SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

P215PR-9200 — Pressure actuated condenser fan speed controller, Series P215PR

Вид документаТехнічний паспорт
ВиробникJCI
МоделіP215PR-9200, P215PR-9202, P215PR-9800
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.2 МБ

Про документ

Direct mount pressure actuated condenser fan speed controllers for single-phase motors (permanent split capacitor or shaded pole), including a built-in RFI suppression filter. The controller varies the motor supply voltage from 30 % to at least 95 % over the proportional band using the phase cutting principle, for head pressure control of refrigeration systems via condenser fan speed variation. Cut-off models (fan stops at low pressure) and minimum speed models (fan keeps running at 30 %) are available.

Ключові дані

Pressure range10 to 25 bar / 22 to 42 bar
Maximum current3 A rms (at maximum voltage output)
Mains supply voltage230 Vac +10 % / -15 %
Mains supply frequency50/60 Hz
Output voltage span30 % to ≥ 95 % of supply voltage
Cut-off point / Minimum speed30 % of supply voltage
EnclosureIP65
Operating ambient temperature-20 to +55 °C

Застосування

  • Head pressure control of refrigeration systems by varying the speed of the fan on an air-cooled condenser
  • Non-corrosive refrigerant systems
  • Outdoor mounting possible (IP65)

Особливості

  • Condenser pressure control by fan speed variation; optimum condenser pressure control all year round; less noise during colder periods
  • Pressure input gives direct and fast response to pressure variations
  • Direct mount — easy to install
  • Setpoint screw on top — easy setpoint adjustment after installation
  • Built-in suppression filter meeting the EMC requirements of directive 89/336/EEC
  • IP65 — can be mounted outdoors
  • Compact design — fits in small units
  • Quick connector plug included for easy wiring and quick replacement

Технічні дані

Parameter Value
Product type P215PR
Pressure range 10 to 25 bar / 22 to 42 bar
Maximum overrun pressure 22 to 42 bar = 48 bar; 10 to 25 bar = 40 bar
Pressure connection style 47 (7/16-20 UNF female incl. valve depressor); style 28 (with 100 mm tube 6 mm ODM)
Control action direct
Maximum output voltage ≥ 95 % of supply voltage
Maximum current 3 A rms (at maximum voltage output); special models up to 4 A possible
Minimum current ≥ 100 mA
Power factor (cosϕ) motor ≥ 0.6
Mains supply voltage 230 Vac +10 % / -15 %
Mains supply frequency 50/60 Hz
Operating ambient temperature -20 to +55 °C
Storage ambient temperature -40 to +85 °C
Storage ambient humidity 10 to 98 % R.H. (non-condensing)
Cut-off point / Minimum speed 30 % of supply voltage
Proportional band range 10 to 25 bar = 4.5 ± 1 bar; range 22 to 42 bar = 5.5 ± 1.5 bar
Factory setpoint range 10 to 25 bar: 19 bar; range 22 to 42 bar: 26 bar (setpoint defined at 90% output value)
Hysteresis built-in (fixed), included in prop. band
Enclosure IP65
Material top/bottom Polycarbonate (glass filled)
Heatsink aluminium
Pressure connection material Brass
Bellows Phosphor bronze
Shipping weight (individual pack) 0,3 kg
Residual current motor in cut-off mode ≤ 15 mA
Wiring connections screw terminals 1½ mm² max.; quick connector plug PG9 (6 up to 8 mm cable)

Note: values at 50 Hz power supply; at 60 Hz the cut-off and proportional band values decrease with 20 %. For measuring amps or volts use a true rms meter.

Варіанти замовлення

Order nr. Range (bar) Element style Setting (bar) Prop. band (bar) Controller Mode
P215PR-9200 10 to 25 47 19 4.5 Cut-off
P215PR-9202 22 to 42 47 26 5.5 Cut-off
P215PR-9800 10 to 25 28 19 4.5 Cut-off

Element styles: style 47 direct mount 7/16–20 UNF female (incl. valve depressor); style 28 braze connection 6 mm ODM. Note: 1 bar = 100 kPa ≈ 14.5 psi

Допуски та стандарти

  • Meets EMC requirements of directive 89/336/EEC (built-in suppression filter)
  • Ingress protection IP65

Позиції каталогу з цим документом

Текст документа

PSC 0435                                                   European Refrigeration Controls Catalogue
                                                                                    Catalog Section         4
                                                                                    Product Bulletin        P215PR
                                                                                               Issue        12/11/2004

                                              Series P215PR
               Direct Mount Pressure Actuated Condenser Fan Speed Controllers
                  For Single Phase Motors (incl. built-in RFI suppression filter)

Introduction

These Direct Mount pressure actuated condenser fan
speed controllers are designed for speed variation of
single-phase motors.
Head pressure control of a refrigeration system,
through speed variation of the fan on an air-cooled
condenser, results in optimum performance
throughout the year.

