| Вид документа | Інструкція |
|---|---|
| Виробник | JCI |
| Моделі | M9108, M9116, M9124, M9132 |
| Група обладнання | automation |
| Мова документа | англійська |
| Розмір файлу | 0.6 МБ |
Про документ
Electric non-spring return actuators for driving dampers and valves on 3/8 to 3/4 in. round or 3/8 to 5/8 in. square shafts. The series spans four torque sizes (70 to 280 lb∙in) with on/off, floating, proportional, or resistive input control depending on the model suffix. Tandem mounting doubles available torque for GGx/HGx (and AGx on larger models), except the M9108 which is not intended for tandem use.
Ключові дані
| running torque | M9108: 70 lb∙in (8 N∙m); M9116: 140 lb∙in (16 N∙m); M9124: 210 lb∙in (24 N∙m); M9132: 280 lb∙in (32 N∙m) |
|---|---|
| power supply | 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; Class 2 |
| rotation range | 0 to 90° in 5-degree increments, mechanically limited to 93° |
| input signal | AGx: 24 VAC/VDC; GGx, HGx: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA; JGx: potentiometer 100 to 10,000 ohms |
| enclosure | NEMA 2, IP42 |
| operating temperature | -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing |
| rotation time | M9108: 30 s at 50% rated load; M9116: 80 s; M9124: 130 s; M9132: 140 s at 50% rated load |
| dimensions | 7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm) |
Застосування
- Control of equipment under normal operating conditions (dampers, valves); indoor mounting only, no direct exposure to water beyond NEMA 2 conditions
- Variable Air Volume applications (secure coupler to shaft with damper fully open for M9108)
- Tandem operation for doubled torque with load split evenly between units
Особливості
- Factory set 0 to 90° rotation; adjustable in 5-degree increments via coupler repositioning
- Direct acting (factory set) or reverse acting operation (jumper W1 selectable on GGx/HGx/JGx; wiring reversal on AGx)
- Two built-in SPDT auxiliary switches on xGC models, adjustable between 0 and 90° (factory set 10° and 80°)
- Feedback signals: 0–135 Ω (AGD), 0–1000 Ω (AGE), 0–10 VDC / 2–10 VDC (GGx/HGx/JGx)
- Adjustable zero and span potentiometers on HGx models (zero: 0 to 6 VDC / 12 VDC / 12 mA; span: 2 to 10 VDC / 4 to 20 VDC / 4 to 20 mA)
- Master/subordinate jumper for tandem synchronization; total wire length up to 30 ft (9 m)
- Pluggable 3-terminal blocks on M9124-/M9132-AGx models
Технічні дані
| Parameter | Value |
|---|---|
| Power requirements | M9108-, M9116-AGx: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 6.5 VA supply, Class 2; all other models: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 7.5 VA supply, Class 2 |
| Input signal | AGx: 24 VAC at 50/60 Hz or 24 VDC; GGx, HGx: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA; JGx: potentiometer 100 ohms minimum to 10,000 ohms maximum |
| Input impedance | GGx, HGx voltage input: 205,000 ohms (0 (2)-10 V), 410,000 ohms (0 (4)-20 V); current input: 500 ohms; JGx potentiometer input: 1.8 megohms |
| Feedback signal | AGD: 135 ohm feedback potentiometer; AGE: 1,000 ohm feedback potentiometer; GGx, HGx: 0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA); JGx: 0 to 10 VDC for 90° |
| Auxiliary switch rating | xGC: two SPDT switches rated 24 VAC 1.5 A inductive, 3.0 A resistive; 35.0 VA maximum per switch, Class 2 |
| Mechanical output (running torque) | M9108: 70 lb∙in (8 N∙m); M9116: 140 lb∙in (16 N∙m); M9124: 210 lb∙in (24 N∙m); M9132: 280 lb∙in (32 N∙m); tandem: M9116 280 lb∙in (32 N∙m), M9124 420 lb∙in (48 N∙m), M9132 560 lb∙in (64 N∙m) |
| Audible noise rating | 45 dBA at 1 m |
| Rotation range | 0 to 90° in 5-degree increments, mechanically limited to 93° |
| Rotation time | M9108: 30 s at 50% rated load (25 to 50 s for 0 to 70 lb∙in); M9116: 80 s (70 to 115 s for 0 to 140 lb∙in); M9124: 130 s (115 to 175 s for 0 to 210 lb∙in); M9132: 140 s (115 to 205 s for 0 to 280 lb∙in) |
