| Вид документа | Каталожна сторінка |
|---|
| Виробник | JCI |
|---|
| Моделі | TC-8900, PM-8900, TC-8903-1131-WK, TC-8901-2131-WK, TC-8904-2131-WK, TC-8906-2131-WK, TC-8903-1132-WK, TC-8901-2132-WK |
|---|
| Група обладнання | automation |
|---|
| Мова документа | англійська |
|---|
| Розмір файлу | 0.2 МБ |
|---|
Про документ
A family of electromechanical modulating room thermostats for fan coil applications with 2-pipe, 2-pipe with change-over, 2-pipe with electrical coil or 4-pipe configurations. Stand-alone units (TC-890x), local controllers with remote setpoint module (TC-893x / ES-8930), local controllers with central setpoint module (TC-894x / ES-8940) and PM-8900 power modules are available.
Ключові дані
| Setpoint range | 12…28 °C |
|---|
| Sensing element | Built-in NTC K10 |
|---|
| Setpoint input | 0...10 V |
|---|
| Power supply | 24 VAC for the TC-8900 controls; 230 VAC in connection with the PM-8900 power module |
|---|
| Fan output | 3-speed fan override |
|---|
| Relay output | Relay 3A 230 V/24 V |
|---|
Застосування
- Fan coil units with 2-pipe configuration
- 2-pipe with change-over
- 2-pipe with electrical coil
- 4-pipe configurations
- With and without 3-speed fan override
Особливості
- Built-in NTC K10 sensing element
- Setpoint input/output 0...10 V
- 24 VAC power supply for the TC-8900 controls; 230 VAC in connection with the PM-8900 power module
- Remote setpoint module (ES-8930) and central setpoint module (ES-8940)
- Power modules (PM-8900) for fan speed control
Технічні дані
| Parameter |
Value |
| Sensing element |
Built-in NTC K10 |
| Setpoint range |
12…28 °C |
| Alternative setpoint range |
0…40 °C |
| Humidity range (models -1183/-2183) |
0…100% |
| Setpoint input |
0...10 V |
| Outputs |
PAT 0...10 V, DAT 0...10 V, On/Off |
| Fan output |
3-speed |
| Power module outputs |
DAT 230 V, DAT 24 V, Relay 3A 230 V/24 V |
| Power supply |
24 VAC (TC-8900 controls); 230 VAC in connection with the PM-8900 power module |
Варіанти замовлення
Stand-alone units (TC-890x):
| Model |
PAT 0...10 V |
DAT 0...10 V |
On/Off |
| TC-8903-1131-WK |
1 |
--- |
--- |
| TC-8901-2131-WK |
--- |
2 |
--- |
| TC-8904-2131-WK |
--- |
--- |
2 |
| TC-8906-2131-WK |
--- |
--- |
2 |
| TC-8903-1132-WK |
1 |
--- |
--- |
| TC-8901-2132-WK |
--- |
2 |
--- |
| TC-8904-2132-WK |
--- |
--- |
2 |
| TC-8906-2132-WK |
--- |
--- |
2 |
| TC-8903-1151-WK |
1 |
--- |
--- |
| TC-8903-1152-WK |
1 |
--- |
--- |
| TC-8903-1183-WK |
1 |
--- |
--- |
| TC-8901-2183-WK |
--- |
2 |
--- |
Local controllers with remote setpoint module:
| Model |
PAT 0...10 V |
DAT 0...10 V |
On/Off |
| TC-8933-1112-W |
1 |
--- |
--- |
| TC-8931-2112-W |
--- |
2 |
--- |
| TC-8934-2112-W |
--- |
--- |
2 |
| TC-8936-2112-W |
--- |
--- |
2 |
| ES-8930-3031-WK |
setpoint module, 12…28 °C |
--- |
--- |
Local controllers with central setpoint module:
| Model |
PAT 0...10 V |
DAT 0...10 V |
On/Off |
| TC-8943-1141-WK |
1 |
--- |
--- |
| TC-8941-2141-WK |
--- |
2 |
--- |
| TC-8944-2141-WK |
--- |
--- |
2 |
| TC-8946-2141-WK |
--- |
--- |
2 |
| ES-8940-4130-WK |
setpoint module, 12…28 °C |
--- |
--- |
Power modules and combinations:
| Model |
Outputs |
Ordering codes |
Configuration |
| TC-8902-1031-WK |
1 x 0...10 VDC |
PM-8902-0500 |
2 pipe |
| TC-8907-1031-WK |
1 x DAT 230 V / 1 x DAT 24 V / 1 x Relay 3A 230 V/24 V |
PM-8905-0300 / PM-8905-0500 / PM-8907-0300 |
2 pipe with change over |
| TC-8902-2031-WK |
2 x 0...10 VDC |
PM-8902-0500 |
4 pipe |
| TC-8907-2031-WK |
2 x DAT 230 V / 2 x DAT 24 V / 2 x Relay 3A 230 V/24 V |
PM-8905-0300 / PM-8905-0500 / PM-8907-0300 |
4 pipe |
| TC-8902-1032-WK |
1 x 0...10 VDC |
PM-8902-0500 |
2 pipe with change over, 3 speed |
| TC-8907-1032-WK |
1 x DAT 230 V / 1 x DAT 24 V / 1 x Relay 3A 230 V/24 V |
PM-8905-0300 / PM-8905-0500 / PM-8907-0300 |
2 pipe with change over, 3 speed |
| TC-8902-2032-WK |
2 x 0...10 VDC |
PM-8902-0500 |
4 pipe |
| TC-8907-2032-WK |
2 x DAT 230 V / 2 x DAT 24 V / 2 x Relay 3A 230 V/24 V |
PM-8905-0300 / PM-8905-0500 / PM-8907-0300 |
4 pipe |
| TC-8942-2041-WK (only with ES-8940-4130-WK) |
2 x 0...10 VDC / 2 x DAT 230 V / 2 x DAT 24 V |
PM-8902-0500 / PM-8905-0300 / PM-8905-0500 |
4 pipe, +/- on local controller TC-89, on ES-8940 |
| TC-8947-2041-WK (only with ES-8940-4130-WK) |
2 x Relay 3A 230 V/24 V |
PM-8907-0300 |
4 pipe, central setpoint module |
Позиції каталогу з цим документом
Текст документа
hvac control products
Thermostats
Electromechanical Modulating
TC-8900 and PM-8900
Room Thermostat
T
coils with 2-pipe, 2-pipe with change-over, 2-pipe with electrical coil
or 4-pipe configurations.
