| Вид документа | Технічний паспорт |
|---|
| Виробник | JCI |
|---|
| Моделі | FX14, LP-FX14D10-000C, LP-FX14D11-000C, LP-FX14D12-000C, LP-FX14D13-000C, LP-FX14D14-000C, LP-FX14D60-000C, LP-FX14D61-000C |
|---|
| Група обладнання | automation |
|---|
| Мова документа | англійська |
|---|
| Розмір файлу | 0.1 МБ |
|---|
Про документ
The FX14 is a high performance, freely programmable field controller designed specifically for commercial Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR) applications. It supports 29 physical inputs and outputs and includes an onboard real-time clock for start-stop scheduling, real-time based control sequences, and time stamping of events and trend records. It can be fitted with an N2 Open, LONWORKS®, or BACnet® communication card to integrate into a Building Automation System (BAS), or an RS-232C card to send SMS event notifications via a GSM modem.
Ключові дані
| I/O count | 29 physical inputs and outputs (6 AIs, 12 DIs, 2 AOs, 9 DOs) |
|---|
| Power supply | 24 VAC ±15%, 50/60 Hz |
|---|
| Power consumption | 19.5 VA at max. load |
|---|
| Ambient operating conditions | -40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing) |
|---|
| Protection class | IP20 CEI/EN60529 |
|---|
| Analog input resolution | 16-bit |
|---|
| Analog output | 0-10 VDC, max. 3 mA or PWM, 100 Hz, 13-bit resolution |
|---|
| Network options | N2 Open, LONWORKS, BACnet, RS-232C |
|---|
Застосування
- Multi-compressor and scroll compressors
- Close control units
- Unit ventilators
- Packaged rooftop units
Особливості
- Freely programmable controller (FX Tools software package)
- Network communication card options - N2 Open, LONWORKS, and BACnet Protocols
- Remote communication services
- Choice of user interfaces: integral or remote
- Onboard real-time clock
- Selectable analog input types in software
- Analog outputs with Pulse Width Modulation (PWM) option
- Models with various output configurations of solid-state triacs and line voltage relays
- Network Room Module (NRM)
Технічні дані
| Parameter |
Value |
| Product codes |
LP-FX14Dxx-xxx |
| Power supply requirements |
24 VAC ±15%, 50/60 Hz – Safety Extra-Low Voltage (SELV) in Europe – Class 2 North America |
| Power consumption |
19.5 VA at max. load |
| Housing material |
ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating |
| Protection class |
IP20 CEI/EN60529 |
| Ambient operating conditions |
-40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing); integral user interface does not operate below -20°C (-4°F) |
| Ambient storage conditions |
-40°C (-40°F) to 70°C (158°F), 10 to 95% RH (noncondensing) |
| Weight (with package) |
0.74 kg (1.6 lb) |
| Real-time clock accuracy |
better than ±200 ms per day at constant ambient temperature of 25°C; back up: minimum 10 days without power at 25°C |
| Integrated LCD display numeric resolution |
-999 to 999 or -99.9 to 99.9 |
| Connection terminals for AIs, DOs and power supply |
Screw terminals for max. 2 x 1.5 mm² (16 AWG) wires, included in the package |
| Connection terminals for AOs, DIs and remote display |
Screw terminals for max. 1 x 1.5 mm² (16 AWG) wires included in the package |
| Connection terminals for LON/N2 Open/BACnet networks |
Screw terminals for max. 1 x 1.5 mm² (16 AWG) wires or 2 x Belden® cable, 2-core twisted pair with shield ≥0.8 mm (20 AWG), included in the package |
| BACnet compliance |
BACnet Testing Laboratories™ (BTL) Listing; B-AAC (BACnet Advanced Application Controller); PICS available on request |
| Analog inputs (AI1–AI6) |
TB1 (1-15), freely software configurable, 16-bit resolution; application: temperature, humidity, or pressure |
| AI voltage reference |
AI V Ref: 16 V, max. 20 mA or 5 V, max. 15 mA (jumper selection) |
| Digital inputs (DI1–DI12) |
TB2 (21-36), potential free contacts; transition counter function, maximum 10 ms on and 10 ms off (at 50 Hz) |
| Relay outputs |
SPST 6(3)A, 250 V relays; dielectric test voltage on open relay contact: 1,000 VAC RMS; max. switching rate at nominal load: six operations/min.; motor: 0.5 hp 230 VAC, 0.25 hp 120 VAC; rating (resistive): 6A 125 VAC, 6A 30 VDC, 6A 250 VAC; UL tested life (min. operations): 30,000 operations (at 360 operations x hour); dielectric strength coil-contacts: 4,000 V RMS for 1 minute |
