Electric non-spring return damper actuators, M9108/M9116/M9124/M9132 Series

Файл за старою адресою не зберігся. Нижче — документ виробника на те саме обладнання.

Вид документаІнструкція
ВиробникJCI
МоделіM9108, M9116, M9124, M9132
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.6 МБ

Про документ

Electric non-spring return actuators for driving dampers and valves on 3/8 to 3/4 in. round or 3/8 to 5/8 in. square shafts. The series spans four torque sizes (70 to 280 lb∙in) with on/off, floating, proportional, or resistive input control depending on the model suffix. Tandem mounting doubles available torque for GGx/HGx (and AGx on larger models), except the M9108 which is not intended for tandem use.

Ключові дані

running torqueM9108: 70 lb∙in (8 N∙m); M9116: 140 lb∙in (16 N∙m); M9124: 210 lb∙in (24 N∙m); M9132: 280 lb∙in (32 N∙m)
power supply20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; Class 2
rotation range0 to 90° in 5-degree increments, mechanically limited to 93°
input signalAGx: 24 VAC/VDC; GGx, HGx: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA; JGx: potentiometer 100 to 10,000 ohms
enclosureNEMA 2, IP42
operating temperature-4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing
rotation timeM9108: 30 s at 50% rated load; M9116: 80 s; M9124: 130 s; M9132: 140 s at 50% rated load
dimensions7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm)

Застосування

  • Control of equipment under normal operating conditions (dampers, valves); indoor mounting only, no direct exposure to water beyond NEMA 2 conditions
  • Variable Air Volume applications (secure coupler to shaft with damper fully open for M9108)
  • Tandem operation for doubled torque with load split evenly between units

Особливості

  • Factory set 0 to 90° rotation; adjustable in 5-degree increments via coupler repositioning
  • Direct acting (factory set) or reverse acting operation (jumper W1 selectable on GGx/HGx/JGx; wiring reversal on AGx)
  • Two built-in SPDT auxiliary switches on xGC models, adjustable between 0 and 90° (factory set 10° and 80°)
  • Feedback signals: 0–135 Ω (AGD), 0–1000 Ω (AGE), 0–10 VDC / 2–10 VDC (GGx/HGx/JGx)
  • Adjustable zero and span potentiometers on HGx models (zero: 0 to 6 VDC / 12 VDC / 12 mA; span: 2 to 10 VDC / 4 to 20 VDC / 4 to 20 mA)
  • Master/subordinate jumper for tandem synchronization; total wire length up to 30 ft (9 m)
  • Pluggable 3-terminal blocks on M9124-/M9132-AGx models

Технічні дані

Parameter Value
Power requirements M9108-, M9116-AGx: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 6.5 VA supply, Class 2; all other models: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 7.5 VA supply, Class 2
Input signal AGx: 24 VAC at 50/60 Hz or 24 VDC; GGx, HGx: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA; JGx: potentiometer 100 ohms minimum to 10,000 ohms maximum
Input impedance GGx, HGx voltage input: 205,000 ohms (0 (2)-10 V), 410,000 ohms (0 (4)-20 V); current input: 500 ohms; JGx potentiometer input: 1.8 megohms
Feedback signal AGD: 135 ohm feedback potentiometer; AGE: 1,000 ohm feedback potentiometer; GGx, HGx: 0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA); JGx: 0 to 10 VDC for 90°
Auxiliary switch rating xGC: two SPDT switches rated 24 VAC 1.5 A inductive, 3.0 A resistive; 35.0 VA maximum per switch, Class 2
Mechanical output (running torque) M9108: 70 lb∙in (8 N∙m); M9116: 140 lb∙in (16 N∙m); M9124: 210 lb∙in (24 N∙m); M9132: 280 lb∙in (32 N∙m); tandem: M9116 280 lb∙in (32 N∙m), M9124 420 lb∙in (48 N∙m), M9132 560 lb∙in (64 N∙m)
Audible noise rating 45 dBA at 1 m
Rotation range 0 to 90° in 5-degree increments, mechanically limited to 93°
Rotation time M9108: 30 s at 50% rated load (25 to 50 s for 0 to 70 lb∙in); M9116: 80 s (70 to 115 s for 0 to 140 lb∙in); M9124: 130 s (115 to 175 s for 0 to 210 lb∙in); M9132: 140 s (115 to 205 s for 0 to 280 lb∙in)
Electrical connection M9124-, M9132-AGx: 1/4 in. spade terminals with pluggable 3-terminal blocks; all other models: screw terminals for 22 to 14 AWG; maximum of two 18, 20, or 22 AWG per terminal
Mechanical connection 3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or 3/8 to 5/8 in. (10 to 16 mm) square shaft
Conduit openings Threaded actuator conduit openings accept 1/2 in. trade size conduit fittings
Enclosure NEMA 2, IP42
Ambient conditions Operating: -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing; Storage: -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing
Dimensions (H x W x D) 7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm)
Shipping weight 2.9 lb (1.3 kg)
Mounting hardware U-bolt clamp nut torque: 100 to 125 lb∙in (11 to 14 N∙m); M9000-154 1 in. Jackshaft Coupler Kit for 1 in. (25.4 mm) OD shafts

