Текст документа

FANs 791, 930
                                                                            Product/Technical Bulletin    CLK350-2
                                                                                          Issue Date      0300

                    CLK350-2 Low Voltage, 7-Day Programmable,
                           Single-Circuit Control Clock

The CLK350-2 single-circuit control clock is designed
to provide 7-day, programmable, ON/OFF control for
low-voltage DC and low-current (40VDC, 25mA
maximum) field devices.
The CLK350-2 clock is typically used to schedule the
temperature reset function on the A350R Electronic
Temperature Reset Control or offset temperature
function on the A419 Electronic Temperature Control
with Display.
ON and OFF events can be programmed to occur on a
single day of the week, multiple days of the week, or a
combination of both.

                                                                 Figure 1: CLK350-2 Low Voltage, 7-Day
                                                               Programmable, Single-Circuit Control Clock

                                             Features and Benefits
                      Single-day or Block           Permits versatility in programming; adapts to
                      Programming                   a wide range of scheduling needs

                      Daylight Saving Time          Provides either automatic Daylight Saving
                      Changeover Options            time changeover every year, or one button
                                                    manual Daylight Saving time changeover

                      Holiday Programming           Allows for a special holiday or vacation
                                                    program for one or multiple days

                      Liquid Crystal Display        Clearly displays the time of day, day of week,
                                                    and program ON/OFF status

                      Manual Override               Overrides the programmed event control and
                                                    maintains the controlled device On or Off,
                                                    either temporarily or continuously

                      Internal Battery Backup       Retains time/date settings and event
                                                    programs upon loss of power for up to
                                                    two weeks

                      Minute-to-minute              Allows load switching in precise time
                      Programming                   increments

© 2000 Johnson Controls, Inc.                                                                                       1
  Part No. 24-7664-141, Rev. B                                                                 www.johnsoncontrols.com
  Code No. LIT-930100
A pplication                                                         O peration
The CLK350-2 Low Voltage, 7-Day Programmable,                        The CLK350-2 control clock employs a
Single-Circuit Control Clock is designed to provide                  polarity-sensitive, open-collector transistor output that
user-defined, time-of-day and day-of-week, ON/OFF                    energizes during programmed ON times and
scheduling for a variety of field devices that have a low            de-energizes during OFF times. During a programmed
DC voltage, and low current control circuit. (Maximum                ON time, the transistor between the output terminals is
output load circuit rating is 40VDC, 25mA.)                          on and the LCD displays the ON symbol ( ).
The CLK350-2 control clock is typically used to provide              During a programmed OFF time, the transistor
ON/OFF scheduling of the temperature reset function                  between the output terminals is off and the LCD
on the A350R Electronic Temperature Reset Control                    displays the OFF symbol ( ).
or the temperature offset function on the
A419 Electronic Temperature Control with Display.                    Manual override allows the user to turn the electronic
                                                                     output ON or OFF (temporarily or continuously)
 IMPORTANT:          The CLK350-2 control clock is                   without changing the stored programs.
                     intended to control equipment                   In the event of a power loss, a built-in, lithium battery
                     under normal operating                          maintains the time of day, day of week and
                     conditions. Where failure or                    programmed event times for up to two weeks. During a
                     malfunction of the                              power outage, the clock’s output is OFF.
                     CLK350-2 control clock could
                     lead to an abnormal operating                   The CLK350-2 clock turns a field device ON and OFF
                     condition that could cause                      according to a user-defined, time-of-day schedule.
                     personal injury or damage to the                Two schedule types are available when programming:
                     equipment or other property,
                     other devices (limit or safety                  •     block programming, which allows a block of
                     controls) or systems (alarm or                        multiple days (up to seven) to be programmed with
                     supervisory systems) intended to                      the same ON and OFF times
                     warn of, or protect against, failure            •     day-to-day programming, which allows each day
                     or malfunction of the                                 to be programmed independently.
                     CLK350-2 control clock must be
                     incorporated into and maintained                The user can choose block programming, day-to-day
                     as part of the control system.                  programming, or a combination of both as long as the
                                                                     ON and OFF times do not overlap.

