Product/Technical F61
Issue Date July 30, 2002
F61 Series Flow Switches
The F61 Series Flow Switches respond to fluid flow in
lines carrying water, ethylene glycol, or other
nonhazardous fluids. Two subseries are available.
F61 Series Sensitive Flow Switches respond to low
fluid flow rates in applications with pipe sizes under
1-inch trade size. (See Figure 1.) Figure 1: F61MD (Left) and F61KD (Right)
Sensitive Flow Switches
F61 Series Standard Flow Switches use a variety of
paddle sizes to respond to fluid flow rates in
applications with pipe sizes greater than 1-inch trade
size. (See Figure 2.)
Single-Pole, Double-Throw (SPDT) and Single-Pole,
Single-Throw (SPST) open-low versions of these flow
switches are available.
Figure 2: F61KB Standard Flow Switch
Features and Benefits
NEMA 3 or NEMA 3R Allows use in indoor or outdoor applications
Enclosure on Selected Models
Stainless Steel Bellows on Allow use in fluid lines carrying chlorinated water,
Selected Models treated water, or other nonhazardous fluids
Actuates switch with less than 1.0 GPM (3.8 L/min)
Low-Flow Operation on flow for water applications or 9.0 GPM (34.1 L/min)
Selected (Sensitive) Models
flow for steam applications
Gold-Plated Contacts on Reduces intermittent contact problems in
MG Models low-voltage and low-current circuits
Maximum Fluid Pressure Permits use in a wide range of pressure flow
of 150 psig (1034 kPa) conditions
© 2002 Johnson Controls, Inc. 1
Code No. LIT-125225 www.johnsoncontrols.com
Application Standard Flow Switches
Use F61 Series Standard Flow Switches in
IMPORTANT: All F61 Series Flow Switches are applications with fluid pressures up to 150 psig
intended to control equipment under normal (1034 kPa). A typical application for a standard
operating conditions. Where failure or malfunction of F61 flow switch is to shut down the refrigeration
an F61 Flow Switch could lead to an abnormal compressor on a fluid chiller system if flow stops,
operating condition that could cause personal injury reducing chances of chiller freeze-ups.
or damage to the equipment or other property, other
devices (limit or safety controls) or systems (alarm or
NEMA 1 Enclosures
supervisory) intended to warn of, or protect against,
failure or malfunction of the F61 Flow Switch must Use models with NEMA 1 enclosures for indoor
be incorporated into and maintained as part of the applications where they are protected from weather
control system. and splashing water. Use these models with pipes
carrying fluids at temperatures in the range of
32 to 250F (0 to 121C) where fluid temperatures are
above ambient dew point.
!
CAUTION: Risk of Equipment Damage. NEMA 3/NEMA 3R Enclosures
Do not use F61 Series Flow Switches with Use models with NEMA 3/NEMA 3R (rain-tight)
hazardous fluids or in hazardous atmospheres. Use enclosures for indoor or outdoor applications in
in these conditions may cause malfunction or high-humidity environments. Use these models in
improper operation. applications with pipes carrying fluids at temperatures
below dew point temperature or below 32F (0C) but
above -20F (-29C). Do not use these models in
applications or environments where the temperature
IMPORTANT: F61 Series Flow Switches must not may cause the fluid to freeze.
be used where the fluid in the pipes drops below the
fluid’s freezing point, causing an internal freeze-up. Gold Contacts
Models with gold-plated contacts provide improved
Sensitive Flow Switches electrical performance in low-voltage, low-current
The F61 Series Sensitive Flow Switches have circuits. Use these models for low-energy loads to
1/2 in. Female NPTF or 3/4 in. Female NPTF inlet and operate small relays, solenoid valves, and electronic
outlet connections. control circuits.
