Текст документа
Code No. LIT-1922340
Issued February 1, 2009
F61 Series
Flow Switch (Low Flow Rate – SPDT)
Description Applications
For use on liquid lines using water, ethylene Typical applications include:
glycol solutions, or other liquids not corrosive
• water purification and treatment systems
to the brass or phosphor bronze parts. The
SPDT contact switch is activated by a low flow • booster pumps
rate; however, it has a large flow capacity with • fast shutdown on high input boilers to guard
a minimum pressure drop. against circulation failure
• cooling systems for electronic tubes,
bearings, and compressors
F61KD-4
Selection Chart
Code Inlet and Outlet Enclosure Adjustment Range – GPM (L/Min) Maximum Minimum Maximum
Number Size Female NPT NEMA R to Y Closes R to Y Opens Liquid Temp Liquid Temp Liquid
Type Flow Increase Flow Decrease Pressure
F61KD-3C 1/2 x 1/2 in. (13 x 13 mm) 1 Minimum 0.6 (2.27) Minimum 0.3 (1.14) 250°F 32°F 150 psig
F61KD-4C 3/4 x 3/4 in. (19 x 19 mm) 1 Maximum 1.1 (4.17) Maximum 0.9 (3.4) (121°C) (0°C) (1034 kPa)
F61KD-8C 3/4 x 3/4 in. (19 x 19 mm) 1 Minimum 8.5 (32.2) Minimum 4.5 (17.1)
Maximum 9.0 (34.1) Maximum 6.3 (23.9)
F61MD-1C 1/2 x 1/2 in. (13 x 13 mm) 3R Minimum 0.6 (2.27) Minimum 0.3 (1.14) -20°F
F61MD-2C 3/4 x 3/4 in. (19 x 19 mm) 3R Maximum 1.1 (4.17) Maximum 0.9 (3.4) (-29°C)
Technical Specifications
Dimensions
F61 Series Flow Switch (Low Flow Rate - SPDT)
Height 5-1/32 in. (127 mm)
Width 4 in. (102 mm)
Depth 2-13/16 in. (71 mm)
Electrical Ratings
Motor Ratings VAC 120 VAC 208 VAC 240 VAC 277 VAC
Horsepower 1 1 1 –
AC Full Load A 16.0 8.8 8.0 –
AC Locked Rotor A 96.0 52.8 48.0 –
Non-Inductive or 16 16 16 16
Resistance Load A
Pilot Duty – 125 VA, 24/277 VAC
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc. www.johnsoncontrols.com