| Electrical connection | M9124-, M9132-AGx: 1/4 in. spade terminals with pluggable 3-terminal blocks; all other models: screw terminals for 22 to 14 AWG; maximum of two 18, 20, or 22 AWG per terminal |
| Mechanical connection | 3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or 3/8 to 5/8 in. (10 to 16 mm) square shaft |
| Conduit openings | Threaded actuator conduit openings accept 1/2 in. trade size conduit fittings |
| Enclosure | NEMA 2, IP42 |
| Ambient conditions | Operating: -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing; Storage: -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing |
| Dimensions (H x W x D) | 7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm) |
| Shipping weight | 2.9 lb (1.3 kg) |
| Mounting hardware | U-bolt clamp nut torque: 100 to 125 lb∙in (11 to 14 N∙m); M9000-154 1 in. Jackshaft Coupler Kit for 1 in. (25.4 mm) OD shafts |
Допуски та стандарти
- UL Listed, File E27734, CCN XAPX
- CSA Certified, File LR85083, Class 3221 02
- CE Mark – EMC Directive compliance
Текст документа
*34636399R*
34-636-399 Rev. R
Installation Instructions M91xx
Issue Date May 2021
M9108, M9116, M9124, and M9132 Series
Electric Non-Spring Return Actuators
Installation Special Tools Needed
• torque wrench with 10 mm socket
IMPORTANT: Use this M9108, M9116,
M9124, or M9132 Series Electric Non-Spring Return • digital voltmeter
Actuator only to control equipment under normal
operating conditions. Where failure or malfunction of Mounting
the actuator could lead to personal injury or damage
to the controlled equipment or other property, IMPORTANT: The actuator is intended for
additional precautions must be designed into the indoor mounting only, with no direct exposure to
control system. Incorporate and maintain other water beyond NEMA 2 conditions. Use an
devices, such as supervisory or alarm systems or appropriate shield or enclosure where the
safety or limit controls, intended to warn of or protect environment exceeds NEMA 2 specifications.
against failure or malfunction of the actuator.
IMPORTANT: Utiliser ce M9108, M9116, Mount M91xx Series actuators in any convenient
M9124, or M9132 Series Electric Non-Spring Return orientation. Install the actuators on a 3/8 to 3/4 in.
Actuator uniquement pour commander des (9.5 to 19 mm) round shaft or a 3/8 to 5/8 in.
équipements dans des conditions normales de (9.5 to 16 mm) square shaft, 2 in. (51 mm) or longer.
fonctionnement. Lorsqu'une défaillance ou un If the shaft is less than 2 in. (51 mm) long, install an
dysfonctionnement du actuator risque de provoquer extension recommended by the damper or valve
des blessures ou d'endommager l'équipement manufacturer. Use the M9000-154 1 in. Jackshaft
contrôlé ou un autre équipement, la conception du Coupler Kit for 1 in. (25.4 mm) outside diameter shafts.
système de contrôle doit intégrer des dispositifs de To mount the actuator, proceed as follows:
protection supplémentaires. Veiller dans ce cas à
intégrer de façon permanente d'autres dispositifs, 1. Press and hold the gear release lever, and rotate
tels que des systèmes de supervision ou d'alarme, the coupler to the 0 or 90° position. Release the
ou des dispositifs de sécurité ou de limitation, ayant gear release lever. (See Figure 1.)
une fonction d'avertissement ou de protection en cas
U-bolt
de défaillance ou de dysfonctionnement du actuator. with
Clamp Shaft Center
Nuts (2)
Parts Included
All Models 90 0 Coupler
60 30
• M91xx Series actuator
90
0
30 60
A
• M9000-160 anti-rotation bracket
Gear
• two No. 12-24 x 1/2 in. self-tapping hex Release
washer-head screws
M9124- and M9132-AGA Models Anti-Rotation
Bracket
Includes one M9000-105 pluggable 3-terminal block.
Note: A is the distance from the center of the
M9124- and M9132-AGD and AGE Models holes in the anti-rotation bracket to the center
of the shaft. (See Table 1.)
Includes two M9000-105 pluggable 3-terminal blocks.
M9124- and M9132-AGC Models
Includes three M9000-105 pluggable 3-terminal Figure 1: Mounting Positions
blocks.
