| Вид документа | Керівництво користувача |
|---|---|
| Виробник | JCI |
| Код документа | dx-lcd-display-user-guide |
| Група обладнання | DX LCD Display Terminal |
| Сторінок | 77 |
| Мова документа | англійська |
| Розмір файлу | 1.0 МБ |
Текст документа
Table of Contents
DX LCD Display User’s Guide
Chapter 1 Using This Guide .......................................................1-1
Introduction...................................................................................................... 1-1
Key Concepts................................................................................................... 1-2
Chapter Organization .....................................................................................................1-2
Manual Conventions ......................................................................................................1-2
Chapter 2 Introduction to DX LCD Display.........................................2-1
Introduction...................................................................................................... 2-1
Key Concepts................................................................................................... 2-2
DX LCD Display .............................................................................................................2-2
Features .........................................................................................................................2-2
Theory of Operation .......................................................................................................2-3
Display Configurations ...................................................................................................2-4
Related Information........................................................................................................2-5
Chapter 3 Installing the DX LCD Display............................................3-1
Introduction...................................................................................................... 3-1
Key Concepts................................................................................................... 3-2
Mounting Options ...........................................................................................................3-2
Considering Unit Dimensions.........................................................................................3-3
Internal Wiring of Adapters for Serial Communications Cable .......................................3-4
Procedure Overview........................................................................................ 3-5
© Johnson Controls, Inc. www.johnsoncontrols.com
2 Display Terminals
Detailed Procedures........................................................................................ 3-7
Mounting the DX LCD Display on a Wall .......................................................................3-7
Mounting the DX LCD Display on a UPM ......................................................................3-9
Mounting the DX LCD Display in a Panel ....................................................................3-10
Cabling a Permanently Mounted Device......................................................................3-13
Cabling a Portable Device............................................................................................3-19
Chapter 4 Operating the DX LCD Display...........................................4-1
Introduction...................................................................................................... 4-1
Key Concepts................................................................................................... 4-2
Display and Keypad .......................................................................................................4-2
Menu System .................................................................................................................4-5
Home Page ....................................................................................................................4-6
Password .......................................................................................................................4-6
Point Data ......................................................................................................................4-7
Point Value.....................................................................................................................4-7
Alarm Summary .............................................................................................................4-8
Most Recent Alarm and Total Alarms ............................................................................4-8
Alarm Log.......................................................................................................................4-9
Clock ..............................................................................................................................4-9
Time Schedules ...........................................................................................................4-10
Holidays .......................................................................................................................4-10
Optimal Start/Stop Parameters ....................................................................................4-10
Trend Data ...................................................................................................................4-11
Digital Trend.................................................................................................................4-13
Procedure Overview...................................................................................... 4-15
Detailed Procedures...................................................................................... 4-16
Establishing Communication with a DX Controller .......................................................4-16
Connecting to a DX Controller via the N2 Bus (Firmware Version 3.x only) ................4-17
Displaying the Main Menu............................................................................................4-19
Displaying the Home Page...........................................................................................4-20
Entering a Password ....................................................................................................4-21
Viewing Point Data.......................................................................................................4-24
Table of Contents 3
Adjusting and Overriding Points...................................................................................4-25
Releasing Overridden Points .......................................................................................4-28
Viewing the Alarm Summary ........................................................................................4-29
Viewing the Alarm Log .................................................................................................4-30
Setting the Clock ..........................................................................................................4-32
Editing Time Schedules ...............................................................................................4-33
Defining Holidays .........................................................................................................4-35
Changing Optimal Start/Stop Parameters ....................................................................4-36
Viewing Trend Data......................................................................................................4-39
Connecting to Another Controller.................................................................................4-42
Appendix A Specifications and Technical Data ................................ A-1
Introduction..................................................................................................... A-1
Key Concepts.................................................................................................. A-2
Ordering Codes............................................................................................................. A-2
Specifications ................................................................................................................ A-3
DX LCD Display User’s Guide 1-1
Chapter 1
Using This Guide
Introduction
The DX LCD Display User’s Guide provides information about how to
use the DX LCD Display. This chapter outlines the guide’s
organization and content.