Use F61 Sensitive Flow Switches in applications
where flow rates are low, such as:
Operation
The flow switch responds to pressure exerted on the
water purification and treatment systems fluid paddle by the flowing fluid. A range adjustment
booster pumps screw adjusts the rate of flow required to actuate the
switch.
cooling systems for electronic tubes, bearings, and
compressors Table 1: SPDT Switch Wiring
rapid recovery water heaters (starting the water Types Switch Wiring
heater when water is withdrawn) F61KB, F61KD, F61LB color-coded terminals
control of food waste disposal units (starting motor F61MB, F61MD, F61MG four color-coded wire leads
when a predetermined amount of water is flowing
through the unit and stops when the flow
The red terminal or wire is the Common. The green
decreases to a predetermined rate)
wire is Ground. Red to Yellow closes on flow increase.
switch to shut down the refrigeration compressor Red to Blue closes on flow decrease. See Table 4
on a fluid chiller system if flow stops, reducing through Table 8 for flow rates.
chances of chiller freeze-ups
2 F61 Series Flow Switches Product/Technical Bulletin
Dimensions
NEMA1 Enclosures
7/8
Diameter Hole for 1/2 in. Trade Size Conduit
(22)
1-1/16 Diameter Knockout Ring for 3/4 in. Trade Size Conduit
4 (27)
(102) 2-3/4
2 1-3/8 (71)
(51) (35)
Dimension by
2-11/16
Liquid Line Size
(68)
1-3/4 A B
(44) 1 1-7/16 1
(25) (37) (25)
1-1/4 Grounding 2 2-1/2 1-1/8
4-3/4 Screw (51) (64) (29)
(33) 1-1/8
(121) Hole
(29) 3 3-1/2 1-1/8
Use these (76) (89) (29)
wrench flats
to tighten 4 6-5/8 1-1/8
the flow switch (101) (168) (29)
at installation. 1 in.
11-1/2 NPT A B 5 6-5/8 1-1/8
Paddle (152) (168) (29)
Screw
Figure 3: Standard Flow Switch (F61KB Type), in./mm
4 2-3/4
(102) (71)
2 1-3/8 7/8
(35) Diameter Hole for
(51) (22)
1/2 in. Trade Size
Conduit
2-11/16
(68) 1-1/8
Diameter Knockout
1-3/4 29
Ring for 3/4 in.
(44) Trade Size
Conduit
Grounding
1-1/2
Screw
2-3/8 (38) Hole
(60)
1-1/2 Hex,
1-3/16 38 Both
7/8 Ends
(30) 1/2 in.-14 Dryseal Thread
2-5/16 (22)
OR
(59) 1-3/4
3/4 in.-14 Dryseal Thread
As Specified (Both Ends) (44)
Figure 4: Sensitive Flow Switch (F61KD Type), in./mm
F61 Series Flow Switches Product/Technical Bulletin 3
NEMA 3/NEMA 3R Enclosures
1-1/8 On MB and MG Types
(29)
1/2-14 NPSM Thread
3-11/16 5/8
On LB Types
(94) (15) 2-3/4
1-13/16 1-3/8 (71)
(47) Dimension by
(35) Liquid Line Size
A B
1 1-7/16 1
2-7/8 (25) (37) (25)
(73)
1-9/16 2 2-1/2 1-1/8
(40) (51) (64) (29)
3 3-1/2 1-1/8
(76) (89) (29)
1-1/4 4-3/4
(33) (121) 1-1/16 4 6-5/8 1-1/8
(27) (101) (168) (29)
Use these
wrench flats 5 6-5/8 1-1/8
to tighten (152) (168) (29)
the flow switch
at installation.
1 in. 11-1/2 NPT B
A
Paddle
Screw
Figure 5: Standard Flow Switch (F61LB, F61MB, F61MG Types), in./mm
3-11/16 1-1/8 1/2 in.-14 NPSM 2-3/4
(94) (29) Thread (71)
1-13/16 on MD Types 1-3/8
(47) (35)
2-7/8
(73)
1-9/16
(40)
1-1/2
2-3/8 (38)
(60)
1-1/2
Hex,
1-3/16 7/8 (38)
(30) Both
2-5/16 1/2 in.-14 Dryseal Thread (22) Ends
(59) OR 1-3/4
3/4 in.-14 Dryseal Thread (44)
As Specified (Both Ends)
Figure 6: Sensitive Flow Switch (F61MD Type), in./mm
4 F61 Series Flow Switches Product/Technical Bulletin
Installation
F61 Series Sensitive Flow Switches do not require
adjustment or installation of paddles prior to mounting
the flow switch.
