Metasys Ethernet Router
     JC-MER-CXB

    User Manual
     #TD060100-0MA
        Version 1.1
Trademarks
Contemporary Controls, ARC Control, ARC DETECT and
EXTEND-A-BUS are trademarks or registered trademarks of
Contemporary Control Systems, Inc. ARCNET is a registered
trademark of Datapoint Corporation. Other product names may be
trademarks or registered trademarks of their respective companies.
Copyright
© Copyright 1998-2006 by Contemporary Control Systems, Inc.
All rights reserved. Metasys® is a registered trademark of Johnson
Controls, Inc. © 2007 Johnson Controls, Inc. No part of this
publication may be reproduced, transmitted, transcribed, stored in
a retrieval system, or translated into any language or computer
language, in any form or by any means, electronic, mechanical,
magnetic, optical, chemical, manual, or otherwise, without the prior
written permission of:
Contemporary Control Systems, Inc.    Contemporary Controls Ltd
2431 Curtiss Street                   Sovereign Court Two
Downers Grove, Illinois 60515 USA     Univ. of Warwick Science Park
Tel:    +1-630-963-7070               Sir William Lyons Road
Fax:    +1-630-963-0109               Coventry CV4 7EZ UK
E-mail: info@ccontrols.com            Fax: +44 (0)24 7641 3786
WWW:    http://www.ccontrols.com
                   :                  Tel: +44 (0)24 7641 3923
                                      E-mail: info@ccontrols.co.uk

Disclaimer
Contemporary Control Systems, Inc. reserves the right to make
changes in the specifications of the product described within this
manual at any time without notice and without obligation of
Contemporary Control Systems, Inc. to notify any person of such
revision or change.

                          TD060100-0MA
                                2
Contents
Chapter 1 Introduction ......................................................... 6
                Description ................................................................... 6
                Specifications ............................................................... 7
                Connector Information ................................................. 8
                Mechanical Drawing .................................................... 9
                Ordering Information .................................................. 9
Chapter 2 Operation .......................................................... 10
                Description ................................................................. 10
                Theory of Operation .................................................... 11
                   Setup and Addressing ........................................... 11
                   Protocols ............................................................... 11
                   Subnet Communication Upon
                   Network Failure .................................................... 12
                Hardware Requirements ............................................. 12
                Design Considerations ................................................ 13
                   NCM Compatibility .............................................. 13
                   Quantity of Routers Needed ................................. 13
                   Physical Considerations ....................................... 13
                   Design Summary .................................................. 13
                   Design Restrictions .............................................. 15
                   Network Management Staff Involvement ............ 16
                   Metasys May Be Affected. .................................... 16
Chapter 3 Installation and Commissioning ........................ 17
                Hardware Installation ................................................. 17
                   Mounting ............................................................... 17
                   Powering ............................................................... 18
                   Indicator Lights and Booting ................................ 20
                   Bash Prompt & JC-MER-CXB Commands .......... 20
                Configuring the JC-MER-CXB .................................. 21
                Connecting Field Cables ............................................. 22
                Reconfiguring the System .......................................... 24
                Adding a New NCM or PMI/OWS to
                   an Existing Subnet ............................................... 24
                Moving an Existing NCM or
                   PCI/OWS to a Different Subnet ........................... 25
                Adding a New Metasys ARCNET Subnet ................. 26
                Changing the Ethernet Network ................................. 28
                Changing the Layout of the Metasys Network .......... 28

                                 TD060100-0MA
                                       3
Chapter 4 Troubleshooting ................................................ 30
                                    .................................................. 30
                Booting Up the Router
                Debugging Ethernet ...
                                    Failures ..................................... 30
                   Ping Command ................................................ 32
                   Ipstat Command .............................................. 33
                   Testnet Command          .......................................... 33
                General Problem Prevention ...................................... 33
                Debugging ARCNET Failures .................................. 34
                Debugging Router Failures ........................................ 34
                   JC-MER-CXB Does Not Run When Booted ...... 34
                   Status Screen Indicates Failure Number 113 ...... 34
                   Status Screen Indicates Failure Number 101 ...... 34
                   Status Screen Indicates Invalid Messages ........... 34
                   Metasys Devices Do Not Respond ....................... 35
                   All the Devices on One ARCNET
                   Segment Do Not Respond ................................... 35
                   Multiple ARCNET Segments
                   Do Not Respond .................................................. 35
                   JC-MER-CXB Does Not
                   Respond to Ping Requests ................................... 35
                   N1 Communications Are
                   Occasionally Unreliable ...................................... 36
                   Data Cannot Be Viewed on OWS
                   Across Network ................................................... 36
Chapter 5 Service ............................................................... 37
                Warranty ..................................................................... 37
                Technical Support ...................................................... 38
                Warranty Repair ......................................................... 38
                Non-Warranty Repair ................................................ 38
                Returning Products for Repair ................................... 39

                                 TD060100-0MA
                                      4
Appendices
             Appendix A: Metasys Router Planning Forms............. 40
             Appendix B: Common Commands and
                Software Switches .................................................. 42
                JC-MER-CXB Program (router) ............................ 42
                Ethernet Communications Tests (testnet) .............. 42
                Determining the MAC Address (getmac) ............... 42
                Configuration Download (download) .................... 43
                Software Switches ................................................... 43
                Other Linux Commands .......................................... 45
                FTP Files from JC-MER-CXB ................................ 45
             Appendix C: Statistics Screen Information .................... 46
             Appendix D: Setting Up HyperTerminal ....................... 47
             Appendix E: Field Connections ...................................... 48
             Appendix F: UDP Port Address Assignments ............... 49
             Appendix G: Linux Trademark Information .................. 50