© May, 2000 Johnson Controls, Inc. www.johnsoncontrols.com
Code No. LIT-6364120a
1-2 Display Terminal
Key Concepts
Chapter Organization
Each chapter of this DX LCD Display User’s Guide is divided into
four sections as described in Table 1-1.
Table 1-1: Chapter Organization
Section Description
Introduction Briefly outlines the contents of the chapter.
Key Concepts Describes background information necessary
to perform or understand specific tasks.
Procedure Overview Describes general steps for performing the
tasks described in the Detailed Procedures
section.
Detailed Procedures Describes in detail the steps needed to
complete specific tasks described within the
chapter. This sections is geared toward users
who are new to DX LCD Display.
Manual Conventions
As in most Windows based programs, sometimes there are multiple
ways to perform the same tasks. This manual does not describe how to
use both the mouse and the keyboard to perform the same step. In
general, Microsoft® conventions are used to describe software
features.
DX LCD Display User’s Guide 2-1
Chapter 2
Introduction to DX LCD Display
Introduction
The DX LCD Display unit is a person/controller interface used with
the DX-9100 series of controllers. The display can act as a simple
adjust and indication unit or be used for more complex tasks often
associated with a workstation. The display is designed for the
maintenance person who needs a straightforward way to monitor and
adjust points in a controller without being limited in capability. This
chapter gives an overview of the DX LCD Display.
Note: In this guide, Building Automation System (BAS) is a
generic term, which refers to the Metasys® Network,
Companion ™, and Facilitator™ supervisory systems. The
specific system names are used when referring to system-
specific applications.
© May, 2000 Johnson Controls, Inc. www.johnsoncontrols.com
Code No. LIT-6364120b
2-2 Display Terminals
Key Concepts
DX LCD Display
Figure 2-1 shows the DX LCD Display.
Dxlcd_1
Figure 2-1: DX LCD Display
Use the display as either a portable, hand-held unit for use with more
than one controller, or it can be permanently mounted on the wall, on a
Universal Packaging Module (UPM) or in a panel as an integral part of
the controller application.
Features
The DX LCD Display:
• Stores up to eight configurations.
• Displays up to 8 pages of 12 points per page (up to 96 points) for
each configuration.
• Chooses the appropriate configuration to match the connected
controller.
• Allows you to configure the display unit to communicate with any
one of eight controllers connected to an N2 Bus, using the
appropriate configuration to match the selected controller.
No other supervisory system may be connected in this
configuration.
• Allows you to fully configure point data using the GX-9100
software configuration tool.
Introduction to DX LCD Display 2-3
• Indicates alarms both visually and audibly.
• Maintains an Alarm Summary of points currently in an alarm state.
• Maintains an Alarm Log of the last 96 alarm and return-to-normal
Changes-of-State (COSs) with time and date stamp. For the Alarm
Log feature to operate as described, the DX LCD Display must be
permanently connected to one DX controller.
• Displays Trend Data collected in the DX controller (if supported
by the controller).
• Allows you to define and change Time Schedule parameters.
• Allows you to define and change Optimal Start/Stop parameters.
• Allows you to set the system clock, date, and daylight saving
times.
• Includes sealed membrane keypad.
• Provides backlit, 240 by 128 pixel Liquid Crystal Display (LCD)
(equivalent to 16 lines of text with 40 characters per line).
• Displays graphical Home Pages with selected ‘live’ data that can
be customized according to Original Equipment Manufacturer
(OEM) or end user requirements.
• Allows use of the DX LCD Display as either a portable, hand-held
device or permanently mounted in a panel or on the wall. A wire
stand pulls out of the back of the display to set it at an angle on a
table top or hang it on a door panel during portable operation.
Theory of Operation
The DX LCD Display works with the DX-9100 (Version 2.0 or later)
and DX-9120 Series of digital controllers. The display connects
directly to the built-in RS-232 serial port of the DX controller,
allowing easy access to all of the system functions available at the
user’s password level.
