. x 2 in. x 2 in. tee is used,              WARNING: Risk of Electrical Shock.
    install a face or hex bushing in the top opening to        Disconnect power supply before making electrical
    reduce it to 1 in.                                         connections. Failure to follow this precaution may
                                                               result in equipment damage, electrical shock or
Mount the flow switch so the terminals or wire leads           death.
are easily accessible for wiring. Screw the flow switch
in position so the flat of the paddle is at a right angle to
the flow. The arrow on the side of the case must point
in the direction of the flow.                                     !
                                                                       CAUTION: Risk of Equipment Damage.
Location Considerations                                        Using terminal screws other than those provided will
Mount the F61 flow switch in a horizontal pipeline or a        void the warranty and may damage the switch. Use
vertical pipeline with upward fluid flow. Do not use in a      only the terminal screws furnished.
vertical pipeline with downward flow. When mounted in
a vertical pipe with upward flow, the switch trips at a
slightly higher flow than shown in Table 4 through
Table 8, due to the effect of gravity on the switch            IMPORTANT: To prevent moisture from entering
mechanism.                                                     and condensate forming inside the NEMA 3R
                                                               enclosure, do not remove the cover gasket or the
Mount the F61 flow switch in a section of pipe where           wire grommet from the conduit opening.
there is a straight run of at least five pipe diameters on
each side of the flow switch from the nearest elbow,
valve, or other pipe restriction. See Figure 9.

6   F61 Series Flow Switches Product/Technical Bulletin
IMPORTANT: Install all wiring in accordance with             !
the National Electrical Code and local regulations.               CAUTION: Risk of Equipment Damage.
Make all wiring connections using copper conductors       Sealed settings (screws marked with black paint) are
only. Do not exceed the control’s electrical rating.      not intended to be changed. Adjustment attempts
                                                          may damage the control or cause loss of calibration,
                                                          voiding the warranty.
Models of the F61KB, F61KD, and F61LB types have
three color-coded terminals. Red is common. See
Table 3 and Figure 11. Models of the F61MB, F61MD        To adjust the setting of the flow switch:
and F61MG types have four color-coded wire leads.
Red is common; green is ground. See Table 3.             1. Disconnect power supply before making electrical
                                                            connections.
Table 3: Switch Action                                   2. Remove the F61 flow switch cover.
       Flow Action                   Switch Closure      3. Turn the adjusting screw clockwise to raise the
        Increase                       Red to Yellow        flow rate. Turn the adjusting screw
        Decrease                        Red to Blue         counterclockwise to lower the flow rate. See
                                                            Figure 12.
                                                         4. Replace the cover after completing adjustments.
        Increase in Flow            Decrease in Flow        Tighten the cover screws to 12 inlbs of torque.
         Above Setpoint              Above Setpoint
                                                         Note: Do not lower the flow rate unless it has been
                                                         raised from the factory setting.
                           Red
                                                            Lower Flow Rates                          Higher Flow Rates
                                                              Less liquid flow                          More liquid flow
                           Yellow                           required to switch                        required to switch
                                                             from R-Y to R-B.                Red       from R-Y to R-B.
                                                                                             Yellow
                                                                                             Blue
                           Blue

             Figure 11: Switch Action                                            Adjusting Screw
                                                                    Figure 12: Flow Rate Adjustment
Adjustment
   !
         WARNING: Risk of Electrical Shock.
Disconnect power supply before making electrical
connections. Failure to follow this precaution may
result in equipment damage, electrical shock or
death.

   !
         CAUTION: Risk of Improper Operation.
The switch is factory set at approximately the
minimum flow rate (see Table 4 through Table 8). Do
not set lower than the factory setting as this may
result in the switch failing to return to a “no flow”
position.

                                                        F61 Series Flow Switches Product/Technical Bulletin                7
To verify that the flow rate is set above the factory
minimum (see Figure 13):
1. Depress the main lever numerous times. If the                                                            Adjusting
                                                                                                             Screw
   lever fails to click upon return at any time, the flow
   rate is set below the factory-set minimum.
2. Raise the flow rate to approximately the factory
   minimum by turning the adjusting screw clockwise
   until the lever clicks upon return every time.