Figures
             1: RJ-45 Connector ......................................................... 8
             2: 3-Pin Connector .......................................................... 8
             3: DB9 Connector ........................................................... 8
             4: Null-Modem Cable Wiring ......................................... 8
             5: JC-MER-CXB Dimensions ......................................... 9
             6: Sample Layout of Metasys Ethernet Router ............. 14
             7: Using the Panel-Mounting Brackets ......................... 17
             8: DC Powered .............................................................. 18
             9: Redundant DC Power ............................................... 18
             10: AC Powered ............................................................ 19
             11: AC Power with Grounded Secondary ..................... 19
             12: AC Power with Battery Backup .............................. 19
             13: Bash Prompt for the JC-MER-CXB ........................ 20
             14: Configuration Screen .............................................. 21
             15: Statistics Screen available at COM2 ....................... 31
             16: Example of Testnet Results Screen ......................... 42
             17: Example of Statistics Screen ................................... 46

Tables
             1: Common Ethernet Errors ........................................... 32

                               TD060100-0MA
                                    5
1 Introduction
Description
The Metasys Ethernet Router (JC-MER-CXB) provides either router
or gateway connectivity between ARCNET and Ethernet networks.
Sometimes in router/gateway applications, a desktop PMI/OWS
compatible computer is dedicated to the task of executing the applica-
tion program from either a hard disk or floppy disk. On the PMI/OWS
motherboard, two network interface modules are used to connect to
the two networks of interest. With the JC-MER-CXB, this same
functionality can be provided in a compact and reliable configuration.
On the front panel of the JC-MER-CXB is a BNC connector for the
ARCNET and an RJ-45 connector for the Ethernet.
Resident in the JC-MER-CXB is an embedded computer with a solid-
state flash disk capable of executing an application program. This user-
supplied application program routes packets between ARCNET and
Ethernet networks that utilize the same network layer or serve as a
gateway between different protocols used by the ARCNET and
Ethernet networks. For example, a popular transport layer for
Ethernet is TCP/IP. To route between ARCNET and Ethernet at the
network layer (IP), ARCNET would need to be operating a TCP/IP
stack as well. For all other situations where different higher-level
protocols are involved, a gateway program would be needed to effect
connectivity between ARCNET and Ethernet. Either situation can
be addressed by the JC-MER-CXB.
To provide ARCNET-to-Ethernet connectivity within a Metasys
system, the JC-MER-CXB was created by installing the necessary
application program onto the flash disk. This product replaces the
JC-MH-16, JC-EP-RG and JC-EP-CS version or model of the
Ethernet router. To configure the JC-MER-CXB, a laptop computer
running a terminal emulation program, like HyperTerminal, is
attached to one of the COM ports using a null-modem cable. Once
configured, the program runs continually.

                          TD060100-0MA
                                6
SPECIFICATIONS

Electrical                  DC              AC
 Input voltage:             10–36 volts     8–24 volts
 Input power:               8W              8 VA
 Input frequency:           N/A             47–63 Hz
Environmental
 Operating temperature: 0°C to +60°C
 Storage temperature: –40°C to +85°C
 Humidity:              10% to 95%, non-condensing

Ethernet Data Rates
  10/100 Mbps
ARCNET Data Rate
 2.5 Mbps
Shipping Weight
 1 lb. (.45 kg)
Compatibility
 ANSI/ATA 878.1 and IEEE 802.3
Regulatory Compliance
 CE Mark
 CFR 47, Part 15 Class A
 UL 508 Listed Device
 cUL 22.222 #14
 (intended for use with Class 2 circuits)

LED Indicators
 Status — multicolor (see page 20 for details)
 ARCNET                Ethernet
   RX — green          LINK/ACT — green/yellow
   ACT — yellow        DUP — green/yellow

                        TD060100-0MA
                              7
Connector Information
Ethernet Socket Pin Assignments (RJ-45 Connector)
     1        TD+
     2        TD–
     3        RD+
     6        RD–
    (all other pins are unused)

                                          Figure 1 — RJ-45 Connector
ARCNET Socket Pin Assignments (RJ-45 connector)
     4        Line – (Phase B)
     5        Line + (Phase A)
    (all other pins are unused)

ARCNET Socket Pin Assignments (3-pin screw terminal connector)
              485           485X
     SH       Shield        Shield
     B        Line –        Line
     A        Line +        Line
                                           Figure 2 — 3-pin Connector

COM1 & COM2 Pin Assignments (DB9 connectors)
    PIN       Signal        Function
    2         RXD           Receive Data
    3         TXD           Transmit Data
    5         GND           Ground
    (all other pins are unused)

                                               Figure 3 — DB9 Pins

COM1 & COM2 EIA-232 Communication Parameters (DB9 connectors)
    Baud Rate          57,600 bps
    Data Bits          8
    Parity             No Parity
    Stop Bit           1
                                  Figure 4 — Null-Modem Cable Wiring

                             TD060100-0MA
                                   8
Mechanical

                Figure 5 — JC-MER-CXB Dimensions

       Metasys Ethernet Router Ordering Information
  JC-MER-CXB                    Coaxial Cable Dipulse Transceiver

ELECTROMAGNETIC COMPATIBILITY
JC-MER-CXB units comply with Class A radiated and conducted
emissions as defined by CFR 47, Part 15 and by EN55022. This
equipment is intended for use in non-residential areas.

Warning
This is a Class A product as defined in EN55022. In a domestic
environment this product may cause radio interference — in which
case the user may be required to take adequate measures.

                        TD060100-0MA
                              9
2 Operation
Description
The JC-MER-CXB integrates Metasys N1 LAN segments with an
Ethernet network that uses the TCP/IP (Transmission Control
Protocol/Internet Protocol) suite. The router provides the physical
connection between a Metasys ARCNET segment and the Ethernet
network. It takes advantage of a customer’s existing Ethernet
network, while maintaining the dedicated Facility Management
System (FMS) communications necessary for complex, time-critical,
local control strategies.
With the JC-MER-CXB, Metasys controllers communicate transparently
over Ethernet, using standard components and maintaining complete
compatibility with existing network equipment. From an operator’s
view, this coupling of the N1 LAN to Ethernet creates a single large
network. No special commands are necessary to switch between
networks; data automatically transmits between networks without
operator knowledge or intervention.
The JC-MER-CXB communicates over an Ethernet network using the
TCP/IP protocol. Two networked JC-MER-CXBs pass ARCNET
data between themselves using the User Datagram Protocol (UDP)
service provided by TCP/IP. On the Ethernet network, the router is
seen as a workstation passing messages to another workstation. If a
power failure occurs, the router automatically restarts communications
once power is restored.
The JC-MER-CXB is derived from an earlier version of this device that
was an expansion module that occupied two slots of a Contemporary
Controls MOD HUB ARCNET Modular Active Hub. The new device
can be powered from an available low-voltage source or with an
optional wall-mount transformer. The ARCNET and the Ethernet
connections are made through ports on the front panel of the device.
Unlike a PMI/OWS, the JC-MER-CXB has no monitor or keyboard.
Instead, the monitor/keyboard functionality is done by an external
laptop or desktop computer running a terminal emulation program (like
HyperTerminal), while connected to COM ports on the JC-MER-CXB.