© 2021 Johnson Controls 1
Part No. 34-636-399, Rev. R www.johnsoncontrols.com
Table 1: Shaft Sizes and Distances from the IMPORTANT: For Variable Air Volume
Anti-Rotation Bracket to Shaft Center applications that use an M9108 Series actuator,
Shaft Diameter 5/8 in. 1/2 in. 3/8 in. secure the coupler to the shaft with the damper in
A Dimensions 6-1/8 in. 6-3/16 in. 6-1/4 in. the fully open position to avoid damaging the open
(See Figure 1.) (155 mm) (157 mm) (159 mm) position end-stop.
8. Hold the actuator in place, and evenly hand
2. Bend or cut the anti-rotation bracket to fit the tighten each clamp nut onto the U-bolt. Secure the
damper frame or duct as shown in Figure 2. U-bolt to the damper shaft to achieve a torque of
100 to 125 lb∙in (11 to 14 N∙m).
Cover Screw Anti-Rotation
Bracket Tab 9. Press and hold the gear release. Rotate the
Slot for Bracket
coupler fully closed to fully open to verify that the
No. 12-24 Sheet
Metal Screws (2)
damper and actuator rotate freely throughout the
range.
Rotation Range
Anti-Rotation Bracket The actuator is factory set for 0 to 90° rotation. To
change the rotation range to less than 90°, use the
Damper top scale on the actuator cover, refer to Figure 3, and
Frame
proceed as follows:
1. Press and hold the gear release, and rotate the
Figure 2: Anti-Rotation Bracket Positions
actuator coupler Counterclockwise (CCW) to the
3. Close the damper. 0° position. Release the gear release.
4. Insert the anti-rotation bracket tab into the slot at Coupler
the bottom of the actuator (shown in Figure 2), and Position
Back of the
slide the actuator onto the shaft. Indicator
Actuator
90
Hub
0
IMPORTANT: The tab on the anti-rotation 0
60
30
30
60
90
bracket must fit midpoint in the actuator slot to Gear Locking
CCW Clip
Release
prevent actuator binding and premature wear.
Note: The locking clip is factory
5. Use the anti-rotation bracket as a guide, and drill set at the missing tooth of the
actuator hub for 90° rotation.
the holes in the damper frame or duct for the
bracket (using dimension A shown in Figure 1 and Figure 3: M91xx Actuator Components
the measurements in Table 1).
2. Turn the actuator over. Use a flat-blade
Note: When installing the actuator to a screwdriver to release the locking clip, and remove
Johnson Controls damper, use the existing holes in the coupler from the front of the actuator.
the damper frame.
3. Reinsert the coupler into the front of the actuator,
6. Attach the anti-rotation bracket to the damper and align the position indicator with the starting
frame or duct with the two self-tapping screws point of the desired rotation range.
provided, using a 1/4 in. (7 mm) flat-blade
screwdriver or 5/16 in. (8 mm) nut driver. IMPORTANT: Advancing the coupler 90° from
the factory setting prevents the actuator from driving
IMPORTANT: Do not overtighten the mounting in either the Clockwise (CW) or CCW direction.
screws to avoid stripping the threads.
4. Push the coupler into the actuator until the
7. Slide the actuator onto the damper shaft, locking clip snaps over the hub, securing it in
positioning the tab on the anti-rotation bracket place.
midway into the slot at the bottom of the actuator.
2 M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
Note: To change the rotation range on:
• -xGC models with auxiliary switches, ! CAUTION: Risk of Property Damage.
one or both of the switches may need Do not apply power to the system before checking
adjustment. See the Auxiliary all wiring connections. Short circuited or improperly
Switches (xGC Models) section. connected wires may result in permanent damage to
the equipment.
• -HGx models with zero and span
potentiometers, adjust both MISE EN GARDE : Risque de dégâts matériels.
potentiometers. See the Ne pas mettre le système sous tension avant d'avoir
Potentiometers (HGx Models) section. vérifié tous les raccords de câblage. Des fils formant
un court-circuit ou connectés de façon incorrecte
Feedback Signal risquent d'endommager irrémédiablement
For AGD and AGE models, resistance feedback is l'équipement.
reduced corresponding to the reduced rotation range.
For the GGx, HGx, and JGx models, changing the
rotation range changes the feedback signal and the IMPORTANT: Make all wiring connections in
operating range proportionally. (See Figure 4.) accordance with local, national, or regional
regulations.