Some models of the F61 Series Standard Flow
Switches require installation or adjustment of paddles
prior to mounting. See Installing the Flow Paddles.
Parts Included
F61 Series Standard Flow Switches have a
three-piece flow paddle installed at the factory. Some
1 in.
models also include a large flow paddle for large pipe
sizes. 1-1/2 in.
Table 2: Replacement Parts 2 in.
Kit Number Description
KIT21A-600 Stainless Steel three-piece Paddle
(3 in., 2 in., and 1 in. Segments) 2-1/2 in.
KIT21A-601 Stainless Steel 6 in. Paddle
PLT52A-600R Stainless Steel three-piece Paddle
(3 in., 2 in., and 1 in. Segments) and
6 in. Paddle 3 in.
CVR62A-600R Replacement Cover Assembly for LB,
MB, MD, and MG Types
Installing the Flow Paddles
4 in.
IMPORTANT: To allow the switch to detect changes
in the fluid flow, the flow paddle must not touch the
pipe or any restrictions in the pipe.
Adjust flow paddles to the size of the pipe used. Install 5 in.
the large flow paddle, if needed. Trim the flow paddle
at the arc corresponding to the pipe size (see Figure 7
and Figure 8).
Original
Length 6 in.
Figure 8: Trimming Diagram for Large Flow Paddle
Flow
Paddle Trim flow paddles to fit
pipe diameter or remove
Screw
flow paddles that are
too large to fit pipe diameter.
Figure 7: Installing the Paddles
F61 Series Flow Switches Product/Technical Bulletin 5
Mounting
Tee or Welded
! Half-coupling
CAUTION: Risk of Equipment Damage.
To avoid damaging the switch, do not tighten the
switch to the tee by grasping the switch enclosure.
Use only the wrench flats provided.
A A
Mount the F61 Series Flow Switches using the Dimension A must be at least
following guidelines: five pipe diameters from the nearest
elbow, valve, or other pipe restriction.
Install the switch so that the cover and interior are
accessible. Figure 9: Required Piping Distance
Mount the switch so that the flow of fluid is in the Do not subject the flow switches to water hammer.
direction of the arrow on the switch casing. Use a suitable water hammer arrester if a fast-closing
valve is located downstream of the flow switch. See
Use a pipe union on each side of the flow switch to Figure 10.
allow easy removal or replacement.
Do not allow the pipe to extend too far into the flow
switch casing. F
l
o w
Use pipe thread sealer on male threads only. F
low Wat
er
S
wi
tch H
ammer
Do not remove the cover gasket or the wire A
r
res
ter
grommet from the conduit opening. V
a
lv
e
For 1 in. pipe installation, mount the F61 flow switch in Figure 10: Water Hammer Arrester Location
a standard 1 in. x 1 in. x 1 in. tee. For larger sizes of Schematic
pipe, use a reducing tee to keep the flow switch close
to the pipe and provide adequate paddle length in the Wiring
flow stream.
!
Example: Use a 2 in. x 2 in. x 1 in. tee for a 2 in.
pipe. If a standard 2 in. x 2 in. x 2 in. tee is used, WARNING: Risk of Electrical Shock.
install a face or hex bushing in the top opening to Disconnect power supply before making electrical
reduce it to 1 in. connections. Failure to follow this precaution may
result in equipment damage, electrical shock or
Mount the flow switch so the terminals or wire leads death.
are easily accessible for wiring. Screw the flow switch
in position so the flat of the paddle is at a right angle to
the flow. The arrow on the side of the case must point
in the direction of the flow. !