A DX LCD Display unit with an earlier firmware version (2.x) can
communicate directly with one DX controller by a direct connection,
but not via the N2 Bus. The DX LCD Display with firmware starting
from Version 3 can use an RS-232/RS-485 converter (with plug
adapter) to communicate, via the N2 Bus, with one of up to eight DX
controllers working in standalone mode (that is with no supervisory
system monitoring the N2 Bus).
The DX LCD Display is operated through a keypad and menu system
to provide access to the data and parameters stored in the DX
controller.
2-4 Display Terminals
Note: In the remainder of this guide, the DX-9100 and DX-9120
controllers are referred to simply as DX controllers.
Display Configurations
Each DX LCD Display unit stores up to eight display configurations.
Different configurations customize the display as required for different
applications or situations. When defining a configuration you can
describe point names, point units, and digital (binary) state names, and
each configuration can indicate whether a specific point can be
commanded (adjusted or overridden) by the user of the display. Each
configuration specifies a graphical Home Page, allowing you to
display pictures such as a company logo or a system diagram. You can
map live data points to the Home Page as desired.
Each display configuration is identified by a configuration name and
configuration code. The configuration (i.e., application) stored in the
DX controller is also identified by a configuration code (also called the
User Config Code). When you attach the DX LCD Display to a
controller, the display unit attempts to match one of its stored
configuration codes with the User Config Code defined in the
controller configuration. If it finds a match, then the DX LCD Display
uses the corresponding display configuration. If it does not find a
match, it uses the default configuration.
In N2 Bus mode, the DX LCD Display unit matches the available
configurations to the DX controllers found on the bus.
Both DX controller configurations and DX LCD Display
configurations are defined using the GX-9100 Software Configuration
Tool, part of M-Tool. The configurations are then downloaded to the
controller or display unit through the serial interface.
Introduction to DX LCD Display 2-5
Related Information
This guide describes how to install and operate the DX LCD Display.
Refer to Table 2-1 for additional information on configuring the DX
LCD Display, and installing and configuring DX-9100 controllers:
Table 2-1: Related Information
Description Document
Configuring the DX LCD GX-9100 Software Configuration Tool LIT-6364060
Display (FAN 636.4 and 1628.4)
Configuring the DX-9100 DX-9100 Configuration Guide, LIT-6364030
Controller GX-9100 Software Configuration Tool LIT-6364060
(FAN 636.4 and 1628.4)
Installing and Operating DX-9100 Extended Digital Controller Technical
the DX-9100 Controller Bulletin, LIT-6364020 (FAN 636.4 and 1628.4)
2-6 Display Terminals
DX LCD Display User’s Guide 3-1
Chapter 3
Installing the DX LCD Display
Introduction
Use the DX LCD Display as either a portable device, or permanently
mount it in a panel or on the wall. For panel and wall mounting
applications, the display unit is permanently connected to one DX
controller or to an N2 Bus with up to eight DX controllers.
This chapter describes how to:
• mount the DX LCD Display on a wall
• mount the DX LCD Display on a UPM
• mount the DX LCD Display in a panel
• cable a permanently mounted device
• cable a portable device
© May, 2000 Johnson Controls, Inc. www.johnsoncontrols.com
Code No. LIT-6364120c
3-2 Display Terminals
Key Concepts
Mounting Options
Mount the DX LCD Display in a standard enclosure or standard
cabinet door, such as the range of Universal Packaging Modules
(UPMs) from Johnson Controls (shown in Figure 3-1).
esc
!
dxtk_2
DX LCD Display
Figure 3-1: DX LCD Display UPM
Installing the DX LCD Display 3-3
Considering Unit Dimensions
Figure 3-2 shows the overall dimensions of the DX LCD Display. For
panel cutout dimensions or wall bracket drill hole spacing, see
Detailed Procedures in this chapter.
143 mm (5.63 in.)
47 mm (1.85 in.)
180 mm (7.09 in.)
esc
!
173 mm (6.81 in.)
150 mm (5.91 in.)
