Single pressure control, series P735

Вид документаКаталожна сторінка
ВиробникJCI
МоделіP735AAA, P735BCA, P735BEA, P735AAW, P735BEB, P735BES, P735BCB
Група обладнанняpressure
Мова документаанглійська
Розмір файлу1.6 МБ

Про документ

The P735 series are single pressure controls for refrigeration high or low pressure applications, usable for control or limit functions depending on model. They have a "whole range" design for all non-corrosive refrigerants within the operating range, and models suitable for ammonia (stainless steel bellows) and PED 97/23EC Cat. IV approved HP models (double bellows) are included.

Ключові дані

Contact rating400 V ∼ 16(10) A; 230 V – 12 W (pilot duty only)
Protection classIP30
Ambient temperature limit-50 to +55 °C (+70 °C max. duration two hours); -20 to +55 °C for PED approved models
Ranges-0.5 to 7 bar; -0.2 to 10 bar; 3 to 30 bar; 3.5 to 21 bar
Differentials0.6 to 3 bar; 1 to 4.5 bar; 3 to 12 bar; 2.1 to 5.5 bar; 3.5 to 12 bar
Max. bellows pressureup to 33 bar (range dependent)
ContactsSPDT with alarm contacts
Shipping weight0.42 kg (ind. pack)

Застосування

  • Refrigeration high or low pressure control/limit functions
  • Air-conditioning and heat pump applications
  • Other high or low pressure applications such as air, water etc.
  • Ammonia applications (-97xx series)

Особливості

  • Generous wiring space — easy wiring and maintenance
  • SPDT contacts as standard on single pressure controls — can be wired for alarm functions
  • Trip-free manual reset — override is not possible in the control function
  • All models provided with alarm contacts
  • Phosphor bronze bellows and brass connections (standard); stainless steel bellows/connectors for ammonia models; double bellows on PED-conforming HP models

Технічні дані

Parameter Value
Pressure connections Style 5: 7/16"-20 UNF male; Style 15: 1/4"-18 NPT female; Style 28: braze connection 6 mm ODM; Style 30: braze connection 1/4" ODF
Operating ranges / differential See type number selection table
Adjustments Hexagonal range screw and differential screw; manual reset models have range screw only
Ambient temp. limit -50 to +55 °C (+70 °C max. duration two hours); -20 to +55 °C for PED approved models
Storage temp. -50 to +55 °C
Electrical ratings 400 V ∼ 16(10) A; 230 V – 12 W (pilot duty only)
Max. contact current max. 20 A
Pulsation plug Fitted into all HP bellows on models with range 3.5 to 21 bar and up
Protection Class IP30 (according to DIN 40050 and IEC144)
Case material 1.5 mm cold-rolled zinc plated steel
Cover material 2 mm ABS plastic blue (RAL 5007)
Contact unit Large copper-backed silver contacts
Mounting Mounting bracket 271-51L (order separately) or directly on surface; mounting holes M4
Locking plate and screw Standard on types P735AAW, BEB, BES and BCB; optional on all other types (quantity orders only)
Cable inlet grommet cable range to Ø 16 mm
Wire size 0.5 to 4 mm² (20–12 AWG)
Shipping weight ind. pack 0.42 kg
Repair Not possible; replace via supplier
Type number selection table — Non-corrosive refrigerants
Family Code Style codes Range (bar) Diff. (bar) Contact function Bellows (Figure) Max. pressure (bar)
P735AAA -9300/-9320/-9400 -0.5 to 7 0.6 to 3 1 22
P735AAA -9301 -0.2 to 10 1 to 4.5 1 15
P735AAA -9350/-9370/-9450 3 to 30 3 to 12 2 33
P735AAA -9351/-9371/-9451 3.5 to 21 2.1 to 5.5 2 30
P735BCA -9300/-9320/-9400 -0.5 to 7 Man. res.** 1 22
P735BEA -9350/-9370/-9450 3 to 30 Man. res.* 3 33

* Resetable at 3 bar below cut-out point; ** Resetable at 0.5 bar above cut-out point

