FX14 Field Controller

Вид документаТехнічний паспорт
ВиробникJCI
МоделіFX14, LP-FX14D10-000C, LP-FX14D11-000C, LP-FX14D12-000C, LP-FX14D13-000C, LP-FX14D14-000C, LP-FX14D60-000C, LP-FX14D61-000C
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.1 МБ

Про документ

The FX14 is a high performance, freely programmable field controller designed specifically for commercial Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR) applications. It supports 29 physical inputs and outputs and includes an onboard real-time clock for start-stop scheduling, real-time based control sequences, and time stamping of events and trend records. It can be fitted with an N2 Open, LONWORKS®, or BACnet® communication card to integrate into a Building Automation System (BAS), or an RS-232C card to send SMS event notifications via a GSM modem.

Ключові дані

I/O count29 physical inputs and outputs (6 AIs, 12 DIs, 2 AOs, 9 DOs)
Power supply24 VAC ±15%, 50/60 Hz
Power consumption19.5 VA at max. load
Ambient operating conditions-40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing)
Protection classIP20 CEI/EN60529
Analog input resolution16-bit
Analog output0-10 VDC, max. 3 mA or PWM, 100 Hz, 13-bit resolution
Network optionsN2 Open, LONWORKS, BACnet, RS-232C

Застосування

  • Multi-compressor and scroll compressors
  • Close control units
  • Unit ventilators
  • Packaged rooftop units

Особливості

  • Freely programmable controller (FX Tools software package)
  • Network communication card options - N2 Open, LONWORKS, and BACnet Protocols
  • Remote communication services
  • Choice of user interfaces: integral or remote
  • Onboard real-time clock
  • Selectable analog input types in software
  • Analog outputs with Pulse Width Modulation (PWM) option
  • Models with various output configurations of solid-state triacs and line voltage relays
  • Network Room Module (NRM)

Технічні дані

Parameter Value
Product codes LP-FX14Dxx-xxx
Power supply requirements 24 VAC ±15%, 50/60 Hz – Safety Extra-Low Voltage (SELV) in Europe – Class 2 North America
Power consumption 19.5 VA at max. load
Housing material ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating
Protection class IP20 CEI/EN60529
Ambient operating conditions -40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing); integral user interface does not operate below -20°C (-4°F)
Ambient storage conditions -40°C (-40°F) to 70°C (158°F), 10 to 95% RH (noncondensing)
Weight (with package) 0.74 kg (1.6 lb)
Real-time clock accuracy better than ±200 ms per day at constant ambient temperature of 25°C; back up: minimum 10 days without power at 25°C
Integrated LCD display numeric resolution -999 to 999 or -99.9 to 99.9
Connection terminals for AIs, DOs and power supply Screw terminals for max. 2 x 1.5 mm² (16 AWG) wires, included in the package
Connection terminals for AOs, DIs and remote display Screw terminals for max. 1 x 1.5 mm² (16 AWG) wires included in the package
Connection terminals for LON/N2 Open/BACnet networks Screw terminals for max. 1 x 1.5 mm² (16 AWG) wires or 2 x Belden® cable, 2-core twisted pair with shield ≥0.8 mm (20 AWG), included in the package
BACnet compliance BACnet Testing Laboratories™ (BTL) Listing; B-AAC (BACnet Advanced Application Controller); PICS available on request
Analog inputs (AI1–AI6) TB1 (1-15), freely software configurable, 16-bit resolution; application: temperature, humidity, or pressure
AI voltage reference AI V Ref: 16 V, max. 20 mA or 5 V, max. 15 mA (jumper selection)
Digital inputs (DI1–DI12) TB2 (21-36), potential free contacts; transition counter function, maximum 10 ms on and 10 ms off (at 50 Hz)
Relay outputs SPST 6(3)A, 250 V relays; dielectric test voltage on open relay contact: 1,000 VAC RMS; max. switching rate at nominal load: six operations/min.; motor: 0.5 hp 230 VAC, 0.25 hp 120 VAC; rating (resistive): 6A 125 VAC, 6A 30 VDC, 6A 250 VAC; UL tested life (min. operations): 30,000 operations (at 360 operations x hour); dielectric strength coil-contacts: 4,000 V RMS for 1 minute
Digital outputs (DO1–DO9) TB6 (41-48): DO1–DO3; TB7 (51-55): DO4, DO5; TB7 (57-58): DO6 (relay or 0.5 A, 24 VAC triac); TB8 (61-68): DO7–DO9 (relays or 0.5 A, 24 VAC triacs)
Analog outputs (AO1, AO2) TB9 (72-73), TB10 (75-76): 0-10 VDC, max. 3 mA or PWM, 100 Hz; 13-bit resolution; AO V Ref: 15 VDC, max. 10 mA
Analog input types
Sensor Type Linearization Range Accuracy at 20°C (68°F) Ambient (Sensor Not Included)
A99 -50 to 100°C (-58 to 212°F) ±0.5°C (1°F)
NTC 10k -40 to 150°C (-40 to 300°F) ±0.5°C (1°F)
Pt 1000 -50 to 160°C (-58 to 320°F) ±0.5°C (1°F)
Ni 1000 (Johnson Controls) -45 to 120°C (-49 to 248°F) ±0.5°C (1°F)
Active Voltage 0-10 VDC ±0.05 VDC
Active Ratiometric 0.5-4.5 VDC ±0.05 VDC

