Metasys Network Control Engine, MS-NCE25 series

Вид документаКаталожна сторінка
ВиробникJCI
МоделіMS-NCE25xx-x, MS-NCE2500-0, MS-NCE2506-0, MS-NCE2510-0, MS-NCE2511-0, MS-NCE2516-0, MS-NCE2517-0, MS-NCE2520-0
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.7 МБ

Про документ

The Metasys® Network Control Engine (NCE) Series controllers provide a cost-effective solution for integrating central plants and large built-up air handlers into existing Metasys networks. They combine the network supervisor capabilities and IP connectivity of a Network Automation Engine (NAE) with the I/O point connectivity and direct digital control of a Field Equipment Controller (FEC). NCEs provide supervisory control of a specified field bus trunk with up to 32 field controllers and integrate many protocols: BACnet/IP, BACnet MS/TP, N2 Bus, Modbus RTU, Modbus TCP, M-Bus (EN 13757-3), KNX IP, LonWorks (Release 9.0 models), and other third-party protocols.

Ключові дані

Integral I/O points33 (supports up to 128 additional I/O points on SA Bus)
Field bus supervisionup to 32 field controllers per trunk
Power requirementDedicated nominal 24 VAC, Class 2 (NA) / SELV (EU), 50/60 Hz (20 VAC min to 30 VAC max)
Power consumption25 VA maximum for NCE25 only
Analog input/output resolution16-bit; ±200 mV accuracy on 0–10 VDC outputs
Ambient operating conditions0°C to 50°C (32°F to 122°F), 10 to 90% RH, 30°C maximum dew point
Housing protectionIP20 (IEC60529)
Dimensions155 mm x 270 mm x 64 mm (6.1 in. x 10.6 in. x 2.5 in.)

Застосування

  • Integration of central plants and large built-up air handlers into Metasys networks
  • Supervisory control of Johnson Controls and third-party protocol devices (BACnet MS/TP, BACnet/IP, N2 Bus, Modbus RTU/TCP, M-Bus EN 13757-3, KNX IP, LonWorks)
  • Expansion of field-level control via NS Series Network Sensors, VFDs, and IOMs connected to the SA Bus
  • Data visibility and energy usage monitoring/control over enterprise IP networks with https encryption

Особливості

  • Use of commonly accepted IT standards at automation and enterprise level; standard IT communication services over intranet/WAN/public Internet with firewall protection; encrypted client communication via https
  • Web-based user interface accessible from a supported web browser
  • Secure Linux operating system (Buildroot 2017.08.2 with Linux kernel 14.4 at Release 9.0.7); upgrade from Windows CE via simple network download — no hardware to replace
  • Integral field controller with 33 I/O points
  • Expandable I/O point capacity, NS sensor connectivity, and VFD control on the field controller SA Bus
  • Some models include an integral display screen with navigation keypad for easy field modifications
  • Optional internal modem (dial-up) on some models; modem functions not available after update to Release 9.0.7