Dxtk_3
Figure 3-2: DX LCD Display Dimensions
3-4 Display Terminals
Internal Wiring of Adapters for Serial Communications Cable
Figure 3-3 shows the internal wiring of the adapters available for the
DX LCD Display serial communications cable. The DX/PC adapter is
provided with the DX LCD Display unit. The IU adapter (Europe) or
the CVT adapter (North America) is required for N2 communications.
Order the IU and CVT adapters separately. See Ordering Codes in
Appendix A Specifications and Technical Data.
6 DTR 5
5 GND 4 PC/DX
DX LCD Display 3 RX 3 9-Pin
Phone Jack Female Port
1+2 TX 2
DX/PC Adapter
5 GND 1 IU-9100
DX LCD Display 3 RX 3 9-Pin
Phone Jack Male Port
1-2 TX 5
IU Adapter
6 DTR
5 GND 2
DX LCD Display 4 RTS 3 MM-CVT101
Phone Jack 3 4
RX 25-Pin
1-2 TX Male Port
7
20
CVT Adapter dtwire
Figure 3-3: Serial Cable Wiring
Installing the DX LCD Display 3-5
Procedure Overview
Table 3-1: Installing the DX LCD Display
To Do This Follow These Steps:
Mount the DX LCD Display on Attach the wall mounting bracket to the wall and place the display unit
a Wall onto the bracket.
Connect the serial cable and power supply to the display.
Attach the display unit to the mounting bracket.
Connect the serial cable from the display to the DX controller and apply
power.
Mount the DX LCD Display on Drill pilot holes for mounting the base.
a UPM Drill a hole for communication and power cables.
Position washers over the two holes on the right side of the UPM and
secure the mounting bracket to the UPM cover.
Detach the flap covering the connectors from the DX LCD Display.
Connect the serial cable and power connector to the display.
Connect the serial cable from the display to the DX controller place the
display unit onto the bracket.
Apply power.
Mount the DX LCD Display in a Make a cutout in the panel and insert the display unit into the cutout.
Panel Insert and tighten the locking tabs.
Connect the serial cable between the display and the DX controller.
Connect power to the display unit.
Cable a Permanently Mounted To establish a direct connection to the DX controller:
Device Connect the serial communications cable into the phone jack labeled
RS232 INPUT on the display unit.
Plug the other end of the serial communications cable into the 9-pin
adapter marked DX/PC and plug the DX/PC adapter into the DX
controller.
If required, wire the alarm contacts to the alarm horn.
Use the 24 VAC supply voltage available at the DX controller to power the
DX LCD Display.
To extend the serial cable with line drivers:
Wire the short-haul modem using Figure 3-12 as a guide.
Use the cable provided with the modem to connect the DX controller to
Modem 1.
Using Figure 3-13 as a guide, set the S1 switch and the RTS/DTR control
jumper.
Using Figure 3-14 as a guide, connect the cables to the DX LCD Display
and Modem 2 using a 9-pin connector, a 9-9-pin gender changer, and a
9-pin DX/PC adapter.
Set the S1 switch and the RTS/DTR control jumper on Modem 2 as
shown in Figure 3-13.
Plug in the power supply for each modem.
Apply power to the DX LCD Display.
Continued on next page . . .
3-6 Display Terminals
To Do This (Cont.) Follow These Steps:
Cable a Permanently Mounted To establish the N2 Bus connection:
Device (Cont.) Plug the connector on one end of the serial communications cable into the
DX LCD Display.
Plug the other end of the serial communications cable into the 9-pin
adapter marked IU for the IU-9100 in Europe, or into the 25-pin adapter
marked CVT for the MM-CVT101 in North America.
Plug the adapter into the RS-232 serial port socket of the IU-9100 or
MM-CVT101 RS-232/RS-485 converter.
Cable a Portable Device Plug one end of the serial communications cable into the DX LCD Display
and the other end into the adapter marked DX/PC.
Plug the adapter into the DX controller.
Plug the power supply adapter into the DX LCD Display and into wall
socket.
Installing the DX LCD Display 3-7
Detailed Procedures
Mounting the DX LCD Display on a Wall
Note: A separately available wall mounting kit is required to mount
the DX LCD Display on a wall (see Ordering Codes in
Appendix A).
