EP-8000 Series Electro-Pneumatic Transducers
Product/Technical Bulletin
Code No. LIT-216370
Part No. 24-85368-36, Rev. H
Issued February 2016
EP-8000 Series Electro-Pneumatic Transducers
convert a voltage or current signal from an electronic
controller into a pneumatic output pressure signal. An
increase or decrease in the input signal proportionally
increases or decreases (respectively) the output
pressure signal from the EP-8000. Four models are
available, which are grouped into two basic versions:
low-volume output units (non-relay) and high-volume
output units (relay).
The EP-8000 is designed to output a proportional
pneumatic control signal in response to an electronic
control signal. All units feature barbed air connections
for 5/32 or 1/4 inch O.D. polytubing. Sequencing of
pneumatic valve or damper actuators can be
accomplished using a Johnson Controls® V-9502
(Valve) or D-9502 (Damper) Actuator Positioner.
Figure 1: EP-8000 Low Volume (Left) and
EP-8000 High Volume (Right) Transducers
Table 1: Features and Benefits
Features Benefits
Compact, Simple Design Eases installation on a variety of mounting surfaces, including direct
mounting on pneumatic valve actuators
Choice of 0-10 VDC or4-20 mA Input Range Interfaces with a wide range of controllers, making the unit ideal for
retrofit installations
Hypodermic Needle Test Point Allows for fast and easy output pressure signal measurement
Factory Set, Fully Adjustable Zero and Span Facilitates field calibration, saving installation costs
High Accuracy with Low Hysteresis Provides many years of use with less time spent on maintenance
EP-8000 Series Electro-Pneumatic Transducers Product/Technical
Bulletin
1
Operation Input Versus Output Relationship
A change in the electrical input signal modulates the
amount of air that exhausts from the leakport,
producing an output pressure directly proportional to
the input signal. Input and output pressure and flow
relationships are detailed in Figures 3 through 5.
A potentiometer located next to the wiring terminal
block is provided for field span adjustment, and a screw
located on the side of the EP-8000 is provided for zero
adjustment. (See Figure 2 for adjustment locations.)
The low-volume models are 1-pipe instruments, which
require a 0.007 inch restrictor (R-3710 Series, ordered
separately) in the supply air line.
Figure 3: EP-8000-1 and EP-8000-2,
Output (psig) versus Input (Volts DC)
Figure 4: EP-8000-3 and EP-8000-4,
Figure 2: EP-8000-1 Adjustment Points (Cover Output (psig) versus Input (mA DC)
Removed)
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin
2
VDC
Figure 5: High-Volume Models, Output Flow
Capacity (scim and mL/s) versus Input Signal
(Volts DC and mA)
Dimensions
5° 5°
Figure 7: EP-8000 High Volume Output Model
Dimension (in./mm)
Installation
Parts Included
• EP-8000 Transducer
• No. 8 3/8 in. sheet metal screws (2)
Tools Required
• flat-blade screwdrivers, 3/32 in. and 1/4 in.
• 5/32 in. drill bit and drill
Mounting
Regardless of the mounting method chosen, the
EP-8000 must be mounted within 5° of vertical for
proper operation. (Refer to Figures 6 and 7.) In most
cases, the vertical position of the EP-8000 can be
obtained by correctly positioning the transducer's
mounting bracket and/or angle bracket. Do not mount
Figure 6: EP-8000 Low Volume Output Module an EP-8000 directly to a damper actuator.
Dimensions (in./mm)
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin
3
To mount an EP-8000 on a pneumatic valve actuator, Panel Mounting
the EP-8000-101 Mounting Kit (ordered separately) Mount the EP-8000 on a flat, vibration-free surface,
must be used. The EP-8000, in conjunction with the using the following steps:
EP-8000-101, can be mounted on the following
actuators: 4R, 5R, 8R, V-400, V-500, or V-3000-1 1. Mark two mounting slots on the mounting surface
Series Valve Actuator with or without a V-9502 Valve using the integral mounting bracket as a template.
Actuator Positioner. (See Figure 8.) It can also be used 2. Drill a pilot hole at each of the marked locations.
with a V-3000-8001 Series Valve Actuator with or
without a V-9502. (See Figure 9.) 3. Secure the EP-8000 in place using the two No. 8
screws provided.
V-3000-1
Mounting Detail
Figure 8: EP-8000-101 Mounting Kit for Installation of the EP-8000 to
a 4R, 5R, 8R, V-400, V-500, and V-3000-1 Valve Actuator With or
Without a V-9502 Positioner
Mounting
Bracket
Screws (2)
Figure 9: EP-8000-101 Mounting Kit for Installation of the EP-8000 to a
V-3000-8001 Valve Actuator With or Without a V-9502 Positioner
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin
4
Wiring and Pneumatic Connections • Observe the polarity as designated on the terminal
block of the EP-8000.