                                                                                                                              Main
                                                                                                                              Lever
                                                                                      Figure 13: Minimum Adjustment

Typical Flow Rates for F61 Series Standard Flow Switches

Table 4: F61KB, F61LB, and F61MB Types, 1-3 in. Paddles
                                          GPM (m3/hr) Required to Actuate Switch
        Pipe Size (in.)            1      1-1/41 1-1/21    2      2-1/22   3                        43           53      63            83
                      Flow
                    Increase      4.20      5.80      7.50      13.7         18.0        27.5       65.0       125       190           375
                     (R to Y     (0.95)    (1.32)    (1.70)    (3.11)       (4.09)      (6.24)     (14.8)     (28.4)    (43.2)        (85.2)
     Minimum         Closes)
    Adjustment       Flow
                   Decrease       2.50      3.70      5.00      9.50         12.5        19.0       50.0       101       158           320
                    (R to B      (0.57)    (0.84)    (1.14)    (2.16)       (2.84)      (4.32)     (11.4)     (22.9)    (35.9)        (72.7)
                    Closes)
                      Flow
                    Increase      8.80      13.3      19.2      29.0         34.5        53.0       128        245       375           760
                     (R to Y     (2.00)    (3.02)    (4.36)    (6.59)       (7.84)      (12.0 )    (29.1)     (55.6)    (85.2)        (173)
     Maximum         Closes)
    Adjustment       Flow
                   Decrease       8.50      12.5      18.0      27.0         32.0        50.0       122        235       360           730
                    (R to B      (1.93)    (2.84)    (4.01)    (6.13)       (7.27)      (11.4)     (27.7)     (53.4)    (81.8)        (166)
                    Closes)
 1.    Values for 2 in. paddle trimmed to fit pipe.
 2.    Values for 3 in. paddle trimmed to fit pipe.
 3.    Values calculated for factory-installed set of 1, 2, and 3 in. paddles.

Table 5: F61KB, F61LB, and F61MB Types, 6 in. Paddles*
                                          GPM (m3/hr) Required to Actuate Switch
                    Pipe Size (in.)                         4              5                                 6                   8
     Minimum         Flow Increase (R to Y Closes)            37.0 (8.40)            57.0 (12.9)         74.0 (16.8)       205 (46.6)
    Adjustment       Flow Decrease (R to B Closes)            27.0 (6.13)            41.0 (9.31)         54.0 (12.3)       170 (38.6)
     Maximum         Flow Increase (R to Y Closes)            81.0 (18.4)            118 (26.8)          144 (32.7)        415 (94.3)
    Adjustment       Flow Decrease (R to B Closes)            76.0 (17.3)            111 (25.2)          135 (30.7)        400 (90.8)
 *     Where paddle size is larger than pipe size, values are for 6 in. paddle trimmed to fit pipe.

8     F61 Series Flow Switches Product/Technical Bulletin
Table 6: F61MG Types, 1-3 in. Paddles
                                         GPM (m3/hr) Required to Actuate Switch
      Pipe Size (in.)            1       1-1/41 1-1/21    2     2-1/22    3                        43           53     63           83
                    Flow
                  Increase      3.80      5.30       6.90      12.7         16.7        24.3      61.0       118       183          362
                   (R to Y     (0.86)    (1.20)     (1.57)    (2.88)       (3.79)      (5.52)     (13.8     (26.8)    (41.6)       (82.2)
  Minimum          Closes)
 Adjustment        Flow
                 Decrease       2.50      3.70       5.00      9.50         12.5        19.0       50.0      101       158          320
                  (R to B      (0.57)    (0.84)     (1.14)    (2.16)       (2.84)      (4.32)     (11.4)    (22.9)    (35.9)       (72.7)
                  Closes)
                    Flow
                  Increase      8.70      13.1       18.8      28.9         33.7        52.1       126       243       372          753
                   (R to Y     (1.98)    (2.98)     (4.27)    (6.56)       (7.65)      (11.8)     (28.6)    (55.2)    (84.5)       (171)
  Maximum          Closes)
 Adjustment        Flow
                 Decrease       8.50      12.5       18.0      27.0         32.0        50.0       122       235       360          730
                  (R to B      (1.93)    (2.84)     (4.09)    (6.13)       (7.27)      (11.4)     (27.7)    (53.4)    (81.8)       (166)
                  Closes)
 1.   Values for 2 in. paddle trimmed to fit pipe.
 2.   Values for 3 in. paddle trimmed to fit pipe.
 3.   Values calculated for factory-installed set of 1, 2, and 3 in. paddles.

