Metasys Network Sales Resource Manual       635
                                                                          Operator Devices Section
                                                                                   Product Bulletin
                                                                                        Issue Date      0300

                                DX LCD Display Terminal

The DX LCD Display Terminal is a local user
interface for DX-9100 Series controllers. It is
designed for the operator or maintenance person
who needs a straightforward way to monitor and
adjust controller points. Information may be
presented graphically and in textual format. The
display can be used as a portable, hand-held unit,
or permanently mounted in a panel or on the wall
to monitor a single controller, or any one of up to
eight controllers by keyboard selection.

                                                               Figure 1: DX LCD Display Terminal

                                       Features and Benefits

             ❑ Menu Operation                    Provides easy/intuitive operation - select from
                                                 a list of functions to monitor and control the
                                                 system

             ❑ Alarm/Summary Log                 Provides a quick view of current and past
                                                 alarm conditions

             ❑ Trend Log Display                 Provides graphical display of analog and
                                                 textual display of binary trend values

             ❑ Password Access                   Provides protection against unauthorized use

             ❑ Edit Time Schedules               Allows time schedules and holiday definitions
                                                 to be modified

             ❑ Adjusting/Overriding              Allows authorized users to adjust setpoints
                                                 and to override outputs between defined limits

             ❑ N2 Communications                 Communicates with any one of eight DX-9100
                                                 controllers as master on the N2 Bus

             ❑ Graphic Display                   Up to eight graphic displays of controlled
                                                 equipment

             ❑ Flash Memory                      Allows the user to configure the database and
                                                 upgrade the firmware of the DX LCD Display
                                                 from the GX-9100 Software Configuration
                                                 Tool

© 2000 Johnson Controls, Inc.                                                                                 1
  Code No. LIT- 635010                                                                 www.johnsoncontrols.com
P roduct Overview                                        P assword Protection
The DX LCD Display provides system diagnostic            The DX LCD Display has a password system with
views of the system controlled by the DX                 three possible security clearances:
controller. For example, you can view mixed air,
discharge air, and zone temperature at the same          •     No Clearance – Monitor equipment only
time. You can view setpoints, actual temperatures,       •     Level 2 – Monitor equipment and
and controller outputs on a single screen. User                adjust/override setpoints and outputs
defined text provides familiar point descriptions
unique to specific installation.                         •     Level 1 – Full access – Edit Time Schedules
The DX LCD Display comes from the factory with                 and Optimal start/stop parameters
a default configuration showing the value of each
input and output. For basic operation, it is not
necessary to load the DX LCD Display, just plug it in.   P rogramming
The DX LCD Display plugs directly into the               The DX LCD Display is programmed with the
controller. Convenient portability and simultaneous      standard GX-9100 software tool. You can select
display of multiple data points make it the ideal        and name points for a particular controller, using
hand-held tool.                                          the predefined point descriptions in the application
The DX LCD Display can be used with multiple             program, or modify them as you see fit, in terms
DX controllers. Communication is established by          familiar to the end user.
configuring and installing the unit as a master on
an N2 Bus with up to eight DX controllers, or
by simply plugging the cable into any                    U pgradeable Firmware
one DX controller. When connected to a controller,       The DX LCD Display firmware (Version 3 or later)
the proper configuration is automatically selected.      is upgradeable using the standard GX-9100
                                                         Software Configuration Tool (Version 6.0 or later).
D isplay Configurations
The DX LCD Display unit stores up to
eight separate display configurations. A
                                                         N 2 Communications
configuration specifies up to 96 points (items) of       The DX LCD Display can communicate with any
the DX controller that can be displayed and              one of up to eight DX Series controllers, acting as
monitored by the DX LCD Display. Each unique             a supervisory system for small to mid-size
configuration includes 12 trend definition variables     systems.
and a graphical display (home page). Each                               N2
configuration is identified by a configuration code,
which allows the display to automatically select the
appropriate configuration for the connected
controller.
                                                             DX LCD            DX-9100 Series Controllers

A   larm Indication                                          Display

When an alarm condition is detected, an alarm                          Figure 2: N2 Communications
sounds and a Light-Emitting Diode (LED) flashes.
Acknowledgment, by pressing a key, silences the
audible alarm. The LED also stops blinking, but
remains on steady until the alarm is cleared.
The Alarm Summary provides an overview of all
points currently in alarm state in the connected
controller.
The Alarm Log shows the history of the last
96 alarms that occurred in your system and the
date and time of their occurrence.