Rotation Range
90° Coupler Adjustment 0°
75° 60° 45° 30° 15°
0° 15° 30° 45° 60° 75° 90°
Direct 0-10 V
10.0 V 8.3 V 6.7 V 5.0 V 3.3 V 1.7 V 0.0 V
Acting Feedback
(DA) 2-10 V
10.0 V 8.7 V 7.3 V 6.0 V 4.7 V 3.3 V 2.0 V
Feedback
Reverse 0-10 V
0.0 V 1.7 V 3.3 V 5.0 V 6.7 V 8.3 V 10.0 V
Acting Feedback
(RA) 2-10 V
2.0 V 3.3 V 4.7 V 6.0 V 7.3 V 8.7 V 10.0 V
Feedback
Direct or 0-135 ohms 135 Ω 113 Ω 90 Ω 68 Ω 45 Ω 23 Ω 0 Ω
Reverse Feedback
Acting 0-1000 ohms1000 Ω 833 Ω 667 Ω 500 Ω 333 Ω 167 Ω 0 Ω
Feedback
Note: 0 to 10 V or 2 to 10 V feedback is available on all GGx, HGx,
and JGx models, 0 to 135 ohms feedback is available on AGD
models, and 0 to 1000 ohms feedback is available on AGE models.
Figure 4: Nominal Feedback Signal Relative to the
Rotation Range
Wiring
! CAUTION: Risk of Electric Shock.
Disconnect the power supply before making
electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge
électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 3
Refer to Figure 5 for the applicable M91xx actuator. Through the Conduit Openings
Terminal Block 1 Depending on the M91xx Series model selected, use
1 2 3 1 2 3 one or both conduit openings. The threaded actuator
^- ~
+
~
+ ^- + ~
~ + conduit openings accept 1/2 in. trade size conduit
COM CW CCW COM CW CCW fittings. Refer to Figure 6 and proceed as follows:
1. Loosen the cover screw with a Phillips No. 1
24 VAC 24 VAC screwdriver, and remove the actuator cover.
24 VDC 24 VDC Cover
On/Off Control Floating Control Screw
Models AGA, AGC, AGD, and AGE
1 2 3 4 5 6 1 2 3 4 5 6
^- ~ ^- + ~ ^-
+ + + + + + + +
24V 24V
CCW CW Plugs
COM (Conduit Openings)
0-20 mA
0-20V 100-10K ohms
0-10V 0-10V Figure 6: Location of the Conduit Openings
Proportional Control Resistive Input Control 2. Push the plastic plug out of the conduit opening
Models: GGA, GGC, HGA, Models: JGA and JGC
and HGC
with fingertip.
1 = Common Note: Terminals 3 and 4
2 = Power
3. Use the Phillips screwdriver to puncture a hole
function as CCW and CW
3 = Calibration Out references when the through the center of the plug, and reinsert the
(for HGA and HGC Resistive models are in plug into the conduit opening.
models only) the DA mode but as CW
4 = Current Input and CCW references Note: For applications requiring metal conduit,
5 = Voltage Input when these models are thread the conduit fitting into the conduit opening and
6 = Feedback Output in the RA mode. hand tighten.
Terminal Block 2
Auxiliary Switches IMPORTANT: Use flexible metallic tubing or its
Switch Switch Switch Switch equivalent with the fitting. Do not overtighten the
S1 S2 S1 S2
10° 80° 10° 80°
conduit fitting into the actuator to avoid damaging
NC NO NO NC the actuator threads.
4. Insert the cable wires through the plastic plug or
21 22 23 24 25 C1 NC1 NO1 C2 NO2 NC2
conduit fitting, and connect to the terminal block
(Shown Factory Set) (Shown Factory Set)
Models: M9108- and Models: M9124- and
using the applicable wiring diagrams in Figure 5.
M9116-AGC M9132-AGC
5. Perform the procedures appropriate to the specific
Feedback Potentiometer
CW CW
application, as described in the Tandem Operation
and Setup and Adjustments sections.
0% 100% 0% 100%
6. Reattach the cover and tighten the cover screw.
11 12 13 Wiper (W) CCW CW Tandem Operation
Models: M9108 and M9116 Models: M9124 and M9132
AGD = 0 to 135 ohms AGD = 0 to 135 ohms The tandem configuration provides twice the torque of
AGE = 0 to 1000 ohms AGE = 0 to 1000 ohms a single actuator as follows:
• 280 lb∙in (32 N∙m) for two M9116-GGx or
Figure 5: Wiring Diagrams for M91xx Models M9116-HGx units
• 420 lb∙in (48 N∙m) for two M9124-GGx or
M9124-HGx units
• 560 lb∙in (64 N∙m) for two M9132-GGx or
M9132-HGx units
The actuators operate in exact synchronization,
ensuring the load is split evenly between each unit.