Table 7: F61MG Types, 6 in. Paddles*
                                         GPM (m3/hr) Required to Actuate Switch
                   Pipe Size (in.)                         4              5                                 6                  8
  Minimum           Flow Increase (R to Y Closes)            35.0 (7.95)            53.0 (12.0)         69.0 (15.7)       197 (44.7)
 Adjustment         Flow Decrease (R to B Closes)            27.0 (6.13)            41.0 (9.31)         54.0 (12.3)       170 (38.6)
  Maximum           Flow Increase (R to Y Closes)            80.0 (18.2)            116 (26.3)          142 (32.2)        412 (93.6)
 Adjustment         Flow Decrease (R to B Closes)            76.0 (17.3)            111 (25.2)          135 (30.7)        400 (90.8)
 *    Where paddle size is larger than pipe size, values are for 6 in. paddle trimmed to fit pipe.

                                                                   F61 Series Flow Switches Product/Technical Bulletin                      9
Typical Flow Rates for F61 Series Sensitive Flow Switches

Table 8: F61 Series Sensitive Flow Switches
                                       GPM (L/Min) Required to Actuate Switch
                Pipe Size (in.)                  1/2 in. x 1/2 in. Female NPTF1                       3/4 in. x 3/4 in. Female NPTF3
                                                 3/4 in. x 3/4 in. Female NPTF2
  Minimum         Flow Increase (R to Y Closes)                       0.60 (2.27)                                 8.50 (32.2)
 Adjustment      Flow Decrease (R to B Closes)                        0.30 (1.14)                                 4.50 (17.1)
  Maximum         Flow Increase (R to Y Closes)                       1.10 (4.17)                                 9.00 (34.1)
 Adjustment      Flow Decrease (R to B Closes)                        0.90 (3.41)                                 6.30 (23.9)
 1.   F61KD-3C, F61MD-1C
 2.   F61KD-4C, F61MD-2C
 3.   F61KD-8C (designed for steam applications)

                                                                Flow Rate
                                                                 (L/Min)
                         0   7.6 15.1 22.7 30.3 37.9 45.4 53.0 60.6 68.1 75.7 83.3 90.9 98.4 106
                    20                                                                           137.9

                    18                                                                                           124.1

                    16                                                                                           110.3

                    14                                                                                            96.5

           Pressure 12                                                                                            82.7
                                                                                                                         Pressure
            Drop                                                                                                           Drop
             PSI    10                                                                                            69.0
                                                                                                                           kPa
                                            1/2 in. Pipe Size                     3/4 in. Pipe Size
                     8                                                                                            55.2

                     6                                                                                            41.4

                     4                                                                                            27.6

                     2                                                                                            13.8

                     0                                                                                             0
                      0      2    4     6      8     10    12    14    16    18     20   22    24      26   28
                                                                 Flow Rate
                                                                    GPM

               Figure 14: Pressure Drop versus Flow Rate, F61 Series Sensitive Flow Switches
                                         (F61KD and F61MD Types)

10    F61 Series Flow Switches Product/Technical Bulletin
Checkout                                                      Repairs and Replacement
 IMPORTANT: Ensure installation, wiring and control           Field repairs, except for replacement of the cover and
 settings are according to the application                    paddles, must not be made. For a replacement flow
 requirements. Refer to the controlled system’s               switch, paddle kit or cover, contact the nearest
 manufacturer specifications for the proper settings          Johnson Controls/PENN™ distributor. For more
 when adjusting these controls.                               information, contact Refrigeration Application
                                                              Engineering at (800) 275-5676.
 Apply power to the control and controlled equipment.
 Cycle the controlled system at least three times at
 normal operating conditions.

The circuit between the red and the yellow leads
(terminals) closes when sufficient fluid flows through
the pipe to trip the F61 flow switch.

Troubleshooting
Table 9: Troubleshooting
                   Symptom/Problem                                                     Solution
 Water (condensate) is within the enclosure.                 Use a model with a NEMA 3R enclosure. If using a model
                                                             with a NEMA 3R enclosure, inspect the grommet in the
                                                             conduit fitting. Replace grommet if defective.
 Fluid from the tank is leaking into enclosure due to        Replace flow switch.
 bellows failure.
 Switch does not activate due to debris caught within the    Clear any debris within the switch mechanism. Test the
 switch mechanism.                                           operation of switch several times for proper operation.
 Control switch action is reversed.                          Ensure connections follow wiring diagrams.

 Control does not switch.                                    Check connections.

 Switch fails to return to the no flow position.             Switch is set lower than the factory setting. Increase the
                                                             setting.
                                                             On vertical pipes, ensure that direction of flow is up. The
                                                             arrow on switch must point in direction of flow (up).

 Control does not switch on flow increase.                   Check for cracked/broken paddle. Replace if necessary.