Технічні дані

Parameter Value
Power requirement Dedicated nominal 24 VAC, Class 2 power supply (North America), SELV power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum)
Power consumption 25 VA maximum for NCE25 only (BO devices powered by an NCE can require an additional 125 VA maximum)
Power source +15 VDC terminals provide 100 mA total current; five inputs located in Universal IN terminals, for active (3-wire) input devices
Ambient operating conditions 0°C to 50°C (32°F to 122°F), 10 to 90% RH, 30°C (86°F) maximum dew point
Ambient storage conditions -40°C to 70°C (-40°F to 158°F), 5% to 95% RH, 30°C (86°F) maximum dew point
Data protection battery Rechargeable NiMH battery: 3.6 VDC 500 mAh, typical life 5 to 7 years at 21°C (70°F); Product Code Number: MS-BAT1020-0
Processors Supervisory Controller: 192 MHz Renesas SH4 7760 RISC processor; Field Controller: 20 MHz Renesas H8S2398 processor
Memory Supervisory Controller: 128 MB flash nonvolatile memory + 128 MB SDRAM; Field Controller: 1 MB flash memory and 1 MB RAM
Operating system Microsoft® Windows Embedded CE 6.0 (Release 9.0); Buildroot 2017.08.2 with Linux kernel 14.4 (Release 9.0.7)
Network and serial interfaces One Ethernet port; 10/100 Mbps; 8-pin RJ-45 connector • One optically isolated RS-485 SA Bus port, pluggable keyed 4-position terminal block (all NCE25 models) • One optically isolated RS-485 port (N2 Bus or MS/TP trunk models) • One LonWorks port; FTT10 78 Kbps (LonWorks models only, Release 9.0 software only) • One RS-232-C serial port, standard 9-pin sub-D connector • One USB serial port (optional external modem; Release 9.0 only) • Option: telephone port for internal modem; up to 56 Kbps; 6-pin modular connector
Universal inputs 10 universal inputs: 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact
Binary inputs 8 binary inputs: Dry Contact Maintained or Pulse/Accumulator Mode (High Speed, 100Hz)
Analog outputs 4 analog outputs: 0–10 VDC or 4–20 mA
Binary outputs 7 binary outputs: 24 VAC Triac (selectable internal or external source power)
Configurable outputs 4 configurable outputs: 0–10 VDC or 24 VAC Triac BO
Analog input/output resolution Analog Input Points: 16-bit resolution; Analog Output Points: 16-bit resolution and ±200 mV accuracy on 0–10 VDC applications
Dimensions 155 mm x 270 mm x 64 mm (6.1 in. x 10.6 in. x 2.5 in.); minimum mounting space required: 250 mm x 370 mm x 110 mm (9.8 in. x 14.6 in. x 4.3 in.)
Housing Plastic housing; ABS and polycarbonate material; Protection: IP20 (IEC60529)
Mounting On a flat surface with screws, on three mounting clips, or a single 35 mm DIN rail
Shipping weight 1.2 kg (2.7 lb)

Варіанти замовлення

Base features on each NCE25 (MS-NCE25xx-x): requires a 24 VAC power supply; includes one RS-232-C serial port, one RS-485 optically isolated SA Bus port, one USB serial port, one Ethernet port, and an MS-BAT1020-0 data protection battery; 33 integral I/O points; supports up to 128 additional I/O points on the SA Bus; supports BACnet IP network.

Product code number Release Description
MS-NCE2500-0 9.0.7 Base features with no physical field controller trunk connection (Europe only)
MS-NCE2506-0 9.0.7 Base features, no physical field controller trunk connection; includes integral display screen (Europe only)
MS-NCE2510-0 9.0.7 Two third-party trunks (Modbus RTU or TCP, M-Bus, or KNX) and one N2 Bus (up to 32 devices on N2 Bus)
MS-NCE2511-0 9.0.7 As above plus internal modem
MS-NCE2516-0 9.0.7 As MS-NCE2510-0 plus integral display screen
MS-NCE2517-0 9.0.7 As MS-NCE2516-0 plus internal modem
MS-NCE2520-0 9.0 One LonWorks trunk with up to 32 LonWorks devices
MS-NCE2521-0 9.0 LonWorks trunk plus internal modem
MS-NCE2526-0 9.0 LonWorks trunk plus integral display screen
MS-NCE2527-0 9.0 LonWorks trunk plus integral display screen and internal modem
MS-NCE2560-0 9.0.7 Two third-party trunks (Modbus RTU or TCP, M-Bus, or KNX) and one MS/TP Bus (up to 32 devices)
MS-NCE2561-0 9.0.7 As above plus internal modem
MS-NCE2566-0 9.0.7 As above plus integral display screen
MS-NCE2567-0 9.0.7 As above plus integral display screen and internal modem

Accessories:

Product code number Description
MS-BAT1020-0 Replacement data protection battery; rechargeable NiMH: 3.6 V 500 mAh, typical life 5 to 7 years at 21°C (70°F)
TL-MAP1810-xx Pocket-sized wireless mobile user interface web server (Mobile Access Portal Gateway, LIT-1900869)
MS-DIS1710-0 Local Controller Display connects to NCE on SA Bus with menu display and navigation keypad (not operable on NCE models with integral controller display)
AS-XFR100-1 Power transformer (Class 2, 24 VAC, 92 VA maximum output), with enclosure
AS-XFR010-1 Power transformer (Class 2, 24 VAC, 92 VA maximum output), no enclosure
MS-EXPORT-0 Metasys Export Utility for historical trend, alarm, and audit data extraction (provided with ADS/ADX solution)