A pressure actuated device, gives the most direct and
fastest response to pressure variations in the
refrigerant system. The controller varies the supply
voltage to the motor from 30 % to at least 95 % over
the proportional band using the phase cutting principle.
This provides speed variation of permanent split
capacitor or shaded pole motors that do not draw more
than 3 A (rms) full load current.

Cut-off models (fan stops at low pressure) as well as                                P215PR
minimum speed models (fan keeps running at 30%)                           Direct Mount Pressure Actuated
are available.                                                            Condenser Fan Speed Controller
The controllers can be used in non-corrosive
refrigerant systems.                                             It is recommended to confirm with the electric motor
                                                                 manufacturer, that the motor can be used with a
The motor manufacturer should have approved his                  controller, using the phase cutting principle for speed
product for this speed control principle.                        variation. You can also provide a copy of this product
                                                                 data sheet to the motor manufacturer/supplier for
                                                                 review.



                                              Feature and Benefits
           q   Condenser pressure control by fan           Optimum condenser pressure control all the
               speed variation.                            year round.
                                                           Less noise during colder (night) period.
           q   Pressure input.                             Direct and fast response to pressure variations.
           q   Direct mount.                               Easy to install.
           q   Setpoint screw on top.                      Easy setpoint adjustment after installation.
           q   Built-in suppression filter.                The controller meets the electro-magnetic
                                                           compatibility requirements of the 89/336/EEC
                                                           directive.
           q   IP65                                        Can be mounted outdoors
           q   Compact design                              Small turn-around circle. Fits in small units.
           q   Attractive styling                          Upgrades your equipment
           q   Quick connector plug included               For easy wiring and quick replacement




© 2004 Johnson Controls, Inc.                                                                         Catalogue Section 4
Order No. PD-P215PR-E
                                                                                                     P215PR
2                                                                                            Issue 12/11/2004



     !    Caution                                      Wiring
                                                       The built-in EMC filter is designed for a maximum
     The P215PR is intended to control equipment       distance of two meters between the controller and the
    under normal operating conditions. Where failure   motor. Non-shielded cable must be used. The rubber
    or malfunction of the P215PR could lead to an      gasket must be placed between the quick connector
    abnormal operating condition that could cause      plug and the controller terminals to keep the IP65
    personal injury or damage to the equipment or      protection class.
    other property, other devices (limit or safety
    controls) or systems (alarm or supervisory
    systems) intended to warn of or protect against
    failure or malfunction of the P215PR must be
    incorporated into and maintained as part of the
    control system.



Installation
The controller must be mounted in upright
position on the refrigerant line and preferable at
the condenser outlet side (to prevent pulsation as
much as possible). If a pump-down system is
used the pressure connection must be made at
the high-pressure side of the system and before
the solenoid valve (to avoid low pressures during
pump-down). An angle of 45° is allowed to both         EMC
sides. This to avoid the accumulation of oil inside    The controller has a built-in suppression filter and
the bellows and to fulfil class IP65.                  meets all required EC directives. Please note that
                                                       when two or more EMC compliant components are
                                                       built together the total system may not be compliant.
                                  45°                  To make the total system compliant is the
                                                       responsibility of the producer.


                                                       Note
                                                       More motors can be wired in parallel, provided that the
                                                       total current will not exceed the maximum limit.


The controller (IP65) can be mounted outdoors. When
mounted inside a cabinet, holes for air circulation       ! Caution
should be provided. About 4 Watt heat will be
generated at the maximum load of 3 A.                   The enclosed quick connector plug is especially
                                                        designed (special terminal numbering) for this
                                                        control and should not be used for other
                                                        purposes.


                                                       Measuring
                                                       For measuring amps or volts values a true rms
                                                       meter should be used.


                                                          !    Caution
                                                         The P215PR is not equipped with a power
                                                        switch. Therefore an additional switch to isolate
                                                        the device should be used in the power supply
                                                        wiring to the P215PR. Also the P215PR should
                                                        be externally fused against miswiring or short
                                                        circuits. Use a thermal/current overload relay
                                                        with a current rating according to the motor (max.
                                                        6 A/slow).




Catalogue Section 4                                                                © 2004 Johnson Controls, Inc.
                                                                                       Order No. PD-P215PR-E
P215PR
Issue 12/11/2004                                                                                                    3


Adjustments
The setpoint is defined at 90% output value. The fixed             SETPOINT SCREW
min. speed or cut-off value is 30% of the supplied
voltage. Please note that the load and the supply
voltage can affect the controller characteristic.