Type number selection table — Ammonia and non-corrosive refrigerants
Family Code Style codes Range (bar) Diff. (bar) Contact function Bellows (Figure) Max. pressure (bar)
P735AAA -9700 -0.5 to 7 0.6 to 3 1 20
P735AAA -9750/-9770 3 to 30 3.5 to 12 2 33
P735BCA -9700 -0.5 to 7 Man. res.** 1 20
P735BEA -9750 3 to 30 Man. res.* 3 33
Type number selection table — Non-corrosive refrigerants incl. lock plate assy (PED 97/23EC Cat. IV)
Family Code Style codes Range (bar) Diff. (bar) Contact function Max. pressure (bar) Approved according to PED 97/23EC Cat. IV
P735AAW -9300/-9800 -0.5 to 7 0.6 to 3 1 20
P735AAW -9350/-9370/-9850 3 to 30 3.5 to 12 2 33 Yes
P735BCB -9300 -0.5 to 7 Man. res.** 1 20
P735BEB -9350/-9370/-9850 3 to 30 Man. res.* 3 33 Yes
P735BES -9350/-9370 3 to 30 Man. res.* 3 33 Yes

* Resetable at 3.5 bar below cut-out point; ** Resetable at 0.5 bar above cut-out point

Type number selection table — Ammonia and non-corrosive refrigerants incl. lock plate assy (PED 97/23EC Cat. IV)
Family Code Style codes Range (bar) Diff. (bar) Contact function Max. pressure (bar) Approved according to PED 97/23EC Cat. IV
P735AAW -9750 3 to 30 3.5 to 12 2 33 Yes
P735BEB -9750 3 to 30 Man. res.* 3 33 Yes

Note: 100 kPa = 1 bar ≈ 14.5 psi

Варіанти замовлення

Type number matrix:

  • P735AAA — Automatic reset
  • P735BCA — Open low – manual reset
  • P735BEA — Open high – manual reset
  • P735AAW — HP or LP Limit (Auto reset), HP conforming PED 97/23CE
  • P735BEB — HP Limit (Man. Reset), conforming PED 97/23CE
  • P735BES — HP Safety Limit (Man. Reset), conforming PED 97/23CE
  • P735BCB — LP Limit (Man. Reset), including lock plate assy

Contact functions:

  • Fig. 1: A–C open on pressure decrease
  • Fig. 2: A–B open on pressure increase
  • Fig. 3: A–C open on pressure increase

Accessories (optional):

Description Application Order number
Compression coupling (fits into style 15 pressure connectors) For 6 mm copper or steel tubing CNR003N001R
Compression coupling (fits into style 15 pressure connectors) For 8 mm copper or steel tubing CNR003N002R
Locking kit To lock and seal range/differential screw KIT023N600
90 cm capillary with (2) flare nuts (1/4" SAE) SEC002N600
90 cm flexible synthetic refrigeration hose with (2) flare nuts (1/4" SAE) H735AA-90D
Mounting bracket 271-51L

Packaging: -93xx/-97xx Ind. overpack 36 pcs. (16 kg), Bulk pack 35 pcs. (15 kg); -94xx/-98xx Ind. overpack 16 pcs. (7.5 kg)

Допуски та стандарти

  • PED 97/23EC Cat. IV (HP models: P735AAW, P735BEB, P735BES)
  • EN 60730: type 1 action, incorporated control, surface mounting on plane surface, normal pollution situation
  • IP30 according to DIN 40050 and IEC144

Текст документа

PSC1302                                                   European Refrigeration Controls Catalogue
                                                                                   Catalog Section 6
                                                                                    Product Bulletin P735
                                                                                               Issue 13/05/2003


                                          Series P735
                           Single Pressure Controls for Refrigeration,
                          Air-conditioning and Heatpump Applications

Introduction
These pressure controls are designed for use in
a variety of applications involving refrigeration
high or low pressure. Models supplied have a
“whole range” design, enabling them to be
used with all non-corrosive refrigerants which
are within the operating range of the control.
They may also be used for other high or low
pressure applications such as air, water etc.
Models which can be used with ammonia are
included in the program.
Also models tested and approved according to
PED 97/23EC Cat. IV are included in the
program.

Description
The P735 series pressure controls may be used
for control functions or limit functions, depending
on model number. All models are provided with
alarm contacts. All standard models have
phosphor bronze bellows and brass pressure
                                                                        P735 Single Pressure Control
connections. Models for use with ammonia are
                                                                              for Refrigeration
provided with stainless steel bellows and
connectors.
Devices conforming PED 97/23EC (HP models)
have a double bellows.




                                      Feature and Benefits

       ‰ Generous wiring space                        Easy wiring and maintenance

       ‰ SPDT contacts are provided as                Can be wired for alarm functions
         standard on single pressure
         controls.