To mount the DX LCD Display on a wall:
1. Drill appropriate holes for the wall mounting bracket using the
dimensions shown in Figure 3-4.
76 mm
(3.0 in.)
20 mm
(0.79 in.)
6 x 30 mm
(0.24 x 1.18 in.)
dxtk_6
Figure 3-4: Wall Mounting Bracket
2. Attach the wall mounting bracket to the wall using the screws
provided in the wall mounting kit (Figure 3-4).
3. Connect the serial cable and power supply to the display. Refer to
Cabling a Permanently Mounted Device in this chapter.
3-8 Display Terminals
4. Place the DX LCD Display on the bracket, as indicated by in
Figure 3-5.
Note: The springs of the bracket fit into the rounded cavities in the
back of the display. Align the slots in the bracket and the
slots in the sides of the display unit.
2
1
3
Dxtk_7
Figure 3-5: Securing the DX LCD Display to the Wall
5. Secure the DX LCD Display to the bracket by inserting the
locking tabs supplied with the wall mounting kit into the
corresponding slots at the sides of the DX LCD Display, as
indicated by and in Figure 3-5.
Note: Apply a slight pressure on the front of the display against the
springs of the bracket while inserting the tabs. Make sure to
push the tabs all the way in so that they pass through the
bracket and re-enter the second slot in the back of the display
unit.
6. Connect the serial cable from the display to the DX controller.
Refer to the Cabling a Permanently Mounted Device section in
this chapter.
Installing the DX LCD Display 3-9
Mounting the DX LCD Display on a UPM
To mount the DX LCD Display on a UPM:
1. Position the wall mounting bracket on the UPM to allow
mounting of the DX LCD Display (Figure 3-6).
2. Mark four mounting holes.
3. Mark a cable hole.
4. Drill four pilot holes for mounting the base (hole size should be
between 0.160 inch and 0.170 inch, bit size No. 18, 19, or 20).
5. Drill a 1/2 inch hole for communication and power cables.
76 mm
(3.00 in)
Washer
20 mm
(0.79 in)
Four Holes at
4.3 mm (0.17 in) Diameter
upmfront
Figure 3-6: Mounting the Wall Mounting Bracket on a UPM
6. Position the two washers provided in the Wall Mounting Kit over
the two holes on the right side of the UPM. The washers must be
on the outside of the UPM. These washers compensate for the
indentation on the right side of the UPM.
7. Secure the mounting bracket to the UPM cover using the
four bolts and nuts included with the Wall Mounting Kit.
8. Detach the flap covering the connectors from the DX LCD
Display. This allows cables to be routed through cable hole.
9. Connect the serial cable and power connector to the display.
10. Connect the serial cable from the display to the DX controller
place the display unit onto the bracket.
3-10 Display Terminals
11. Attach the unit to the UPM. See Figure 3-5.
12. Apply power.
Mounting the DX LCD Display in a Panel
The panel mounting kit, supplied as standard equipment with the
DX LCD Display, is required to mount the display in a panel or
cabinet door. To mount the DX LCD Display in a panel or cabinet
door:
1. Make an appropriate cutout in the panel or cabinet door using the
dimensions shown in Figure 3-7 (note the maximum panel
thickness shown in the figure).
WARNING: Cutting a hole in a panel may compromise the
Underwriters Laboratories (UL) rating for the
panel.
Installing the DX LCD Display 3-11
16 mm Maximum
(0.63 in. Maximum)
174 mm
(6.85 in.)
1
144 mm
(5.67 in.)
Panelmt
Figure 3-7: Panel Mounting Dimensions
Note: If the panel thickness is greater than 5 mm (0.19 in), remove
the flap on the back of the display covering the erminals
(see Figure 3-10) prior to mounting the display.
2. Insert the DX LCD Display into the cutout, as indicated by in
Figure 3-7.
3. From the rear of the panel, insert the locking tabs supplied with
the panel mounting kit into the corresponding slots in the sides
and back of the DX LCD Display, as indicated by in
Figure 3-8.