                                                        Terminal   Guide
                                                         Base       Pins
                                                                     Clock
                                                                     Module
                      Mounting Holes
                    (Lower-right hole not
                                                                                    Housing
                    visible in this view.)

                                                                                              Captive
                                                                                               Screw
                                             Terminal
                                              Cover
                                                                                                        Clear
                                                                                                        Cover
                                                              Break-away Tabs
                                                           for DIN Rail Mounting
                                                            (One on each side.)    Captive
                                                                                   Screw

    Figure 2: CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock: Exploded View

2   CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin
D imensions
                                                                         2-1/16
                                        2-13/16
                                                                          (52)
                                          (71)

                                                         4-1/4
                                  CH1
                                                         (105)

                   Figure 3: CLK350-2 Dimensions, Front View and Side View, in. (mm)

I nstallation
                                                                 IMPORTANT:       In areas where high electrical
DIN Rail Mounting                                                                 noise is present, locate the clock
Refer to Figure 2 and follow the instructions below to                            at least five feet away from the
mount the clock on a standard 35 mm DIN rail.                                     noise source to avoid possible
                                                                                  electrical interference.
 IMPORTANT:         Do not DIN Rail mount the clock
                    in locations where excessive
                    vibrations are present.

1. Remove the clear cover from the front of the unit.
2. Using a 1/8 in. flat-blade screwdriver, loosen the
   two captive screws located in the upper right and
   lower left corners of the housing.
3. Remove the housing by pulling forward.
4. Using blunt-nosed pliers, remove the break-away
   tabs from the housing. (See Figure 4.)
5. Remove the terminal cover by pulling forward.
1. Snap the CLK350-2 clock onto the DIN rail.
                                                                       Figure 4: Removing the DIN Rail
2. Make wiring connections (See Wiring section).                              Break-away Tabs
   Remove the appropriate knockouts on the terminal
   cover for either conduit or wire entry. (See
   Figure 5.)
3. Replace the terminal cover and housing, tighten
   the captive screws, and replace the clear cover.

     CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin          3
Surface Mounting                                               Wiring
The CLK350-2 clock is not position sensitive and may
be mounted in any orientation. However, vertical                  !     WARNING: Risk of Electrical Shock.
mounting is recommended to facilitate programming
                                                                                 Disconnect power supply before
the clock. Refer to Figure 2 and follow the instructions
                                                                                 making wire connections to avoid
below to surface mount the clock.
                                                                                 possible electrical shock or
1. Remove the clear cover from the housing.                                      damage to equipment.
2. Using a small flat-blade screwdriver, loosen the            Select a power source: either the Y350R power
   two captive screws located in the upper right and           module (only with the A350R control) or a separate
   lower left corners of the housing.                          24 VAC transformer.
3. Remove the housing by pulling forward.
                                                                IMPORTANT:          The CLK350-2 clock can be
4. Remove the terminal cover by pulling forward.                                    affected by electrical spikes and
                                                                                    other line noise. It is
5. Remove clock module from the terminal base by
                                                                                    recommended that the clock be
   firmly grasping it on both sides and pulling the
                                                                                    powered from a voltage source
   module forward (without twisting it).
                                                                                    that has no switching devices or
6. Place the terminal base against the desired                                      inductive loads connected.
   mounting surface, and, using the base as a
   template, mark the three mounting holes. Drill              Wire the clock using 16 to 24 AWG wire. Refer to
   three 1/16 in. holes for No.6 screws.                       Table 1 and the appropriate wiring diagram in the
                                                               figures below. All wiring should conform to the National
7. Center the terminal base to the mounting surface            Electrical Code and local regulations.
   using the three holes and fasten the unit securely
   with the No.6 screws (provided). If necessary, use          Before applying power, make sure installation and wire
   the drywall anchors provided.                               connections are according to job specifications. Then
                                                               power up the clock and proceed to the Setting the
8. Make wiring connections. (See Wiring section.)              Time, Day, and Daylight Saving Time section.
   Remove the appropriate knockouts on the terminal
   cover for conduit entry. (See Figure 5.)
4. Replace the clock module, terminal cover, and                  !     CAUTION:     Equipment Damage Hazard.
   housing. Tighten the captive screws, and replace                                  The switching output on the
   the clear cover.                                                                  CLK350 is rated for 1 to 25 mA
                                                                                     at 1.5 to 40 VDC. Proper
                                                                                     polarity through the output
                                                                                     switch must be maintained.
                                                                                     (See Table 1.)
                                                                                     Exceeding the clock or control
                                                                                     input or output voltage or output
                                                                                     current ratings voids the
                                                                                     warranty.