       ‰ Trip-free manual reset                       Override is not possible in the control function




© 2003 Johnson Controls Inc                                                                    Catalogue Section 6
Order No. PD-P735-E
                                                                                                   P735
2                                                                                      Issue 13/05/2003


Note                                                 Contact functions
    The controls are intended to control             (see also “Type Number Selection” table)
    equipment under normal operating                                                   C
    conditions. Where failure or malfunctioning                                                    M
    of the controls could lead to an abnormal                               A
    operating condition that could cause             Line ~
                                                                                       B
    personal injury or damage to the
    equipment or other property, other                         max. 20 A
    devices (limit or safety controls) or
    systems (alarm or supervisory systems)
    intended to warn of or protect against
    failure or malfunctioning of the controls
    must be incorporated into and maintained
    as part of the control system.
                                                              A - C open on pressure decrease
                                                                           Fig. 1

Type number matrix                                                                       C
P735AAA Automatic reset                                                     A
P735BCA Open low - manual reset                       Line ~
                                                                                         B
P735BEA Open high - manual reset                                max. 20 A                            M
P735AAW HP or LP Limit (Auto reset)
        HP conforming PED 97/23CE
P735BEB HP Limit (Man. Reset)
        Conforming PED 97/23CE
P735BES HP Safety Limit (Man. Reset)
        Conforming PED 97/23 CE
P735BCB LP Limit (Man. Reset)                                  A - B open on pressure increase
                                                                           Fig. 2
        Including lock plate assy.
                                                                                           B
Mounting
                                                                            A
Mounting can easily be done with mounting            Line ~                                C
bracket 271-51L (order separately) or directly
on a surface. Mounting holes M4 are provided.                  max. 20 A                               M

Adjustment
Adjustment of range and differential can be done
by turning the hexagonal range screw and
differential screw. Manual reset models have a
range screw only. The adjustment screw can
also be locked by a lock plate accessory                       A - C open on pressure increase
(KIT023N600). On all models the scale indicates                            Fig. 3
the high switch point (Except type
P735BCA,P735BCB, here the scale indicates
the low (cut-out) switch point). The low switch      Optional construction note
point can be derived by deducting the differential   If your requirements are not in the type number
value from the high switch point.                    selection table, then please contact your
                                                     Johnson Controls representative.


                                                     Repair and replacement
                                                     Repair is not possible. In case of an improperly
                                                     functioning control, please check with your
                                                     nearest supplier. When contacting the supplier
                                                     for a replacement you should state the
                                                     type/model number of the control. This number
                                                     can be found on the data plate.



Catalogue Section 6                                                             © 2003 Johnson Controls Inc
                                                                                     Order No. PD-P735-E
P735
Issue 13/05/2003                                                                                                                        3


Type number selection table
Pressure controls for Non-corrosive refrigerants
 Family                        Style 5                   Style 30      Range       Diff.          Contact     Max.
 Code                                                                  (bar)       (bar)          function    Bellows
                Ind.                     Bulkpack        Ind.                                     (Figure)    pressure
                Pack.                                    Pack.
                -9300                    -9320           -9400         -0.5 to 7   0.6 to 3       1           22
 P735AAA        -9301                                                  -0.2 to10   1 to 4.5       1           15
                -9350                    -9370           -9450         3 to 30     3 to 12        2           33
                -9351                    -9371           -9451         3.5 to 21   2.1 to 5.5     2           30
     P735BCA    -9300                    -9320           -9400         -0.5 to 7   Man. res.**    1           22
     P735BEA    -9350                    -9370           -9450         3 to 30     Man. res.*     3           33


**     Resetable at 0.5 bar above cut-out point
*      Resetable at 3 bar below cut-out point




Pressure controls for Ammonia and Non-corrosive refrigerants
 Family                 Style 15             Range       Diff.             Contact         Max.
 Code                                        (bar)       (bar)             function        Bellows
                Ind.         Bulkpack                                      (Figure)        pressure
                Pack.
 P735AAA        -9700                        -0.5 to 7   0.6 to 3          1               20
                -9750        -9770           3 to 30     3.5 to 12         2               33
 P735BCA        -9700                        -0.5 to 7   Man. res.**       1               20
 P735BEA        -9750                        3 to 30     Man. res.*        3               33

**     Resetable at 0.5 bar above cut-out point
*      Resetable at 3 bar below cut-out point
Note: 100 kPa = 1 bar ≈ 14.5 psi