Допуски та стандарти

  • UL Listed, File E27734, CCN XAPX
  • CSA Certified, File LR85083, Class 3221 02
  • CE Mark – EMC Directive compliance

Текст документа

                                                                          *34636399R*
                                                                                               34-636-399 Rev. R



                                                                              Installation Instructions               M91xx
                                                                                            Issue Date                May 2021


                         M9108, M9116, M9124, and M9132 Series
                          Electric Non-Spring Return Actuators

Installation                                                Special Tools Needed
                                                            •   torque wrench with 10 mm socket
 IMPORTANT:            Use this M9108, M9116,
 M9124, or M9132 Series Electric Non-Spring Return          •   digital voltmeter
 Actuator only to control equipment under normal
 operating conditions. Where failure or malfunction of      Mounting
 the actuator could lead to personal injury or damage
 to the controlled equipment or other property,              IMPORTANT:           The actuator is intended for
 additional precautions must be designed into the            indoor mounting only, with no direct exposure to
 control system. Incorporate and maintain other              water beyond NEMA 2 conditions. Use an
 devices, such as supervisory or alarm systems or            appropriate shield or enclosure where the
 safety or limit controls, intended to warn of or protect    environment exceeds NEMA 2 specifications.
 against failure or malfunction of the actuator.
 IMPORTANT:           Utiliser ce M9108, M9116,             Mount M91xx Series actuators in any convenient
 M9124, or M9132 Series Electric Non-Spring Return          orientation. Install the actuators on a 3/8 to 3/4 in.
 Actuator uniquement pour commander des                     (9.5 to 19 mm) round shaft or a 3/8 to 5/8 in.
 équipements dans des conditions normales de                (9.5 to 16 mm) square shaft, 2 in. (51 mm) or longer.
 fonctionnement. Lorsqu'une défaillance ou un               If the shaft is less than 2 in. (51 mm) long, install an
 dysfonctionnement du actuator risque de provoquer          extension recommended by the damper or valve
 des blessures ou d'endommager l'équipement                 manufacturer. Use the M9000-154 1 in. Jackshaft
 contrôlé ou un autre équipement, la conception du          Coupler Kit for 1 in. (25.4 mm) outside diameter shafts.
 système de contrôle doit intégrer des dispositifs de       To mount the actuator, proceed as follows:
 protection supplémentaires. Veiller dans ce cas à
 intégrer de façon permanente d'autres dispositifs,         1. Press and hold the gear release lever, and rotate
 tels que des systèmes de supervision ou d'alarme,             the coupler to the 0 or 90° position. Release the
 ou des dispositifs de sécurité ou de limitation, ayant        gear release lever. (See Figure 1.)
 une fonction d'avertissement ou de protection en cas
                                                                        U-bolt
 de défaillance ou de dysfonctionnement du actuator.                     with
                                                                       Clamp                                  Shaft Center
                                                                       Nuts (2)
Parts Included

All Models                                                                              90           0        Coupler
                                                                                             60 30
•   M91xx Series actuator
                                                                                                         90
                                                                                    0
                                                                                         30     60
                                                                                                                             A
•   M9000-160 anti-rotation bracket
                                                                                                                Gear
•   two No. 12-24 x 1/2 in. self-tapping hex                                                                    Release
    washer-head screws

M9124- and M9132-AGA Models                                                                                    Anti-Rotation
                                                                                                                 Bracket
Includes one M9000-105 pluggable 3-terminal block.
                                                                    Note: A is the distance from the center of the
M9124- and M9132-AGD and AGE Models                                 holes in the anti-rotation bracket to the center
                                                                    of the shaft. (See Table 1.)
Includes two M9000-105 pluggable 3-terminal blocks.