                                                             Setpoint
                                                             The pressure setpoint at which your equipment has to
                                                             work can be adjusted by above setpoint adjusting
                                                             screw.
                                                             The setpoint is factory set at:
                                                              range 10 to 25 bar         19 bar
                                                              range 22 to 42 bar         26 bar




                                                             Repair and replacement
The proportional band is fixed and defined as the            Repair is not possible. In case of an improperly
pressure difference between the points where the             functioning control, please check with your nearest
output values are 30% and 90% of the supply voltage.         supplier. When contacting the supplier for a
                                                             replacement you should state the type-model number
                           Range (bar)                       of the control. This number can be found on the data
                                                             plate.
                   10 to 25     22 to 42
 Prop. band        4.5 ± 1      5.5 ± 1.5

There is a built-in (fixed) hysteresis. This is not
indicated in the control characteristic. The hysteresis is
included in the prop. band.


Note
The values indicated are at 50Hz power supply.
At 60 Hz the cutt-off and proportional band values
decrease with 20 %.




© 2003 Johnson Controls, Inc.                                                                  Catalogue Section 4
Order No. PD-P215DP-E
                                                                                                    P215PR
4                                                                                           Issue 12/11/2004



                                   Type number selection table

          Order nr.        Range         Element       Setting    Prop. band         Controller
                           (bar)         style         (bar)      (bar)              Mode


          P215PR-9200      10 to 25      47            19         4.5                Cut-off
          P215PR-9202      22 to 42      47            26         5.5                Cut-off
          P215PR-9800      10 to 25      28            19         4.5                Cut-off


      Note: 1 bar = 100 kPa ≈ 14.5 psi

                        Pressure connections and Dimensions (mm)
                         There are two types of pressure connections available.




             Style 47 Direct mount                      Style 28 Braze connection 6 mm ODM
               7/16 –20 UNF female
             (incl. valve depressor)




Catalogue Section 4                                                               © 2004 Johnson Controls, Inc.
                                                                                      Order No. PD-P215PR-E
P215PR
Issue 12/11/2004                                  5


Note




© 2003 Johnson Controls, Inc.   Catalogue Section 4
Order No. PD-P215DP-E
                                                                                                                          P215PR
6                                                                                                                 Issue 12/11/2004


Specifications
                                     Product type     P215PR
                                                      10 to 25 bar
                               Pressure range
                                                      22 to 42 bar
                                                      22 to 42 bar = 48 bar
            Maximum overrun pressure
                                                      10 to 25 bar = 40 bar
                                                      style 47 ( 7/16-20UNF female incl. valve depressor)
                      Pressure connection
                                                      style 28 (with 100 mm tube 6 mm ODM)
                        Control action                direct
                Maximum output voltage                ≥ 95 % of supply voltage
                                                      3 A rms (at maximum voltage output)
                            Maximum current           Special models up to 4 A are possible. Please contact your
                                                      supplier.
                    Minimum current                   ≥ 100 mA
         Power factor (cosϕ ) motor                   ≥ 0.6
                Mains supply voltage                  230 Vac +10 % / -15 %
             Mains supply frequency                   50/60 Hz
     Operating ambient temperature                    -20 to +55 °C
         Storage ambient humidity.                    10 to 98 % R.H. (non-condensing)
             Storage ambient Temp.                    -40 to 85 °C
       Cut-off point /Minimum speed                   30 % of supply voltage
               Prop. band      range                  22 to 42 bar = 5.5 ± 1.5 bar
                               range                  10 to 25 bar = 4.5 ± 1 bar
                           Enclosure                  IP65
      Material            top/bottom                  Polycarbonate (glass filled)
                            heatsink                  aluminium
                   press. connection                  Brass
                             bellows                  Phosphor bronze
                        Shipping weight               individual pack 0,3 kg
                  Residual current motor              in cut-off mode ≤ 15 mA
                                                      screw terminals 1½ mm2 max.
                        Wiring connections
                                                      quick connector plug PG9 (6 up to 8 mm cable)

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond
these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.




Johnson Controls International, Inc.
Headquarters:                  Milwaukee, WI, USA
European Headquarters:         Westendhof 8, 45143 Essen, Germany
European Factories:            Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany)
Branch Offices:                Principal European Cities.
This document is subject to change                                                                                 Printed in Europe


Catalogue Section 4                                                                                    © 2004 Johnson Controls, Inc.
                                                                                                           Order No. PD-P215PR-E


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.