Pressure controls for Non-corrosive refrigerants (including lock plate assy)
 Family                        Style 5                   Style 28      Range       Diff.          Contact     Max.          Approved
 Code                                                                  (bar)       (bar)          function    Bellows       according
                Ind. Pack.           Bulkpack            Ind.                                     (Figure)    pressure      to PED
                                                         Pack.                                                              97/23EC
                                                                                                                            Cat. IV
 P735AAW        -9300                                    -9800         -0.5 to 7   0.6 to 3       1           20
                -9350                -9370               -9850         3 to 30     3,5 to 12      2           33            Yes
 P735BCB        -9300                                                  -0,5 to 7   Man. res.**    1           20
 P735BEB        -9350                -9370               -9850         3 to 30     Man. res.*     3           33            Yes
 P735BES        -9350                -9370                             3 to 30     Man. res.*     3           33            Yes


**     Resetable at 0.5 bar above cut-out point
*      Resetable at 3,5 bar below cut-out point

Pressure controls for Ammonia and Non-corrosive refrigerants (including lock plate assy)
 Family                 Style 15             Range       Diff.             Contact         Max. Bellows      Approved
 Code                                        (bar)       (bar)             function        pressure          according to
                Ind.         Bulkpack                                      (Figure)                          PED
                Pack.                                                                                        97/23EC
                                                                                                             Cat. IV
 P735AA         -9750                        3 to 30     3.5 to 12         2               33                Yes
 W
 P735BEB        -9750                        3 to 30     Man. res.*        3               33                Yes

**     Resetable at 0.5 bar above cut-out point
*      Resetable at 3,5 bar below cut-out point

Note: 100 kPa = 1 bar ≈ 14.5 psi

© 2003 Johnson Controls Inc.                                                                                       Catalogue Section 6
Order No. PD-P735-E
                                                                                                     P735
4                                                                                        Issue 13/05/2003


                                       Pressure connections




        Fig. 4                   Fig. 5                            Fig. 6                    Fig. 7
        Style 5                Style 15                           Style 28                  Style 30
   Male connector          Female connector                   Braze connection          Braze connection
7
 /16"-20 UNF for 1/4"        1
                              /4"-18 NPT                        6 mm ODM                   1/4" ODF
    6 mm flare nut.




                                      Accessories (optional)




                                                     Fig. 8

    Description                Application                               Order number
    Fits into style 15         For 6 mm copper or steel tubing           CNR003N001R
    pressure connectors        For 8 mm copper or steel tubing           CNR003N002R




                                                                  Fig. 11                     Fig. 12
                                     Fig. 10                     Locking kit         90 cm Flexible synthetic
                           90 cm Capillary with (2) flare       Order number         refrigeration hose with (2)
                                  nuts (1/4" SAE)               KIT023N600           flare nuts (1/4" SAE)
           Fig. 9
                           Order number SEC002N600                                          Order number
       Mounting bracket
                                                                                            H735AA-90D
    Order number 271-51L




Catalogue Section 6                                                               © 2003 Johnson Controls Inc
                                                                                       Order No. PD-P735-E
P735
Issue 13/05/2003                                                                                   5


                                          Dimensions (mm)




                               1. lock plate (if applied)
                               2. two mounting holes Ø 4.5 mm
                               3. two mounting holes Ø M4 (back side)
                               4. cable inlet grommet (cable range to Ø 16 mm)
                               5. power element:
                                  Style 5: 7/16"-20 UNF male (shown)
                                  Style 15: 1/4"-18 NPT female
                               6. reset button ( on manual reset models only)

                                                 Fig. 13



© 2003 Johnson Controls Inc.                                                     Catalogue Section 6
Order No. PD-P735-E
                                                                                           P735
6                                                                              Issue 13/05/2003


                                 Dimensions (mm)




                      1. lock plate (if applied)
                      2. two mounting holes Ø 4.5 mm
                      3. two mounting holes Ø M4 (back side)
                      4. cable inlet grommet (cable range to Ø 16 mm)
                      5. power element:
                         Style 28: Braze connection 6 mm ODM (shown)
                         Style 30: Braze connection 1/4" ODF
                      6. reset button (on manual reset models only)

                                        Fig. 14




Catalogue Section 6                                                     © 2003 Johnson Controls Inc
                                                                             Order No. PD-P735-E
P735
Issue 13/05/2003                                 7


Notes




© 2003 Johnson Controls Inc.   Catalogue Section 6
Order No. PD-P735-E
                                                                                                                           P735
8                                                                                                              Issue 13/05/2003


Specifications

        Pressure connections                   Style 5, 15, 28, 30 (see drawings)
    Operating ranges and diff.                 See type number selection