For applications without fan speed control the family includes stand
alone units (TC-890x), local controllers (TC-893x) with remote setpoint
module (ES-8930) and local controllers (TC-894x) with central setpoint
module (ES-8940).
For applications with fan speed control the family includes the
PM-8900 power modules in connection with TC-894x with or without
central setpoint module (ES-8940).
Features
z 2 2 hange-over, 2-pipe with electrical coil
or 4-pipe configurations with and withoput 3-speed fan override
z 8 oom enclosures
z T 22
z 2 AC power supply for the TC-8900 controls, °C
230 VAC in connection the the PM-8900 power module
Dimensions in mm
!"#$%& '()*+ ,-.*/ !.*(0.--/01
Built-in NTC K10 Setpoint Input Fan Outputs
O3453679 :;45< Sensing Element Range 0...10 V Output PAT 0...10 V DAT On/Off
TC-8903-1131-WK 1 --- --- ---
TC-8901-2131-WK --- 2 --- ---
y
TC-8904-2131-WK --- --- 2 ---
TC-8906-2131-WK --- --- --- 2
12…28 °C
TC-8903-1132-WK 1 --- --- ---
---
TC-8901-2132-WK --- 2 --- ---
--- ---
TC-8904-2132-WK --- --- 2 ---
TC-8906-2132-WK --- --- --- 2
TC-8903-1151-WK y 1 --- --- ---
0…40 °C
TC-8903-1152-WK 1 --- --- ---
TC-8903-1183-WK --- 1 --- --- ---
0…100% y
TC-8901-2183-WK --- 2 --- ---
88
The European Products Catalogue 2013
Manufacturer reserves the right to change specifications without prior notice
hvac control products
Thermostats
Electromechanical Modulating
TC-8900 and PM-8900
!"#$=& >.?)- !.*(0.--/01 @A(B C'"#$=%"=%=D"EF 0/G.(/ 1/(H.A*( G.+I-/
Built-in NTC K10 Setpoint Outputs
O3453679 :;45< Sensing Element Range Fan Output PAT 0...10 V DAT On/Off
TC-8933-1112-W 1 --- --- ---
TC-8931-2112-W --- 2 --- ---
--- ---
TC-8934-2112-W --- --- --- 2 ---
TC-8936-2112-W --- --- --- 2
ES-8930-3031-WK y 12…28 °C --- --- --- ---
!"#$J& >.?)- !.*(0.--/01 @A(B C'"#$J% ?/*(0)- 1/(H.A*( G.+I-/
Built-in NTC K10 Setpoint Outputs
O3453679 :;45< Sensing Element Range Fan Output PAT 0...10 V DAT On/Off
TC-8943-1141-WK 1 --- --- ---
TC-8941-2141-WK --- 2 --- ---
y +/-
TC-8944-2141-WK --- --- --- 2 ---
TC-8946-2141-WK --- --- --- 2
ES-8940-4130-WK --- 12…28 °C --- --- --- ---
!"#$J& >.?)- !.*(0.--/01 @A(B C'"#$J% ?/*(0)- 1/(H.A*( G.+I-/
Built-in NTC K10 Fan Power module
O3453679 :;45< Sensing Element Setpoint Range Output Outputs Ordering Codes Configuration
1 x 0...10 VDC PM-8902-0500
TC-8902-1031-WK 1 x DAT 230 V PM-8905-0300 2 pipe
1 x DAT 24 V PM-8905-0500 with change over
TC-8907-1031-WK 1 x Relay 3A 230 V/24 V PM-8907-0300
y PM-8902-0500
2 x 0...10 VDC
TC-8902-2031-WK 2 x DAT 230 V PM-8905-0300
2 x DAT 24 V PM-8905-0500 4 pipe
TC-8907-2031-WK 2 x Relay 3A 230 V/24 V PM-8907-0300
12...28 °C
1 x 0...10 VDC PM-8902-0500
TC-8902-1032-WK 1 x DAT 230 V PM-8905-0300 2 pipe
1 x DAT 24 V PM-8905-0500 with change over
3 Speed
TC-8907-1032-WK 1 x Relay 3A 230 V/24 V PM-8907-0300
---
2 x 0...10 VDC PM-8902-0500
TC-8902-2032-WK 2 x DAT 230 V PM-8905-0300
2 x DAT 24 V PM-8905-0500
TC-8907-2032-WK 2 x Relay 3A 230 V/24 V PM-8907-0300
TC-8942-2041-WK 2 x 0...10 VDC PM-8902-0500 4 pipe
(only in connection with 2 x DAT 230 V PM-8905-0300
ES-8940-4130-WK) +/- on local controller TC-89,
2 x DAT 24 V PM-8905-0500
y 12...28 °C on ES-8940
TC-8947-2041-WK central setpoint module
(only in connection with 2 x Relay 3A 230 V/24 V PM-8907-0300
ES-8940-4130-WK)
89
The European Products Catalogue 2013
Manufacturer reserves the right to change specifications without prior notice
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.