                         TD060100-0MA
                               10
The JC-MER-CXB program is accessed via COM2. The embedded
operating system is accessed via COM1. If a terminal emulation
program is attached to COM2, real-time routing statistics can be
observed. But once the router is started, no such cable connection is
required for continued operation.

Theory of Operation
Setup and Addressing
The method of linking the two networks is to separate the N1 LAN
into a number of ARCNET subnets. (In this document, the terms
“subnet” and “ARCNET segment” are the same.) Each ARCNET
subnet then connects to the customer’s Ethernet network via a single
JC-MER-CXB.
The router uses the N1 network addressing scheme to route messages
among the various ARCNET segments. Dividing Metasys into
multiple subnets has no affect on existing Ethernet communications,
and again, remains transparent to the operator.
To the operator, the router is simple to use and maintain. Once it is
configured to the customer’s network, the router works on its own,
uninterrupted. Branch office personnel configure the unit (via
HyperTerminal) by accessing a single screen. Once set, the data is
saved to a flash disk. Upon power up, the program and configuration
data is executed without any intervention. There are no moving
storage devices on the unit.
Protocols
The JC-MER-CXB uses the UDP/IP communications protocol to
transmit messages across the Ethernet network. This is important
because it allows the router to easily integrate into existing customer
networks that comprise multiple Internet (TCP/IP protocol suite)
networks.

                          TD060100-0MA
                                11
Even though the JC-MER-CXB looks like a data router to the Metasys
Network, most communications experts would call it a network
gateway. To the Ethernet network, the router looks like a normal
IBM PMI/OWS workstation. Unlike typical network gateways and
routers, the JC-MER-CXB does not process:

•       routing protocols used by standard network routers, except for
        UDP/IP communications from other JC-MER-CXB units

•       messages not generated by Metasys
The JC-MER-CXB responds to TCP/IP “ping” commands, allowing
you to verify that the router is operational and properly connected to
the Ethernet network. However, the ping could fail if a firewall
blocks it from reaching the intended target.

Subnet Communication Upon Network Failure
If the Ethernet network goes down, or the router disconnects or fails,
each Metasys subnet continues to function on a standalone basis. A
JC-MER-CXB: failure looks like a general failure of the Metasys N1
network. Devices on a subnet are still able to communicate with other
devices on that subnet, but devices on a different subnet are offline.

Hardware Requirements
The following are other hardware requirements of the JC-MER-CXB:

    •     Metasys Network with NCM200 or NCM300 or NCM4500 at
          any revision; or, NCM101/NCM401at Revision K or later

    •     10BASE-T/100BASE-TX Ethernet connection

    •     ARCNET connection (i.e., Metasys N1 LAN)

    •     10–36 VDC or 8–24 VAC power at each JC-MER-CXB location

                             TD060100-0MA
                                   12
Design Considerations
NCM Compatibility
The JC-MER-CXB is compatible with all versions of the NCM200,
NCM300 and NCM4500. If NCM101s/401s are used, they must be
Revision K or later. EPROM chips in older NCM101s/401s can be
upgraded for compatibility with the JC-MER-CXB. For information
about upgrading, contact Field Support Services. (The NCM102 does
not contain an N1 connection.)
Quantity of Routers Needed
The quantity of JC-MER-CXBs you need is identical to the number of
ARCNET segments connected through the Ethernet system. For
example, two units are required to connect two ARCNET segments
over one Ethernet segment (see Figure 6). A router is placed at each
location where the Ethernet segment meets the ARCNET segment.
Up to 50 JC-MER-CXB units can be used on each Metasys Network
(i.e., all ARCNET segments).
Physical Considerations
The router can be installed in a variety of ways, depending on the job
site. When selecting a location, consider the following:
1.    The location must have access to the customer’s Ethernet
      network, the ARCNET segment being serviced, and power.
2.    A JC-MER-CXB can be panel-mounted or DIN-rail mounted.
3.    Need power: either 10–36 VDC or 8–24 VAC.

Design Summary
Use these steps as a guideline when designing a JC-MER-CXB
Network, referring to Figure 6 for an example:
1.   Lay out the network as you would a normal Metasys N1
     Network. Determine the number and location of NCMs and
     Operator Workstations that will service the facility.
2.   Determine which portions of the network will use ARCNET and
     which will use Ethernet. The network layout must consist of
     multiple ARCNET segments connected by the customer’s
     Ethernet network.
     The Ethernet network must be a single Local Area Network
     (LAN) that can interconnect all of the ARCNET segments.

                          TD060100-0MA
                                13
   Note: If the Ethernet network consists of multiple Ethernet segments,
         the segments must be connected using LAN Routers that
         support the TCP/IP protocol suite. Intermediate networks
         that use other communications technology (FDDI, Token
         Ring) are acceptable if the intermediate networks are high
         speed. Low speed networks (e.g., 9600-baud serial lines) will
         cause unacceptable delays to Metasys N1 communications.

   The resulting network layout will be similar to the sample
   network shown in Figure 6. Each ARCNET segment will have
   one JC-MER-CXB attached to it. The ARCNET node address
   on each JC-MER-CXB has been preassigned 255.
3. Assign a subnet address to each ARCNET segment. We
   recommend using the subnet address “1” for the primary
   ARCNET segment, or the segment that has the most devices
   attached to it. Assign a unique node address to each NCM or
   Operator Workstation attached to the N1 network. Node
   addresses must be unique even if the NCMs are attached to
   different subnets. Record the subnet and node address
   information on the JC-MER-CXB Planning Form A.
   (See Appendix A: Metasys Ethernet Router Planning Forms.)