                                                            F61 Series Flow Switches Product/Technical Bulletin            11
Ordering Information
Table 10: F61 Series Standard Flow Switch Models
     Product
      Code         Enclosure            Bellows                                           Paddle
     Number
                                                           Stainless Steel; three-piece Paddle (3 in., 2 in., and 1 in. Segments)
 F61KB-11C          NEMA 1
                                                                       Installed; 6 in. Paddle Supplied Uninstalled
                                    Phosphor Bronze        Stainless Steel; three-piece Paddle (3 in., 2 in., and 1 in. Segments)
     F61LB-1C
                                                                                         Installed
                    NEMA 3/
     F61MB-1C       NEMA 3R
                   (Rain-Tight)                            Stainless Steel; three-piece Paddle (3 in., 2 in., and 1 in. Segments)
 F61MB-5C                             Stainless Steel
                                                                       Installed; 6 in. Paddle Supplied Uninstalled
 F61MG-1C*                          Phosphor Bronze
 *     Gold-Plated Contacts

Table 11: F61 Series Sensitive Flow Switch Models
     Product
      Code        Enclosure            Bellows                                     Inlet and Outlet
     Number
 F61KD-3C                                                                     1/2 in. x 1/2 in. Female NPTF
 F61KD-4C          NEMA 1          Phosphor Bronze
                                                                              3/4 in. x 3/4 in. Female NPTF
 F61KD-8C
 F61MD-1C         NEMA 3/3R                                                   1/2 in. x 1/2 in. Female NPTF
                                    Stainless Steel
 F61MD-2C         (Rain-Tight)                                                3/4 in. x 3/4 in. Female NPTF

Table 12: Replacement Paddle Kits
 Product Code
                                                                     Description
    Number
     KIT21A-600                           Stainless Steel three-piece Paddle (3 in., 2 in., and 1 in. Segments)
     KIT21A-601                                               Stainless Steel 6 in. Paddle
     PLT52A-600R                  Stainless Steel three-piece Paddle (3 in., 2 in., and 1 in. Segments) and 6 in. Paddle
 CVR62A-600R                                 Replacement Cover Assembly for LB, MB, MD and MG types

12     F61 Series Flow Switches Product/Technical Bulletin
Electrical Ratings
Table 13: Electrical Ratings for F61KB, F61 KD, F61LB, F61MB and F61MD Types
            Electrical Ratings                 120 VAC          208 VAC          240 VAC          277 VAC
               Horsepower                         1                 1                1                -
            Full Load Amperes                   16.0               8.8              8.0               -
          Locked Rotor Amperes                  96.0              52.8              48.0              -
          Non-inductive Amperes                 16.0              16.0              16.0             16.0
                Pilot Duty                                         125 VA at 24/277 VAC

Table 14: Electrical Ratings for F61MG Types
            Electrical Ratings                                            120 VAC
            Full Load Amperes                                                1
          Locked Rotor Amperes                                               6
          Non-inductive Amperes                                              2
                Pilot Duty                                          125 VA at 24/277 VAC

                                                       F61 Series Flow Switches Product/Technical Bulletin   13
Technical Specifications
                          Product    F61 Series Flow Switches
     Maximum Fluid Pressure          150 psig (1034 kPa)
                Minimum Fluid        32°F (0°C) (F61KB, F61KD, F61LB)
                  Temperature        -20°F (-29°C) (F61MB, F61MD, F61MG)
                Maximum Fluid
                                     250°F (121°C)
                  Temperature
                           Switch    SPDT
                                     Screw Type Terminals (F61KB, F61KD, F61LB)
          Wiring Connections         Four Color-coded No. 14 AWG Solid Conductor Wire Leads, 7 in. (178 mm) (F61MB,
                                     F61MD, F61MG)
       Pipe              Standard    1 in. 11-1/2 NPT Threads
  Connector              Sensitive   See Table 11.
                                     One 7/8 in. (22 mm) Hole for 1/2 in. Conduit with 1-1/8 in. (29 mm) Knockout Ring for
          Conduit Connection         3/4 in. Conduit (F61KB)
                                     Female Hub for 1/2 in. Conduit, 1/2-14 NPSM Threads (F61LB, F61MB, F61MG)
                         UL Listed   E5368, CCN NMFT
     Agency                          LR948, Class 3211 06, Class 4813 02, Class 1222 01 (F61KB, F61KD)
     Listings     CSA Certified      (F61LB - Not CSA Certified)
                                     LR948, Class 3211 06 (F61MB, F61MD, F61MG)
              Shipping Weight        2.8 lb (1.3 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                                Printed in U.S.A.
Milwaukee, WI 53201                                                                                                 www.johnsoncontrols.com

14    F61 Series Flow Switches Product/Technical Bulletin