| Вид документа | Каталожна сторінка |
|---|
| Виробник | JCI |
|---|
| Моделі | HT-1000, HT-1201-UR, HT-1300-UR, HT-1301-UR, HT-1303-UR, HT-1306-UR |
|---|
| Група обладнання | automation |
|---|
| Мова документа | англійська |
|---|
| Розмір файлу | 0.3 МБ |
|---|
Про документ
Wall-mount room humidity sensors providing active sensing of relative humidity and, on specific models, active/passive sensing of temperature in HVAC applications. They use a polymer capacitance humidity sensing element with either ±2% or ±4% accuracy and a voltage output signal proportional to 0 to 100% relative humidity.
Ключові дані
| Humidity range | 0…100 % RH |
|---|
| Humidity accuracy | ±2% or ±4% (model-dependent) |
|---|
| Output RH | 0…10 VDC |
|---|
| Temperature output | 0…10 VDC, NTC K2, Pt1000 |
|---|
| Supply voltage | 15 VAC / 24 VAC (12 to 30 VDC / 24 VAC ±15% per model) |
|---|
| Protection class | IP30 |
|---|
Застосування
- HVAC applications, room relative humidity sensing
- Compatible with any type of Johnson Controls or third-party HVAC controllers
Особливості
- Supply voltage: 15 VAC / 24 VAC
- Output RH%: 0…10 VDC
- Output temperature: 0…10 VDC, NTC K2, Pt1000
- Protection class: IP30
Технічні дані
| Parameter |
Value |
| Sensing element |
Polymer capacitance |
| Humidity output |
0…10 VDC |
| Humidity accuracy |
±2% or ±4%, depending on model |
| Supply voltage |
12 to 30 VDC; 24 VAC ±15%; 15 VAC / 24 VAC |
| Protection class |
IP30 |
Варіанти замовлення
| Code |
Humidity range |
Humidity output |
Humidity accuracy |
Temperature range |
Temperature output |
Supply voltage |
| HT-1201-UR |
0…100% RH |
0…10 VDC |
±2% |
— |
— |
12 to 30 VDC |
| HT-1300-UR |
--- |
--- |
— |
— |
— |
12 to 30 VDC |
| HT-1301-UR |
0…100% RH |
0…10 VDC |
±4% |
0 to 40°C |
0…10 VDC |
24 VAC ±15% |
| HT-1303-UR |
0…100% RH |
0…10 VDC |
±4% |
0 to 40°C |
NTC K2 |
24 VAC ±15% |
| HT-1306-UR |
0…100% RH |
0…10 VDC |
±4% |
0 to 60°C |
Pt1000 |
24 VAC ±15% |
Note: In the source table the humidity range/output columns for HT-1300-UR are printed as "--- ---"; no humidity range or accuracy value is given there for this model.
Позиції каталогу з цим документом
Текст документа
SENSORS
ROOM
HUMIDITY
HT-1000
WALL MOUNT
The HT-1000 series room humidity sensors provide active sensing of relative
humidity and on specific models, also active/passive sensing of temperature in
HVAC applications.
It features a polymer capacitance humidity sensing element and provides within either ±2% or ±4% accuracy a voltage output
signal proportional 0 to 100% relative humidity.
The HT-1000 series room humidity sensors are designed for use with any type of Johnson Controls or third party HVAC
controllers.
FEATURES
Supply voltage: 15 VAC / 24 VAC
Output RH%: 0...10 VDC
Output Temperature: 0...10 VDC, NTC K2, Pt1000
Protection class: IP30
DIMENSIONS (in mm)
136
European Products Catalogue 2019
SENSORS
HT-1000 ROOM HUMIDITY
ORDERING INFORMATION
HUMIDITY HUMIDITY HUMIDITY TEMPERATURE TEMPERATURE SUPPLY
CODES RANGE OUTPUT ACCURACY RANGE OUTPUT VOLTAGE
HT-1201-UR ±2% 0 to 40°C 0…10 VDC
HT-1300-UR --- ---
12 to 30 VDC
HT-1301-UR 0…100% RH 0…10 VDC 0…10 VDC
±4% 0 to 40°C 24 VAC ±15%
HT-1303-UR NTC K2
HT-1306-UR 0 to 60°C Pt1000
137
European Products Catalogue 2019
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.