         Figure 6 — Sample Layout of the JC-MER-CXB

                          TD060100-0MA
                                14
4.   Have the customer’s network communications staff assign IP
     addresses and provide IP routing information for each
     JC-MER-CXB. Record this information on the JC-MER-CXB
     Planning Form B. (See Appendix A: Metasys Ethernet Router
     Planning Forms.) Append the ARCNET Subnet addresses from
     Form A to Form B.
5.   Using the JC-MER-CXB Planning Form B, configure each
     router by accessing its configuration screen. (See Chapter 3.)
6.   Use the assigned subnet and node addresses to address each of
     the Metasys NCMs and PMI/OWSs. When creating the DDL
     files for the system, use the subnet and node addresses in the
     NETWORK and GLOBAL DDL files.

Note:    Since you are converting multiple standalone networks into
         one large network, verify that no duplicate system names
         exist. If duplicates exist, you must change them to unique
         system names in both DDL and GPL.
If you are converting an existing system to use JC-MER-CXB units,
you’ll need to update and recompile the DDL files when the routers
are installed. Be sure to recompile all of the DDL files, including
all of the NC files. Failure to recompile all of the DDL files and
download ALL devices could result in application failures for those
NCMs located on new ARCNET segments.

Note:    Global and Model DDL file must be the same at all of the
         OWS (Operator Work Stations).
Design Restrictions
1.   The system should not use any realtime control strategies that
     require data transfers across the Ethernet network. Because the
     Ethernet network may experience delays and down time caused
     by non-Metasys equipment, the network is subject to variations
     in performance.
     Realtime control strategies can be used between NCMs located
     on a common ARCNET segment.
2.   Use caution when defining critical alarm reports that must cross
     the Ethernet. Avoid alarms related to life safety because they
     may not arrive at the Operator Workstation or printer if the
     customer’s Ethernet network is down.

                          TD060100-0MA
                                15
3.   Use of a customer’s Wide Area Network (WAN) is not
     recommended. The delays associated with Wide Area Networks
     may be unacceptable for operation of the Metasys Network.
4.   If the system contains a JC/85 Gateway, the Gateway points should
     not be mapped to objects that reside in NCMs located on different
     subnets.
     The JC/85 Gateway obtains the status for all objects that are
     defined in the Gateway at frequent intervals (every 1-5 seconds).
     This creates a large amount of message traffic on the N1
     network. If this message traffic is routed across the Ethernet, it
     will (a) add excessive loading to the customer’s Ethernet
     network, (b) slow down the operation of the JC/85 Gateway, and
     (c) result in sporadic offline reports for objects located in the
     remote NCMs.
5.   For the same reasons, if the system contains a Network Port, the
     Network Port cannot map its analog data points to objects that
     reside in NCMs located on different subnets.
6.   As with all Metasys networks, each NCM and PCI/OWS in the
     network must use a common time zone, even if the devices
     physically reside in different time zones.
Network Management Staff Involvement
When installing the JC-MER-CXB, work closely with the network
management staff at the job site. They will know the intricacies of
the Ethernet network to which you will be connecting. Get them
involved as much as possible. They should be able to provide you
with the following:

•    Ethernet connections
•    assignment of IP addresses
•    debugging expertise during installation and commissioning of
     the JC-MER-CXB
Metasys May Be Affected
Realize that the Ethernet network will affect the Metasys N1
Network. It can do so in these ways:

•    Ethernet traffic may slow down the performance of the Metasys
     N1 Network.

                            TD060100-0MA
                                  16
3 Installation and Commissioning
Hardware Installation

Mounting
The JC-MER-CXB is designed for mounting in an industrial enclosure
or wiring closet using either set of provided mounting hardware listed
below. The unit can also rest unsecured on a flat surface, if desired.

         TS-35 DIN Rail Mounting         Panel Mounting
         DIN rail clip                   Panel mounting brackets
         DIN rail clip support bracket   4-40 screws, flat-head (4)
         4-40 screws, pan-head (2)       #8 screws, pan-head (2)

For quick snap-mounting to 35 mm DIN rail, a reinforced DIN rail clip
is pre-attached to the back of the enclosure with two #4-40 pan-head
screws. If the clip is removed, the unit can be panel-mounted by
extending the top and bottom brackets which are shipped in retracted
position. The extended brackets can then anchor the unit to a wall or
other flat vertical surface with two #8 pan-head screws (also provided).
The left illustration of Figure 7 shows a rear view of the unit with the
brackets in retracted position. The right illustration of Figure 7 shows
the brackets extended and secured to the unit enclosure with the same
screws that were used in the retracted position.

          Figure 7 — Using the Panel-Mounting Brackets

                             TD060100-0MA
                                   17
Powering the JC-MER-CXB

To operate, the JC-MER-CXB requires low-voltage AC or DC power
provided to its four-pin removable keyed connector. Consult the
specifications for power requirements. There are several means for
providing power.

DC Powered
Make connections as shown in the diagram. The unit uses a DC-DC
converter that accepts a wide range of voltage (10–30 VDC) which it
converts for internal use. The “0Vdc” connection is connected to
chassis within the unit. Input connections are reverse-voltage protected.

                         Figure 8 — DC Powered

Redundant DC Powered
Redundant diode-isolated DC power inputs are provided on the unit
when a concern exists that the unit remain operational in the event of
a primary power failure. Make connections as shown in the diagram.
Each power supply must be capable of powering the unit. Do not
assume that input currents from the two supplies will be balanced.

                    Figure 9 — Redundant DC Power

                          TD060100-0MA
                                18
AC Powered
If only AC power is available, the JC-MER-CXB can be powered by
the secondary of a low-voltage transformer whose primary is
connected to the AC mains. The secondary must be 8–24 VAC and
ungrounded. When using a grounded secondary transformer, refer to
Figure 11. For convenience, two auxiliary power supplies are
available from Contemporary Controls: the AI-XFMR is for 120 VAC
primary power and the AI-XFMR-E uses 230 VAC.