                                                               Note:    When first applying power, it takes several
Figure 5: Removing the Knockouts for Conduit or                         minutes for the battery to charge. If the LCD
                  Wire Entry                                            does not come on after a few minutes, press
                                                                        the Res. key (with a pen point).

Table 1: Terminal Designations for Wiring the CLK350-2 with the A350R and the A419
       CLK350-2             CLK350-2 Terminal              Corresponding                Corresponding
    Terminal Number            Description                 A350R Terminal          A419 Terminal/Connection
           1                + Supply Power Input               24 VAC           Separate 24VAC Supply Transformer
           2              – Supply Power Common                 COM             Separate 24VAC Supply Transformer
           3                 (+) Switched Output               CLK IN                        BIN (+)
           4                 (-) Output Common                  COM                          COM (-)

4    CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin
                                                                              Cable Shield                                      A419ABC-1
    A350R
                                 A350R                                                                                        (+) BIN
                                  Wire
                                Terminal         CLK350-2                                                                     (–) COM

                                                                                             CLK COM
                                 Block                                                                                        (+) SEN

                                                 1 2 3 4 5                                                                          NC NO
                                                                                                                        240
                                  24                                  CLK350-2                                             AC 120
    NO   C   IN COM COM 24                                                                                                            C

                                                                                    CLK IN
                       VAC
                                 VAC                                                                                      COM
                                           COM
                                                                     1 2 3 4 5
                                        CLK IN

                                                                                                       To Sensor
    Controlled                         CLK COM
      Load               24
                        VAC                                          24
    < 30 VAC
                                                                    VAC
    < 100 VA        COM                                                                                                            Controlled
                                            120/240 VAC              COM
                                                                                                                                     Load
                          24 VAC
                        Transformer

  Figure 6: A350R Temperature Control (with a                                 24 VAC
                                                                            Transformer                       120 VAC
   24 VAC Transformer Power Supply) Using a                                                            (Use 240 and AC COM
                                                                   120/240
 CLK350-2 Clock to Schedule the Reset Function                       VAC
                                                                                                       terminals for 240 VAC)

                                                               Figure 8: A419ABC-1 (120/240 VAC Model)
    A350R                      Y350R
                 A350R Wire                                  Temperature Control Using a CLK350-2 Clock to
                  Terminal       Power                         Schedule the Offset Temperature Function
                   Block         Module           CLK350-2

                                 240 120
                                 VAC VAC         1 2 3 4 5
                         24                                               Cable Shield                                           A419GBF-1
    NO   C   IN COM COM
                        VAC
                                                                                                                               (+) BIN
                           24 VAC                                                                                              (–) COM
                       24 VAC COM                                                                                              (+) SEN

                                                                                                CLK COM
                        CLK IN
    Controlled         CLK COM                                                                                                          C NO
      Load                                   120 VAC                 CLK350-2
                                                                                                                         T1        NC
    < 30 VAC                                  Supply                                                                          T2