Допуски та стандарти

  • United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A
  • Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment Industry Canada Compliant, ICES-003
  • Europe: CE Mark — compliance with essential requirements and other relevant provisions of the EMC Directive
  • Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
  • BACnet International: BTL 135-2010 Listed B-BC at Metasys system Release 8.1

Позиції каталогу з цим документом

Текст документа

Network Control Engine Catalog Page




                          MS-NCE25xx-x



Johnson Controls                                     LIT-1900455
www.johnsoncontrols.com                  2018-12-17 Release 9.0.7
Introduction
The Metasys® Network Control Engine (NCE) Series controllers provide a cost-effective solution
designed for integrating central plants and large built-up air handlers into your existing Metasys
networks.
These network control engines combine the network supervisor capabilities and IP network
connectivity of a Network Automation Engine (NAE) with the I/O point connectivity and direct
digital control capabilities of a Field Equipment Controller (FEC), making them the ideal choice for
expanding and improving your Metasys installation for greater data visibility and control over your
energy usage.
NCEs provide supervisory control of a specified field bus trunk with up to 32 field controllers. NCE25
Series controllers provide integration to many network protocols, including BACnet®/IP, BACnet
MS/TP, N2 Bus, Modbus® RTU, Modbus TCP, M-Bus (EN 13757-3), KNX IP, and other third-party
protocols. The MS-NCE2500-0 and MS-NCE2506-0 models, which are available in Europe only, do not
provide a physical field controller trunk connection.
All NCE models feature 33 integral I/O points and a Sensor/Actuator (SA) Bus, which allow you to
increase the NCE's I/O field point capacity and integrate NS Series Network Sensors, and VFDs into
your NCE application.
Some NCE models feature an integral field controller display screen with a navigation keypad,
allowing for easy modifications in the field.

Application documentation
Refer to the Network Engines Product Bulletin (LIT-12012138) for important product application
information.

Repair information
If the network engine fails to operate within its specifications, replace the unit. For a replacement
network engine, contact the nearest Johnson Controls® representative.

Features and benefits
  Use of commonly accepted IT standards at the automation and enterprise level
      Allows you to install the network engine on the existing IT infrastructure within a building
      or enterprise and use standard IT communication services over the company intranet, WAN,
      or public Internet with firewall protection. Communication between the network engine and
      clients is encrypted with Hypertext Transfer Protocol Secure (https).
  Web-based user interface
     Allows you to access, monitor, and control the network engine from a supported web
     browser connected to the network.
  Secure Linux® operating system
      Provides a high level of protection from threats with the adoption of the Linux operating
      system, a full replacement of the recently expired Windows® CE operating system.
  Supervision of controller networks including Johnson Controls and third-party protocol
  devices
      Supports connectivity to open network standards for complete flexibility in the selection of
      field devices. Supported protocols are model and software release dependent. They include
      BACnet MS/TP, BACnet/IP, N2 Bus, Modbus RTU, Modbus TCP, M-Bus (EN 13757-3), KNX IP,
      and other third-party protocols. Prior to Metasys system Release 9.0.7, only the Network



Network Control Engine Catalog Page                                                                     3
         Integration Engines (NIE29s) provided the Modbus, M-Bus, and KNX integrations. At Release
         9.0.7, these third-party integrations are included with all NCEs.
     Multiple connection options for data access
         Allow connection of a web browser through the IP network using the Ethernet port. At
         Release 9.0 or earlier, you can use the optional internal or external modem for a dial-up
         connection. Modem functions are not available for an NCE25 at Release 9.0.7.
     Integral field controller with 33 I/O points
         Provides field-level control of central plant and large air-handler applications combined with
         enterprise level IP network connectivity.
     Expandable I/O point capacity, NS sensor connectivity, and VFD control on field controller
     SA Bus
         Allow you to connect multiple IOMs, NS Series Network Sensors, and VFDs to the field
         controller SA Bus, which greatly expands the network engine's field level control capabilities.
     No hardware to replace
         Upgrade from Windows CE to Linux OS using a simple network download.

