Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1928025
digitmod whole 1928025 9thcc:8-16 FMS Metasys ® Network Rev:
07/18/97
logo:
JCI
left ft:
(none)
Digital Control Module right ft:
standard
Sect# = 0
seQ# = 6
dcm140.tif Description Features
The Digital Control Module (DCM) performs • up to 20 universal (analog/binary) inputs
direct digital control of devices such as valves, and up to 20 universal (analog/binary)
actuators, and variable speed drives. The outputs can be interfaced to the controller
DCM is actually a co-processor for the NCM, • provides accurate PID control
executing Proportional-Integral-Derivative
• self-tuning program fine tunes PID loop
(PID) loop calculations. This frees the NCM to
perform duties such as scheduling, interlocks, accuracy
and operation sequences. The DCM employs • “Softstart” algorithm brings chillers and fan
a “self-tuning” algorithm that automatically systems under normal control from start-up
and continually fine tunes PID loop without setpoint hunting
parameters to maintain a correct feedback • plug-in installation and easy commissioning
value. Self-tuning adjusts the control strategy
due to mechanical aging of devices or shifting To Order
variables, such as varying temperatures.
Contact your local Johnson Controls
The DCM can be installed in a 2-slot Representative.
NCU/NEU CU. or 5-slot NCU.
Selection Chart
Code Number Description
NU-DCM140-0 Digital Control Module 140
Repair Parts Accessories
Code Number Description Code Number Description
Digital Control Module 140 2 Slot Base Frame for
NU-DCM140-700 EN-BSF201-0
Repair Module DCM140
5 Slot Base Frame for
EN-BSF501-0
DCM140
NU-PWR101-0 Power Supply for DCM140
Specifications
Digital Control Module
Inputs 10 function module slots, handling up to 20 inputs
Voltage and Current: 12 bit resolution (.0244% at room temperature)
100 ohm RTD (DIN platinum): Resolution = .07°F over full range
Input Accuracies 1000 ohm RTD (JCI nickel): Resolution = .07°F over full range
1000 ohm RTD (DIN platinum): Resolution = .10°F over full range
1000 ohm RTD (JCI silicon): Resolution = .05°F over full range
Outputs 10 function module slots, handling up to 20 outputs
Output Accuracy Resolution is 10 bits (.0977% over the full range). Output accuracy is further affected by the individual output function module.
Source Power Power is from the power module (NU-PWR101-0).
32 to 122°F (0 to 50°C)
Ambient Operating Conditions
10% to 90% RH
-40 to 158°F (-40 to 70°C)
Ambient Storage Conditions
5% to 95% RH
Dimensions (H x W x D) 14 in. x 1.5 in. x 6 in. (355 x 36 x 152 mm)
Shipping Weight 2.6 lbs (1.18 kg)
FCC Part 15 Subpart J Class A
Agency Compliance UL 916
CSA C22.2 No. 205
Agency Listing UL Listed and CSA Certified as part of the Metasys Network
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 09/00 Johnson Controls, Inc