| Digital outputs (DO1–DO9) |
TB6 (41-48): DO1–DO3; TB7 (51-55): DO4, DO5; TB7 (57-58): DO6 (relay or 0.5 A, 24 VAC triac); TB8 (61-68): DO7–DO9 (relays or 0.5 A, 24 VAC triacs) |
| Analog outputs (AO1, AO2) |
TB9 (72-73), TB10 (75-76): 0-10 VDC, max. 3 mA or PWM, 100 Hz; 13-bit resolution; AO V Ref: 15 VDC, max. 10 mA |
Analog input types
| Sensor Type |
Linearization Range |
Accuracy at 20°C (68°F) Ambient (Sensor Not Included) |
| A99 |
-50 to 100°C (-58 to 212°F) |
±0.5°C (1°F) |
| NTC 10k |
-40 to 150°C (-40 to 300°F) |
±0.5°C (1°F) |
| Pt 1000 |
-50 to 160°C (-58 to 320°F) |
±0.5°C (1°F) |
| Ni 1000 (Johnson Controls) |
-45 to 120°C (-49 to 248°F) |
±0.5°C (1°F) |
| Active Voltage |
0-10 VDC |
±0.05 VDC |
| Active Ratiometric |
0.5-4.5 VDC |
±0.05 VDC |
Варіанти замовлення
FX14 Controllers
| Product Code Number |
Description |
| LP-FX14D10-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), no communication card |
| LP-FX14D11-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), N2 Open card |
| LP-FX14D12-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), LONWORKS card |
| LP-FX14D13-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), RS-232C card |
| LP-FX14D14-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), BACnet card |
| LP-FX14D60-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface, no communication card |
| LP-FX14D61-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and N2 Open card |
| LP-FX14D62-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and LONWORKS card |
| LP-FX14D63-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and RS-232C card |
| LP-FX14D64-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and BACnet card |
| LP-FX14D20-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), no communication card |
| LP-FX14D21-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), N2 Open card |
| LP-FX14D22-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), LONWORKS card |
| LP-FX14D23-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), RS-232C card |
| LP-FX14D24-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), BACnet card |
| LP-FX14D70-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface, no communication card |
| LP-FX14D71-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and N2 Open card |
| LP-FX14D72-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and LONWORKS card |
| LP-FX14D73-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and RS-232C card |
| LP-FX14D74-000C |
FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and BACnet card |
FX14 Communications Cards
| Product Code Number |
Description |
| LP-NET151-010C |
N2 Open communication card for FX14 Rev. A |
| LP-NET142-000C |
LONWORKS communication card for FX14 Rev. A |
| LP-NET163-000C |
RS-232C communication card for FX14 Rev. A |
| LP-NET164-000C |
BACnet communication card for FX14 Rev. B only |
TM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
| Product Code Number |
Description |
| TM-2140-0000 |
Room Command Module, temperature sensor only |
| TM-2150-0000 |
Room Command Module, occupancy button and LED |
| TM-2160-0000 |
Room Command Module, 12-28°C setpoint dial, occupancy button and LED |
| TM-2160-0002 |
Room Command Module, 12-28°C setpoint dial, occupancy button and LED, fan speed override |
| TM-2160-0005 |
Room Command Module, ± setpoint dial, occupancy button and LED |
| TM-2160-0007 |
Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override |
| TM-2190-0000 |
Room Command Module, 12-28°C setpoint dial |
| TM-2190-0005 |
Room Command Module, ± setpoint dial |
Network Room Modules (Available in Europe)
| Product Code |
Size (mm) |
Type |
Service Port |
LCD Display |
Temperature Adjust Dial |
Fan Speed Selector Button |
°F/°C |
Addressable |
| LP-NRM001-000C |
80 x 80 |
Program Key |
No |
No |
No |
No |
No |
No |
| LP-NRM002-000C |
80 x 80 |
Program Key |
Yes |
Yes |
No |
No |
No |
No |
| LP-NRM003-000C |
80 x 80 |
Program Key |
Yes |
Yes |
Yes |
No |
No |
No |
| LP-NRM511-000C |
80 x 80 |
MUI |
No |
No |
No |
No |
No |
Yes |
| LP-NRM502-000C |
80 x 80 |
MUI |
Yes |
Yes |
No |
No |
No |
No |
| LP-NRM503-000C |
80 x 80 |
MUI |
Yes |
Yes |
Yes |
No |
No |
No |
TM Series Room Command Modules (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
| Product Code Number |
Description |
| TM-2141-0000 |
Room Command Module, temperature sensor only |
| TM-2151-0000 |
Room Command Module, occupancy button and LED |
| TM-2161-0000 |
Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED |
| TM-2161-0002 |
Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED, fan speed override |
| TM-2161-0005 |
Room Command Module, ± setpoint dial, occupancy button and LED |
| TM-2161-0007 |
Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override |
| TM-2191-0000 |
Room Command Module, 54-82°F/12-28°C setpoint dial |
| TM-2191-0005 |
Room Command Module, ± setpoint dial |
Network Room Modules (Available in North America)
| Product Code |
Size, mm (inch) |
Type |
Service Port |
LCD Display |
Temperature Adjust Dial |
Fan Speed Selector Button |
°F/°C |
Addressable |
| LP-NRM511-000C |
80 x 80 (3.15 x 3.15 in.) |
MUI |
No |
No |
No |
No |
No |
Yes |
| LP-NRM552-000C |
80 x 80 (3.15 x 3.15 in.) |
MUI |
Yes |
Yes |
No |
Yes |
No |
No |
| LP-NRM553-000C |
80 x 80 (3.15 x 3.15 in.) |
MUI |
Yes |
Yes |
Yes |
Yes |
No |
No |
| LP-NRM611-000C |
120 x 80 (4.72 x 3.15 in.) |
MUI |
No |
No |
No |
No |
No |
Yes |
| LP-NRM652-000C |
120 x 80 (4.72 x 3.15 in.) |
MUI |
Yes |
Yes |
No |
Yes |
No |
No |
| LP-NRM653-000C |
120 x 80 (4.72 x 3.15 in.) |
MUI |
Yes |
Yes |
Yes |
Yes |
No |
No |
Medium User Interfaces
| Product Code Number |
Description |
| LP-DIS60P20-0C |
Medium User Interface display (non-isolated version); can be mounted up to 3 m (9.8 ft) from the FX14 and includes panel mounting hardware |
| LP-DIS60P21-0C |
Medium User Interface display (isolated version); can be mounted up to 300 m (984 ft) from the FX14 and includes panel and wall mounting hardware |
| LP-KIT007-000C |
Link cable for the connection of the FX14 to the Panel Mount MUI display - 3 m (9.8 ft) |
Programming/Commissioning Tools
| Product Code Number |
Description |
| LP-FXTPRO-0 |
FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) – New User |
| LP-FXTPRO-6 |
FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) - Upgrade |
| LP-KIT200-000C |
N2 Commissioning Adapter: Includes port powered RS-232 to RS-485 converter and wiring harness with mating connectors for FX Field Controller supervisory link interface |
| LP-KIT204-000C |
BACnet Commissioning Adapter: Includes BACnet Internet Protocol (IP) to MS/TP adapter, Ethernet cable, and Universal Serial Bus (USB) cable (USB port required for powering the adapter) |
| LN-75010 |
LONWORKS Commissioning Adapter: Includes USB to LONWORKS TP/FT-10 Network Interface |
| IU-9100-8401 |
RS-232 to RS-485 Converter: 230 VAC (Europe only) |
| LP-KIT100-000C |
FX Programming Key |
| DT-9100-8901 |
Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe Only) |
Accessories
| Product Code Number |
Description |
| LP-KIT007-001C |
Interface Cable for standard land-line modem, 1.5 m (4.9 ft) |
| LP-KIT007-002C |
Interface Cable for GSM modem, 1.5 m (4.9 ft) |
| LP-KIT007-013C |
Null modem cable for computer connection, 3 m (9.8 ft) |
| LP-KIT007-014C |
Null modem cable for computer connection, 15 m (49.2 ft) |
| LP-KIT007-020C |
Replacement communication wiring connectors kit |
| LP-KIT014-000C |
Replacement input/output wiring connectors kit |
Допуски та стандарти
- Europe – 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-2
- Europe – 2006/95/EEC, Low Voltage Directive: EN 60730
- Canada – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
- Canada – Industry Canada, ICES-003
- United States – UL Listed (PAZX), UL 916, Energy Management Equipment
- United States – FCC compliant to CFR 47, Part 15, Subpart B, Class A
Позиції каталогу з цим документом
Текст документа
Code No. LIT-1900407
Issued January 22, 2010
Facility Explorer
FX14 Field Controller
Description Using the FX Tools software package, you
can program the FX14 field controller to
The FX14 is a high performance field
operate a wide variety of commercial HVACR
controller designed specifically for commercial
equipment, including multi-compressor and
Heating, Ventilating, Air Conditioning, and
scroll compressors, close control units, unit
Refrigeration (HVACR) applications.
ventilators and packaged rooftop units.
The FX14 supports 29 physical inputs and
Refer to the FX14 Field Controller Product
outputs including a wide range of sensors and
Bulletin (LIT-12011163) for important product
actuating devices. The FX14 includes an
application information.
onboard real-time clock to support the
start-stop scheduling of equipment, real-time
based control sequences, and the time
Features FX14 Field Controller
stamping of events and trend records. • freely programmable controller
The FX14 can be fitted with an N2 Open,
• network communication card options - N2 Repair Information
Open, LONWORKS, and BACnet Protocols If the FX14 Field Controller fails to operate
LONWORKS®, or BACnet® communication
card to integrate the controller into a • remote communication services within its specifications, replace the unit. For a
compatible Building Automation System • choice of user interfaces: integral or replacement controller, contact the nearest
(BAS). Alternatively, the FX14 can be fitted remote Johnson Controls® representative.
with an RS-232C serial communication card to • onboard real-time clock
transmit event notification messages via Short • selectable analog input types in software
Messaging Service (SMS) through a Global • analog outputs with Pulse Width
System for Mobile (GSM) modem. Modulation (PWM) option
• models with various output configurations
of solid-state triacs and line voltage relays
• Network Room Module (NRM)
Selection Charts
FX14 Controllers Ordering Information
Product Code Number Description
LP-FX14D10-000C FX14: 6 Analog Inputs (AIs), 12 Digital (Binary) Inputs (DIs), 2 Analog Outputs (AOs) (0-10 V or PWM), and 9 Digital (Binary)
Outputs (DOs) (5 Relays and 4 Triacs), no communication card
LP-FX14D11-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), N2 Open card
LP-FX14D12-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), LONWORKS card
LP-FX14D13-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), RS-232C card
LP-FX14D14-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), BACnet card
LP-FX14D60-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface, no communciation
card
LP-FX14D61-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and N2 Open card
LP-FX14D62-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and LONWORKS card
LP-FX14D63-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and RS-232C card
LP-FX14D64-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and BACnet card
LP-FX14D20-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), no communciation card
LP-FX14D21-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), N2 Open card
LP-FX14D22-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), LONWORKS card
LP-FX14D23-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), RS-232C card
LP-FX14D24-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), BACnet card
LP-FX14D70-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface, no communciation card
LP-FX14D71-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and N2 Open card
LP-FX14D72-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and LONWORKS card
LP-FX14D73-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and RS-232C card
LP-FX14D74-000C FX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and BACnet card
FX14 Communications Cards Ordering Information
Product Code Numbers Description
LP-NET151-010C N2 Open communication card for FX14 Rev. A
LP-NET142-000C LONWORKS communication card for FX14 Rev. A
LP-NET163-000C RS-232C communication card for FX14 Rev. A
LP-NET164-000C BACnet communication card for FX14 Rev. B only
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc. www.johnsoncontrols.com
1 of 4
FX14 Field Controller (Continued)
TM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
Product Code Number Description
TM-2140-0000 Room Command Module, temperature sensor only
TM-2150-0000 Room Command Module, occupancy button and LED
TM-2160-0000 Room Command Module, 12-28°C setpoint dial, occupancy button and LED
TM-2160-0002 Room Command Module, 12-28°C setpoint dial, occupancy button and LED, fan speed override
TM-2160-0005 Room Command Module, ± setpoint dial, occupancy button and LED
TM-2160-0007 Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override
TM-2190-0000 Room Command Module, 12-28°C setpoint dial
TM-2190-0005 Room Command Module, ± setpoint dial
Network Room Modules Ordering Information (Available in Europe)
Product Code Features/Options
Size (mm) Service Port LCD Display Temperature Fan Speed °F/°C Addressable
Type Adjust Dial Selector
Button
LP-NRM001-000C 80 x 80 Program Key No No No No No
LP-NRM002-000C Yes Yes No No No
LP-NRM003-000C Yes Yes Yes No No
LP-NRM511-000C MUI No No No No Yes
LP-NRM502-000C Yes Yes No No No
LP-NRM503-000C Yes Yes Yes No No
TM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
Product Code Number Description
TM-2141-0000 Room Command Module, temperature sensor only
TM-2151-0000 Room Command Module, occupancy button and LED
TM-2161-0000 Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED
TM-2161-0002 Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED, fan speed override
TM-2161-0005 Room Command Module, ± setpoint dial, occupancy button and LED
TM-2161-0007 Room Command Module, ± setpoint dial, occupancy button and LED, fan speed override
TM-2191-0000 Room Command Module, 54-82°F/12-28°C setpoint dial
TM-2191-0005 Room Command Module, ± setpoint dial
Network Room Modules Ordering Information (Available in North America)
Product Code Features/Options
Size, mm Service Port LCD Display Temperature Fan Speed °F/°C Addressable
(inch) Type Adjust Dial Selector
Button
LP-NRM511-000C 80 x 80 MUI No No No No Yes
LP-NRM552-000C (3.15 x 3.15 in.) Yes Yes No Yes No
LP-NRM553-000C Yes Yes Yes Yes No
LP-NRM611-000C 120 x 80 MUI No No No No Yes
LP-NRM652-000C (4.72 x 3.15 in.) Yes Yes No Yes No
LP-NRM653-000C Yes Yes Yes Yes No
Medium User Interfaces Ordering Information
Product Code Numbers Description
LP-DIS60P20-0C Medium User Interface display (non-isolated version); can be mounted up to 3 m (9.8 ft) from the FX14 and includes panel
mounting hardware.
LP-DIS60P21-0C Medium User Interface display (isolated version); can be mounted up to 300 m (984 ft) from the FX14 and includes panel and
wall mounting hardware.
LP-KIT007-000C Link cable for the connection of the FX14 to the Panel Mount MUI display - 3 m (9.8 ft)
Programming/Commissioning Tools Ordering Information (Part 1 of 2)
Product Code Numbers Description
LP-FXTPRO-0 FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) – New User
LP-FXTPRO-6 FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) - Upgrade
LP-KIT200-000C N2 Commissioning Adapter: Includes port powered RS-232 to RS-485 converter and wiring harness with mating connectors for
FX Field Controller supervisory link interface.
LP-KIT204-000C BACnet Commissioning Adapter: Includes BACnet Internet Protocol (IP) to MS/TP adapter, Ethernet cable, and Universal Serial
Bus (USB) cable (USB port required for powering the adapter).
LN-75010 LONWORKS Commissioning Adapter: Includes USB to LONWORKS TP/FT-10 Network Interface
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc. www.johnsoncontrols.com
2 of 4
FX14 Field Controller (Continued)
Programming/Commissioning Tools Ordering Information (Part 2 of 2)
Product Code Numbers Description
IU-9100-8401 RS-232 to RS-485 Converter: 230 VAC (Europe only)
LP-KIT100-000C FX Programming Key
DT-9100-8901 Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe Only)
Accessories
Product Code Numbers Description
LP-KIT007-001C Interface Cable for standard land-line modem, 1.5 m (4.9 ft)
LP-KIT007-002C Interface Cable for GSM modem, 1.5 m (4.9 ft)
LP-KIT007-013C Null modem cable for computer connection, 3 m (9.8 ft)
LP-KIT007-014C Null modem cable for computer connection, 15 m (49.2 ft)
LP-KIT007-020C Replacement communication wiring connectors kit
LP-KIT014-000C Replacement input/output wiring connectors kit
Technical Specifications
I/O Details
Terminals Channel Type Remark/Application
Analog Input (AI)
TB1 (1-15) AI1, AI2, AI3, AI4, See Analog Input table. Freely software configurable
AI5, AI6 16-bit resolution Application: temperature, humidity, or pressure
TB1 (3,8,13) AI V Ref 16 V, max. 20 mA or To power active 0-10 V sensors or potentiometers or
5 V, max. 15 mA To power ratiometric sensors or potentiometers
(jumper selection)
Digital Input (DI)
TB2 (21-36) DI1, DI2, DI3, DI4, Potential free contacts Transition counter function, maximum 10 ms on and 10 ms off (at 50 Hz).