CAUTION: Risk of Equipment Damage.
Location Considerations Using terminal screws other than those provided will
Mount the F61 flow switch in a horizontal pipeline or a void the warranty and may damage the switch. Use
vertical pipeline with upward fluid flow. Do not use in a only the terminal screws furnished.
vertical pipeline with downward flow. When mounted in
a vertical pipe with upward flow, the switch trips at a
slightly higher flow than shown in Table 4 through
Table 8, due to the effect of gravity on the switch IMPORTANT: To prevent moisture from entering
mechanism. and condensate forming inside the NEMA 3R
enclosure, do not remove the cover gasket or the
Mount the F61 flow switch in a section of pipe where wire grommet from the conduit opening.
there is a straight run of at least five pipe diameters on
each side of the flow switch from the nearest elbow,
valve, or other pipe restriction. See Figure 9.
6 F61 Series Flow Switches Product/Technical Bulletin
IMPORTANT: Install all wiring in accordance with !
the National Electrical Code and local regulations. CAUTION: Risk of Equipment Damage.
Make all wiring connections using copper conductors Sealed settings (screws marked with black paint) are
only. Do not exceed the control’s electrical rating. not intended to be changed. Adjustment attempts
may damage the control or cause loss of calibration,
voiding the warranty.
Models of the F61KB, F61KD, and F61LB types have
three color-coded terminals. Red is common. See
Table 3 and Figure 11. Models of the F61MB, F61MD To adjust the setting of the flow switch:
and F61MG types have four color-coded wire leads.
Red is common; green is ground. See Table 3. 1. Disconnect power supply before making electrical
connections.
Table 3: Switch Action 2. Remove the F61 flow switch cover.
Flow Action Switch Closure 3. Turn the adjusting screw clockwise to raise the
Increase Red to Yellow flow rate. Turn the adjusting screw
Decrease Red to Blue counterclockwise to lower the flow rate. See
Figure 12.
4. Replace the cover after completing adjustments.
Increase in Flow Decrease in Flow Tighten the cover screws to 12 inlbs of torque.
Above Setpoint Above Setpoint
Note: Do not lower the flow rate unless it has been
raised from the factory setting.
Red
Lower Flow Rates Higher Flow Rates
Less liquid flow More liquid flow
Yellow required to switch required to switch
from R-Y to R-B. Red from R-Y to R-B.
Yellow
Blue
Blue
Figure 11: Switch Action Adjusting Screw
Figure 12: Flow Rate Adjustment
Adjustment
!
WARNING: Risk of Electrical Shock.
Disconnect power supply before making electrical
connections. Failure to follow this precaution may
result in equipment damage, electrical shock or
death.
!
CAUTION: Risk of Improper Operation.
The switch is factory set at approximately the
minimum flow rate (see Table 4 through Table 8). Do
not set lower than the factory setting as this may
result in the switch failing to return to a “no flow”
position.
F61 Series Flow Switches Product/Technical Bulletin 7
To verify that the flow rate is set above the factory
minimum (see Figure 13):
1. Depress the main lever numerous times. If the Adjusting
Screw
lever fails to click upon return at any time, the flow
rate is set below the factory-set minimum.
2. Raise the flow rate to approximately the factory
minimum by turning the adjusting screw clockwise
until the lever clicks upon return every time.
Main
Lever
Figure 13: Minimum Adjustment
Typical Flow Rates for F61 Series Standard Flow Switches
Table 4: F61KB, F61LB, and F61MB Types, 1-3 in. Paddles
GPM (m3/hr) Required to Actuate Switch
Pipe Size (in.) 1 1-1/41 1-1/21 2 2-1/22 3 43 53 63 83
Flow
Increase 4.20 5.80 7.50 13.7 18.0 27.5 65.0 125 190 375
(R to Y (0.95) (1.32) (1.70) (3.11) (4.09) (6.24) (14.8) (28.4) (43.2) (85.2)
Minimum Closes)
Adjustment Flow
Decrease 2.50 3.70 5.00 9.50 12.5 19.0 50.0 101 158 320
(R to B (0.57) (0.84) (1.14) (2.16) (2.84) (4.32) (11.4) (22.9) (35.9) (72.7)
Closes)
Flow
Increase 8.80 13.3 19.2 29.0 34.5 53.0 128 245 375 760
(R to Y (2.00) (3.02) (4.36) (6.59) (7.84) (12.0 ) (29.1) (55.6) (85.2) (173)
Maximum Closes)
Adjustment Flow
Decrease 8.50 12.5 18.0 27.0 32.0 50.0 122 235 360 730
(R to B (1.93) (2.84) (4.01) (6.13) (7.27) (11.4) (27.7) (53.4) (81.8) (166)
Closes)
1. Values for 2 in. paddle trimmed to fit pipe.
2. Values for 3 in. paddle trimmed to fit pipe.
3. Values calculated for factory-installed set of 1, 2, and 3 in. paddles.
Table 5: F61KB, F61LB, and F61MB Types, 6 in. Paddles*
GPM (m3/hr) Required to Actuate Switch
Pipe Size (in.) 4 5 6 8
Minimum Flow Increase (R to Y Closes) 37.0 (8.40) 57.0 (12.9) 74.0 (16.8) 205 (46.6)
Adjustment Flow Decrease (R to B Closes) 27.0 (6.13) 41.0 (9.31) 54.0 (12.3) 170 (38.6)
Maximum Flow Increase (R to Y Closes) 81.0 (18.4) 118 (26.8) 144 (32.7) 415 (94.3)
Adjustment Flow Decrease (R to B Closes) 76.0 (17.3) 111 (25.2) 135 (30.7) 400 (90.8)
* Where paddle size is larger than pipe size, values are for 6 in. paddle trimmed to fit pipe.
8 F61 Series Flow Switches Product/Technical Bulletin
Table 6: F61MG Types, 1-3 in. Paddles
GPM (m3/hr) Required to Actuate Switch
Pipe Size (in.) 1 1-1/41 1-1/21 2 2-1/22 3 43 53 63 83
Flow
Increase 3.80 5.30 6.90 12.7 16.7 24.3 61.0 118 183 362
(R to Y (0.86) (1.20) (1.57) (2.88) (3.79) (5.52) (13.8 (26.8) (41.6) (82.2)
Minimum Closes)
Adjustment Flow
Decrease 2.50 3.70 5.00 9.50 12.5 19.0 50.0 101 158 320
(R to B (0.57) (0.84) (1.14) (2.16) (2.84) (4.32) (11.4) (22.9) (35.9) (72.7)
Closes)
Flow
Increase 8.70 13.1 18.8 28.9 33.7 52.1 126 243 372 753
(R to Y (1.98) (2.98) (4.27) (6.56) (7.65) (11.8) (28.6) (55.2) (84.5) (171)
Maximum Closes)
Adjustment Flow
Decrease 8.50 12.5 18.0 27.0 32.0 50.0 122 235 360 730
(R to B (1.93) (2.84) (4.09) (6.13) (7.27) (11.4) (27.7) (53.4) (81.8) (166)
Closes)
1. Values for 2 in. paddle trimmed to fit pipe.
2. Values for 3 in. paddle trimmed to fit pipe.
3. Values calculated for factory-installed set of 1, 2, and 3 in. paddles.
Table 7: F61MG Types, 6 in. Paddles*
GPM (m3/hr) Required to Actuate Switch
Pipe Size (in.) 4 5 6 8
Minimum Flow Increase (R to Y Closes) 35.0 (7.95) 53.0 (12.0) 69.0 (15.7) 197 (44.7)
Adjustment Flow Decrease (R to B Closes) 27.0 (6.13) 41.0 (9.31) 54.0 (12.3) 170 (38.6)
Maximum Flow Increase (R to Y Closes) 80.0 (18.2) 116 (26.3) 142 (32.2) 412 (93.6)
Adjustment Flow Decrease (R to B Closes) 76.0 (17.3) 111 (25.2) 135 (30.7) 400 (90.8)
* Where paddle size is larger than pipe size, values are for 6 in. paddle trimmed to fit pipe.