M9124- and M9132-AGC Models
Includes three M9000-105 pluggable 3-terminal                           Figure 1: Mounting Positions
blocks.
© 2021 Johnson Controls                                                                                                             1
  Part No. 34-636-399, Rev. R                                                                                  www.johnsoncontrols.com
Table 1: Shaft Sizes and Distances from the                        IMPORTANT:            For Variable Air Volume
Anti-Rotation Bracket to Shaft Center                              applications that use an M9108 Series actuator,
    Shaft Diameter         5/8 in.        1/2 in.      3/8 in.     secure the coupler to the shaft with the damper in
     A Dimensions          6-1/8 in.     6-3/16 in.   6-1/4 in.    the fully open position to avoid damaging the open
    (See Figure 1.)    (155 mm)        (157 mm)       (159 mm)     position end-stop.

                                                                  8. Hold the actuator in place, and evenly hand
2. Bend or cut the anti-rotation bracket to fit the                  tighten each clamp nut onto the U-bolt. Secure the
   damper frame or duct as shown in Figure 2.                        U-bolt to the damper shaft to achieve a torque of
                                                                     100 to 125 lb∙in (11 to 14 N∙m).
                           Cover Screw         Anti-Rotation
                                               Bracket Tab        9. Press and hold the gear release. Rotate the
                 Slot for Bracket
                                                                     coupler fully closed to fully open to verify that the
        No. 12-24 Sheet
        Metal Screws (2)
                                                                     damper and actuator rotate freely throughout the
                                                                     range.

                                                                  Rotation Range
                 Anti-Rotation Bracket                            The actuator is factory set for 0 to 90° rotation. To
                                                                  change the rotation range to less than 90°, use the
             Damper                                               top scale on the actuator cover, refer to Figure 3, and
             Frame
                                                                  proceed as follows:
                                                                  1. Press and hold the gear release, and rotate the
    Figure 2: Anti-Rotation Bracket Positions
                                                                     actuator coupler Counterclockwise (CCW) to the
3. Close the damper.                                                 0° position. Release the gear release.
4. Insert the anti-rotation bracket tab into the slot at                                   Coupler
   the bottom of the actuator (shown in Figure 2), and                                            Position
                                                                                                                        Back of the
   slide the actuator onto the shaft.                                                             Indicator
                                                                                                                         Actuator
                                                                               90
                                                                                                                Hub
                                                                                               0

 IMPORTANT:           The tab on the anti-rotation                         0
                                                                                     60
                                                                                    30
                                                                                          30
                                                                                          60
                                                                                                   90

 bracket must fit midpoint in the actuator slot to                                                      Gear               Locking
                                                                                     CCW                                     Clip
                                                                                                        Release
 prevent actuator binding and premature wear.
                                                                                                        Note: The locking clip is factory
5. Use the anti-rotation bracket as a guide, and drill                                                  set at the missing tooth of the
                                                                                                        actuator hub for 90° rotation.
   the holes in the damper frame or duct for the
   bracket (using dimension A shown in Figure 1 and                     Figure 3: M91xx Actuator Components
   the measurements in Table 1).
                                                                  2. Turn the actuator over. Use a flat-blade
Note:    When installing the actuator to a                           screwdriver to release the locking clip, and remove
Johnson Controls damper, use the existing holes in                   the coupler from the front of the actuator.
the damper frame.
                                                                  3. Reinsert the coupler into the front of the actuator,
6. Attach the anti-rotation bracket to the damper                    and align the position indicator with the starting
   frame or duct with the two self-tapping screws                    point of the desired rotation range.
   provided, using a 1/4 in. (7 mm) flat-blade
   screwdriver or 5/16 in. (8 mm) nut driver.                      IMPORTANT:            Advancing the coupler 90° from
                                                                   the factory setting prevents the actuator from driving
 IMPORTANT:           Do not overtighten the mounting              in either the Clockwise (CW) or CCW direction.
 screws to avoid stripping the threads.
                                                                  4. Push the coupler into the actuator until the
7. Slide the actuator onto the damper shaft,                         locking clip snaps over the hub, securing it in
   positioning the tab on the anti-rotation bracket                  place.
   midway into the slot at the bottom of the actuator.