3-12 Display Terminals
2
3
2
3
Panelbac
Figure 3-8: Securing the DX LCD Display in the Panel
4. Secure the DX LCD Display in the panel by tightening the screws
of the locking tabs, as indicated by in Figure 3-8.
5. From the rear of the panel, connect the serial cable between the
DX controller and the display unit, and connect the power supply
to the display. Refer to Cabling a Permanently Mounted Device in
this chapter.
Installing the DX LCD Display 3-13
Cabling a Permanently Mounted Device
Establishing a Direct Connection to the DX Controller
Figure 3-9 shows the connections made to the DX LCD Display for
power and communications with the DX controller.
24 VAC
24 VAC Com
91 92 93
esc
!
DX LCD 91 92 93 94 95 96 DX-9100/9120
Display RS-232 Serial Controller
Port Connector
Serial Cable
15 m (50 ft)
Maximum Length
Alarm Contacts to External
Annunciation Device (35 V, 1 Ampere Maximum)
dtdxcab
Alarm
Horn
Figure 3-9: Connections to Permanently Mounted DX LCD Display
3-14 Display Terminals
To establish a direct connection to a DX controller:
1. Lift the flap covering the connectors on the back of the DX LCD
Display as Figure 3-10).
Cover
Figure 3-10: Connector Location
2. The serial communications cable has a telephone-type connector
on each end. Plug one end of the cable into the phone jack labeled
RS232 INPUT on the DX LCD Display (Figure 3-11).
91 92 93 94 95 96
24 VAC com 24 VAC C NC NO 9/12 VDC
RS232 INPUT
dtconn
Power Supply External Alarm
Contacts
Figure 3-11: Connectors
3. Plug the other end of the serial communications cable into the
9-pin adapter marked DX/PC.
4. Plug the DX/PC adapter into the RS-232 serial port socket on the
front of the DX controller.
Installing the DX LCD Display 3-15
5. If required, wire the alarm contacts (Pins 94-96) to the external
annunciation device (alarm horn). The circuit voltage must not
exceed 35 VAC/VDC.
Note: The alarm contacts are provided only on the DX LCD
Display, Version 3 (DT-9100-8104).
6. The VDC supply voltage already available at the DX controller
can power the DX LCD Display. Wire a supply voltage cable to
Pins 91-93, using the 24 VAC pin assignments shown in Figure
3-11.
Extending the Serial Cable with Line Drivers
Note: You can extend the RS-232 serial cable maximum distance
of 15 meters (50 feet) by using line drivers or leased line
modems. We recommend the ME800A-R2 Short-Haul
modem from the Black Box Company. The maximum
distance allowed between the two modems is 3.2 km
(2 miles). If you use shielded cable, the distance is reduced
to 1.1 km (0.7 miles).
To connect the two modems:
1. Use 4-wire 0.6…0.8 mm (24…22 AWG) unshielded twisted pair
telephone cable to wire the short-haul modems so Transmit +
(TX+) on one modem is wired to Receive + (RX+) on the other
modem and Transmit - (TX-) is wired to Receive - (RX-).
A ground connection is optional. See Figure 3-12.
Modem 1 Modem 2
(Transmit +) TX+ (Receive +) RX+
(Transmit -) TX-
} Pair 1
(Receive -) RX-
(Receive +) RX+ (Transmit +) TX+
(Receive -) RX-
} Pair 2
(Transmit -) TX-
DTMODEM
Figure 3-12: Modem Wiring
2. Using the cable provided with the modem, connect the cable’s
9-pin connector to the RS-232 serial port socket at the front of the
DX controller.
3. Plug cable’s 25-pin connector into Modem 1. See Figure 3-14.
3-16 Display Terminals
4. Set the S1 switch on the modem circuit board to DCE (Modem 1).
5. Set the RTS/DTR control jumper to DIS position.
See Figure 3-13.
Ground Jumpers
TX- DIS
TX+ RTS/DTR
RD- Control
DCE
RD+
S1
Switch
DTE
dtmodjmp
Figure 3-13: Modem Jumper and Switch Settings
6. Plug the telephone-type connector on one end of the DX LCD
Display serial communications cable into the phone jack labeled
RS232 INPUT on the DX LCD Display.