Варіанти замовлення

FX14 Controllers
Product Code Number Description
LP-FX14D10-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), no communication card
LP-FX14D11-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), N2 Open card
LP-FX14D12-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), LONWORKS card
LP-FX14D13-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), RS-232C card
LP-FX14D14-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), BACnet card
LP-FX14D60-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface, no communication card
LP-FX14D61-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and N2 Open card
LP-FX14D62-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and LONWORKS card
LP-FX14D63-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and RS-232C card
LP-FX14D64-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and BACnet card
LP-FX14D20-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), no communication card
LP-FX14D21-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), N2 Open card
LP-FX14D22-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), LONWORKS card
LP-FX14D23-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), RS-232C card
LP-FX14D24-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), BACnet card
LP-FX14D70-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface, no communication card
LP-FX14D71-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and N2 Open card
LP-FX14D72-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and LONWORKS card
LP-FX14D73-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and RS-232C card
LP-FX14D74-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and BACnet card
FX14 Communications Cards
Product Code Number Description
LP-NET151-010C N2 Open communication card for FX14 Rev. A
LP-NET142-000C LONWORKS communication card for FX14 Rev. A
LP-NET163-000C RS-232C communication card for FX14 Rev. A
LP-NET164-000C BACnet communication card for FX14 Rev. B only
TM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
Product Code Number Description
TM-2140-0000 Room Command Module, temperature sensor only
TM-2150-0000 Room Command Module, occupancy button and LED
TM-2160-0000 Room Command Module, 12-28°C setpoint dial, occupancy button and LED
TM-2160-0002 Room Command Module, 12-28°C setpoint dial, occupancy button and LED, fan speed override
TM-2160-0005 Room Command Module, ± setpoint dial, occupancy button and LED
TM-2160-0007 Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override
TM-2190-0000 Room Command Module, 12-28°C setpoint dial
TM-2190-0005 Room Command Module, ± setpoint dial
Network Room Modules (Available in Europe)
Product Code Size (mm) Type Service Port LCD Display Temperature Adjust Dial Fan Speed Selector Button °F/°C Addressable
LP-NRM001-000C 80 x 80 Program Key No No No No No No
LP-NRM002-000C 80 x 80 Program Key Yes Yes No No No No
LP-NRM003-000C 80 x 80 Program Key Yes Yes Yes No No No
LP-NRM511-000C 80 x 80 MUI No No No No No Yes
LP-NRM502-000C 80 x 80 MUI Yes Yes No No No No
LP-NRM503-000C 80 x 80 MUI Yes Yes Yes No No No
TM Series Room Command Modules (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
Product Code Number Description
TM-2141-0000 Room Command Module, temperature sensor only
TM-2151-0000 Room Command Module, occupancy button and LED
TM-2161-0000 Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED
TM-2161-0002 Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED, fan speed override
TM-2161-0005 Room Command Module, ± setpoint dial, occupancy button and LED
TM-2161-0007 Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override
TM-2191-0000 Room Command Module, 54-82°F/12-28°C setpoint dial
TM-2191-0005 Room Command Module, ± setpoint dial
Network Room Modules (Available in North America)
Product Code Size, mm (inch) Type Service Port LCD Display Temperature Adjust Dial Fan Speed Selector Button °F/°C Addressable
LP-NRM511-000C 80 x 80 (3.15 x 3.15 in.) MUI No No No No No Yes
LP-NRM552-000C 80 x 80 (3.15 x 3.15 in.) MUI Yes Yes No Yes No No
LP-NRM553-000C 80 x 80 (3.15 x 3.15 in.) MUI Yes Yes Yes Yes No No
LP-NRM611-000C 120 x 80 (4.72 x 3.15 in.) MUI No No No No No Yes
LP-NRM652-000C 120 x 80 (4.72 x 3.15 in.) MUI Yes Yes No Yes No No
LP-NRM653-000C 120 x 80 (4.72 x 3.15 in.) MUI Yes Yes Yes Yes No No
Medium User Interfaces
Product Code Number Description
LP-DIS60P20-0C Medium User Interface display (non-isolated version); can be mounted up to 3 m (9.8 ft) from the FX14 and includes panel mounting hardware
LP-DIS60P21-0C Medium User Interface display (isolated version); can be mounted up to 300 m (984 ft) from the FX14 and includes panel and wall mounting hardware
LP-KIT007-000C Link cable for the connection of the FX14 to the Panel Mount MUI display - 3 m (9.8 ft)
Programming/Commissioning Tools
Product Code Number Description
LP-FXTPRO-0 FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) – New User
LP-FXTPRO-6 FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) - Upgrade
LP-KIT200-000C N2 Commissioning Adapter: Includes port powered RS-232 to RS-485 converter and wiring harness with mating connectors for FX Field Controller supervisory link interface
LP-KIT204-000C BACnet Commissioning Adapter: Includes BACnet Internet Protocol (IP) to MS/TP adapter, Ethernet cable, and Universal Serial Bus (USB) cable (USB port required for powering the adapter)
LN-75010 LONWORKS Commissioning Adapter: Includes USB to LONWORKS TP/FT-10 Network Interface
IU-9100-8401 RS-232 to RS-485 Converter: 230 VAC (Europe only)
LP-KIT100-000C FX Programming Key
DT-9100-8901 Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe Only)
Accessories
Product Code Number Description
LP-KIT007-001C Interface Cable for standard land-line modem, 1.5 m (4.9 ft)
LP-KIT007-002C Interface Cable for GSM modem, 1.5 m (4.9 ft)
LP-KIT007-013C Null modem cable for computer connection, 3 m (9.8 ft)
LP-KIT007-014C Null modem cable for computer connection, 15 m (49.2 ft)
LP-KIT007-020C Replacement communication wiring connectors kit
LP-KIT014-000C Replacement input/output wiring connectors kit