2    M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
Note:       To change the rotation range on:
             •     -xGC models with auxiliary switches,                  !     CAUTION: Risk of Property Damage.
                   one or both of the switches may need               Do not apply power to the system before checking
                   adjustment. See the Auxiliary                      all wiring connections. Short circuited or improperly
                   Switches (xGC Models) section.                     connected wires may result in permanent damage to
                                                                      the equipment.
             •     -HGx models with zero and span
                   potentiometers, adjust both                        MISE EN GARDE : Risque de dégâts matériels.
                   potentiometers. See the                            Ne pas mettre le système sous tension avant d'avoir
                   Potentiometers (HGx Models) section.               vérifié tous les raccords de câblage. Des fils formant
                                                                      un court-circuit ou connectés de façon incorrecte
Feedback Signal                                                       risquent d'endommager irrémédiablement
For AGD and AGE models, resistance feedback is                        l'équipement.
reduced corresponding to the reduced rotation range.
For the GGx, HGx, and JGx models, changing the
rotation range changes the feedback signal and the                    IMPORTANT:          Make all wiring connections in
operating range proportionally. (See Figure 4.)                       accordance with local, national, or regional
                                                                      regulations.
                                Rotation Range
                       90°         Coupler Adjustment       0°
                             75°     60° 45° 30° 15°
                        0°   15° 30° 45° 60° 75° 90°
 Direct     0-10 V
                     10.0 V 8.3 V 6.7 V 5.0 V 3.3 V 1.7 V 0.0 V
 Acting    Feedback
  (DA)       2-10 V
                     10.0 V 8.7 V 7.3 V 6.0 V 4.7 V 3.3 V 2.0 V
           Feedback
 Reverse     0-10 V
                      0.0 V 1.7 V 3.3 V 5.0 V 6.7 V 8.3 V 10.0 V
  Acting Feedback
   (RA)      2-10 V
                      2.0 V 3.3 V 4.7 V 6.0 V 7.3 V 8.7 V 10.0 V
           Feedback
Direct or 0-135 ohms 135 Ω 113 Ω 90 Ω 68 Ω 45 Ω 23 Ω 0 Ω
 Reverse Feedback
  Acting 0-1000 ohms1000 Ω 833 Ω 667 Ω 500 Ω 333 Ω 167 Ω 0 Ω
           Feedback
Note: 0 to 10 V or 2 to 10 V feedback is available on all GGx, HGx,
and JGx models, 0 to 135 ohms feedback is available on AGD
models, and 0 to 1000 ohms feedback is available on AGE models.

Figure 4: Nominal Feedback Signal Relative to the
                Rotation Range

Wiring

    !   CAUTION: Risk of Electric Shock.
Disconnect the power supply before making
electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge
électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.




          M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions                 3
Refer to Figure 5 for the applicable M91xx actuator.                  Through the Conduit Openings
                            Terminal Block 1                          Depending on the M91xx Series model selected, use
               1    2   3                1  2 3                       one or both conduit openings. The threaded actuator
               ^-   ~
                    +
                        ~
                        +                ^- + ~
                                            ~  +                      conduit openings accept 1/2 in. trade size conduit
              COM CW CCW               COM CW CCW                     fittings. Refer to Figure 6 and proceed as follows:
                                                                      1. Loosen the cover screw with a Phillips No. 1
                   24 VAC                     24 VAC                     screwdriver, and remove the actuator cover.
                   24 VDC                     24 VDC                                            Cover
              On/Off Control     Floating Control                                               Screw
               Models AGA, AGC, AGD, and AGE
      1 2      3   4    5    6           1 2       3 4 5         6
     ^-   ~                              ^- + ~    ^-
          +    +    +   +    +                        + +        +
       24V                                 24V
                                                  CCW CW                                   Plugs
                                        COM                                                (Conduit Openings)
        0-20 mA
             0-20V                             100-10K ohms
                0-10V                             0-10V                  Figure 6: Location of the Conduit Openings
      Proportional Control              Resistive Input Control       2. Push the plastic plug out of the conduit opening
    Models: GGA, GGC, HGA,               Models: JGA and JGC
             and HGC
                                                                         with fingertip.
     1 = Common                        Note: Terminals 3 and 4
     2 = Power
                                                                      3. Use the Phillips screwdriver to puncture a hole
                                       function as CCW and CW
     3 = Calibration Out               references when the               through the center of the plug, and reinsert the
         (for HGA and HGC              Resistive models are in           plug into the conduit opening.
          models only)                 the DA mode but as CW
     4 = Current Input                 and CCW references             Note:     For applications requiring metal conduit,
     5 = Voltage Input                 when these models are          thread the conduit fitting into the conduit opening and
     6 = Feedback Output               in the RA mode.                hand tighten.
                            Terminal Block 2
                     Auxiliary Switches                                IMPORTANT:             Use flexible metallic tubing or its
         Switch Switch             Switch              Switch          equivalent with the fitting. Do not overtighten the
           S1    S2                  S1                 S2
       10°           80°            10°                         80°
                                                                       conduit fitting into the actuator to avoid damaging
       NC NO NO NC                                                     the actuator threads.

                                                                      4. Insert the cable wires through the plastic plug or
       21 22 23 24 25          C1 NC1 NO1 C2 NO2 NC2
                                                                         conduit fitting, and connect to the terminal block
      (Shown Factory Set)         (Shown Factory Set)
      Models: M9108- and          Models: M9124- and
                                                                         using the applicable wiring diagrams in Figure 5.
          M9116-AGC                  M9132-AGC
                                                                      5. Perform the procedures appropriate to the specific
                  Feedback Potentiometer
                 CW                          CW
                                                                         application, as described in the Tandem Operation
                                                                         and Setup and Adjustments sections.
          0%        100%                       0%      100%
                                                                      6. Reattach the cover and tighten the cover screw.

        11 12 13                        Wiper (W) CCW CW              Tandem Operation
    Models: M9108 and M9116           Models: M9124 and M9132
      AGD = 0 to 135 ohms               AGD = 0 to 135 ohms           The tandem configuration provides twice the torque of
      AGE = 0 to 1000 ohms             AGE = 0 to 1000 ohms           a single actuator as follows:
                                                                      •   280 lb∙in (32 N∙m) for two M9116-GGx or
    Figure 5: Wiring Diagrams for M91xx Models                            M9116-HGx units
                                                                      •   420 lb∙in (48 N∙m) for two M9124-GGx or
                                                                          M9124-HGx units
                                                                      •   560 lb∙in (64 N∙m) for two M9132-GGx or
                                                                          M9132-HGx units
                                                                      The actuators operate in exact synchronization,
                                                                      ensuring the load is split evenly between each unit.



4   M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
Models with the same torque and control input may be           • Terminal 102 from the master actuator to
mounted in tandem. For example:                                  Terminal 102 on the subordinate actuator.
•   M9116: two GGx, two HGx, or one GGx and                    • Terminal 103 from the master actuator to
    one HGx                                                      Terminal 103 on the subordinate actuator.
•   M9124: two AGx, two GGx, two HGx, or one GGx            b. When mounting two actuators back-to-back on
    and one HGx                                                the same shaft, connect:
•   M9132: two AGx or two GGx                                  • Terminal 101 from the master actuator to
                                                                 Terminal 102 on the subordinate actuator.
Note:   Do not use M9108 Series models in
tandem.                                                        • Terminal 102 from the master actuator to
                                                                 Terminal 101 on the subordinate actuator.
The Master/Subordinate Jumper is factory set in the
master position. Determine the method for mounting             • Terminal 103 from the master actuator to
the two actuators in tandem: front-to-back (Figure 7             Terminal 103 on the subordinate actuator.
shows the front view) or back-to-back, and proceed as
follows:                                                The total wire length for these connections may be up
                                                        to 30 ft (9 m).




         Figure 7: Settings on AGx Models
1. Designate one actuator as the master, and move
   Master/Subordinate Jumper on the other actuator
   to the subordinate position.
2. Connect Terminal 101, Terminal 102, and
   Terminal 103 from the master actuator to the
   corresponding terminals on the subordinate
   actuator. (Refer to Figure 7 for AGx models and
   Figure 8 for GGx and HGx models.)
    a. When mounting two actuators front-to-back on
       the same shaft, connect:
      • Terminal 101 from the master actuator to            Figure 8: Settings on GGx and HGx Models
        Terminal 101 on the subordinate actuator.



     M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions       5
3. Connect the input control signal:                      AGx Models
    • For AGx models, connect the input control           To set one of these models for RA operation, reverse
      signal to the common, CW, and CCW terminals         the control wiring connections at Terminal 2 and
      on both the master and the subordinate              Terminal 3. (See Terminal Block 1 in Figure 5.)
      actuators. (See Figure 7.)
                                                          GGx, HGx, and JGx Models
    • For GGx and HGx models, connect the                 To set one of these models for RA operation, proceed
      control signal to the master actuator, and          as follows:
      connect 24 VAC/VDC power to both the master
      and subordinate actuators.                          1. Press and hold the gear release, rotate the
                                                             actuator coupler until it is in the full CW position,
 IMPORTANT:          For proper tandem operation, do         and release the gear release.
 not connect the control input to the subordinate unit.   2. Move Jumper W1 from the factory-set DA position
                                                             to the RA position. (See Figure 8.)
Note:    Set the master actuator jumpers on the GGx
and HGx models according to the action and signal         3. Apply power and then a control signal to the
range desired before proceeding. (Refer to Figure 8          actuator to verify that the actuator is fully CW at
and the Setup and Adjustments, Calibration section.)         minimum control input, and fully CCW at maximum
                                                             control input.
4. Make sure of the following if the actuators
   configured for tandem operation stall or fail to       Note:    HGA and HGC models may require
   drive:                                                 potentiometer settings. Proceed to the Potentiometer
                                                          (HGx Models) section.
    a. Both actuators have the same torque and
       control input.                                     Jumpers
    b. One actuator is set as the master and the other    AGx models come factory set with the
       as the subordinate.                                Master/Subordinate Jumper in the master position and
    c. The control signal is connected to the master      have no additional jumpers. GGx, HGx, and JGx
       actuator only.                                     models come factory set with Jumper W1 in the DA
                                                          position. GGx and HGx models have additional
    d. Terminal 101, Terminal 102, and Terminal 103       jumpers factory set as follows: Jumper W2 is in the 0
       are connected properly, as described in Step 2.    to 10 VDC or 0 to 20 mA position, and Jumper W4 is in
                                                          the 0 to 10 VDC position. (See Figure 8.)
Setup and Adjustments                                     Note:    HGx models have an additional jumper,
Calibration                                               Jumper (W3), factory set in the fixed position. The
                                                          AGx models do not have jumpers.
Calibrate only the actuator designated as the master
when using two AGx, GGx, or HGx models in                 Potentiometers (HGx Models)
tandem.
                                                           IMPORTANT:           Adjust both zero and span
Direction of Action                                        potentiometers for full actuator travel and complete
In the DA mode (factory set), a minimum control signal     calibration.
drives the actuator to the full CCW position, and a
maximum control signal drives it fully CW. In the         The HGx models have zero and span potentiometers
Reverse Acting (RA) mode, a minimum control signal        that do not require adjustment when Jumper W3 is
drives the actuator to the full CW position, and a        factory set in the fixed position. When Jumper W3 is in
maximum control signal drives it fully CCW. To set an     the Adjustable (ADJ) position, without waiting for the
actuator for RA, proceed to the section for the           actuator to drive to the final position, proceed as
appropriate model.                                        follows:
                                                          Adjust the zero and span potentiometers using either
 IMPORTANT:           Adjust the rotation range before    Terminal 3 and Terminal 5 or Terminal 3 and
 changing the direction of action.                        Terminal 4, a control signal, and a voltmeter.




6   M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
Adjusting the Zero and Span                               Switch S1
To adjust the zero and span potentiometers on the         To change the angle of Switch S1 to 20°, refer to
HGx models:                                               Figure 9 and proceed as follows:
1. Verify that Jumper W2 is in the 0 to 10 VDC
   position, and provide 24 VAC or 24 VDC power to
                                                                     Position
   Terminal 1 (Common) and Terminal 2.                              Indicator
                                                                                                 Nodule Guides
                                                                                                 (10° Increments)
2. Connect the Common from the controller to                                    90°         0°
   Terminal 1, and either a voltage signal to                 Plunger                 CCW         Edge of
   Terminal 5 or a current signal to Terminal 4.                                                 Switch S1
                                                                                      CW
3. Connect Terminal 1 and Terminal 3 to a voltmeter                                              Gear Release
   to monitor the calibration output.
                                                                                                   Edge of
4. Use a 1/8 in. (3 mm) flat-blade screwdriver to turn                                            Switch S2
   the zero potentiometer fully CW and the span
   potentiometer fully CCW.                                         Figure 9: Switch Angle Settings
5. Apply the minimum (zero point) control signal          1. Depress the gear release, and using the 0 to 90°
   required for positioning the actuator at the              nodule guides, rotate the coupler until the position
   minimum position.                                         indicator is at 20°.
6. Monitor DC calibration output. To adjust the           2. Loosen the screw on Switch S1 with a
   zero potentiometer, turn it CCW until the voltmeter       Phillips No.1 screwdriver.
   displays 0 V or slightly less.                         3. Rotate Switch S1 CCW, and align the edge of the
7. Adjust the control signal to the maximum voltage          switch with the plunger until the plunger rises.
   desired to cause full rotation.                        Note:     The normally closed contact closes, and the
8. Monitor the calibration output at Terminal 1 and       normally open contact opens. (See Auxiliary Switches
   Terminal 3. Adjust the span potentiometer CW to        in Terminal Block 2 of Figure 5.)
   increase the calibration output to 10 V.               4. Retighten the Phillips-head screw on Switch S1,
9. Verify that the actuator is properly calibrated by        while holding it in the designated position.
   adjusting the control signal to the minimum and
   maximum levels.                                        Switch S2
Example for a zero of 3 VDC and a span of 5 VDC:          To change the angle of Switch S2 to 70°, refer to
                                                          Figure 9 and proceed as follows:
•   Apply a 3 volt control signal to the actuator, and
                                                          1. Depress the gear release, and using the 0 to 90°
    turn the zero potentiometer CCW until the
                                                             nodule guides, rotate the coupler until the position
    calibration output at Terminal 3 is 0 V.
                                                             indicator is at 70°.
•   Apply maximum voltage. (In this case, it is 8 VDC,
                                                          2. Loosen the screw on Switch S2 with a
    which results in a span of 5 volts.)
                                                             Phillips No. 1 screwdriver.
•   Monitor calibration output at Terminal 3, and
                                                          3. Rotate Switch S2 CW, and align the edge of the
    adjust the span potentiometer CW to 10 V.
                                                             switch with the plunger until the plunger rises.
Auxiliary Switches (xGC Models)                           Note:     The normally closed contact opens, and the
The M91xx-xGC models have two built-in                    normally open contact closes. (See Auxiliary Switches
auxiliary switches that allow setting at any angle        in Terminal Block 2 of Figure 5.)
between 0 and 90° (factory set for 10 and 80°,            4. Retighten the Phillips-head screw on Switch S2,
nominal). Refer to the Technical Specifications section      while holding it in the designated position.
for auxiliary switch ratings.
                                                          5. Depress the gear release, and rotate the coupler
The following procedures serve as examples to                until the position indicator is back to 0°.
change the position of the auxiliary switch angles:




      M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions          7
Repairs and Replacement
Do not field repair the M9100 Series actuators. To
order a replacement or an accessory, refer to the
Ordering Information section in the M9108, M9116,
M9124, and M9132 Series Electric Non-spring Return
Actuators Product Bulletin (LIT-2681058).