7. Connect the other end of the serial communications cable into the
adapter marked DX/PC.
8. Connect the DX/PC adapter’s 9-pin connector to a 9 to 9-pin
gender changer.
9. Connect the gender changer to the 9-pin connector of the cable
supplied with the modem.
10. Connect the 25-pin end to Modem 2. See Figure 3-14.
Installing the DX LCD Display 3-17
DX-9100/9121
Controller
9-pin
Connector
9 to 25-pin Modem Cable
(Maximum 15 m (50 ft)
Modem 1 Modem 2 Maximum 15 m (50 ft) Total Cable Length
(Transmit+)TX+ (Receive +)RX+ from Modem 2 to DX LCD Display
(Transmit -) TX- } Pair 1 (Receive -) RX-
(Receive +) RX+ (Transmit +)TX+
} Pair 2
25-pin (Receive-) RX- (Transmit -) TX- 25-pin 9 to 25-pin Modem Cable
Connector Connector
4-Wire Cable
(Maximum distance: 3.2 km (2 miles)
Using shielded cable will reduce 9-pin
distance by 66%, but will prevent Connector DX LCD
transmission errors in noisy (Female) Display
electrical environments.)
9-9-pin
Gender Changer
9-pin
DX/PC
Adapter esc
!
DX LCD Display
dtmmdx
Serial Cable
Figure 3-14: Extension Cabling
11. Set the S1 switch on the Modem 2 (modem at the DX LCD
Display unit) circuit board to DTE.
12. Set the RTS/DTR control jumper to DIS position.
13. Plug in the power supply for each modem.
14. Apply power to the DX LCD Display and it will scan for the DX
address and come online.
3-18 Display Terminals
Establishing an N2 Bus Connection
Figure 3-15 shows the DX LCD Display on the N2 Bus.
IU-9100
Converter (or MM-CVT)
DX LCD
Display
DX-9100
DX-9100
DX-9100
DX-9100
N2
Bus dtn2bus
Figure 3-15: Devices on the N2 Bus
To establish a connection to the N2 Bus:
1. Lift the flap covering the connectors on the back of the DX LCD
Display.
2. Plug one end of the telephone-type connector on the serial
communications cable into the phone jack labeled RS232
INPUT on the DX LCD Display.
3. To connect the DX LCD Display unit to the N2 Bus via the
IU-9100 or MM-CVT101 RS-232/RS-485 converter, plug the
other end of the serial communications cable into the 9-pin
adapter marked IU for the IU-9100 in Europe, or into the 25-pin
adapter marked CVT for the MM-CVT101 in North America.
4. Plug the adapter into the RS-232 serial port socket of the IU-9100
or MM-CVT101 RS-232/RS-485 converter.
Installing the DX LCD Display 3-19
Cabling a Portable Device
Figure 3-16 shows the connections between the DX LCD Display and
a DX controller.
DX LCD Display Unit DX-9100/9120 Controller
esc
!
Serial Cable
RS-232 Serial Port
Connector
9/12 VDC Power Supply
(AC Adapter) dtportca
Figure 3-16: Connections to the DX LCD Display
To establish a connection to a DX controller:
1. Lift the flap covering the connectors on the back of the DX LCD
Display.
2. Plug the telephone-type connector of a serial communications
cable into the phone jack labeled RS232 INPUT on the DX LCD
Display.
3. Plug the other end of the serial communications cable into the
adapter marked DX/PC.
4. Plug the DX/PC adapter into the RS-232 serial port on the front of
the DX Controller.
5. Plug the small connector of the power supply adapter
(order separately) into the jack labeled 9/12 VDC on the DX LCD
Display.
6. Plug the power supply adapter into a standard AC wall socket.
3-20 Display Terminals
DX LCD Display User’s Guide 4-1
Chapter 4
Operating the DX LCD Display
Introduction
The DX LCD Display is operated through a simple keypad and menu
system interface that provides easy, intuitive access to the data and
parameters stored in the DX controller. It provides password
protection for those functions that change data in the DX controller,
such as adjusting/overriding point values, editing time schedules, and
changing optimal start/stop parameters.