Допуски та стандарти

  • Europe – 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-2
  • Europe – 2006/95/EEC, Low Voltage Directive: EN 60730
  • Canada – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
  • Canada – Industry Canada, ICES-003
  • United States – UL Listed (PAZX), UL 916, Energy Management Equipment
  • United States – FCC compliant to CFR 47, Part 15, Subpart B, Class A

Позиції каталогу з цим документом

Текст документа

                                                                                                                                                  Code No. LIT-1900407
                                                                                                                                                  Issued January 22, 2010

Facility Explorer
FX14 Field Controller
Description                                                     Using the FX Tools software package, you
                                                                can program the FX14 field controller to
The FX14 is a high performance field
                                                                operate a wide variety of commercial HVACR
controller designed specifically for commercial
                                                                equipment, including multi-compressor and
Heating, Ventilating, Air Conditioning, and
                                                                scroll compressors, close control units, unit
Refrigeration (HVACR) applications.
                                                                ventilators and packaged rooftop units.
The FX14 supports 29 physical inputs and
                                                                Refer to the FX14 Field Controller Product
outputs including a wide range of sensors and
                                                                Bulletin (LIT-12011163) for important product
actuating devices. The FX14 includes an
                                                                application information.
onboard real-time clock to support the
start-stop scheduling of equipment, real-time
based control sequences, and the time
                                                                Features                                                                         FX14 Field Controller
stamping of events and trend records.                           •    freely programmable controller
The FX14 can be fitted with an N2 Open,
                                                                •    network communication card options - N2                     Repair Information
                                                                     Open, LONWORKS, and BACnet Protocols                        If the FX14 Field Controller fails to operate
LONWORKS®, or BACnet® communication
card to integrate the controller into a                         •    remote communication services                               within its specifications, replace the unit. For a
compatible Building Automation System                           •    choice of user interfaces: integral or                      replacement controller, contact the nearest
(BAS). Alternatively, the FX14 can be fitted                         remote                                                      Johnson Controls® representative.
with an RS-232C serial communication card to                    •    onboard real-time clock
transmit event notification messages via Short                  •    selectable analog input types in software
Messaging Service (SMS) through a Global                        •    analog outputs with Pulse Width
System for Mobile (GSM) modem.                                       Modulation (PWM) option
                                                                •    models with various output configurations
                                                                     of solid-state triacs and line voltage relays
                                                                •    Network Room Module (NRM)