F61 Series Flow Switches Product/Technical Bulletin 9
Typical Flow Rates for F61 Series Sensitive Flow Switches
Table 8: F61 Series Sensitive Flow Switches
GPM (L/Min) Required to Actuate Switch
Pipe Size (in.) 1/2 in. x 1/2 in. Female NPTF1 3/4 in. x 3/4 in. Female NPTF3
3/4 in. x 3/4 in. Female NPTF2
Minimum Flow Increase (R to Y Closes) 0.60 (2.27) 8.50 (32.2)
Adjustment Flow Decrease (R to B Closes) 0.30 (1.14) 4.50 (17.1)
Maximum Flow Increase (R to Y Closes) 1.10 (4.17) 9.00 (34.1)
Adjustment Flow Decrease (R to B Closes) 0.90 (3.41) 6.30 (23.9)
1. F61KD-3C, F61MD-1C
2. F61KD-4C, F61MD-2C
3. F61KD-8C (designed for steam applications)
Flow Rate
(L/Min)
0 7.6 15.1 22.7 30.3 37.9 45.4 53.0 60.6 68.1 75.7 83.3 90.9 98.4 106
20 137.9
18 124.1
16 110.3
14 96.5
Pressure 12 82.7
Pressure
Drop Drop
PSI 10 69.0
kPa
1/2 in. Pipe Size 3/4 in. Pipe Size
8 55.2
6 41.4
4 27.6
2 13.8
0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28
Flow Rate
GPM
Figure 14: Pressure Drop versus Flow Rate, F61 Series Sensitive Flow Switches
(F61KD and F61MD Types)
10 F61 Series Flow Switches Product/Technical Bulletin
Checkout Repairs and Replacement
IMPORTANT: Ensure installation, wiring and control Field repairs, except for replacement of the cover and
settings are according to the application paddles, must not be made. For a replacement flow
requirements. Refer to the controlled system’s switch, paddle kit or cover, contact the nearest
manufacturer specifications for the proper settings Johnson Controls/PENN™ distributor. For more
when adjusting these controls. information, contact Refrigeration Application
Engineering at (800) 275-5676.
Apply power to the control and controlled equipment.
Cycle the controlled system at least three times at
normal operating conditions.
The circuit between the red and the yellow leads
(terminals) closes when sufficient fluid flows through
the pipe to trip the F61 flow switch.
Troubleshooting
Table 9: Troubleshooting
Symptom/Problem Solution
Water (condensate) is within the enclosure. Use a model with a NEMA 3R enclosure. If using a model
with a NEMA 3R enclosure, inspect the grommet in the
conduit fitting. Replace grommet if defective.
Fluid from the tank is leaking into enclosure due to Replace flow switch.
bellows failure.
Switch does not activate due to debris caught within the Clear any debris within the switch mechanism. Test the
switch mechanism. operation of switch several times for proper operation.
Control switch action is reversed. Ensure connections follow wiring diagrams.
Control does not switch. Check connections.
Switch fails to return to the no flow position. Switch is set lower than the factory setting. Increase the
setting.
On vertical pipes, ensure that direction of flow is up. The
arrow on switch must point in direction of flow (up).
Control does not switch on flow increase. Check for cracked/broken paddle. Replace if necessary.