                 Adjustments                   See type number selection
            Ambient temp. limit                -50 to +55 °C (+70 °C max. duration two hours)
                                                -20 to +55 °C for PED approved models
                Electrical ratings             400 V ∼ 16(10) A
                                               230 V – 12 W (pilot duty only)
               Pulsation plug                  Fitted into all HP bellows on models with range 3.5 to 21 bar and up
     Locking plate and screw                   To lock and seal range and/or differential screw.
                                               Standard included on types P735AAW,BEB,BES and BCB.
                                               Optional on all other types (quantity orders only)
                Protection Class               IP30
                         Material              Case                    1, 5 mm cold-rolled zinc plated steel
                                               Cover                   2 mm ABS plastic blue (RAL 5007)
                                               Contact unit            Large copper-backed silver contacts

     Accessories (see pag. 4)                  Mounting bracket
                                               Compression coupling
                                               90 cm capillary with two flare nuts
                                               90 cm flexible synthetic hose with two flare nuts
                  Shipping weight              ind. pack 0.42 kg
                                               -93xx
                                               -97xx
                                                           {Ind. overpack 36 pcs. (16 kg)
                                                            Bulk pack        35 pcs. (15 kg)
                                               -94xx
                                               -98xx
                                                           {Ind. overpack 16pcs. (7.5 kg)

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond
these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.




Johnson Controls International, Inc.
Headquarters:                   Milwaukee, WI, USA
European Headquarters:          Brussels, Belgium
European Factories:             Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany)
Branch Offices:                 Principal European Cities.                                           www.johnsoncontrols.com
This document is subject to change                                                                                Printed in Europe


Catalogue Section 6                                                                                    © 2003 Johnson Controls Inc
                                                                                                            Order No. PD-P735-E
                                                    PSC0122            Mounting                   Montage             Montage               Adjustment                    Réglage                            Einstellung
                                             SHT080N603(001)            Montage                    Montaje           Montaggio               Instelling                    Ajuste                            Regolazione                                           FRANÇAIS
                                                                       Montagem                   Montering           Kiinnitys                Ajuste                    Justering                              Säätö
                                                                       Montering                  Montering          Mοντάρισµα              Justering                   Justering                            Pύθµιση                         LISEZ ATTENTIVEMENT CES INSTRUCTIONS AVANT DE COM-
                                                                       Instalace                                                              Seřízení                                                                                  !     MENCER L’INSTALLATION ET CONSERVEZ- LES POUR VOUS Y
        Instruction sheet                                                                                                                                                                                                                     REFERER ULTERIEUREMENT

                                                                                                                                                                     LP versions aut. reset                                        1. Vis de réglage de la consigne (P)
                                                                                 2x                                                                                                                                                2. Vis de réglage du différentiel (pas sur les modèles de réenclenchement
              P735                                                              M4x6 + d                                                                         A
                                                                                                                                                                          C
                                                                                                                                                                              On                                                      manuel)( P )
                                                                                                                                                                                                                                   3. Indicateur de consigne
   Single Pressure Control                                                                                                                                                B
                                                                                                                                                                                                                                   4. Indicateur du différentiel (pas sur les modèles de réenclenchement
                                                                                                                                                                                                                                      manuel)
                                                                                                                                                                 A
                                                                                                                                                                          C                                                        5. Case de serrure (si elle existe)
 Specification           Description              Spezifikation                                                                                                               Off                                                  6. Vis de la case de serrure (si elle exixte)
  Specificatie          Especificación             Specifiche                                                                                                             B                                                        7. Bouton de réenclenchement (pour les modèles à réenclenchement
 Especificação          Specifikationer             Erittely                                                                                                                                                               P          manuel uniquement)
  Beskrivelse           Spesifikasjoner          Προδιαγραφέσ                                                   25                                                                      min. - 0.5 bar
                                                                                                                                                                                                              Setpoint
Technická data                                                                                                                                                                                                                     Le modèle P735 est un régulateur de pression destiné à détecter la pression
                                                                                                                       55                                                                                                          de réfrigérants non corrosifs. Les séries P735xxx-97xx conviennent égale-
                                                                                                                                                                                                                                   ment dans l’emploi d’applications d’ammoniaque.
                                                                                                                                                                     LP versions man. reset
                                                                                                                                                                          C   On                          > 0.5 bar                D’après la norme EN 60730 c’est un régulateur incorporé, action type 1,
                                                                                                                                                                 A                                                                 conçu pour un montage sur surface plane et utilisé dans des environnements
                                                                                                                                                                          B                                                        normalement pollués.