Selection Charts
FX14 Controllers Ordering Information
Product Code Number           Description
LP-FX14D10-000C                            FX14: 6 Analog Inputs (AIs), 12 Digital (Binary) Inputs (DIs), 2 Analog Outputs (AOs) (0-10 V or PWM), and 9 Digital (Binary)
                                           Outputs (DOs) (5 Relays and 4 Triacs), no communication card
LP-FX14D11-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), N2 Open card
LP-FX14D12-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), LONWORKS card
LP-FX14D13-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), RS-232C card
LP-FX14D14-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), BACnet card
LP-FX14D60-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface, no communciation
                                           card
LP-FX14D61-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and N2 Open card
LP-FX14D62-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and LONWORKS card
LP-FX14D63-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and RS-232C card
LP-FX14D64-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and BACnet card
LP-FX14D20-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), no communciation card
LP-FX14D21-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), N2 Open card
LP-FX14D22-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), LONWORKS card
LP-FX14D23-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), RS-232C card
LP-FX14D24-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), BACnet card
LP-FX14D70-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface, no communciation card
LP-FX14D71-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and N2 Open card
LP-FX14D72-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and LONWORKS card
LP-FX14D73-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and RS-232C card
LP-FX14D74-000C                            FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and BACnet card

FX14 Communications Cards Ordering Information
Product Code Numbers      Description
LP-NET151-010C                             N2 Open communication card for FX14 Rev. A
LP-NET142-000C                             LONWORKS communication card for FX14 Rev. A
LP-NET163-000C                             RS-232C communication card for FX14 Rev. A
LP-NET164-000C                             BACnet communication card for FX14 Rev. B only


The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       1 of 4
FX14 Field Controller (Continued)

TM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
Product Code Number     Description
 TM-2140-0000                              Room Command Module, temperature sensor only
 TM-2150-0000                              Room Command Module, occupancy button and LED
 TM-2160-0000                              Room Command Module, 12-28°C setpoint dial, occupancy button and LED
 TM-2160-0002                              Room Command Module, 12-28°C setpoint dial, occupancy button and LED, fan speed override
 TM-2160-0005                              Room Command Module, ± setpoint dial, occupancy button and LED
 TM-2160-0007                              Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override
 TM-2190-0000                              Room Command Module, 12-28°C setpoint dial
 TM-2190-0005                              Room Command Module, ± setpoint dial

Network Room Modules Ordering Information (Available in Europe)
Product Code                                                                                                Features/Options
                                                   Size (mm)             Service Port           LCD Display Temperature                   Fan Speed          °F/°C        Addressable
                                                                         Type                               Adjust Dial                   Selector
                                                                                                                                          Button
 LP-NRM001-000C                                    80 x 80               Program Key            No                  No                    No                 No           No
 LP-NRM002-000C                                                                                 Yes                 Yes                   No                 No           No
 LP-NRM003-000C                                                                                 Yes                 Yes                   Yes                No           No
 LP-NRM511-000C                                                          MUI                    No                  No                    No                 No           Yes
 LP-NRM502-000C                                                                                 Yes                 Yes                   No                 No           No
 LP-NRM503-000C                                                                                 Yes                 Yes                   Yes                No           No

TM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
Product Code Number   Description
 TM-2141-0000                          Room Command Module, temperature sensor only
 TM-2151-0000                          Room Command Module, occupancy button and LED
 TM-2161-0000                          Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED
 TM-2161-0002                          Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED, fan speed override
 TM-2161-0005                          Room Command Module, ± setpoint dial, occupancy button and LED
 TM-2161-0007                          Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override
 TM-2191-0000                          Room Command Module, 54-82°F/12-28°C setpoint dial
 TM-2191-0005                          Room Command Module, ± setpoint dial