2   Operator Devices—DX LCD Display Terminal
E dit and Command Capabilities                                                        H ome Page
When connected to a DX controller, the DX LCD                                         The DX LCD Display shows a graphical home
Display can adjust/override points in the point data                                  page as the default initial screen. Each of the
screens and view and edit the following:                                              eight display configurations can have a different
! time and date                                                                       home page. The home pages are customizable,
                                                                                      and typically show a customer logo or graphical
! eight time schedules and thirty holidays                                            representation of the controlled equipment
! optimal Start/Stop module parameters                                                including live point data from the DX controller.
The Point Data screen provides fast identification                                    A sample custom home page is shown here.
of operating values, showing input, setpoint, and
output values simultaneously.
                                                                                                                 ON
      FLOOR 8 AHU                    POINT DATA 1/8                           11:40                 42%

                                                                                                                 ON        o
                                                                                                    CLEAN                22 C
      HA        Room Temperature                        25.8      Deg C
                Room Set Point
                Room     Point                          24.0      Deg C
                Supply Air Temp                         17.5      Deg C
                                                                                               o
      OVR       Supply Fan                 On                                                12 C
                Return Fan                 On
                Mixing Dampers                          10.0      %
                Heating Coil                                0.0   %
                Cooling Coil                            75.0      %                       Figure 5: Sample Customized Home Page
                Supply Filter              Clean
                Outside Air Temp                        29.7      Deg C

                                                                                      M ounting Options
                Electric Meter                       1234567      KWattH
      ALM       Humidifier S/S             Fault
                                                                            More...
      ALARM: Room Temperature              HA                              Total:02

     Figure 3: Point Data Screen Example

V iew Trend Data
A DX controller (Version 2.3 or 3.3 firmware or
later) that supports Trend Log can collect and
store trend data for up to 12 analog and logic
variables. The 12 trend variables may also be
defined for display on the DX LCD Display. The
trend data is shown graphically for analog values
and as text for binary values.
                                                                                                     Figure 6: Wall Mounting
       GROUND FLOOR                        TREND 5                           11:40
       Green Room Temp                             SAMPLE MODE: Actual
                 06 June 1997      13:23             23.4             Deg C
        100

       Auto

            0

       ALARM:                                                              Total:00

                          Figure 4: Trend Data

                                                                                                    Figure 7: Panel Mounting

                                                                                       Operator Devices—DX LCD Display Terminal           3
O rdering Codes
Table 1: Ordering Codes
 Item                                                              Part Number
 DX LCD Display Unit (includes Serial                              DT-9100-8104
 Communication Cable and Panel Mounting Kit)
 Wall Mounting Kit                                                 DT-9100-8902
 Replacement Panel Mount Kit                                       DT-9100-8903
 Plug Adapter for MM-CVT Converter                                 DT-9100-8904
 Replacement Serial Communication Cable                            DT-9100-6801
                                                                   0.45m (18 in) extending to >= 1.4m (4 ft 6 in) length
 9 VDC Power Supply (AC Adapter)                                   NP-PWR1209-0
 (120 VAC source - North America)
 RS-232 to N2 Communications Converter                             MM-CVT101-0
 M-Tool Programming Toolset                                        MW-MTool-0 (new user)
 (includes GX-9100 Tool)                                           MW-MTool-6 (upgrade)

S pecifications
        Power Requirements          Power supplied from 24 VAC @ 4 VA or 9-18 VDC from AC Adapter
                                    (nominal: 250 mA @ 12 VDC)
                                                                                  2
                 Terminations       Separable Terminal Block for 1-1.5 mm (14 AWG [maximum]) cables for 24 VAC
                                    supply and alarm relay contacts
                                    Universal jack connection for DC power supply (AC Adapter)
         DX Communication           9600 baud asynchronous, half duplex via 6-pin RJ12 telephone style jack
              Cable/Wiring                  2
                                    0.09 mm (28 AWG) phone cable Maximum 15m (50 ft) (RS-232C)
                                    DX/PC plug adapter supplied. Order MM-CVT101 adapters separately.
          Ambient Operating         0 to 50°C (32 to 122°F)
                Conditions          10 to 90% relative humidity (non-condensing)
                                    30°C (86°F) maximum dew point
             Ambient Storage        -20 to 60°C (-4 to 140°F)
                  Conditions        10 to 90% relative humidity (non-condensing)
                                    30°C (86°F) maximum dew point
    Dimensions (H x W x D)          150 x 180 x 47 mm (5.91 x 7.09 x 1.85 in.)
             Shipping Weight        0.78 kg (1.72 lb)
                         Display    LCD 16 x 40 characters (240 x 128 pixels)
                                    Screen Size: 110 x 60 mm (4.3 x 2.4 in)
                                    Backlit with time-out for extended life
              Alarm Indicator       Red LED, Beep Tone, and Relay Contacts (30 VAC/48 VDC, 1 ampere maximum)
             Agency Listings        CE Directive 89/336/EEC: EN 50081-1, EN 50082-1
                                    UL and CUL per UL 916 (pending)
                                    FCC Part 15 - Class A - CISPR22B
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.

Controls Group                                                                                       www.johnsoncontrols.com
507 E. Michigan Street                                                                                                   FAN 635
P.O. Box 423                                                                              Metasys Network Sales Resource Manual
Milwaukee, WI 53201                                                                                              Printed in U.S.A.

4   Operator Devices—DX LCD Display Terminal

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.