Point type counts
Table 1: Point type counts

Point type                       Signals accepted                                           Count
Universal input                  Analog Input, Voltage Mode, 0–10 VDC                       10
                                 Analog Input, Current Mode, 4–20 mA
                                 Analog Input, Resistive Mode, 0–2k ohm, RTD (1k
                                 [Johnson Controls], 1k PT, A99B SI), NTC (10k Type L,
                                 2.252k Type 2)
                                 Binary Input, Dry Contact Maintained Mode
Binary input                     Dry Contact Maintained Mode                                8
                                 Pulse Counter/ Accumulator Mode (High Speed),
                                 100Hz
Configurable output              Analog Output, Voltage Mode, 0–10 VDC                      4
                                 Binary Output Mode, 24 VAC Triac
Analog output                    Analog Output, Voltage Mode, 0–10 VDC                      4
                                 Analog Output, Current Mode 4–20 mA
Binary output                    24 VAC Triac                                               7


Ordering information
Contact the nearest Johnson Controls representative to order an NCE25 or accessories. Specify the
desired product code number using the following NCE ordering information tables.




 4                                                                      Network Control Engine Catalog Page
Table 2: NCE25 Ordering Information (Releases 9.0 and 9.0.7 Only)

Product code              Release     Description
number
MS-NCE25xx-x (Base        N/A         Each NCE25 Series model requires a 24 VAC power supply and
Features on Each                      includes one RS-232-C serial port, one RS-485 optically isolated
NCE25)                                SA Bus port, one USB serial port, one Ethernet port, and an MS-
                                      BAT1020-0 Data Protection Battery. Each NCE25 Series model
                                      has 33 integral I/O points and supports up to 128 additional I/O
                                      points on the SA Bus. Supports BACnet IP network.
MS-NCE2500-0              9.0.7       Base features with no physical field controller trunk connection.
(Europe only)
MS-NCE2506-0              9.0.7       Base features with no physical field controller trunk connection.
(Europe only)                         Includes integral display screen.
MS-NCE2510-0              9.0.7       Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                      KNX) and one N2 Bus. The number of supported devices on the
                                      third-party trunk depends on the protocol. For the N2 Bus, up to
                                      32 devices are supported.
MS-NCE2511-0              9.0.7       Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                      KNX) and one N2 Bus. The number of supported devices on the
                                      third-party trunk depends on the protocol. For the N2 Bus, up to
                                      32 devices are supported. Includes internal modem.
                                          Note: Modem functions are no longer available after this
                                          engine is updated with Metasys Release 9.0.7 or later.
MS-NCE2516-0              9.0.7       Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                      KNX) and one N2 Bus. The number of supported devices on the
                                      third-party trunk depends on the protocol. For the N2 Bus, up to
                                      32 devices are supported. Includes integral display screen.
MS-NCE2517-0              9.0.7       Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                      KNX) and one N2 Bus. The number of supported devices on the
                                      third-party trunk depends on the protocol. For the N2 Bus, up to
                                      32 devices are supported. Includes integral display screen and
                                      internal modem.
                                          Note: Modem functions are no longer available after this
                                          engine is updated with Metasys Release 9.0.7 or later.
MS-NCE2520-0              9.0         Supports one LonWorks trunk with up to 32 LonWorks devices.
MS-NCE2521-0              9.0         Supports one LonWorks trunk with up to 32 LonWorks devices.
                                      Includes internal modem.
MS-NCE2526-0              9.0         Supports one LonWorks trunk with up to 32 LonWorks devices.
                                      Includes integral display screen.
MS-NCE2527-0              9.0         Supports one LonWorks trunk with up to 32 LonWorks devices.
                                      Includes integral display screen and internal modem.
MS-NCE2560-0              9.0.7       Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                      KNX) and one MS/TP Bus. The number of supported devices on
                                      the third-party trunk depends on the protocol. For the MS/TP
                                      bus, up to 32 devices are supported.




