Code No. LIT-1922495
                                                                                                                                                  Issued October 27, 2011

EP-8000 Series

Electro-Pneumatic Transducer
Description                                                     Applications
The EP-8000 Electro-Pneumatic Transducer                        •   typically used with pneumatic valve or
converts a 0 to 10 VDC or 4 to 20 mA signal                         damper actuators
from an electric controller into a proportional                 •   sequencing can be provided through a
pneumatic output pressure signal. Four                              Johnson Controls® V-9502 Valve Actuator
models are available, which are grouped into                        Positioner or D-9502 Damper Actuator
two basic versions: low-volume output units                         Positioner
(non-relay) and high-volume output units
(relay).                                                        Repair Information
                                                                If the EP-8000 Series Electro-Pneumatic
Features                                                        Transducer fails to operate within its
•     hypodermic needle test point allows easy                  specifications, replace the unit. For a
      output pressure signal measurement                        replacement transducer, contact the nearest
•     barbed air connections for 5/32 or 1/4 in.                Johnson Controls representative.
      O.D. polytubing
•     compact, simple design for ease of                        To Order
      installation on a wide range of mounting                  Specify the code number from the following
      surfaces, including direct mounting on                    selection chart.
      pneumatic valve actuators                                                                                                    EP-8000 Electro-Pneumatic Transducer
•     factory set, fully adjustable zero and span
      facilitates field calibration

Selection Chart
Code Number Output                                             Input                       Input Range                Factory Output Range psig (kPa)
EP-8000-11             Low Volume (Non-Relay)                  Voltage                     0.5 to 9 VDC               1 to 18 (7 to 126)
    EP-8000-2          High Volume (Relay)                     Voltage                     0.25 to 9.5 VDC            0.5 to 19 (3.5 to 133)
EP-8000-3    1         Low Volume (Non-Relay)                  Current                     4 to 20 mA DC              3 to 15 (21 to 105)
    EP-8000-4          High Volume (Relay)                     Current                     4 to 20 mA DC              3 to 15 (21 to 105)
1. Low-volume models are one-pipe instruments requiring a 0.007 in. (0.017 mm) R-3710 Series Restricter, ordered separately.

Accessories
Code Number Description
R-3710                 0.007 in. Restricter (Required for Low-Volume Models)
EP-8000-101            Electro-Pneumatic Transducer Mounting Kit (For Mounting the EP-8000 to a Pneumatic Valve Actuator)
A-4000-137             In-line Filter (Required for All Models)
A-4000-1037            In-line Filter (Required for all Models; Package of Five)
JC-5361                Hypodermic Needle Test Probe Assembly
G-2010 Series          0 to 30 psig (0 to 210 kPa) Gauge

Specifications
                                                          EP-8000 Electro-Pneumatic Transducer (Part 1 of 2)
Action                                                                       Proportional — Direct Acting
Supply Pressure                                                              18 to 25 psig (126 to 175 kPa); nominal 20 psig (140 kPa); air supply must be clean, dry, and
                                                                             oil-free.
Supply Pressure Sensitivity                                                  0.3 psig/psig (0.3 kPa/kPa
Adjustments                              Voltage Models                      20 VDC Maximum Input; Span Adjustable From 7.5 VDC to 15 VDC; Factory-Set at
                                                                             Approximately 10 VDC
                                         Current Models                      30 mA DC Maximum Input; Span Adjustable From 10 to 20 mA DC; Factory-Set at Approximately
                                                                             16 mA DC
                                         All Models                          Output can be shifted ±9 psig (±63 kPa) using zero adjustment screw.
Linearity                                                                    5% Maximum of Output Span Between 3 to 15 psig (21 to 103 kPa)
Hysteresis                                                                   0.5 psig (1.4 kPa) typical
Temperature Coefficient                                                      0.05 psig/°F (0.64 kPa/°C)
Input Impedance                          Voltage Models                      1,000 Ohms Minimum
                                         Current Models                      350 Ohms Maximum
Air Flow Capacity at 20 psig             Low Volume Models                   45 SCIM (12.3 mL/s) Maximum1
Supply                                   High Volume Models                  1600 SCIM (437 mL/s) Maximum

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       1 of 2
Electro-Pneumatic Transducer (Continued)

                                                           EP-8000 Electro-Pneumatic Transducer (Part 2 of 2)
 Air Consumption                          Low Volume Models                  45 SCIM (12.3 mL/s) Maximum1
                                          High Volume Models                 45 SCIM (12.3 mL/s) Maximum
 Electrical Connections                                                      Two-Wire Terminal Block for 18 AWG Stranded Wire
 Air Connections                                                             Barbed Fittings for 5/32 or 1/4 in. O.D. Polytubing
 Materials                                Body                               Polysulphone
                                          Case and Cover                     Polycarbonate/ABS
                                          Enclosure Protection               IP 20 (IEC 60529)
                                          Air Connections                    Brass
 Ambient Operating Limits                 Temperature                        41 to 122°F (5 to 50°C)
                                          Humidity                           10 to 90% RH, Non-condensing
 Ambient Storage Temperature Limits                                          -4 to 140°F (-20 to 60°C)
 Mounting                                                                    Surface-Mounted or Installed on Pneumatic Valve or Damper Actuator Using Accessory
                                                                             Mounting Kit
 Shipping Weight                          EP-8000-1 and -3                   0.5 lb (227 g)
                                          EP-8000-2 and -4                   0.6 lb (272 g)
1. This value is specified for dead-ended loads or with controlled devices/applications with a maximum air consumption of 10 SCIM (2.7 mL/s).

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       2 of 2