                       Figure 10 — AC Powered

         Figure 11 — AC Power with Grounded Secondary

AC Powered with Battery Backup
The JC-MER-CXB can also be powered from both an AC and DC source.
Usually the DC source is from a battery connected as the DC powered
option. Refer to Figure 12 for details. In this application the unit does
not charge the battery, so separate provisions are required for charging.
If the AC source fails, the unit will operate from the battery.

               Figure 12 — AC Power with Battery Backup

                          TD060100-0MA
                                19
Indicator Lights and Booting
STATUS: At power on, this LED briefly glows red as a test. Then
while Linux boots (about 16 seconds), it flashes green. It then glows
solid to indicate Linux is operational — although another 16 seconds
must pass before ARCNET is functional. If this LED glows red during
normal operation, a power supply problem is indicated; if the external
power source is within specification, the JC-MER-CXB needs service.
ARCNET: If the unit is connected to a working ARCNET network,
the “RX” LED glows green whenever the unit receives data — otherwise
the “RX” LED will remain unlit. If the unit is disconnected from the
network, the “RX” LED will glow by default. The “ACT” LED flashes
yellow whenever the JC-MER-CXB is engaged in ARCNET activity.
Ethernet: After 2–3 seconds into the boot process (and thereafter), the
“LINK/ACT” LED will glow if a valid link exists to an working Ethernet
device. It indicates speed by color: green for 100 Mbps and yellow for
10 Mbps. It flashes to indicate activity. The “DUP” LED glows green to
indicate full-duplex operation and yellow for half-duplex.

Bash Prompt and JC-MER-CXB Commands
The JC-MER-CXB uses the Linux operating system. When the Linux
command line is displayed on screen, a special "bash" prompt appears.
Because it is derived from the Bourne shell, the prompt is known by
the pun: Bourne Again Shell, or bash. It is the standard command-line
interface on most Linux machines. All command-line entries for the
JC-MER-CXB must use lower case letters! The bash prompt for the
JC-MER-CXB is shown below.

           Figure 13 — Bash Prompt for the JC-MER-CXB

                          TD060100-0MA
                                20
Configuring the JC-MER-CXB
The JC-MER-CXB consists of a computer running Linux. It has an
Ethernet port, ARCNET port and a flash disk that emulates a disk
drive. The router program is preloaded at the factory but must be
configured. For this, Planning Forms are provided in Appendix A.

You can monitor JC-MER-CXB statistics (if monitoring has been
enabled) by connecting a null-modem cable from COM2 on the front
of the unit to a COM port on a laptop or desktop computer running a
terminal- emulation program like HyperTerminal. You configure the
parameters by connecting to COM1. Remember: monitor on COM2
and configure on COM1. See Appendix D for using HyperTerminal.

Once the terminal emulator is ready, connect it to COM2 (to monitor
the boot process) then apply power to the JC-MER-CXB. After the
Statistics Screen (see Figure 15 on page 31) appears and the "Idle"
fields begin to count, move the cable to COM1, type config and press
ENTER to access the configuration screen. The bottom of the screen
displays information on using certain keys to perform editing tasks.

The left side of the screen displays the JC-MER-CXB IP address,
Subnet Mask and Existing LAN Router IP address (network gateway,
if one exists). On the right side are switches (e.g., "/S") and all
ARCNET subnet addresses and associated JC-MER-CXB IP addresses.
All of this information is stored to non-volatile memory and, except
switch settings, must be identical on all JC-MER-CXBs.

              Figure 14 — Configuration Screen
                        TD060100-0MA
                             21
There is a provision for setting the Extended Timeout value of the
ARCNET subnet. The default is 0 (meaning normal timeouts) and in
the majority of applications, it should be left at 0. Extended timeouts
are only required on large fiber optic installations where the ARCNET
network diameter exceeds 5 km.

Using the JC-MER-CXB Planning Form B in Appendix A, add to
your right-side screen data with the ARCNET Subnet Address
(Column 1) and IP Address (Column 2) of each Metasys Ethernet
device to be connected. Enter these two addresses on the same line
above the “000” terminating flag at the end of the list. The # symbol
means that the text following the # is a remark. The following is an
example for three Metasys Ethernet devices:
             1    192.168.20.91
             2    192.168.20.23
             3    192.168.20.56

Save the configuration screen data by simultaneously pressing the Ctrl
and "K" keys, then release both keys and press the "S" key to save the
data and automatically reboot the JC-MER-CXB with the new settings.
The RX LED on the ARCNET port should glow and the ACT LED
should flash as the ARCNET port searches for other ARCNET nodes.
Note:    When entering IP addresses, care should be taken to avoid a
         trailing space which, although invisible onscreen, will
         nevertheless cause the address to be incorrect.
Verify no configuration errors exist by typing cat router.err.

Connecting Field Cables
The JC-MER-CXB connects to N1 ARCNET via coaxial as described
in Appendix E. The unit connects to N1 Ethernet via an RJ-45 jack.

1.   Connect the ARCNET cable from the Metasys N1 ARCNET
     subnet to the port on the JC-MER-CXB. If there is activity on the
     subnet, then the ACT LED on the unit should glow.
2.   Connect the cable from the Ethernet network to the unit's
     Ethernet port. If the cabling is correct and there is a working
     Ethernet device on the other end of the cable, the green Link
     LED should glow. If so, proceed to the next step.