Network Control Engine Catalog Page                                                                  5
Table 2: NCE25 Ordering Information (Releases 9.0 and 9.0.7 Only)

Product code          Release   Description
number
MS-NCE2561-0          9.0.7     Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                KNX) and one MS/TP Bus. The number of supported devices on
                                the third-party trunk depends on the protocol. For the MS/TP
                                bus, up to 32 devices are supported. Includes internal modem.
                                      Note: Modem functions are no longer available after this
                                      engine is updated with Metasys Release 9.0.7 or later.
MS-NCE2566-0          9.0.7     Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                KNX) and one MS/TP Bus. The number of supported devices on
                                the third-party trunk depends on the protocol. For the MS/TP
                                bus, up to 32 devices are supported. Includes integral display
                                screen.
MS-NCE2567-0          9.0.7     Supports two third-party trunks (Modbus RTU or TCP, M-Bus, or
                                KNX) and one MS/TP Bus. The number of supported devices on
                                the third-party trunk depends on the protocol. For the MS/TP
                                bus, up to 32 devices are supported. Includes integral display
                                screen and internal modem.
                                      Note: Modem functions are no longer available after this
                                      engine is updated with Metasys Release 9.0.7 or later.

Table 3: NCE25 accessories ordering information

Product Code Number      Description
MS-BAT1020-0             Replacement data protection battery for the NCE25. Rechargeable
                         NiMH battery: 3.6 V 500 mAh, with a typical life of 5 to 7 years at 21°C
                         (70°F)
TL-MAP1810-xx            Pocket-sized web server that provides a wireless mobile user interface
                         to Metasys field controllers, thermostats, and smart rooftop units. Refer
                         to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify
                         the appropriate product for your region.
MS-DIS1710-0             Local Controller Display connects to NCE on SA Bus and provides menu
                         display and navigation keypad for monitoring status and controlling
                         parameters on the NCE’s integral field controller.
                              Note: A DIS1710 display does not operate on NCE models that
                              have an integral controller display.
AS-XFR100-1              Power transformer (Class 2, 24 VAC, 92 VA maximum output), with
                         enclosure
AS-XFR010-1              Power transformer (Class 2, 24 VAC, 92 VA maximum output), no
                         enclosure
MS-EXPORT-0              Metasys Export Utility, which extracts historical trend, alarm, and audit
                         data from the system and presents the historical data in a variety of
                         formats.
                              Note: This option is not necessary for sites that have an ADS/
                              ADX as the Site Director because it is provided with the ADS/ADX
                              solution.



 6                                                                 Network Control Engine Catalog Page
Technical specifications
Table 4: NCE25

Power Requirement             Dedicated nominal 24 VAC, Class 2 power supply (North America),
                              SELV power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC
                              maximum)
Power Consumption             25 VA maximum for NCE25 only
                                      Note: The 25 VA rating does not include any power supplied
                                      by the NCE to devices connected at the NCE BOs. BO devices
                                      connected to and powered by an NCE can require an additional
                                      125 VA (maximum).
Power Source                  +15 VDC power source terminals provide 100 mA total current; quantity
                              of inputs: five, located in Universal IN terminals; for active (3-wire) input
                              devices
Ambient Operating             0°C to 50°C (32°F to 122°F), 10 to 90% RH, 30°C (86°F) maximum dew
Conditions                    point
Ambient Storage               -40°C to 70°C (-40°F to 158°F), 5% to 95% RH, 30°C (86°F) maximum dew
Conditions                    point
Data Protection Battery       Supports data protection on power failure. Rechargeable NiMH battery:
                              3.6 VDC 500 mAh, with a typical life of 5 to 7 years at 21°C (70°F);
                              Product Code Number: MS-BAT1020-0
Processors                    Supervisory Controller: 192 MHz Renesas SH4 7760 RISC processor
                              Field Controller: 20 MHz Renesas H8S2398 processor
Memory                        Supervisory Controller: 128 MB flash nonvolatile memory for
                              operating system, configuration data, and operations data storage and
                              backup and 128 MB SDRAM for operations data dynamic memory
                              Field Controller: 1 MB flash memory and 1 MB RAM
Operating System              Microsoft® Windows Embedded CE 6.0 (Release 9.0)
                              Buildroot 2017.08.2 with Linux kernel 14.4 (Release 9.0.7)