4 M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
Models with the same torque and control input may be • Terminal 102 from the master actuator to
mounted in tandem. For example: Terminal 102 on the subordinate actuator.
• M9116: two GGx, two HGx, or one GGx and • Terminal 103 from the master actuator to
one HGx Terminal 103 on the subordinate actuator.
• M9124: two AGx, two GGx, two HGx, or one GGx b. When mounting two actuators back-to-back on
and one HGx the same shaft, connect:
• M9132: two AGx or two GGx • Terminal 101 from the master actuator to
Terminal 102 on the subordinate actuator.
Note: Do not use M9108 Series models in
tandem. • Terminal 102 from the master actuator to
Terminal 101 on the subordinate actuator.
The Master/Subordinate Jumper is factory set in the
master position. Determine the method for mounting • Terminal 103 from the master actuator to
the two actuators in tandem: front-to-back (Figure 7 Terminal 103 on the subordinate actuator.
shows the front view) or back-to-back, and proceed as
follows: The total wire length for these connections may be up
to 30 ft (9 m).
Figure 7: Settings on AGx Models
1. Designate one actuator as the master, and move
Master/Subordinate Jumper on the other actuator
to the subordinate position.
2. Connect Terminal 101, Terminal 102, and
Terminal 103 from the master actuator to the
corresponding terminals on the subordinate
actuator. (Refer to Figure 7 for AGx models and
Figure 8 for GGx and HGx models.)
a. When mounting two actuators front-to-back on
the same shaft, connect:
• Terminal 101 from the master actuator to Figure 8: Settings on GGx and HGx Models
Terminal 101 on the subordinate actuator.
M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 5
3. Connect the input control signal: AGx Models
• For AGx models, connect the input control To set one of these models for RA operation, reverse
signal to the common, CW, and CCW terminals the control wiring connections at Terminal 2 and
on both the master and the subordinate Terminal 3. (See Terminal Block 1 in Figure 5.)
actuators. (See Figure 7.)
GGx, HGx, and JGx Models
• For GGx and HGx models, connect the To set one of these models for RA operation, proceed
control signal to the master actuator, and as follows:
connect 24 VAC/VDC power to both the master
and subordinate actuators. 1. Press and hold the gear release, rotate the
actuator coupler until it is in the full CW position,
IMPORTANT: For proper tandem operation, do and release the gear release.
not connect the control input to the subordinate unit. 2. Move Jumper W1 from the factory-set DA position
to the RA position. (See Figure 8.)
Note: Set the master actuator jumpers on the GGx
and HGx models according to the action and signal 3. Apply power and then a control signal to the
range desired before proceeding. (Refer to Figure 8 actuator to verify that the actuator is fully CW at
and the Setup and Adjustments, Calibration section.) minimum control input, and fully CCW at maximum
control input.
4. Make sure of the following if the actuators
configured for tandem operation stall or fail to Note: HGA and HGC models may require
drive: potentiometer settings. Proceed to the Potentiometer
(HGx Models) section.
a. Both actuators have the same torque and
control input. Jumpers
b. One actuator is set as the master and the other AGx models come factory set with the
as the subordinate. Master/Subordinate Jumper in the master position and
c. The control signal is connected to the master have no additional jumpers. GGx, HGx, and JGx
actuator only. models come factory set with Jumper W1 in the DA
position. GGx and HGx models have additional
d. Terminal 101, Terminal 102, and Terminal 103 jumpers factory set as follows: Jumper W2 is in the 0
are connected properly, as described in Step 2. to 10 VDC or 0 to 20 mA position, and Jumper W4 is in
the 0 to 10 VDC position. (See Figure 8.)
Setup and Adjustments Note: HGx models have an additional jumper,
Calibration Jumper (W3), factory set in the fixed position. The
AGx models do not have jumpers.
Calibrate only the actuator designated as the master
when using two AGx, GGx, or HGx models in Potentiometers (HGx Models)
tandem.
IMPORTANT: Adjust both zero and span
Direction of Action potentiometers for full actuator travel and complete
In the DA mode (factory set), a minimum control signal calibration.
drives the actuator to the full CCW position, and a
maximum control signal drives it fully CW. In the The HGx models have zero and span potentiometers
Reverse Acting (RA) mode, a minimum control signal that do not require adjustment when Jumper W3 is
drives the actuator to the full CW position, and a factory set in the fixed position. When Jumper W3 is in
maximum control signal drives it fully CCW. To set an the Adjustable (ADJ) position, without waiting for the
actuator for RA, proceed to the section for the actuator to drive to the final position, proceed as
appropriate model. follows:
Adjust the zero and span potentiometers using either
IMPORTANT: Adjust the rotation range before Terminal 3 and Terminal 5 or Terminal 3 and
changing the direction of action. Terminal 4, a control signal, and a voltmeter.
6 M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
Adjusting the Zero and Span Switch S1
To adjust the zero and span potentiometers on the To change the angle of Switch S1 to 20°, refer to
HGx models: Figure 9 and proceed as follows:
1. Verify that Jumper W2 is in the 0 to 10 VDC
position, and provide 24 VAC or 24 VDC power to
Position
Terminal 1 (Common) and Terminal 2. Indicator
Nodule Guides
(10° Increments)
2. Connect the Common from the controller to 90° 0°
Terminal 1, and either a voltage signal to Plunger CCW Edge of
Terminal 5 or a current signal to Terminal 4. Switch S1
CW
3. Connect Terminal 1 and Terminal 3 to a voltmeter Gear Release
to monitor the calibration output.
Edge of
4. Use a 1/8 in. (3 mm) flat-blade screwdriver to turn Switch S2
the zero potentiometer fully CW and the span
potentiometer fully CCW. Figure 9: Switch Angle Settings
5. Apply the minimum (zero point) control signal 1. Depress the gear release, and using the 0 to 90°
required for positioning the actuator at the nodule guides, rotate the coupler until the position
minimum position. indicator is at 20°.
6. Monitor DC calibration output. To adjust the 2. Loosen the screw on Switch S1 with a
zero potentiometer, turn it CCW until the voltmeter Phillips No.1 screwdriver.
displays 0 V or slightly less. 3. Rotate Switch S1 CCW, and align the edge of the
7. Adjust the control signal to the maximum voltage switch with the plunger until the plunger rises.
desired to cause full rotation. Note: The normally closed contact closes, and the
8. Monitor the calibration output at Terminal 1 and normally open contact opens. (See Auxiliary Switches
Terminal 3. Adjust the span potentiometer CW to in Terminal Block 2 of Figure 5.)
increase the calibration output to 10 V. 4. Retighten the Phillips-head screw on Switch S1,
9. Verify that the actuator is properly calibrated by while holding it in the designated position.
adjusting the control signal to the minimum and
maximum levels. Switch S2
Example for a zero of 3 VDC and a span of 5 VDC: To change the angle of Switch S2 to 70°, refer to
Figure 9 and proceed as follows:
• Apply a 3 volt control signal to the actuator, and
1. Depress the gear release, and using the 0 to 90°
turn the zero potentiometer CCW until the
nodule guides, rotate the coupler until the position
calibration output at Terminal 3 is 0 V.
indicator is at 70°.
• Apply maximum voltage. (In this case, it is 8 VDC,
2. Loosen the screw on Switch S2 with a
which results in a span of 5 volts.)
Phillips No. 1 screwdriver.
• Monitor calibration output at Terminal 3, and
3. Rotate Switch S2 CW, and align the edge of the
adjust the span potentiometer CW to 10 V.
switch with the plunger until the plunger rises.
Auxiliary Switches (xGC Models) Note: The normally closed contact opens, and the
The M91xx-xGC models have two built-in normally open contact closes. (See Auxiliary Switches
auxiliary switches that allow setting at any angle in Terminal Block 2 of Figure 5.)
between 0 and 90° (factory set for 10 and 80°, 4. Retighten the Phillips-head screw on Switch S2,
nominal). Refer to the Technical Specifications section while holding it in the designated position.
for auxiliary switch ratings.
5. Depress the gear release, and rotate the coupler
The following procedures serve as examples to until the position indicator is back to 0°.
change the position of the auxiliary switch angles:
M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 7
Repairs and Replacement
Do not field repair the M9100 Series actuators. To
order a replacement or an accessory, refer to the
Ordering Information section in the M9108, M9116,
M9124, and M9132 Series Electric Non-spring Return
Actuators Product Bulletin (LIT-2681058).