                          TD060100-0MA
                               22
3. With HyperTerminal (or similar application) active and the
   JC-MER-CXB booted, attach the null-modem cable to COM2 then
   type “Q” to terminate the application and exit to Linux.
4.   At this point, the null-modem cable must be moved from COM2
     back to COM1 to access Linux. Once the cable is attached to
     COM1, the bash prompt should be visible after the ENTER key
     is pressed. You can clear the screen by typing clear (lower case)
     and pressing ENTER.
5.   Verify that the router is communicating with Metasys by using
     testnet to read the configuration data and then ping each listed
     device. You will notice the ACT LED near the Ethernet port
     will flash, indicating a proper transmission. Run testnet by
     typing the following at the bash prompt:
         testnet

     This will report the communication status for each listed N1
     device which could be an NCM, OWS, NIE or JC-MER-CXB.
     Example:
         Status of the Metasys Ethernet Devices:
         Device 192.168.20.91 is responding
         Device 192.168.23.23 is responding
         Device 192.168.20.56 is responding

Copy the configuration file to every JC-MER-CXB in the network
using the download utility or enter the data manually into each router
(for information on using the download utility see page 43). The
configuration file content must be identical for all routers on the job.
Once the download has been accomplished, execute the router
program by typing router then press ENTER.
Note: The router used for the download will need to be rebooted by
      typing reboot or by recycling power the router.
To view router statistics, the null-modem cable must be reattached to
the COM2 port. If the resulting display is garbled, refresh the screen
by pressing the "R" key. When connected to COM2, the "R" key will
"refresh" the screen and the "C" key will "clear" the statistics counters.

If the router configuration was not set up properly, the router will
stop running and continuously display an error message with the
instruction to press “Q” to quit. To determine the problem, refer to
Chapter 4: Troubleshooting.

                           TD060100-0MA
                                23
Reconfiguring the System
Over time, a Metasys Network that uses JC-MER-CXB devices may
have to be reconfigured to account for additions and changes to the
system. The reconfigurations that a system may undergo can be
classified as:
     •    adding a new NCM or PMI/OWS
     •    moving an NCM or PMI/OWS
     •    adding a new Metasys ARCNET subnet
     •    changing the Ethernet network
     •    changing the layout of the N1 network
This section describes the steps necessary to perform each of these
different types of reconfigurations.
Adding a New NCM or PMI/OWS to an Existing Subnet
Adding a new NCM or PMI/OWS to Metasys does not require any
changes to the JC-MER-CXB hardware or software. An NCM101/401
that is added to a JC-MER-CXB system must be Revision K or later.
All NCM200s and NCM300s are compatible with the JC-MER-CXB.
To add a new NCM or PMI/OWS to an existing subnet:
1.   Determine the correct subnet and node address for the new NCM
     PMI/OWS. The subnet address must match the subnet address
     for the ARCNET segment to which the NCM or PMI/OWS
     connects. The node address must be unique. You cannot duplicate
     any node address, even if the two devices reside on different subnets.
2.   If the device is an NCM, determine the correct subnet and node
     address for its archive device.
3.   Set the device subnet and node address as you normally do.

     •   For a PCI/OWS, set the node address using the switches on the
         ARCNET card (note: PS/2 system cards do not have
         switches, so PS/2 users can ignore this) and specify the
         subnet and node addresses in the DDL network
         configuration file.
     •   For an NCM, use WNCSETUP to set the subnet and node
         addresses. When using WNCSETUP, don’t forget to specify
         the correct subnet and node address for the archive device.

                          TD060100-0MA
                               24
4.   Add the device to the system database, either by updating the
     DDL global file or by using a device definition window.
5.   Physically attach the new NCM or PCI/OWS to the ARCNET
     segment that you have selected.
6.   You do not need to make any changes to the JC-MER-CXB. The
     router automatically routes messages correctly using subnet
     address for the new device.
Moving an Existing NCM or PCI/OWS or NIE to a Different
ARCNET Subnet
You may want to change the ARCNET segment to which an NCM or
PCI/OWS is attached. This may be required because an NCM or PCI/
OWS is moved to a new location or because the ARCNET cable layout
has been changed. Moving an NCM or PCI/OWS to a different subnet
does not require any changes to the JC-MER-CXB software. To move
a device to a different subnet, follow these steps:
1.   Determine the new subnet and node address for the NCM or the
     PCI/OWS. You will probably use the same node address for the
     device, but if you decide to change the node address, it must be
     unique. You cannot duplicate any node addresses, even if the two
     devices reside on different subnets. The device’s subnet address
     will have to change to match the subnet address for the
     ARCNET segment to which the device will be moved.
2.   If the device is an NCM, you may want to change its archive
     device. If you decide to change the archive device for the NCM,
     determine the subnet and node address for the new archive device.
3.   Change the subnet and node address for the device as you
     normally do.
     •   For a PCI/OWS, set the node address using the switches on
         the ARCNET card (note: PS/2 system cards do not have
         switches, so PS/2 users can ignore this) and specify the
         subnet and node addresses in the DDL network
         configuration file.
     •    For an NCM, use NCSETUP to set the subnet and node
         addresses. Once the subnet address for an NCM is changed,
         you will not be able to communicate with the NCM over the
         N1 network until it is physically attached to its new subnet.
         When using NCSETUP, don’t forget to specify the correct
         subnet and node address for the archive device.
                          TD060100-0MA
                               25
4.   Change the subnet and node addresses for the device in the
     Metasys database by updating the DDL Global file, compiling it
     and downloading it to all devices.
5.   Physically attach the device to its new ARCNET segment.
6.   You do not need to make any changes to the JC-MER-CXB. The
     router automatically routes messages correctly based on the new
     subnet address for the device.
Adding a New Metasys ARCNET Subnet
When a new device cannot be attached to one of the existing ARCNET
segments, a new subnet and a new JC-MER-CXB must be added. To
add a new subnet, do the following:
1.   Determine a location for the new JC-MER-CXB. It must have
     access to electrical power, a connection to the customer’s Ethernet
     network, and a connection to the new ARCNET segment.
2.   Select a new subnet address for the new ARCNET segment.
     The subnet address must be unique (not previously used for a
     different ARCNET segment).
3.   Obtain Internet address information for the new JC-MER-CXB
     from the customer’s communications/computer support staff. The
     information should include an IP address for the JC-MER-CXB,
     the subnet mask that is used, and an IP address for the customer’s
     existing LAN Router (if the customer’s Ethernet network uses
     LAN Routers).
4.   Obtain another JC-MER-CXB unit.

5.   Install the new JC-MER-CXB and attach it to the Ethernet network
     and to the ARCNET network. Verify that the JC-MER-CXB is
     communicating by “pinging” it from another Ethernet-equipped
     device. This can be done from another JC-MER-CXB that has a
     terminal emulator attached or from any Ethernet device that has
     TCP/IP communications software. For example, to ping a new
     router with IP address 192.168.22.236, enter:
                   ping   192.168.22.236

     The response to the PING command should indicate that the
     new router is communicating.