                                                                                    CLK IN
    < 100 VA
                                                                    1 2 3 4 5

                                                                                                            To Sensor
Figure 7: A350R Temperature Reset Control (with a
 Y350R Power Module) Using a CLK350-2 Clock to
                                                                    24
           Schedule the Reset Function                             VAC
                                                                                                                                    Controlled
Notes: Power from the Y350R power module is                          COM
                                                                                                                                      Load
                                                                                                                            24
       supplied to the A350R control through a 5-pin                                                                       VAC
                                                                                                                                    < 30 VAC
       connector. Use the 24 VAC and COM                                                                                            < 100 VA
                                                                                                                         COM
       terminals on the A350R control to power the                             24 VAC
       CLK350-2 clock. (See Figure 7.)                                       Transformers

         When used with the A419GBF-1 control                     120/240
         (24 VAC model), the CLK350-2 clock must be                 VAC
         powered by a 24 VAC power supply
         transformer that is separate from the
         A419GBF-1 control power supply.                     Figure 9: A419GBF-1 (24 VAC Model) Temperature
                                                             Control Using a CLK350-2 Clock (with a Separate
         Refer to A350R Electronic Temperature Reset
                                                               24 VAC Power Supply) to Schedule the Offset
         Control (with Relay) Product/Technical Bulletin
                                                                           Temperature Function
         LIT-930033 and A419 Electronic Temperature
         Control with Display Product/Technical Bulletin
         LIT-125188 for additional information on
         installing, wiring, setting up, and operating
         these temperature controls.

         CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin                                       5
D isplay Elements and Programming
Key Functions
        Day Field displays numbers that represent the days of the week. (1 is Monday, 2 is Tuesday, 3 is Wednesday, etc.)
        In the Run mode, the current day of the week is displayed in the Day field.
        In the Programming mode all days of the week are displayed and you omit days that you do not want a scheduled event to occur.
        The Day field is also used to guide you through setting Automatic Daylight-Saving Time changeover.

Daylight-Saving Time Symbol indicates when                                                       Holiday Symbol indicates when the clock is
the clock is operating in Daylight-Saving time                                                   running the Holiday program.

     AM/PM Symbol indicates whether time in
     Time field is am or pm. The AM/PM                                                            Time Field: In the Run mode the Time field
     symbol field is blank when the clock is                                                      displays the current time of day in either
     set to military time.                                                                        AM/PM or military time.
                                                                                                  In the Programming mode, the Time field is
                                                                                                  used to set the time of day when an event is
 Channel Indicator: The CLK350 Time Clock                                                         scheduled to occur.
 has only one channel indicated by CH1.               CH1                                         The Time field is also used to establish days,
                                                                                                  months, and years when setting Automatic
                                                                                                  Daylight-Saving Time changeover.
        Run Mode Symbol indicates when the
        clock is in normal run operation.

ON/OFF Symbol indicates if the clock’s switch is closed (ON = ) or         Temporary Manual Override ON Symbol indicates if the temporary
open (OFF = ). The square brackets indicate that the automatic             manual override function is on and automatic control is overridden
event schedule is overridden and the switch is set to be continuously      until the next scheduled event is initiated. If the symbol is absent,
ON ( [ ] ) or OFF ( [ ] ).                                                 the temporary manual override function is off.

                                    Figure 10: Display Elements and What They Indicate

                                                           ON/OFF Selection Key: In the Programming mode, press             to
                                                      select an ON or OFF event. In the Run mode, press    to select
                                                      temporary or continuous (Fixed) ON or OFF manual override.

           Reset Key: Press Res. to completely
           clear the clock memory of all programs,                                             Daylight-Saving Change Key: Press +1h to
           time of day and date, and reset the                                                 add or subtract one hour from the displayed
           clock for reprogramming. (This is a                                                 time to adjust for daylight-saving time changes.
           recessed key, press with a pen point.)                                              (This is a recessed key, press with a pen point.)
                                                            Mo Tu We Th Fr Sa Su

                                                                                                     Hours Key: Press h to set the hour
                                                                                                     of the day in AM/PM or military
      Program Mode Key: Press Prog.                                                                  time. This key is also used in other
      to go to Programming mode.                                                                     programming procedures. (See
                                                                                                     Programming the CLK350-2 Clock.)