Technical Specifications
Product M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators
Power Requirements M9108-, M9116-AGx: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 6.5 VA supply, Class 2
All Other Models: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%; 7.5 VA supply, Class 2
Input Signal AGx: 24 VAC at 50/60 Hz or 24 VDC
GGx, HGx: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or 0 (4) to 20 mA
JGx: Potentiometer value is 100 ohms minimum to
10,000 ohms maximum
Input Signal Adjustments AGx: Factory Setting: Terminals 1 and 2, CW rotation
Terminals 1 and 3, CCW rotation
GGx, HGx (Voltage Input or Current Input):
Factory Setting: 0 to 10 VDC, 0 to 20 mA, CW rotation with
signal increase
Jumper Selectable: 0 (2) to 10 VDC, 0 (4) to 20 VDC, or
0 (4) to 20 mA
HGx Adjustable Zero: 0 to 6 VDC, 0 to 12 VDC, or 0 to 12 mA
Adjustable Span: 2 to 10 VDC, 4 to 20 VDC, or 4 to 20 mA
GGx, HGx, JGx: Action is jumper selectable Direct (CW) or Reverse (CCW) with
signal increase.
Input Impedance GGx, HGx: Voltage Input: 205,000 ohms for 0 (2) to 10 V and
410,000 ohms for 0 (4) to 20 V
Current Input: 500 ohms
JGx: Potentiometer Input: 1.8 megohms
Feedback Signal AGD: 135 ohm feedback potentiometer
AGE: 1,000 ohm feedback potentiometer
GGx, HGx: 0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA)
Corresponds to input signal span selection.
JGx: 0 to 10 VDC for 90° (10 VDC at 1 mA)
Auxiliary Switch Rating xGC: Two Single-Pole, Double-Throw (SPDT) switches rated at 24 VAC
1.5 A inductive, 3.0 A resistive; 35.0 VA maximum per switch, Class 2
Mechanical Output M9108 Series: 70 lb∙in (8 N∙m) for one unit; not intended for tandem use
(Running Torque) M9116 Series: 140 lb∙in (16 N∙m) for one unit
M9116 (in tandem) 280 lb∙in (32 N∙m) for two units (GGx, HGx)
M9124 Series: 210 lb∙in (24 N∙m) for one unit
M9124 (in tandem) 420 lb∙in (48 N∙m) for two units (AGx, GGx, HGx)
M9132 Series: 280 lb∙in (32 N∙m) for one unit,
M9132 (in tandem) 560 lb∙in (64 N∙m) for two units (AGx, GGx)
Audible Noise Rating 45 dBA at 1 m
Rotation Range 0 to 90° in 5-degree increments, mechanically limited to 93°
Rotation Time M9108: 30 seconds at 50% rated load,
25 to 50 seconds for 0 to 70 lb∙in (0 to 8 N∙m)
M9116: 80 seconds at 50% rated load
70 to 115 seconds for 0 to 140 lb∙in (0 to 16 N∙m)
M9124: 130 seconds at 50% rated load
115 to 175 seconds for 0 to 210 lb∙in (0 to 24 N∙m)
M9132: 140 seconds at 50% rated load
115 to 205 seconds for 0 to 280 lb∙in (0 to 32 N∙m)
Continued on next page. . .
8 M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions
Technical Specifications (Cont.)
Electrical Connection M9124-, M9132-AGx:
1/4 in. spade terminals with pluggable 3-terminal blocks
All Other Models: Screw terminals for 22 to 14 AWG; maximum of two 18, 20, or
22 AWG per terminal
Mechanical Connection 3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or a 3/8 to 5/8 in. (10 to 16 mm) square shaft
Enclosure NEMA 2, IP42
Ambient Conditions Operating: -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing
Storage: -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing
Dimensions (H x W x D) 7.09 x 3.94 x 2.54 in. (180 x 100 x 64.5 mm)
Shipping Weight 2.9 lb (1.3 kg)
Agency Compliance UL Listed, File E27734, CCN XAPX
CSA Certified, File LR85083, Class 3221 02
CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT
45143 ESSEN MILWAUKEE WI 53202 MANAGEMENT
GERMANY USA NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners. © 2021 Johnson Controls.
M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions 9