Controls Group 507 E. Michigan Street
                                                                                                                       P.O. Box 423, Milwaukee, WI 53202
                                                                                                                       Code No. LIT-1928260
dx_lcd                  p;                                1928260        9thcc:na              FMS                                   ?                                            Rev:
                                                                                                                                                                                  09/10/98
                                                                                                                                                                                  logo:
DX                                                                                                                                                                                standard
                                                                                                                                                                                  left ft:
                                                                                                                                                                                  none

LCD Display Terminal (DT-9100)                                                                                                                                                    right ft:
                                                                                                                                                                                  standard
                                                                                                                                                                                  Sect# = 7Se
                                                                                                                                                                                  ct# =
                                                                                                                                                                                  seQ# = 102s
                                                                                                                                                                                  eQ# =
dxlcd.tif                                                  The DX LCD Display provides diagnostic                     • user-defined text for creating familiar point
                                                           views of the system controlled by the DX                     descriptions unique to specific installation
                                                           controller. For example, it can show mixed                 • alarm/summary log for quick view of current
                                                           air, discharge air, and zone temperature at the              and past alarm conditions
                                                           same time. It can also show setpoints, actual
                                                           temperatures, and controller outputs on a                  • password access for protection against
                                                           single screen.                                               unauthorized use
                                                                                                                      • adjusting/overriding capabilities allowing
                                                           The DX LCD Display stores up to
                                                           eight separate display configurations.                       authorized users to adjust setpoints and to
                                                           A configuration specifies up to 96 points                    override outputs between defined limits
                                                           (items) of the DX controller that the DX LCD               • time schedule and holiday definition
                                                           Display can display and monitor. Each unique               • graphical trend log display of analog and
                                                           configuration includes 12 trend definition                   textual digital trend values supported by the
                                                           variables and a graphical home page.                         controller
                                                           When an alarm condition is detected, an                    • user-definable graphical home page that
                                                           audible alarm is sounded and a Light-Emitting                can, for example, display a customer’s logo
Description                                                Diode (LED) flashes. The maintenance                         and live data from the DX controller
The DX LCD Display Terminal is a user                      person can acknowledge and stop the audible
interface for the DX Series controllers. The
                                                           alarm by pressing a key. The Alarm Summary                 Applications
display can function as a simple adjustment                provides an overview of all points currently in
                                                                                                                      Small supervisory system for up to eight
and indication unit, or it can be used to                  alarm state.
                                                                                                                      DX Series controllers using DT-9100 Version
perform more complex workstation tasks. It is                                                                         3.x, communicating over the N2 bus (only
designed for the maintenance person who
                                                           Features
                                                                                                                      when no supervisory controller is used on N2).
needs a straightforward way to monitor and                 • easy, intuitive operating menu for selecting
adjust controller points. The display can be a               functions to monitor and control the system              To Order
portable, hand-held unit for more than one                 • point data screen for fast identification of             Specify the code number from the following
controller, or permanently mounted in a panel                operating values                                         selection chart.
or on the wall as an integral part of a single
                                                           • easy system diagnostic tool showing input,
controller.
                                                             setpoint, and output values simultaneously
                                                           • upgradeable firmware using standard tools

Specifications
                                  DX LCD Display Terminal (DT-9100)
 Power                       Power supplied from 24 VAC @ 4 VA maximum or 9-18 VDC from AC Adaptor                    Selection Chart
 Requirements                (nominal: 50 mA @ 12 VDC)
                                                                                                                        Code Number                  Description
                             Separable Terminal Block for 1-1.5 mm2 /14 AWG (maximum) cables
 Terminations                                                                                                                               DX LCD Display Unit (includes
                             for 24 VAC supply only                                                                    DT-9100-8104
                                                                                                                                            Panel Mounting Kit)
                             Universal jack connection for DC power supply (AC Adaptors)
                                                                                                                       DT-9100-8902         Wall Mounting Kit
                             9600 baud asynchronous, half duplex via 6-pin RJ12 telephone-style jack
 DX                                                                                                                    DT-9100-8903         Replacement Panel Mount Kit
                             0.09 mm2 (28 AWG) phone cable
 Communication
                             Maximum 15 m (50 ft)(RS232C)                                                                                   Plug adapter for MM-CVT
 Cable/Wiring                                                                                                          DT-9100-8904
                             Note: DX/PC plug adapter supplied. Order MM-CVT101 adapters separately.                                        converter
 Ambient                     0 to 50°C (32 to 122°F)                                                                   NP-PWR1209-0
                                                                                                                                        9 VDC Power Supply
 Operating                   10 to 90% non-condensing relative humidity                                                (120 VAC Source)
 Conditions                  30°C (86°F) maximum dew point                                                                                  System Tools
                                                                                                                       MW-MTOOL-0
                             -20 to 60°C (-4 to 140°F)                                                                                      (includes GX-9100 Tool)
 Ambient Storage
                             10 to 90% non-condensing relative humidity                                                MW-MTOOL-6           System Tools Upgrade
 Conditions
                             maximum dew point
                                                                                                                                            RS232 Converter for N2
 Dimensions                                                                                                            MM-CVT101-0
                             150 x 180 x 47 mm (5.91 x 7.09 x 1.85 in)                                                                      Communication
 (H x W x D)
 Shipping Weight             0.78 kg (1.72 lb)                                                                        Repair Parts
                             LCD 16 x 40 characters (240 x 128 pixels)                                                     Code
 Display                     Screen Size: 110 x 60 mm (4.3 x 2.4 in.)                                                                               Description
                                                                                                                          Number
                             Backlit with time-out for extended life
                             CE Directive 89/336/EEC: EN 50081-1, EN 50082-1                                                             Serial Communication Cable
 Agency Listings             UL916 and cUL                                                                             DT-9100-6801      .45 m (1.5 ft) extending to
                             FCC Part 15 - Class A - CISPR22B                                                                            ≥ 1.4 m (4.5 ft) length
                             Housing      UL94-V0
 Standards
                             Protection   IEC529 IP30 for hand-held and wall mounting applications
 Compliance
                                          IEC529 IP42 for panel mounting applications

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson