CCS Handheld VAV Balancing Tool
Technical Bulletin
Code No. LIT-12011470
NS-ATV7003-0
Software Release 1.2
Issued July 15, 2011
Supersedes January 14, 2009
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
CCS Handheld VAV Balancing Tool Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CCS Handheld VAV Balancing Tool Technical Bulletin 1
2 CCS Handheld VAV Balancing Tool Technical Bulletin
CCS Handheld VAV Balancing Tool
Technical Bulletin
Document Introduction
This document describes how to use the NS-ATV7003-0 Handheld Variable Air
Volume (VAV) Balancing Tool for Commercial Comfort System (CCS)
applications. This document also describes the VAV Balancing Tool error codes
you may encounter.
Related Documentation
Table 1 lists the documentation related to the CCS Handheld VAV Balancing Tool.
Table 1: Related Documentation
For Information On See Document LIT or
Part Number
Features, Benefits, and Applications Commercial Comfort System (CCS) Product LIT-12011347
of the CCS Bulletin
Zoning System Application, Design, Commercial Comfort System (CCS) Changeover LIT-12011512
and Installation for the CCS Bypass (COBP) Zoning System Design
Application Note
Configuring Settings and Commercial Comfort System (CCS) System LIT-12011444
Parameters within the CCS Manager and Zone Coordinator User’s Guide
Operating Modes and Strategies of Commercial Comfort System (CCS) Application LIT-12011617
the CCS and Sequence of Operation Overview Technical
Bulletin
Installing and Wiring a VAV Handheld VAV Balancing Tool Installation Part No. 24-10211-2
Balancing Tool and Network Sensor Instructions
Product Overview, Features, and Handheld VAV Balancing Tool Catalog Page LIT-1900348
Benefits of the Handheld Balancing
Tool
CCS Handheld VAV Balancing Tool Overview
The CCS VAV Balancing Tool Liquid Crystal Display (LCD) shows the operating
parameters and/or the VAV parameter values. When the balancing tool is in
balancing mode, the features on the face of the tool also control the balancing
function (Figure 1). These features include:
• an Adjustment Dial, which scrolls through the parameter submenus and
adjusts the input parameters
• an Enter button (indicated by a return arrow), which accepts selections and
allows you to enter into selection submenus
• a Cancel button (indicated by an X), which cancels the selected parameter and
exits into the previous submenu
• a backlit LCD, which activates with any user interaction
CCS Handheld VAV Balancing Tool Technical Bulletin 3
LCD with Backlight
Adjustment Dial
Cancel Button
- -
FIG: sensorface
Enter Button
Figure 1: CCS Handheld VAV Balancing Tool
Upon first entering into balancing mode, the display shows the address of the
controller you are balancing. From here, you can use the Adjustment dial to scroll
through the parameter submenus. If you press Enter, you go into that parameter’s
submenu. For example, if you press Enter at Balancing Mode [BAL], the next
submenu options are Supply Duct [SPLY] and Exit [EXIT].
During longer operations, like Autocalibration, the word Busy [BUSY] appears on
the display until the operation is complete. Do not push any buttons until the
operation is finished.
The balancing tool remains in balancing mode until you exit or the balancing mode
inactivity timer expires. To exit balancing mode, press the Enter button when Exit
appears on the highest submenu, or hold the Enter and Cancel buttons for
5 seconds. The default timeout value is 60 minutes.
Detailed Procedures
To balance your Commercial Comfort System:
1. Connect the balancing tool to the NS Series Network Sensor associated with
the controller you want to balance.
2. Press and hold the Enter and Cancel buttons together for at least 5 seconds
until the word Busy [BUSY] appears on the display.
3. Use Table 2 to navigate through the VAV Balancing Device menus.
4. Press the Enter button when Exit [EXIT] appears on the highest submenu to
exit.
Note: We recommend that you exit the balancing mode before removing power
from the handheld balancing tool. This returns the VAV controller to
normal operation. Otherwise, there may be a 60-minute delay if you
reconnect and try to enter the balancing mode.
4 CCS Handheld VAV Balancing Tool Technical Bulletin
Table 2: Single Duct Balancing Sequence (Part 1 of 2)
Submenu 1 Submenu 2 Submenu 3 Data Range Editable Description
Controller — — 000–127 No DIP switch address of the controller.
Address Enter button moves to next action.
[25]
Balance Supply Duct dP Offset 00.00–99.99 No Absolute value of offset in %. If greater
Mode [SPLY] [dPO] than 10%, the damper may not be closing
[BAL] completely. Verify that the damper shaft
has not slipped and is moving freely.
Then autocalibrate the dP.
Auto No [NO] Yes Selecting Yes closes the box and
Calibrate dP Yes [YES] recalibrates the dP Offset.
[ACAL]
Flow None [NONE] Yes Once entered, the controller drives to the
Setpoint Cooling Max selected setpoint. The override remains
Override [CMAX] active for 30 minutes.
[FLSP] Select None to remove the override.
Cooling Min
[CMIN]
Heating [HTg]
Closed [OFF]
Actual Flow 0001–9999 Yes Displays measured flow until adjusted by
[FLOW] user. When adjusted and entered, it
triggers the controller to recalculate the
Gain. The range is limited to a maximum
value of 9999.
Box Gain - 0.001–9.999 No If actual flow is entered, this displays the
K Factor new current gain (K).
[K]
Exit [EXIT] — No Press the Enter button to return to the
previous menu. Turn the knob to loop
through the current menu.
Exit [EXIT] — — No Press the Enter button to return to the
previous menu. Turn the knob to loop
through the current menu.
Parameter Flow Cooling Max 0001–9999 Yes Occupied Setpoint Only.
Mode Setpoints Flow
[PARM] [FLSP] [CMAX]
Cooling Min 0000–9999 Yes Occupied Setpoint Only.
Flow
[CMIN]
Heating 0000–9999 Yes Occupied Setpoint Only.
Flow [HTg]
Exit [EXIT] — No Press the Enter button to return to the
previous menu. Turn the knob to loop
through the current menu.
CCS Handheld VAV Balancing Tool Technical Bulletin 5
Table 2: Single Duct Balancing Sequence (Part 2 of 2)
Submenu 1 Submenu 2 Submenu 3 Data Range Editable Description
Parameter Supply Duct Box Area 0.001–9.999 Yes Square Feet
Mode [SPLY] [AREA]
[PARM]
Pickup Gain 0.001 - 9.999 No —
(Cont.)
- K Factor
[K]
dP Offset 00.00 - 99.99 No Absolute value of offset in percent
[dPO]
Exit [EXIT] — No Press the Enter button to return to the
previous menu. Turn the knob to loop
through the current menu.
Exit [EXIT] — — No Press the Enter button to return to the
previous menu. Turn the knob to loop
through the current menu.
EXIT — — — No Press the Enter button to return the
[EXIT] Network Sensor to normal operation and
release the Flow Setpoint override (if
required). Turn the knob to loop through
the current menu.
Error Codes
Table 3 describes the CCS VAV Balancing Tool error codes and recovery actions.
Table 3: CCS VAV Balancing Tool Error Codes
Error Number Cause Recovery Action
ERR0 [ERR0] Firmware revision mismatch Replace the balancing tool with an updated version.
ERR1 [ERR1] Commissioning session locked - unable Check to see if a commissioning session has already
to enter Balancing Mode because been started from another VAV Balancing Tool.
another tool/session is currently active.
ERR2 [ERR2] Communication error on the Check cables and connection between Balancing Tool
Sensor Actuator Bus (SA Bus) and the VAV controller (LC-ZEC200-0).
ERR3 [ERR3] Control sequence is currently disabled. N/A
ERR4 [ERR4] Another operation (Auto Calibration or Wait for the other operation to finish and retry the
Gain Calculation) is currently being desired operation. It may take a couple minutes to
performed in the Balancer Primitive. finish.
ERR5 [ERR5] No flow override has been selected. You must select a Flow Setpoint Override. Then, allow
the flow to settle (watch the value displayed on the
balancing tool) and then retry calculating the gain.
ERR6 [ERR6] Flow reading is unreliable. The DP sensor is giving an unreliable value. Check
connections/integrity of the pneumatic tubing. Check
the pickup tubes for a possible obstruction.
ERR7 [ERR7] Value out of range Try increasing or decreasing the value slightly.
ERR8 [ERR8] Autocalibration timed out Check stroke time settings.
ERRX [ERRX] Unknown application error Reboot controller. If problem persists, get a
replacement controller and/or replace the balancing
tool with an updated version.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.
6 CCS Handheld VAV Balancing Tool Technical Bulletin