Network Room Modules Ordering Information (Available in North America)
Product Code                                                           Features/Options
                                                   Size, mm              Service Port           LCD Display Temperature                  Fan Speed           °F/°C       Addressable
                                                   (inch)                Type                               Adjust Dial                  Selector
                                                                                                                                         Button
 LP-NRM511-000C                                    80 x 80               MUI                    No                  No                   No                  No          Yes
 LP-NRM552-000C                                    (3.15 x 3.15 in.)                            Yes                 Yes                  No                  Yes        No
 LP-NRM553-000C                                                                                 Yes                 Yes                  Yes                 Yes         No
 LP-NRM611-000C                                    120 x 80              MUI                    No                  No                   No                  No          Yes
 LP-NRM652-000C                                    (4.72 x 3.15 in.)                            Yes                 Yes                  No                  Yes        No
 LP-NRM653-000C                                                                                 Yes                 Yes                  Yes                 Yes         No

Medium User Interfaces Ordering Information
Product Code Numbers      Description
 LP-DIS60P20-0C                        Medium User Interface display (non-isolated version); can be mounted up to 3 m (9.8 ft) from the FX14 and includes panel
                                       mounting hardware.
 LP-DIS60P21-0C                        Medium User Interface display (isolated version); can be mounted up to 300 m (984 ft) from the FX14 and includes panel and
                                       wall mounting hardware.
 LP-KIT007-000C                        Link cable for the connection of the FX14 to the Panel Mount MUI display - 3 m (9.8 ft)

Programming/Commissioning Tools Ordering Information (Part 1 of 2)
Product Code Numbers   Description
 LP-FXTPRO-0                            FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) – New User
 LP-FXTPRO-6                            FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) - Upgrade
 LP-KIT200-000C                         N2 Commissioning Adapter: Includes port powered RS-232 to RS-485 converter and wiring harness with mating connectors for
                                        FX Field Controller supervisory link interface.
 LP-KIT204-000C                         BACnet Commissioning Adapter: Includes BACnet Internet Protocol (IP) to MS/TP adapter, Ethernet cable, and Universal Serial
                                        Bus (USB) cable (USB port required for powering the adapter).
 LN-75010                               LONWORKS Commissioning Adapter: Includes USB to LONWORKS TP/FT-10 Network Interface

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       2 of 4
FX14 Field Controller (Continued)

Programming/Commissioning Tools Ordering Information (Part 2 of 2)
Product Code Numbers   Description
 IU-9100-8401                           RS-232 to RS-485 Converter: 230 VAC (Europe only)
 LP-KIT100-000C                         FX Programming Key
 DT-9100-8901                           Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe Only)

Accessories
 Product Code Numbers                    Description
 LP-KIT007-001C                          Interface Cable for standard land-line modem, 1.5 m (4.9 ft)
 LP-KIT007-002C                          Interface Cable for GSM modem, 1.5 m (4.9 ft)
 LP-KIT007-013C                          Null modem cable for computer connection, 3 m (9.8 ft)
 LP-KIT007-014C                          Null modem cable for computer connection, 15 m (49.2 ft)
 LP-KIT007-020C                          Replacement communication wiring connectors kit
 LP-KIT014-000C                          Replacement input/output wiring connectors kit