                                                                                                                                                                          C                                                        Le contrôleur P735 est destiné à commander des équipements dans des
                                                                                                               d                                                 A
                                                                                                                                                                              Off                                                  conditions d’exploitation normales. Lorsqu’une défaillance ou un mauvais
                                                                                                                                                                          B                                                        fonctionnement de l’P735 peut entraîner des conditions d’exploitation anor-
                                                                                         70       25                                                                                                                               males pouvant provoquer des dommages corporels ou matériels, il con-
                                                                                                                                                                                                                           P       vient d’intégrer dans le système de commande d’autres dispositifs (com-
                                                                                                                                                                                                 Setpoint                          mandes de limite ou de sécurité) ou systèmes (systèmes d’alarme ou de
                                                                                                                                                                                        min. - 0.5 bar                             surveillance) destinés à prévenir ou à protéger contre toute défaillance ou
                                                                                                                                                                                                                                   dysfonctionnement de l’P735. Ces dispositifs et systèmes complémentai-
                                                                                                                                                                                                                                   res doivent en outre faire l’objet d’un entretien et d’une maintenance
      3       4     1        2      5       7       6                                                                                                                HP versions aut. reset
                                                                                                                                                                          C
                                                                                                                                                                                                                                   appropriés.L’ampérage requis des fusibles dépend des câbles utilisés.
                                                                                                                                                                 A            On                                                   Reportez-vous au tableau ci-dessous.
                                                                                                                                                                          B
                                                                                                                                                                                                                                   INSTALLATION
                                                                                                                                                                          C
                                                                                                                                                                 A
                                                                                                                                                                              Off                                                   !       Couper l’alimentation électrique avant d’enlever le couvercle.
                                                                                                                                                                          B
                                                                                                                                                                                                                                   Pour ôter la couverture
                                                                                                                                                                                                                                   Ouvrez la pression en vous aidant d’un outil dans une main et, avec l’autre
                                                                                                                                                                                                                           P
                                                                                                                                                                                         min. 3 bar
                                                                                                                                                                                                              Setpoint             main, repoussez la couverture comme indiqué sur l’illustration

                                                                                                                                                                                                                                   Câblage
                                                                                                                                                                     HP versions man. reset                                        Tous les raccordements doivent être conformes aux normes en vigueur et ne
                                                                                                                                                                                                          > 3.5 bar (DIN models)   peuvent être réalisés que par du personnel autorisé.
                                                                                                                                                                          B                               > 3 bar
                                                                                                                                                                                  On                                               En cas d’utilisation de câble souple multi-brins, utiliser un embout à sertir.
                                                                                                                                                             A
                                                                                                                                                                          C
                                                                                                                                                                                                                                   Procédure de contrôle
                                                                                                                                                                                                                                   Après avoir terminé l’installation, observez au moins trois cycles complets de
                                                                                                                                                                          B                                                        fonctionnement pour s’assurer que tous les composants fonctionnent cor-
                                                                                                                                                             A                    Off                                              rectement. Si cela n’est pas le cas, contactez votre fournisseur.
                                                                                                                                                                          C