• Provides adequate stress relief for the wiring. A
wiring entry slot is molded into the cover for routing
Risk of Electric Shock. to an analog DC source.
Disconnect the power supply before making electrical Observe the following guidelines when making
connections to avoid electric shock. pneumatic connections:
• Use 5/32 or 1/4 in. polytubing.
• Use clean, dry, oil-free air.
Risque de décharge électrique. IMPORTANT: To avoid contamination of the unit,
Débrancher l'alimentation avant de réaliser tout install an inline supply filter.
raccordement électrique afin d'éviter tout risque de
décharge électrique. Note: For low-volume models, this inline filter must be
installed in the supply air line before the 0.007 inch
restrictor (see Figure 10).
Application Diagrams
Risk of Property Damage.
Do not apply power to the system before checking all
wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
the equipment.
S
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir
Figure 10: Low Volume Models Wiring and
vérifié tous les raccords de câblage. Des fils formant
Tubing
un court-circuit ou connectés de façon incorrecte
risquent d'endommager irrémédiablement
l'équipement.
IMPORTANT: Make all wiring connections in
accordance with the National Electrical Code and
applicable local regulations. S
S
IMPORTANT: All EP-8000 Series transducers are
designed for use only in conjunction with operating
controls. Where an operating control failure would Figure 11: High Volume Models Wiring and
result in personal injury and/or loss of property, it is Tubing
the responsibility of the installer to add safety
devices or alarm systems that protect against, or
warn of, control failure.
Observe the following guidelines when making wiring
connections:
• Remove the cover of the EP-8000 by gently prying
up on the two snap-in cover tabs.
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin
5
S
DA-1
FO-1
P
S
S
P
S Figure 13: Application of a High Volume
S EP-8000 With a V-9502 Positioner
Figure 12: Application of a Low Volume
EP-8000 With a D-9502 Positioner
N.O.
N.C.
S S
S
Figure 14: Application Using High Volume
EP-8000s To Drive Valve and Damper
Pneumatic Actuators
Calibration 3. Calculate the sensitivity using one of the equations
below:
To change the zero and span settings to values other
than the factory settings (Table 1), see Figure 2 for Voltage Models: SV = PH - PL
adjustment locations and proceed as follows: VH - VL
1. Determine the desired high pressure output (PH) Current Models: SI = PH - PL
IH - IL
and, depending on the model chosen, determine
the corresponding input voltage (VH) or input 4. Determine if the calculated sensitivity from Step 3
current (IH). is within one of the ranges below:
2. Determine the desired low pressure output (PL) Voltage Models: 1.33 SV 2.33
and the corresponding input voltage (VL) or input
Current Models: 0.6 SI 1.0
current (IL).
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin
6
If the calculated sensitivity does not fall within these 11. Turn the zero adjustment screw to obtain the
limits, the desired span cannot be obtained. Reselect desired low pressure (PL). Clockwise rotation
new desired values in Steps 1 and 2. Repeat Steps 3 increases the pressure; counterclockwise rotation
and 4. decreases the pressure.
5. Determine if the zero setting is within one of the 12. Set the input signal to the desired high value (VH or
adjustment ranges below: IH).
Voltage Models: –6 PL – (VL x SV) +6 13. Turn the span adjustment potentiometer to obtain
the desired high pressure (PH).
Current Models: –6 PL – (IL x SI) +6
If the zero setting does not fall within one of these IMPORTANT: For voltage models,
limits, the device cannot be zeroed. Reselect new counterclockwise rotation decreases the pressure,
desired values in Steps 1 and 2. Repeat Steps 3 and clockwise rotation increases the pressure. For
through 5. current models, counterclockwise rotation increases
the pressure, and clockwise rotation decreases the
6. Remove the cover from the unit by gently prying up pressure.
on the two snap-in cover tabs.
7. Connect filtered 20 psig (140 kPa) supply pressure 14. Repeat Step 10 to check that the desired low value
to the supply “S” connection on the unit. (PL) has not changed after adjusting the span. If
(Low-volume models require a 0.007 inch necessary, repeat Steps 11 through 13 to fine tune
restrictor.) the unit.
8. Connect a JC 5361 Hypodermic Needle Test 15. Disconnect the test probe assembly and gauge
Probe Assembly with a 0 to 30 psig (0 to 210 kPa) from the unit.
G-2010 Series Air Pressure Gauge (both items 16. Feed the input DC wires through the wiring entry
ordered separately) to the hypodermic needle test slot molded in the transducer cover, and snap the
point on the unit. cover into place.