F61 Series Flow Switches Product/Technical Bulletin 11
Ordering Information
Table 10: F61 Series Standard Flow Switch Models
Product
Code Enclosure Bellows Paddle
Number
Stainless Steel; three-piece Paddle (3 in., 2 in., and 1 in. Segments)
F61KB-11C NEMA 1
Installed; 6 in. Paddle Supplied Uninstalled
Phosphor Bronze Stainless Steel; three-piece Paddle (3 in., 2 in., and 1 in. Segments)
F61LB-1C
Installed
NEMA 3/
F61MB-1C NEMA 3R
(Rain-Tight) Stainless Steel; three-piece Paddle (3 in., 2 in., and 1 in. Segments)
F61MB-5C Stainless Steel
Installed; 6 in. Paddle Supplied Uninstalled
F61MG-1C* Phosphor Bronze
* Gold-Plated Contacts
Table 11: F61 Series Sensitive Flow Switch Models
Product
Code Enclosure Bellows Inlet and Outlet
Number
F61KD-3C 1/2 in. x 1/2 in. Female NPTF
F61KD-4C NEMA 1 Phosphor Bronze
3/4 in. x 3/4 in. Female NPTF
F61KD-8C
F61MD-1C NEMA 3/3R 1/2 in. x 1/2 in. Female NPTF
Stainless Steel
F61MD-2C (Rain-Tight) 3/4 in. x 3/4 in. Female NPTF
Table 12: Replacement Paddle Kits
Product Code
Description
Number
KIT21A-600 Stainless Steel three-piece Paddle (3 in., 2 in., and 1 in. Segments)
KIT21A-601 Stainless Steel 6 in. Paddle
PLT52A-600R Stainless Steel three-piece Paddle (3 in., 2 in., and 1 in. Segments) and 6 in. Paddle
CVR62A-600R Replacement Cover Assembly for LB, MB, MD and MG types
12 F61 Series Flow Switches Product/Technical Bulletin
Electrical Ratings
Table 13: Electrical Ratings for F61KB, F61 KD, F61LB, F61MB and F61MD Types
Electrical Ratings 120 VAC 208 VAC 240 VAC 277 VAC
Horsepower 1 1 1 -
Full Load Amperes 16.0 8.8 8.0 -
Locked Rotor Amperes 96.0 52.8 48.0 -
Non-inductive Amperes 16.0 16.0 16.0 16.0
Pilot Duty 125 VA at 24/277 VAC
Table 14: Electrical Ratings for F61MG Types
Electrical Ratings 120 VAC
Full Load Amperes 1
Locked Rotor Amperes 6
Non-inductive Amperes 2
Pilot Duty 125 VA at 24/277 VAC
F61 Series Flow Switches Product/Technical Bulletin 13
Technical Specifications
Product F61 Series Flow Switches
Maximum Fluid Pressure 150 psig (1034 kPa)
Minimum Fluid 32°F (0°C) (F61KB, F61KD, F61LB)
Temperature -20°F (-29°C) (F61MB, F61MD, F61MG)
Maximum Fluid
250°F (121°C)
Temperature
Switch SPDT
Screw Type Terminals (F61KB, F61KD, F61LB)
Wiring Connections Four Color-coded No. 14 AWG Solid Conductor Wire Leads, 7 in. (178 mm) (F61MB,
F61MD, F61MG)
Pipe Standard 1 in. 11-1/2 NPT Threads
Connector Sensitive See Table 11.
One 7/8 in. (22 mm) Hole for 1/2 in. Conduit with 1-1/8 in. (29 mm) Knockout Ring for
Conduit Connection 3/4 in. Conduit (F61KB)
Female Hub for 1/2 in. Conduit, 1/2-14 NPSM Threads (F61LB, F61MB, F61MG)
UL Listed E5368, CCN NMFT
Agency LR948, Class 3211 06, Class 4813 02, Class 1222 01 (F61KB, F61KD)
Listings CSA Certified (F61LB - Not CSA Certified)
LR948, Class 3211 06 (F61MB, F61MD, F61MG)
Shipping Weight 2.8 lb (1.3 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53201 www.johnsoncontrols.com
14 F61 Series Flow Switches Product/Technical BulletinПозиції каталогу з цим документом