This section describes how to:
• establish communication with a DX controller
• connect to a DX controller via the N2 Bus
• display the Main menu
• display the Home Page
• enter a password
• view point data
• adjust/override points
• release overridden points
• view alarm summary
• view Alarm Log
• set the clock
• edit Time Schedules
• define holidays
• change Optimal Start/Stop parameters
• view Trend data
• connect to another controller
© May, 2000 Johnson Controls, Inc. www.johnsoncontrols.com
Code No. LIT-6364120d
4-2 Display Terminals
Key Concepts
Display and Keypad
The DX LCD Display includes a sealed membrane touchpad, and a
240 by 128 pixel Liquid Crystal Display (LCD) that shows up to
16 lines of text with 40 characters per line.
Figure 4-1 shows the layout of the front panel of the DX LCD Display.
Table 4-1 shows Display Screen Components, Table 4-2 and Table 4-3
describe the keypad.
LCD Display
Name of Display Configuration Time
More …
ALARM: Most Recent Alarm Total: # Alarms
Keypad
esc
!
dxtk_8
Alarm LED
Figure 4-1: DX LCD Display Front Panel
Operating the DX LCD Display 4-3
Display Screen
Certain areas of the display screen always show the same type of
information during normal operation (i.e., once the DX LCD Display
has selected a display configuration). These areas of the screen are
indicated in Figure 4-1 and described in Table 4-1.
Table 4-1: Display Screen Components
Area Description
Name of Display Lists the name of the current configuration. You define the
Configuration name when you create the display configuration in the
GX-9100 software configuration tool.
Time Shows the current time in the connected DX controller in
either 12 or 24 hour format.
More Indicates if there are more pages of data associated with the
current function. Use the page up or page down key to
display the next or previous page.
ALARM: Most Lists the active alarm that occurred most recently and its
Recent Alarm status.
Total: # Alarms Lists the number of points currently in an alarm state.
4-4 Display Terminals
Keypad
Figure 4-2 shows the layout of the sealed membrane keypad:
esc
dxtk_9
Figure 4-2: Keypad
Table 4-2 describes the keypad keys and symbols, and Table 4-3
describes the Light-Emitting Diode (LED) indicator located in the
center of the keypad.
Table 4-2: Keypad Keys
Name Symbol Description
Up/Down Move between lines on a page, for example, to move
the selection bar through different items in a menu.
Page Up/ Scroll between pages if more than one screen of
Page Down information is available for the selected function. This
is indicated by the prompt More... in the bottom right
hand corner of the screen.
Plus / Change values (increased or decreased) while in edit
Minus mode. If either of the keys is held down, then the
auto-repeat function obtains the value you require
without having to use multiple keystrokes.
Escape Leave or abort a menu/submenu or adjust/command
esc procedure.
Enter Confirm an action, for example, when choosing a
menu option or commanding/adjusting a value.
Table 4-3: Keypad Indicator
Name Symbol Description
Alarm In addition to the audible alarm, a red LED positioned
Indicator above this symbol in the center of the keyboard
! membrane indicates whether alarms are present in
the monitored system, as follows:
Flashing At least one unacknowledged alarm
Steady On Alarms are present but all have been
acknowledged.
Off No alarms
Operating the DX LCD Display 4-5
Menu System
Power On
(Diagnostic Self
Test)
Same DX as
Last Connected? Yes
No
Choose
Controller*
esc Twice
(Double Click)
to Reset
Home Page Last Screen
or esc esc
Main Menu
and to highlight
to select
Alarm esc
Point Data Alarm Log Time Optional
Summary Trend Data Password
(page 1 of 8) (page 1 of 24) Schedules Start/Stop
(page 1 of 8)
esc esc esc
esc and
Alarm
Point Data Alarm Log Holidays Time/Date
Summary
(page 2) (page 2)
(page 2) Analog
Trend esc esc
esc
Alarm Digital Trend
Point Data Alarm Log
Summary Groups
(page 8) (page 24)
(page 8)
esc esc esc
Показано початок документа. Повний текст — у PDF за посиланням вище.