                                                                                                                                                                                        min. 3 bar
                                                                                                                                                                                                                           P
                                                                                                                                                                                                              Setpoint
                                                                                                                                                                                                                                                                    DEUTSCH
                                                                                                                                                  LP aut./man.                                        C                                        BITTE LESEN SIE DIESE ANWEISUNGEN VOR DER INSTALLA-
                                                                                                                                                                                                                  M                     !      TION SORGFÄLTIG DURCH UND BEWAHREN SIE SIE ZUR
              T min.:        -50 °C                                                                                                                                           A                                                                WEITEREN VERWENDUNG AUF.
              PED:           -20 °C                                                                                                               Line ~                                                                           1         Sollwerteinstellschraube (P)
              T max.:        +55 °C                                                                                                                     max. 20 A                                                                  2         Differentialeinstellschraube (Nicht bei Modellen mit manueller
                                                                                                                                                                                                      B                                      Rückstellung)(¢P)
                                                                                                                                                                                                                                   3         Sollwertanzeige
                                                                                                                                                                                                                                   4         Differentialanzeige (Nicht bei Modellen mit manueller Rückstellung)
                                                                                                                                                                                                                                   5         Sicherungsscheibe (falls zutreffend)
  Mounting
   Montage
                          Montage
                           Montaje
                                                   Montage
                                                  Montaggio                                                                                       HP aut.
                                                                                                                                                                                                      C                            6         Sicherungsschraube (falls zutreffend)
                                                                                                                                                                                                                                   7         Rückstelltaste (Nur Modelle mit manueller Rückstellung)
  Montagem
  Montering
  Instalace
                          Montering
                          Montering
                                                   Kiinnitys
                                                  Mοντάρισµα                                              2                                       Line ~
                                                                                                                                                                              A                                                    Der P735 ist ein Druckregler zum Fühlen des Drucks nichtagressiver
                                                                                                                                                                                                                                   Kühlmittel. Die Baureihe P735xxx-97xx ist auch für den Einsatz in Verbin-
                                                                                                                                                            max. 20 A                                             M                dung mit Ammoniak geeignet.
                                                                                                                                                                                                      B                            Dieses ist entsprechend EN 60730 ein Wirkungsweise Typ 1, Integriertes
                                                                                                                                                                                                                                   Regel- und Steuergerät, Geeignet als Aufbaugerät, z. B. für Wandmontage
                                                                                                                                                                                                                                   und für Anwendung in Umgebungsbedingungen mit üblicher Verunreini-
                                                                                                                                                                                                                                   gung.
                                                                                                                                                  HP man.                                             B
                                                                                                                       1                                                      A
                                                                                                                                                                                                                                   Das P735 ist zur Steuerung von Geräten unter normalen Betriebs-
                                                                                                                                                                                                                                   bedingungen ausgelegt. In Fällen, in denen eine Fehlfunktion oder ein De-
                                                                                                                                                  Line ~                                                                           fekt des P735 zu außergewöhnlichen Betriebsbedingungen führen könnte,
                                                                                                                                                                                                                  M                die Verletzungen oder die Beschädigung von Geräten oder anderen Ein-
                                                                                                                                                            max. 20 A                                                              richtungsgegenständen nach sich ziehen könnten, sollten andere Geräte
                                                                                                                                                                                                      C                            (Toleranz- oder Sicherheitssteuerungen) oder Systeme (Alarm- oder Über-
                                                                                                                                                                                                                                   wachungssysteme), die vor einem Defekt oder einer Fehlfunktion des P735
                                                                                                                                                                                                                                   warnen oder dagegen schützen, als Teil des Steuersystems eingesetzt und
                                                                                                                                                                                                                                   gewartet werden.
                                                                            Wiring            Raccordement         Verdrahtung           Specification                 Description                           Spezifikation
                                                                          Bedrading             Cableado            Cablaggio                                                                                                      Montage
                                                                                                                                          Specificatie                Especificación                          Specifiche
                                                                          Cablagem              Ledningar            Jodotus             Especificação                Specifikationer                          Erittely
                                                                     Elektrisk installation      Kabling           Kαλωδίωση              Beskrivelse                 Spesifikasjoner                       Προδιαγραφέσ            !       Vor dem Entfernen des Deckels Spannung abschalten.
                                                                           Zapojení                                                     Technická data
                                                                                                                                                                                                                                   Entfernung der Abdeckung.
                                                                                                                                                                                                                                   Mit dem Werkzeug in einer Hand Schnappverschluss öffnen und mit der
                                                                                                                                   Electrical rating:                    16(10) A, 400V ~                                          anderen Hand die Abdeckung zurückziehen, wie das gezeigt wird.
                                                                                                                                                                         230V ... , 12W (pilot duty only)
                                                                                                                                   Enclosure:                            IP30 according to DIN 40050 and IEC144                    Verdrahtung