                           TD060100-0MA
                                26
6.   Modify the information in each JC-MER-CXB using the
     configuration program. Add a new line to the screen that lists
     the subnet address and the IP address for the new router. For
     example, if you are adding subnet number 12 with IP address
     192.168.22.236, add the following line:
                  12   192.168.22.236

     Add the new line before the line containing the three zeros (000).
     After you have edited the screen, save its information using the
     save command (Ctrl-K, S). Then use the download program to
     copy the new address information to all of the JC-MER-CXB
     devices used in the system.
     To download the new information, reboot the JC-MER-CXB that
     contains the new configuration and after the router has started
     running, enter download at the prompt. Follow the instructions
     provided and note any messages displayed. After the new
     configuration has been successfully downloaded to all other
     routers, reboot the originating router by typing in reboot.

     Note:    The IP address of the router with the new configuration
              must appear in the configuration screen of every other
              JC-MER-CXB in the network. A receiving router will
              not accept information from a device that is not listed
              in its existing configuration screen.

7.   Add the new NCM or PCI/OWS to the new ARCNET segment
     by following the procedures for adding an NCM or PCI/OWS to
     an existing ARCNET segment, as described previously.

                          TD060100-0MA
                               27
Changing the Ethernet Network
Occasionally, the customer’s communications/computer staff may
decide to rearrange their Ethernet network. Normally this will not
impact the operation of the JC-MER-CXB, except that it may result
in a temporary loss of communications with one or more of the
routers. Should this happen, each NCMs and PCI/OWS on those
subnets will go offline. If the customer decides to change the
configuration of their Ethernet network, you may have to change the
IP address information stored in each router. To do this, you will
have to change the configuration for each router.
If the IP address for the JC-MER-CXB was modified, you must
update the configuration screen. Change the IP address as needed.
Then use the download program to update all other routers.
Changing the Layout of the Metasys Network
In some situations you may want to reorganize the Metasys Network.
This may involve joining two existing ARCNET subnets into a
single subnet, splitting an existing subnet into two subnets, or
adding new subnets. If you are performing a major reconfiguration
of the network, follow these steps:
1.   Determine the new network layout for Metasys. The new
     network layout should show a number of ARCNET subnets that
     are connected using JC-MER-CXB units and the customer’s
     Ethernet network. Assign a unique subnet number to each
     ARCNET segment.
2.   Using the new network layout, determine where the JC-MER-CXB
     devices will be located. For each router, determine if it is an
     existing router or a new router. If you will be installing new
     routers, you will have to obtain them.
3.   Fill out a set of JC-MER-CXB planning forms for the new
     network layout. You should have filled out a set of forms when
     the routers were first installed. The JC-MER-CXB Planning
     Form B will be used to configure each of the JC-MER-CXB
     units. If you will be installing new routers, follow the procedures
     beginning on page 13.

                           TD060100-0MA
                                28
4.   Use the JC-MER-CXB Planning Form B to generate a new
     router file. The file should be a list of subnet address and IP
     address pairs of the form:
                   nnn   xxx.xxx.xxx.xxx

     where “nnn” is the subnet address and “xxx.xxx.xxx.xxx” is the
     IP address for the JC-MER-CXB attached to that subnet. The
     last line of the router file should be a line containing “000.”
     Once you have built a new router file that lists all of the subnets,
     a copy must be placed in each JC-MER-CXB attached to the
     system.
5.   Configure the new hardware and install it as described in a
     previous section, Adding a New Metasys ARCNET Subnet.
6.   Use the JC-MER-CXB Planning Form B to update the TCP/IP
     configuration on each of the existing JC-MER-CXB units. The
     procedure for updating the TCP/IP information is described in a
     previous section, Changing the Ethernet Network.
7.   To update the DDL files for Metasys, use the JC-MER-CXB
     Planning Form A. The only changes you should have to make
     are to the Network Definition and the Global Definition DDL
     files to change the subnet addresses for each NCM and each
     PCI/OWS. If you add new NCMs to the system, you will most
     likely update the DDL files to add the data base information for
     the new NCMs when you update the subnet and node addresses
     for the Metasys devices.

                           TD060100-0MA
                                29
4 Troubleshooting
Because the JC-MER-CXB hardware consists of an embedded
computer, knowledge of Linux will help in troubleshooting the system.

Booting Up the Router
When first activated, the JC-MER-CXB computer runs through a self
test. If an error is detected, the router will stop operating then repeatedly
display an error message advising the operator to press “Q” to end the
router program and exit to Linux.
Note:    Move the null-modem cable from COM2 to COM1 so that
         so that Linux commands can be entered. At the bash prompt
         type router or reboot.

Debugging Ethernet Failures
Software tools are provided with the product for checking Ethernet
network errors. These include the programs ping, ipstat, testnet and
a router statistics mode. The nature of the ping and ipstat programs
should be familiar to someone with previous experience with
TCP/IP software.
Prior to using the router statistics mode tools, you may need to
modify the router configuration file (router). Add the following
three switches (upper case letters only) if they are not already
present:
    /A

    /S

    /M

When the router is running, it displays statistical information as
shown in the example of Figure 15 — providing the null-modem
cable is attached to COM2. This display shows ARCNET and
Ethernet message counters.

                            TD060100-0MA
                                 30
The statistics screen normally shows the ARCNET and network
message Idle counters rapidly incrementing. The counters for
Invalid, Retry, and Failure messages should be zero. The ARCNET
and network Normal counters and the ARCNET and Ethernet
Broadcast counters increment as messages are received.

           Figure 15 − Statistics Screen available at COM2

•   If an Invalid message counter is non-zero, it indicates that an
    Invalid Metasys message was detected. The last Metasys
    message that was invalid is displayed.

•   To clear or reset the statisics screen counters, press "C".

•   To refresh the statisics screen, press "R".

•   A non-zero Failure counter indicates an Ethernet problem, and
    results in the display of an error number. Common Ethernet
    error numbers are listed on the following page.