                                                             CH1                                    Minutes Key: Press m to set the
       - Set Time/Auto Run Mode Key: Press                                                          minutes of the hour in AM/PM or military
    and hold to set the day of the week, and                                                        time. This key is also used in other
    time of day. Also press this key to return                                                      programming procedures. (See
    the clock to Automatic Run mode.                                                                Programming the CLK350-2 Clock.)

                                                                                              Day of the Week Key: Press Day to set current
                                                                                              day when setting up clock, or to select days of
             Holiday Program Key: Press        to save a                                      the week to be omitted from programmed events
             Holiday program or to establish a day of the                                     in Programming mode. (See Programming the
             week as a holiday.                                                               CLK350-2 Clock.)
                                                                Select Key: Press Sel. to omit the day(s) of the week
                                                                that were selected with the Day of the Week key.

                                       Figure 11: Programming Keys and Their Functions

6     CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin
S etting the Time, Day, and Daylight
Saving Time
 IMPORTANT:          Before setting the time and day,      Changing Daylight Saving Time Manually
                     and programming the clock for         In the Spring when Daylight Savings time is scheduled
                     the first time (or when re-setting    to changeover, press the +1h key once to advance the
                     up the clock for a new                clock display one hour. The +1h symbol appears to
                     application), press the Reset key     the left of the Time field. (See Figure 10.) Press the
                     (Res.) to clear all data from the     +1h key once again in the Fall to set the clock to
                     clock memory.                         standard time. (The +1h symbol disappears.)

Setting the Time of Day and Day                            Setting Automatic Daylight Savings Time
After resetting the CLK350-2 clock, set the clock for      Changeover
the current time-of-day and day by first setting the
display for AM/PM or military time.                        Setting the Daylight Saving time to changeover
                                                           automatically is optional, but you only need to set this
To set the digital clock for AM/PM or military time        function once and the clock will automatically
display:                                                   changeover on the first Sunday in April and the last
1. Press and hold the h key, then press the +1h key.       Sunday in October every year until the year 2079.
   AM/PM time is selected when AM and 12:00                To set automatic Daylight Saving time changeover:
   appears on the display in the Time field.
                                                           1. Press and hold the +1h key and press the Day key
2. Press the +1h key again to select military time.           once. A 1 appears in the Day field at the top of the
   (00:00 appears on the display, and AM/PM is not            LCD, and a flashing 12:31 (December 31st)
   displayed when military time is selected.)                 appears in the Time field AM/PM mode. In Military
To set current time of day and day:                           Time mode 31:12 appears flashing. Release the
                                                              +1h key.
1. Press and hold the       key then,
                                                           2. Enter the current date (in the AM/PM mode) by
2. If Daylight Saving time is in effect, press the +1h        pressing the m key to advance to the current day
   key once. The +1h symbol appears on the display            of the month, then press the h key to advance to
   to the left of the Time field. (See Figure 10.)            the number for the current month. (In the Military
                                                              Time mode use the h key to advance the days and
3. While holding down the     key, press the h key to         the m key to advance the months.)
   advance to the current hour. (Holding the h key for
   longer than 2 seconds advances the hours                3. When the current date is entered, press the +1h
   rapidly.)                                                  key once. A 2 appears in the Day field at the top of
                                                              the display, and 1995 appears in the Time field.
4. While holding down the     key, press the m key
   to advance to the current minute. (Holding the m        4. Press the m key repeatedly to enter the current
   key for longer than 2 seconds advances the                 year. (If you overshoot the current year, press and
   minutes rapidly.)                                          hold the m key down to scroll to 2079 and back to
                                                              1995.)
5. While holding down the         key, press the day key
   repeatedly to advance to the number in the Day          5. When the current year is entered, press the +1h
   field for the current day of the week. (1 is Monday,       key once, a 3 appears in the Day field, and AU
   2 is Tuesday, etc.)                                        appears in the Time field. (AU sets the European
                                                              daylight saving dates.)
Note:   If the day numbers are flashing, the day of
        week was not set. The time clock cannot be         6. Press the m key once, cHA appears in the Time
        programmed unless the day of week is set.             field. (If the m key is inadvertently pressed twice
                                                              and HA appears, press the m key two more times
                                                              until cHA appears.)

        CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin             7
7. When cHA is entered, press the +1h key once, a          IMPORTANT:          If the Day field is flashing, the
   4 appears in the Day field, and 03:30 appears in                            time-of-day and/or day-of-week
   the Time field in the AM/PM mode, which indicates                           have not been set and saved
   March 30. 30:03 appears in Military Time mode.                              properly.
   (Other dates in late March may appear, instead of                           The current time-of-day and
   March 30.)                                                                  day-of-week must be set before
8. Enter the date for the spring time change (in the                           entering programs into the time
   AM/PM mode) for the current year by pressing the                            clock. See Setting the Time, Day,
   h key once to advance to month 04 (April). Then                             and Daylight Saving Time.
   press the m to advance to the date of the first
   Sunday in April of the current year. (In the Military
                                                           Programming Event ON/OFF
   Time mode, use the h key to advance the days
   and the m key to advance the months.) Refer to          To create a program, first select the programmed
   Daylight Saving Time Changeover Dates listed            event to be ON or OFF. To select ON or OFF events:
   below.
                                                           1. Press the Prog. key (only) once, and the Start
9. When the date for the current year’s spring time           Programming display appears. (See Figure 12.)
   change is entered, press the +1h key once, a
   5 appears in the Day field and the month and day
   for the fall time change (for the current year)                             1234567
   appears in the Time field.
10. Press the    to save the previous settings and                                 - -:- -
    enter the Run mode.

Daylight Saving Time Changeover Dates                             Figure 12: Start Programming Display
2000 April 2 – October 29    2004 April 4 – October 31
2001 April 1 – October 28    2005 April 3 – October 30     2. Press the     key once to create an ON event,
                                                              and the ON symbol   appears.
2002 April 7 – October 27    2006 April 2 – October 29
2003 April 6 – October 26                                  3. Or press the     key twice to create an OFF
                                                              event, and the OFF symbol    appears.

P rogramming the CLK350-2 Clock                            Programming Event Time of Day
All programs established on the CLK350-2 clock             After setting an ON or OFF event, set the time of day
consist of:                                                (hours and minutes) that the event occurs.
•   An ON or OFF command                                   To set hours and minutes (and AM or PM in AM/PM
•   A time of day (hour and minute)                        mode):

•   A single day selection or a block selection of         1. Press the h key to scroll to the desired event hour
    multiple days of the week                                 time. (Make sure to scroll to the desired AM or PM
                                                              hours in AM/PM mode.)
A discrete program is required for each ON event and
for each OFF event, except for events that are             2. Press the m key to scroll to the desired minutes.
programmed to occur on multiple days at the same
time of day.
Up to 42 programs may be set on the CLK350-2 clock.
It is helpful to write out the program schedules before
entering the program into the time clock. Use the
schedule form provided to plan and write out the
desired program schedule. See Table 2.