                                                                                                                                   Amb. temp. limits:                    -50 to +55 °C for standard models                         Alle Verdrahtungen müssen den am Einsatzort geltenden Vorschriften
                                                                                                    A                                                                    -20 to +55 °C for PED models                              entsprechen und sind ausschließlich dazu befugten Personen vorbehalten.Bei
                                                                                                                                   Storage temp.:                        -50 to +55 °C                                             Vewendung feindrätiger Leitungen sind Adernendhülsen zuverwenden.
                                                                                              B     C    D                         Max. bellows press.: Range             -0.3 to 2 bar : 4 bar
                                                                                                                   4x M4x8                                                -0.5 to 7 bar : 22 bar
                                                                                                                                                                                                                                   Überprüfung
                                                                                                                                                                                                                                   Vor dem Verlassen der Anlage sollten Sie diese mindestens drei Betriebs-
                                                                                                                                   (ammonia models only)                  -0.5 to 7 bar : 14 bar                                   zyklen beobachten und überprüfen, daß alle Komponenten ordnungsgemäß
                                                                                                                                                                             1 to 10 bar : 15 bar                                  funktionieren. Sollte dies nicht der Fall, wenden Sie sich bitte an Ihren
                                                                                                                                                                         0.35 to 21 bar : 30 bar                                   Händler.
                                                                                     G                                                                                       3 to 30 bar : 33 bar
                                                                                                                            2
                                                                                                              0.5 to 4 mm          note: 1 bar = 100 kPa ≈ 14.5 psi
                                                                                                              (20-12 AWG)
                                                                                                                                                                      ENGLISH                                                                                   NEDERLANDS
                  90°                                                                                                                          READ THIS INSTRUCTION SHEET CAREFULLY BEFORE IN-                                               NEEM DEZE INSTRUCTIES GRONDIG DOOR ALVORENS U BE-
                                                                                                                                        !      STALLING, RETAIN IT SAFELY FOR FUTURE REFERENCE.                                         !     GINT MET HET INSTALLEREN EN BEWAAR ZE VOOR TOEKOM-
                                                                                                                                                                                                                                              STIG GEBRUIK
                                                                                                                                   1         Setpoint adjustment screw (P)
                                                                                                                                   2         Differential adjustment screw (not on manual reset models)(¢P)                        1         Setpoint instelschroef(P)
                                                                       Adjustment                  Réglage           Einstellung   3         Setpoint indicator                                                                    2         Differentie instelschroef (niet op man. reset modellen)(¢P)
                                                                        Instelling                  Ajuste           Regolazione   4         Differential indicator (not on manual reset models)                                   3         Setpoint aanwijsschaal
                                                                          Ajuste                  Justering             Säätö      5         Lock plate (if applied)                                                               4         Differentie aanwijsschaal (niet op man. reset modellen)
                                                                        Justering                 Justering           Pύθµιση      6         Lock plate screw (if applied)                                                         5         Borgplaat (optioneel)
                                                                         Seřízení                                                  7         Reset button (manual reset models only)                                               6         Borgplaat schroef (optioneel)
                                                                                                                                                                                                                                   7         Reset drukknop (allen op man. rest modellen)
                                                                                                                                   The P735 is a pressure control designed to sense pressure of non- corrosive
                                                                                                                                   refrigerants. The P735xxx-97xx series are also suitable for use in ammonia                      De P735 is een pressostaat ontworpen voor het meten van drukken van niet
                                                                                                                                   applications.                                                                                   corrosive koelmiddelen. De P735xxx-97xx series zijn ook te gebruiken voor
                                                                                                                                                                                                                                   ammoniak toepassingen.
                                                                                                                                   According to EN 60730 it is a type 1 action, incorporate control, suitable for
                                                                                                                                   surface mounting on a plane surface and for use in normal pollution situation.                  Volgens EN 60730 is het een type 1 aktie in te bouwen apparaat, geschikt
                                                                                                                                                                                                                                   voor montage op een plat oppervlak en geschikt voor gebruik in een normaal
                                                                                                                                   The P735 is intended to control equipment under normal operating condi-                         vervuilde omgeving.
                                                                                                                                   tions. Where failure or malfunction of the P735 could lead to an abnormal
                                                                                                                                   operating condition that could cause personal injury or damage to the                           De P735 is bedoeld voor het onder normale bedrijfscondities regelen van
                                                                                                                                   equipment or other property, other devices (limit or safety controls) or                        apparatuur. Indien een defect aan of het slecht functioneren van de P735
                                                                                                                                   systems (alarm or supervisory systems) intended to warn of or protect                           regelaar kan leiden tot abnormale bedrijfscondities, welke tot persoonlijk
                                                                                                                                   against failure or malfunction of the P735 must be incorporated into and                        letsel of schade aan de apparatuur of aan andere bezittingen kan leiden,
                                                                                                                                   maintained as part of the control system.
                                                                                                                                                                                                                                   dienen andere apparaten (begrenzing- of beveiligingsapparatuur) of syste-
                                                                                                                                   INSTALLATION                                                                                    men (alarm- of overkoepelende systemen) ter alarmering of beveiliging te-
                                                                                                                                                                                                                                   gen het niet goed functioneren van de P735 te worden geïntegreerd in en te
                                                                                                                                                                                                                                   worden onderhouden als onderdeel van het regel systeem.
                                                                                                                                    !       Disconnect from power supply before the cover is removed.
                                                                                                                                                                                                                                   Montage
                                                                                                                                   Cover removal
                                                                                                                                   Unlock snap with tool in one hand pull back cover with the other hand as
                                                                                                                                   shown.                                             