Technical Specifications
                                                                                         I/O Details
 Terminals               Channel                 Type                                   Remark/Application
 Analog Input (AI)
 TB1 (1-15)              AI1, AI2, AI3, AI4,     See Analog Input table.                Freely software configurable
                         AI5, AI6                16-bit resolution                      Application: temperature, humidity, or pressure
 TB1 (3,8,13)            AI V Ref                16 V, max. 20 mA or                    To power active 0-10 V sensors or potentiometers or
                                                 5 V, max. 15 mA                        To power ratiometric sensors or potentiometers
                                                 (jumper selection)
 Digital Input (DI)
 TB2 (21-36)             DI1, DI2, DI3, DI4, Potential free contacts                    Transition counter function, maximum 10 ms on and 10 ms off (at 50 Hz).
                         DI5, DI6, DI7, DI8,
                         DI9, DI10, DI11,
                         DI12
 Digital Output (DO)
 Relay Outputs           Dielectric test voltage on open relay contact: 1,000 VAC Root Mean Square (RMS)
                         Maximum relay switching rate at nominal load: six operations/min.
 TB6 (41-48)             DO1, DO2, DO3           Single Pole Single Throw               Max. switching power (relays):
                                                 (SPST) 6(3)A, 250 V relays             Motor: 0.5 hp 230 VAC, 0.25 hp 120 VAC
 TB7 (51-55)             DO4, DO5                SPST 6(3)A, 250 V relays               Rating (resistive): 6A 125 VAC, 6A 30 VDC, 6A 250 VAC
 TB7 (57-58)             DO6                     SPST 6(3)A, 250 V relay or             UL tested life (min. operations): 30,000 operations
                                                 0.5 A, 24 VAC triac                    (at 360 operations x hour)
                                                                                        Dielectric strength coil-contacts: 4,000 V RMS for 1 minute
 TB8 (61-68)             DO7, DO8, DO9           SPST 6(3)A, 250 V relays or
                                                 0.5 A, 24 VAC triacs
 Analog Output (AO)
 TB9 (71)                AO V Ref                15 VDC, max. 10 mA                     Voltage Reference signal used for PWM output.
 TB9 (72-73)             AO1                     0-10 VDC, max. 3 mA or PWM, Used to drive motor actuator, control device, or fan speed controller. 13-bit resolution.
                                                 100 Hz
 TB10 (74)               AO V Ref                15 VDC, max. 10 mA                     Voltage Reference signal used for PWM output.
 TB10 (75-76)            AO2                     0-10 VDC, max. 3 mA or                 Used to drive motor actuator, control device, or fan speed controller. 13-bit resolution.
                                                 PWM, 100 Hz

                                                                                  Analog Input Types
 Sensor Type                            Linearization Range                                Accuracy at 20°C (68°F) Ambient (Sensor Not Included)
 A99                                    -50 to 100°C (-58 to 212°F)                        ±0.5°C (1°F)
 NTC 10k                                -40 to 150°C (-40 to 300°F)                        ±0.5°C (1°F)
 Pt 1000                                -50 to 160°C (-58 to 320°F)                        ±0.5°C (1°F)
 Ni 1000 (Johnson Controls)             -45 to 120°C (-49 to 248°F)                        ±0.5°C (1°F)
 Active Voltage                         0-10 VDC                                           ±0.05 VDC
 Active Ratiometric                     0.5-4.5 VDC                                        ±0.05 VDC




The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       3 of 4
FX14 Field Controller (Continued)

                                                                                FX14 Field Controller
Product Codes                                            LP-FX14Dxx-xxx
Power Supply Requirements                                24 VAC ±15%, 50/60 Hz – Safety Extra-Low Voltage (SELV) in Europe - Class 2 North America
Power Consumption                                        19.5 VA at max. load
Housing Material                                         ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating
Protection Class                                         IP20 CEI/EN60529
Ambient Operating Conditions                             -40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing)
                                                         Integral user interface does not operate below -20°C (-4°F).
Ambient Storage Conditions                               -40°C (-40°F) to 70°C (158°F), 10 to 95% RH (noncondensing)
Weight (with Package)                                    0.74 kg (1.6 lb)
Real-Time Clock                                          Accuracy: better than ±200 ms per day at constant ambient temperature of 25°C
                                                         Back up: minimum 10 days without power at 25°C
Integrated LCD Display Numeric Resolution -999 to 999 or -99.9 to 99.9
Connection Terminals for AIs, DOs and                    Screw terminals for max. 2 x 1.5 mm2 (16 AWG) wires, included in the package.
Power Supply
Connection Terminals for AOs, DIs and                    Screw terminals for max. 1 x 1.5 mm2 (16 AWG) wires included in the package.
Remote Display
Connection Terminals for LON/ N2 Open/                   Screw terminals for max. 1 x 1.5 mm2 (16 AWG) wires or 2 x Belden® cable, 2-core twisted pair with shield
BACnet Networks                                          ≥0.8 mm (20 AWG), included in the package.
BACnet Compliance                                        BACnet Testing Laboratories™ (BTL) Listing
                                                         BACnet Interoperability Building Blocks (BIBBs):
                                                         BACnet Advanced Application Controller (B-AAC)
                                                         Protocol Implementation Conformance Statement (PICS) available on request
Agency Compliance                                        Europe                     – 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-2
                                                                                    – 2006/95/EEC, Low Voltage Directive: EN 60730
                                                         Canada                     – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
                                                                                    – Industry Canada, ICES-003
                                                         United States              – UL Listed (PAZX), UL 916, Energy Management Equipment
                                                                                    – FCC compliant to CFR 47, Part 15, Subpart B, Class A




The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       4 of 4


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.