8   CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin
Programming the Days of the Week                               IMPORTANT:         If the ON/OFF symbol is flashing
After setting the time of day at which the event occurs,                          and the program cannot be
select the day or days of the week on which you want                              saved, ON or OFF was not
the event to occur.                                                               selected and entered as part of
                                                                                  the program. ON or OFF must be
The Day and Sel. keys are used to omit days of the                                selected. (See Programming
week that an event is not to occur on. If the event is to                         Event ON/OFF.)
occur every day of the week, ignore the Day and Sel.
keys.
To select and display the day or days of the week on          Changing A Program
which the event is to occur:                                  Select and display the program you want to change by
1. Press the Day key to move the flashing line under          pressing the Prog. key repeatedly. When the desired
   the first number of the day of the week you want to        program is displayed, use the Sel. and Day keys to
   omit from the program. (1 is Monday, 2 is                  omit days or to add days that were previously omitted.
   Tuesday, 3 is Wednesday, etc.)                             Use the h and m keys to change the program’s time
                                                              (hours and minutes).
2. Press the Sel. key to omit the day.The line and
   the selected number start flashing.                        Press the Prog. to save the changed program and go
                                                              to a new Start Programming display or press the
3. Press the Day key and the previously selected day          key to save the changed program and return to Run
   number disappears and the flashing line moves to           mode.
   the next day number position.
4. Repeat steps 1 and 2 to omit additional days of
   the week. (See Figure 13 for examples of                   Deleting Programs
   programmed-event screens.)                                 To delete a single program:
5. When the (remaining) selected day or days of the           1. Press the Prog. key (repeatedly) until the desired
   week are displayed, press the Prog. key once to               program is displayed.
   save the Program (Event Schedule) and return to
   the Start Programming display.                             2. Press the m key to :59 and press once more to
                                                                 blank out the minutes positions in the Time field.
6. Press the     key to return to the Run mode. (Or
                                                              3. Press the h key to 11PM (or 23: in military time
   wait 1 minute for the clock to automatically revert
                                                                 mode) and press once to blank out the hours
   to the Run mode.)
                                                                 position in the Time field.
       A                           B
           1    3   5                         67              4. Press the    key and the display flashes for
                                                                 several seconds and then returns to the Run
           AM
                06:30                    22:15                   mode.
                                                              5. Repeat Steps 1 through 4 for each program you
                                                                 want to delete.
     The A clock display is in    The B clock display is in   To delete all programs:
       AM/PM mode and is          Military Time mode and is
    scheduled for an On event    scheduled for an Off event   Press the Res. key (with a pen) to delete all the clock
      at 6:30 am on Monday,       at 10:15 pm on Saturday
      Wednesday and Friday.              and Sunday.          data, including all programs, the time of day, and
                                                              daylight saving information.
   Figure 13: Examples of Programmed Events

 IMPORTANT:             If an ON event time is
                        programmed and is scheduled to
                        occur earlier than the current
                        time, press the       key to turn
                        the output switch ON. The clock
                        does not “look back” to determine
                        if the output should be ON or
                        OFF.

           CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin            9
Holiday Program                                              On the day the Holiday program is selected to begin
                                                             the program is implemented, and the      symbol is
A Holiday program schedule may be created to use on          displayed, as well as the number of days remaining in
holidays or vacation periods where the regular               the holiday period. To cancel the Holiday program, and
scheduled programs are not needed. More than                 return to the regular programmed schedule, press the
one ON or OFF time may be scheduled for the Holiday             key once.
program.
1. Press the Prog. key (repeatedly) to go to a blank         Reviewing Programs
   Start Programming display. (See Figure 12.)               To review all of the programs:
2. Entered the first desired program for the holiday         1. Press the Prog. key repeatedly and the programs
   according to the instructions in Programming the             appear in the order they were entered. After all the
   CLK350-2 Clock. (Start at Step 2 of Programming              existing programs have been reviewed, the blank
   Event ON/OFF. Do not press Prog. key again as                Start Programming display appears (see
   stated in step 1. Also, days are not programmed in           Figure 12) allowing you to enter additional
   Holiday program.)                                            programs.
3. Press the     key once.                                   2. Press the Prog. key again to display the number
4. Enter any additional programs as above.                      of free event programs available (such as Fr 38 if
                                                                four programs have been entered).
5. Press the      key to save programs and enter the
                                                             3. Press the       key to return to the Run mode.
   Run Mode.

