| Вид документа | Каталожна сторінка |
|---|---|
| Виробник | JCI |
| Код документа | dx-lcd-display-terminal-dt-9100-catalog-page |
| Група обладнання | DX LCD Display Terminal |
| Сторінок | 1 |
| Мова документа | англійська |
| Розмір файлу | 0.1 МБ |
Текст документа
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1928260
dx_lcd p; 1928260 9thcc:na FMS ? Rev:
09/10/98
logo:
DX standard
left ft:
none
LCD Display Terminal (DT-9100) right ft:
standard
Sect# = 7Se
ct# =
seQ# = 102s
eQ# =
dxlcd.tif The DX LCD Display provides diagnostic • user-defined text for creating familiar point
views of the system controlled by the DX descriptions unique to specific installation
controller. For example, it can show mixed • alarm/summary log for quick view of current
air, discharge air, and zone temperature at the and past alarm conditions
same time. It can also show setpoints, actual
temperatures, and controller outputs on a • password access for protection against
single screen. unauthorized use
• adjusting/overriding capabilities allowing
The DX LCD Display stores up to
eight separate display configurations. authorized users to adjust setpoints and to
A configuration specifies up to 96 points override outputs between defined limits
(items) of the DX controller that the DX LCD • time schedule and holiday definition
Display can display and monitor. Each unique • graphical trend log display of analog and
configuration includes 12 trend definition textual digital trend values supported by the
variables and a graphical home page. controller
When an alarm condition is detected, an • user-definable graphical home page that
audible alarm is sounded and a Light-Emitting can, for example, display a customer’s logo
Description Diode (LED) flashes. The maintenance and live data from the DX controller
The DX LCD Display Terminal is a user person can acknowledge and stop the audible
interface for the DX Series controllers. The
alarm by pressing a key. The Alarm Summary Applications
display can function as a simple adjustment provides an overview of all points currently in
Small supervisory system for up to eight
and indication unit, or it can be used to alarm state.
DX Series controllers using DT-9100 Version
perform more complex workstation tasks. It is 3.x, communicating over the N2 bus (only
designed for the maintenance person who
Features
when no supervisory controller is used on N2).
needs a straightforward way to monitor and • easy, intuitive operating menu for selecting
adjust controller points. The display can be a functions to monitor and control the system To Order
portable, hand-held unit for more than one • point data screen for fast identification of Specify the code number from the following
controller, or permanently mounted in a panel operating values selection chart.
or on the wall as an integral part of a single
• easy system diagnostic tool showing input,
controller.
setpoint, and output values simultaneously
• upgradeable firmware using standard tools
Specifications
DX LCD Display Terminal (DT-9100)
Power Power supplied from 24 VAC @ 4 VA maximum or 9-18 VDC from AC Adaptor Selection Chart
Requirements (nominal: 50 mA @ 12 VDC)
Code Number Description
Separable Terminal Block for 1-1.5 mm2 /14 AWG (maximum) cables
Terminations DX LCD Display Unit (includes
for 24 VAC supply only DT-9100-8104
Panel Mounting Kit)
Universal jack connection for DC power supply (AC Adaptors)
DT-9100-8902 Wall Mounting Kit
9600 baud asynchronous, half duplex via 6-pin RJ12 telephone-style jack
DX DT-9100-8903 Replacement Panel Mount Kit
0.09 mm2 (28 AWG) phone cable
Communication
Maximum 15 m (50 ft)(RS232C) Plug adapter for MM-CVT
Cable/Wiring DT-9100-8904
Note: DX/PC plug adapter supplied. Order MM-CVT101 adapters separately. converter
Ambient 0 to 50°C (32 to 122°F) NP-PWR1209-0
9 VDC Power Supply
Operating 10 to 90% non-condensing relative humidity (120 VAC Source)
Conditions 30°C (86°F) maximum dew point System Tools
MW-MTOOL-0
-20 to 60°C (-4 to 140°F) (includes GX-9100 Tool)
Ambient Storage
10 to 90% non-condensing relative humidity MW-MTOOL-6 System Tools Upgrade
Conditions
maximum dew point
RS232 Converter for N2
Dimensions MM-CVT101-0
150 x 180 x 47 mm (5.91 x 7.09 x 1.85 in) Communication
(H x W x D)
Shipping Weight 0.78 kg (1.72 lb) Repair Parts
LCD 16 x 40 characters (240 x 128 pixels) Code
Display Screen Size: 110 x 60 mm (4.3 x 2.4 in.) Description
Number
Backlit with time-out for extended life
CE Directive 89/336/EEC: EN 50081-1, EN 50082-1 Serial Communication Cable
Agency Listings UL916 and cUL DT-9100-6801 .45 m (1.5 ft) extending to
FCC Part 15 - Class A - CISPR22B ≥ 1.4 m (4.5 ft) length
Housing UL94-V0
Standards
Protection IEC529 IP30 for hand-held and wall mounting applications
Compliance
IEC529 IP42 for panel mounting applications
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 02/03 Johnson Controls, Inc