Note: In areas where use of a hypodermic needle Repair Information
test probe is prohibited, an output test port can be
installed on the output side of the unit. If the EP-8000 Series Electro-Pneumatic Transducer
fails to operate within its specifications, replace the
9. Connect an input signal to the unit: 0 to 10 VDC for unit. For a replacement transducer, contact the nearest
voltage models, 4 to 20 mA DC for current models. Johnson Controls representative.
10. Set the input signal to the desired low value (VL or To Order
IL).
Specify the code number from the following selection
chart.
Table 2: Selection Chart
Code Number Output Input Input Range Factory Output Range psig
(kPa)
EP-8000-11 Low Volume (Non-Relay) Voltage 0.5 to 9 VDC 1 to 18 (7 to 126)
EP-8000-2 High Volume (Relay) Voltage 0.25 to 9.5 VDC 0.5 to 19 (3.5 to 133)
EP-8000-31 Low Volume (Non-Relay) Current 4 to 20 mA DC 3 to 15 (21 to 105)
EP-8000-4 High Volume (Relay) Current 4 to 20 mA DC 3 to 15 (21 to 105)
1. Low-volume models are one-pipe instruments requiring a 0.007 in. (0.017 mm) R-3710 Series Restricter, ordered
separately.
Table 3: Accessories
Code Number Description
R-3710 0.007 in. Restricter (Required for Low-Volume Models)
EP-8000-101 Electro-Pneumatic Transducer Mounting Kit (For Mounting the EP-8000 to a Pneumatic Valve Actuator)
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin
7
Table 3: Accessories
Code Number Description
A-4000-137 In-line Filter (Required for All Models)
A-4000-1037 In-line Filter (Required for all Models; Package of Five)
JC-5361 Hypodermic Needle Test Probe Assembly
G-2010 Series 0 to 30 psig (0 to 210 kPa) Gauge
Technical Specifications
Table 4: EP-8000 Specifications (Part 1 of 2)
EP-8000 Electro-Pneumatic Transducer
Action Proportional — Direct Acting
Supply Pressure 18 to 25 psig (126 to 175 kPa); nominal 20 psig (140 kPa); air supply must
be clean, dry, and oil-free.
Supply Pressure Sensitivity 0.3 psig/psig (0.3 kPa/kPa
Adjustments Voltage Models 20 VDC Maximum Input; Span Adjustable From 7.5 VDC to 15 VDC;
Factory-Set at Approximately 10 VDC
Current Models 30 mA DC Maximum Input; Span Adjustable From 10 to 20 mA DC;
Factory-Set at Approximately 16 mA DC
All Models Output can be shifted ±9 psig (±63 kPa) using zero adjustment screw.
Linearity 5% Maximum of Output Span Between 3 to 15 psig (21 to 103 kPa)
Hysteresis 0.5 psig (1.4 kPa) typical
Temperature Coefficient 0.05 psig/°F (0.64 kPa/°C)
Input Impedance Voltage Models 1,000 Ohms Minimum
Current Models 350 Ohms Maximum
Air Flow Capacity at Low Volume 45 SCIM (12.3 mL/s) Maximum1
20 psig Supply Models
High Volume 1600 SCIM (437 mL/s) Maximum
Models
Air Consumption Low Volume 45 SCIM (12.3 mL/s) Maximum1
Models
High Volume 45 SCIM (12.3 mL/s) Maximum
Models
Electrical Connections Two-Wire Terminal Block for 18 AWG Stranded Wire
Air Connections Barbed Fittings for 5/32 or 1/4 in. O.D. Polytubing
Materials Body Polysulphone
Case and Cover Polycarbonate/ABS
Enclosure IP 20 (IEC 60529)
Protection
Air Connections Brass
Ambient Operating Temperature 41 to 122°F (5 to 50°C)
Limits Humidity 10 to 90% RH, Non-condensing
Ambient Storage Temperature Limits -4 to 140°F (-20 to 60°C)
Mounting Surface-Mounted or Installed on Pneumatic Valve or Damper Actuator
Using Accessory Mounting Kit
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin
8
Table 4: EP-8000 Specifications (Part 2 of 2)
EP-8000 Electro-Pneumatic Transducer
Shipping Weight EP-8000-1 and -3 0.5 lb (227 g)
EP-8000-2 and -4 0.6 lb (272 g)
1. This value is specified for dead-ended loads or with controlled devices/applications with a maximum air consumption of
10 SCIM (2.7 mL/s).
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, contact Johnson Controls Application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for damages
resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT
45143 ESSEN MILWAUKEE WI 53202 MANAGEMENT
GERMANY USA NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
EP-8000 Series Electro-Pneumatic Transducers Product/Technical Bulletin