Implementing the Holiday Program                             Overriding the Programmed Schedule
You may select which day of the week the holiday is to       The clock’s current event status (ON or OFF) may be
begin on, up to six days before the holiday. The             overridden, either temporarily or continuously.
holiday may be programmed to continue
1 to 99 (consecutive) days. The regular scheduled            Temporary Override
events are inactive during the Holiday program. To           While in the Run mode, press the       key once to
implement the Holiday program:
                                                             reverse the event output (ON to OFF or OFF to
1. Press the     key once. Ho appears in the Minutes         ON).The        symbol appears on the display to the
   field.                                                    right of the ON/OFF symbol and the     symbol
2. Press the Day key to advance to the desired day           disappears. At the next scheduled event, the clock
   of the week (for the holiday to start).                   reverts to automatic operation.

3. Press the Sel. key once to select one day. Press          Fixed Override
   the Sel. repeatedly to maintain the holiday
   program for multiple days. d appears in the Hour          While in the Run mode, press the        key twice to
   field and the number of days the Holiday program          turn the output ON continuously. The [ ] (Fixed ON)
   will run appears in the Minutes field.                    symbol appears, or press the        key three times to
Note:   If the Sel. key is held down, the days will scroll   turn the output OFF continuously, the [ ] (Fixed OFF)
        rapidly to 99 and then back to 1.                    symbol appears.
4. Press the      key to save the settings and enter         To terminate a fixed override, press the       key
   the Run mode. The         symbol is displayed above       repeatedly until the     symbol appears in the lower
   the time field until the Holiday program is               left corner of the display.
   completed.
To review the Holiday program, press the    key once.        Battery Reserve
The holiday start day and number of days the Holiday
                                                             In the event of a power failure, a built-in, lithium battery
program is active are displayed. Press the   key to
                                                             maintains the time of day, day of week, daylight
return to Run mode.
                                                             settings, and event programs for up to two weeks.
To delete implementing the Holiday program before            When the clock is using battery power, the output is
the program starts, press the   key twice, and the           OFF. The non-replaceable battery is charged while the
   symbol disappears from the display.                       clock is powered.

10   CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin
O rdering Information                                      R epairs and Replacement
The CLK350-2 is not field repairable. To order a           Do not attempt to make field repairs on the CLK350-2
replacement control clock contact the nearest              clock. If the control is not functioning properly, contact
Johnson Controls branch office or authorized               your local Johnson Controls/PENN representive for a
distributor and request Product Code No. CLK350-2C.        replacement.

Table 2: Clock Event Schedule Form
 Program                    Hour      Minutes                                                  Holiday Program
               ON/OFF                                        Days of Week
 Number                      (h)        (m)

     *1           ON        6 AM          30           Monday, Wednesday, Friday                        No

* This program is shown on Display A in Figure 13.

          CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin        11
S pecifications
                          Product    CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock
         Supply Power Rating         20 to 30 VAC/DC; 2 VA@ 24 VAC, 1W @ 24VDC, Class 2
                   Output Type       Open Collector Transistor
          Output Load Rating         1-25 mA @ 1.5 to 40 VDC
               Clock Accuracy        ± 4 minutes per year (5 seconds per week) @ 68.0°F (20°C)
               Battery Backup        Lithium Battery saves clock settings for up to two weeks
                      Programs       42 unique programmed events (ON and/or OFF) may be entered into the clock memory. If
                                     each event is scheduled to occur 7 days per week, 294 switch events occur.
                    Wire Gauge       16 to 24 AWG (22 recommended)
                         Mounting    Surface or DIN Rail
           Ambient Operating         0 to 140°F (-18 to 60°C)
                 Conditions
     Maximum RH Conditions           85% RH @ 85°F (Non-condensing)
                Agency Listing       UL and Canadian UL Recognized: (as Grasslin Model No. FM/1 digi 42) File E83486
              FCC Compliance         Part 15, Class A
      Dimensions (H x W x D)         4-1/4 x 2-13/16 x 2-1/16 in. (105 x 70 x 52 mm)
              Shipping Weight        7.3 oz (206 g)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls/PENN Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be liable
for damages resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                                Printed in U.S.A.
Milwaukee, WI 53201                                                                                                 www.johnsoncontrols.com

12    CLK350-2 Low Voltage, 7-Day Programmable, Single-Circuit Control Clock Product/Technical Bulletin

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.