Network Control Engine Catalog Page                                                                      7
Table 4: NCE25

Network and Serial        • One Ethernet port; 10/100 Mbps; 8-pin RJ-45 connector
Interfaces                • One optically isolated RS-485 SA Bus port; with a pluggable and
(Depending on the NCE       keyed 4-position terminal block (on all NCE25 models)
model.)                   • One optically isolated RS-485 port; with a pluggable and keyed 4-
                            position terminal block (only on NCE25 models that support an N2
                            Bus or MS/TP bus trunk)
                          • One LonWorks port; FTT10 78 Kbps; pluggable, keyed 3-position
                            terminal block (only on NCE25 models that support a LonWorks
                            Network trunk). The LonWorks models are supported to run the
                            Metasys Release 9.0 software, but not the Release 9.0.7 update.
                          • One RS-232-C serial port with a standard 9-pin sub-D connector that
                            supports standard baud rates
                          • One USB serial port with a standard USB connector that supports
                            an optional, user-supplied external modem. Modem functions are
                            available with Metasys Release 9.0, but are not available after the
                            NCE is updated with Release 9.0.7.
                          • Option: One telephone port for the internal modem; up to 56 Kbps;
                            6-pin modular connector (NCE models with an optional internal
                            modem have one RS-232-C serial port only; not supported for an
                            engine with Release 9.0.7).
Analog Input/Analog       • Analog Input Points: 16-bit resolution
Output Point Resolution   • Analog Output Points: 16-bit resolution and ±200 mV accuracy on
                            0-10 VDC applications
Input/Output              • 10-Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or
Capabilities                Binary Dry Contact
                          • 8-Binary Inputs: Defined as Dry Contact Maintained or Pulse/
                            Accumulator Mode
                          • 4-Analog Outputs: Defined as 0–10 VDC or 4–20 mA
                          • 7-Binary Outputs: Defined as 24 VAC Triac (selectable internal or
                            external source power)
                          • 4-Configurable Outputs: Defined as 0–10 VDC or 24 VAC Triac BO
Dimensions               155 mm x 270 mm x 64 mm (6.1 in. x 10.6 in. x 2.5 in.), minimum
(Height x Width x Depth) mounting space required: 250 mm x 370 mm x 110 mm (9.8 in. x 14.6
                         in. x 4.3 in.)
Housing                   Plastic housing
                          Plastic material: ABS and polycarbonate
                          Protection: IP20 (IEC60529)
Mounting                  On a flat surface with screws, on three mounting clips, or a single 35
                          mm DIN rail
Shipping Weight           1.2 kg (2.7 lb)
Compliance                United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy
                          Management Equipment; FCC Compliant to CFR47, Part 15, Subpart B,
                          Class A
                          Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205,
                          Signal Equipment Industry Canada Compliant, ICES-003




 8                                                                  Network Control Engine Catalog Page
Table 4: NCE25

                              Europe: CE Mark - Johnson Controls declares that this product is
                              in compliance with the essential requirements and other relevant
                              provisions of the EMC Directive.
                              Australia and New Zealand: RCM Mark, Australia/NZ Emissions
                              Compliant
                              BACnet International: BTL 135-2010 Listed B-BC at Metasys system
                              Release 8.1


The performance specifications are nominal and conform to acceptable industry standard. For
application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson
Controls shall not be liable for damages resulting from misapplication or misuse of its products.


North American emissions compliance
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le
matériel brouilleur du Canada.

United States
This equipment has been tested and found to comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when this equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area may cause harmful
interference, in which case the users will be required to correct the interference at their own
expense.


Points of single contact
APAC                                            Europe                        NA/SA
JOHNSON CONTROLS                                JOHNSON CONTROLS              JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT                 WESTENDHOF 3                  507 E MICHIGAN ST
NO. 32 CHANGJIJANG RD NEW DISTRICT              45143 ESSEN                   MILWAUKEE WI 53202
WUXI JIANGSU PROVINCE 214028                    GERMANY                       USA
CHINA




Network Control Engine Catalog Page                                                                     9
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision and are subject to change without notice.