Technical Specifications
                    Product    M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators
        Power Requirements     M9108-, M9116-AGx: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 6.5 VA supply, Class 2
                               All Other Models:  20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 7.5 VA supply, Class 2
                Input Signal   AGx:                   24 VAC at 50/60 Hz or 24 VDC
                               GGx, HGx:              0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA
                               JGx:                   Potentiometer value is 100 ohms minimum to
                                                      10,000 ohms maximum
    Input Signal Adjustments   AGx:                   Factory Setting:     Terminals 1 and 2, CW rotation
                                                                           Terminals 1 and 3, CCW rotation
                               GGx, HGx (Voltage Input or Current Input):
                                                    Factory Setting:      0 to 10 VDC, 0 to 20 mA, CW rotation with
                                                                          signal increase
                                                    Jumper Selectable: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or
                                                                          0 (4) to 20 mA
                               HGx                  Adjustable Zero:      0 to 6 VDC, 0 to 12 VDC, or 0 to 12 mA
                                                    Adjustable Span:      2 to 10 VDC, 4 to 20 VDC, or 4 to 20 mA
                               GGx, HGx, JGx:       Action is jumper selectable Direct (CW) or Reverse (CCW) with
                                                    signal increase.
            Input Impedance    GGx, HGx:              Voltage Input:       205,000 ohms for 0 (2) to 10 V and
                                                                           410,000 ohms for 0 (4) to 20 V
                                                      Current Input:       500 ohms
                               JGx:                   Potentiometer Input: 1.8 megohms
            Feedback Signal    AGD:                 135 ohm feedback potentiometer
                               AGE:                 1,000 ohm feedback potentiometer
                               GGx, HGx:            0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA)
                                                    Corresponds to input signal span selection.
                               JGx:                 0 to 10 VDC for 90° (10 VDC at 1 mA)
     Auxiliary Switch Rating   xGC:                 Two Single-Pole, Double-Throw (SPDT) switches rated at 24 VAC
                                                    1.5 A inductive, 3.0 A resistive; 35.0 VA maximum per switch, Class 2
          Mechanical Output    M9108 Series:        70 lb∙in (8 N∙m) for one unit; not intended for tandem use
           (Running Torque)    M9116 Series:        140 lb∙in (16 N∙m) for one unit
                               M9116 (in tandem)    280 lb∙in (32 N∙m) for two units (GGx, HGx)
                               M9124 Series:        210 lb∙in (24 N∙m) for one unit
                               M9124 (in tandem)    420 lb∙in (48 N∙m) for two units (AGx, GGx, HGx)
                               M9132 Series:        280 lb∙in (32 N∙m) for one unit,
                               M9132 (in tandem)    560 lb∙in (64 N∙m) for two units (AGx, GGx)
       Audible Noise Rating    45 dBA at 1 m
             Rotation Range    0 to 90° in 5-degree increments, mechanically limited to 93°
              Rotation Time    M9108:               30 seconds at 50% rated load,
                                                    25 to 50 seconds for 0 to 70 lb∙in (0 to 8 N∙m)
                               M9116:               80 seconds at 50% rated load
                                                    70 to 115 seconds for 0 to 140 lb∙in (0 to 16 N∙m)
                               M9124:               130 seconds at 50% rated load
                                                    115 to 175 seconds for 0 to 210 lb∙in (0 to 24 N∙m)
                               M9132:               140 seconds at 50% rated load
                                                    115 to 205 seconds for 0 to 280 lb∙in (0 to 32 N∙m)
 Continued on next page. . .



8   M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
 Technical Specifications (Cont.)
        Electrical Connection        M9124-, M9132-AGx:
                                                              1/4 in. spade terminals with pluggable 3-terminal blocks
                                     All Other Models:        Screw terminals for 22 to 14 AWG; maximum of two 18, 20, or
                                                              22 AWG per terminal
     Mechanical Connection           3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or a 3/8 to 5/8 in. (10 to 16 mm) square shaft
                      Enclosure      NEMA 2, IP42
          Ambient Conditions         Operating:               -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing
                                     Storage:                 -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing
     Dimensions (H x W x D)          7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm)
              Shipping Weight        2.9 lb (1.3 kg)
         Agency Compliance           UL Listed, File E27734, CCN XAPX
                                     CSA Certified, File LR85083, Class 3221 02
                                     CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the
                                     essential requirements and other relevant provisions of the EMC Directive.

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.




European Single Point of Contact:               NA/SA Single Point of Contact:                   APAC Single Point of Contact:
JOHNSON CONTROLS                                JOHNSON CONTROLS                                 JOHNSON CONTROLS
WESTENDHOF 3                                    507 E MICHIGAN ST                                C/O CONTROLS PRODUCT
45143 ESSEN                                     MILWAUKEE WI 53202                               MANAGEMENT
GERMANY                                         USA                                              NO. 22 BLOCK D NEW DISTRICT
                                                                                                 WUXI JIANGSU PROVINCE 214142
                                                                                                 CHINA




                                                   Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
                                          All other marks herein are the marks of their respective owners. © 2021 Johnson Controls.


       M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions                                    9