                          TD060100-0MA
                               31
        Error Number                  Meaning
            98             Address already in use
            102            Network dropped connection
            74             Not a data message
            112            Host is down
            104            Connection reset by peer
            101           Ethernet Network Unreachable
                          (typically a customer LAN Router failure)
            113           Host unreachable (a remote Metasys
                          Ethernet device such as an NCM, OWS
                          or JC-MER-CXB is off-line)
            110           Connection timed out
            111           Connection refused

                  Table 1 — Common Ethernet Errors

If a defined router is offline when another router boots up, error 113
displays on the statistics screen. This error just means that a router
at one of the defined IP addresses did not respond as expected. The
router software flags this router as offline and will not send any
messages to it until it comes back online.
The other three Ethernet debugging tools are executed from the bash
prompt once the router program has been stopped. After stopping
the router by hitting the “Q” on the keyboard, switch the null-
modem cable to COM1 to exercise Linux control.
Note:    Once “Q” is hit, the router software stops transmitting
         Metasys messages, and its subnet loses communications
         with the rest of the Metasys Network. To restart the router
         program from the bash prompt, type router.
Ping Command
The ping command verifies that messages can be sent and received
over the Ethernet network by transmitting continuous pings. The
basic command format is:
    ping xxx.xxx.xxx.xxx

where “xxx.xxx.xxx.xxx” is the IP address of a device on the Ethernet
network. Other JC-MER-CXB units and TCP/IP-compatible device
systems send back a response. The pinging will continue until you
press Ctrl-C.

                          TD060100-0MA
                               32
Failures are caused by cable problems, device driver configuration
problems, or devices being offline. The display indicates if the ping
was successful and the approximate response time. A normal
response time for Ethernet is 25 to 50 milliseconds.
If there are any Ethernet communications errors, they are noted. If
the Ethernet network is running properly, no errors are reported.
Ipstat Command
The program ipstat reports various useful statistics. To launch
ipstat, type the following at the bash prompt:
                  ipstat

The resultant display reports the routing table, packet count, detected
errors and memory usage. If the Ethernet is operating properly, the
ipstat statistics should not report any errors.
Testnet Command
The testnet command reads the configuration data and attempts to
ping each device that is listed. The command format is:
                  testnet

Testnet lists the communication status for each device. If testnet can
talk to some devices but not others, the configuration data may
contain inaccurate information, such as a wrong address. To correct
bad addresses, access the configuration screen by running the config
command.

General Problem Prevention
1.   Configure the Metasys Ethernet Router’s IP address, existing
     LAN Router IP address, and subnet mask using information
     from the customer’s network manager.
2.   The Metasys ARCNET subnet addresses need to match the
     router configuration screen data. Each ARCNET segment needs
     a unique subnet address. The Metasys DDL files must use the
     correct subnet addresses.
3.   All of the Metasys devices on one ARCNET segment need to
     have the same subnet address. Although ARCNET hubs and
     links result in multiple ARCNET segments, for the purposes of
     the JC-MER-CXB, it is all considered one subnet.
4.   Time-critical control strategies should not cross Ethernet segments.

                           TD060100-0MA
                                33
Debugging ARCNET Failures
Use standard Metasys debugging tools to diagnose and correct
suspected ARCNET failures. The JC-MER-CXB displays message
statistics. The router should increment the ARCNET message counter
(broadcast) when it is connected to any ARCNET NCM or workstation.
This counter will increment even if multiple subnets are not defined.
If this counter does not increment, there may be a problem with the
router itself.

Debugging Router Failures
Several of the difficulties discussed in this section may be caused by
a global DDL file that is inaccurate or has not been downloaded.
Therefore, before going on, verify that the current global file is
up-to-date and fully downloaded.
JC-MER-CXB Does Not Run When Booted
The configuration screen should be examined for errors.
Status Screen Indicates Failure Number 113
One or more JC-MER-CXB units were offline when this router
started. Normal communication resumes when the other routers
come online.
Status Screen Indicates Failure Number 101
This is caused by the customer’s existing LAN Router being offline.
Verify that the existing LAN Router IP address is correct. Check
with the customer’s LAN manager to determine the condition of the
existing LAN Router.
Status Screen Indicates Invalid Messages
1. An operator tried to access an NCM defined in the DDL, but the
    NCM is on a subnet that does not appear in the configuration
    screen. Update the screen to include the undefined subnet.
2.   The Metasys Network generated a message that contained an
     invalid address. Write down the message information that
     appears on the screen and call Field Support Services.

                          TD060100-0MA
                               34
Metasys Devices Do Not Respond
If any other node on the same ARCNET segment responds normally,
the router is not at fault. The problem could be caused by a Metasys
device failure or an ARCNET cable problem. Check the device for
any malfunctions, and use troubleshooting information from the N1
Local Area Network Technical Bulletin (in LIT-636017).
All the Devices on One ARCNET Segment Do Not Respond
1.   If other ARCNET segments are working, the problem is isolated
     to the failing segment. Use ping to find out if the suspect router
     responds to Ethernet messages. (Firewalls may cause issues with
     the ping command.)

2.   If the router responds, look at the ARCNET cable and Metasys
     equipment.
3.   If the router does not respond, look at the router and the
     Ethernet network. (See JC-MER-CXB Does Not Respond to Ping
     Requests, further on.)
Multiple ARCNET Segments Do Not Respond
This could be caused by a router configuration problem or an
Ethernet problem. Use testnet to determine which routers respond.
Verify that the configuration screen entries are correct. Check the
Metasys DDL files for correct subnet/node addresses. Check the
configuration at each failing router. Check the Ethernet LAN for
failures.
JC-MER-CXB Does Not Respond to Ping Requests
This could be caused by problems with the router or problems on the
Ethernet LAN. Check the router configuration screen to see that all
addressing is correct for this router. Use ipstat to look for errors in
connecting to the Ethernet. If the router is running and appears to be
configured properly, the problem is probably due to an Ethernet
failure. Check with the network administrator to verify that the
network has not been changed and is functional.

                          TD060100-0MA
                               35
N1 Communications Are Occasionally Unreliable
1.   Ethernet communication