DI5, DI6, DI7, DI8,
DI9, DI10, DI11,
DI12
Digital Output (DO)
Relay Outputs Dielectric test voltage on open relay contact: 1,000 VAC Root Mean Square (RMS)
Maximum relay switching rate at nominal load: six operations/min.
TB6 (41-48) DO1, DO2, DO3 Single Pole Single Throw Max. switching power (relays):
(SPST) 6(3)A, 250 V relays Motor: 0.5 hp 230 VAC, 0.25 hp 120 VAC
TB7 (51-55) DO4, DO5 SPST 6(3)A, 250 V relays Rating (resistive): 6A 125 VAC, 6A 30 VDC, 6A 250 VAC
TB7 (57-58) DO6 SPST 6(3)A, 250 V relay or UL tested life (min. operations): 30,000 operations
0.5 A, 24 VAC triac (at 360 operations x hour)
Dielectric strength coil-contacts: 4,000 V RMS for 1 minute
TB8 (61-68) DO7, DO8, DO9 SPST 6(3)A, 250 V relays or
0.5 A, 24 VAC triacs
Analog Output (AO)
TB9 (71) AO V Ref 15 VDC, max. 10 mA Voltage Reference signal used for PWM output.
TB9 (72-73) AO1 0-10 VDC, max. 3 mA or PWM, Used to drive motor actuator, control device, or fan speed controller. 13-bit resolution.
100 Hz
TB10 (74) AO V Ref 15 VDC, max. 10 mA Voltage Reference signal used for PWM output.
TB10 (75-76) AO2 0-10 VDC, max. 3 mA or Used to drive motor actuator, control device, or fan speed controller. 13-bit resolution.
PWM, 100 Hz
Analog Input Types
Sensor Type Linearization Range Accuracy at 20°C (68°F) Ambient (Sensor Not Included)
A99 -50 to 100°C (-58 to 212°F) ±0.5°C (1°F)
NTC 10k -40 to 150°C (-40 to 300°F) ±0.5°C (1°F)
Pt 1000 -50 to 160°C (-58 to 320°F) ±0.5°C (1°F)
Ni 1000 (Johnson Controls) -45 to 120°C (-49 to 248°F) ±0.5°C (1°F)
Active Voltage 0-10 VDC ±0.05 VDC
Active Ratiometric 0.5-4.5 VDC ±0.05 VDC
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc. www.johnsoncontrols.com
3 of 4
FX14 Field Controller (Continued)
FX14 Field Controller
Product Codes LP-FX14Dxx-xxx
Power Supply Requirements 24 VAC ±15%, 50/60 Hz – Safety Extra-Low Voltage (SELV) in Europe - Class 2 North America
Power Consumption 19.5 VA at max. load
Housing Material ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating
Protection Class IP20 CEI/EN60529
Ambient Operating Conditions -40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing)
Integral user interface does not operate below -20°C (-4°F).
Ambient Storage Conditions -40°C (-40°F) to 70°C (158°F), 10 to 95% RH (noncondensing)
Weight (with Package) 0.74 kg (1.6 lb)
Real-Time Clock Accuracy: better than ±200 ms per day at constant ambient temperature of 25°C
Back up: minimum 10 days without power at 25°C
Integrated LCD Display Numeric Resolution -999 to 999 or -99.9 to 99.9
Connection Terminals for AIs, DOs and Screw terminals for max. 2 x 1.5 mm2 (16 AWG) wires, included in the package.
Power Supply
Connection Terminals for AOs, DIs and Screw terminals for max. 1 x 1.5 mm2 (16 AWG) wires included in the package.
Remote Display
Connection Terminals for LON/ N2 Open/ Screw terminals for max. 1 x 1.5 mm2 (16 AWG) wires or 2 x Belden® cable, 2-core twisted pair with shield
BACnet Networks ≥0.8 mm (20 AWG), included in the package.
BACnet Compliance BACnet Testing Laboratories™ (BTL) Listing
BACnet Interoperability Building Blocks (BIBBs):
BACnet Advanced Application Controller (B-AAC)
Protocol Implementation Conformance Statement (PICS) available on request
Agency Compliance Europe – 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-2
– 2006/95/EEC, Low Voltage Directive: EN 60730
Canada – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
– Industry Canada, ICES-003
United States – UL Listed (PAZX), UL 916, Energy Management Equipment
– FCC compliant to CFR 47, Part 15, Subpart B, Class A
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2010 Johnson Controls, Inc. www.johnsoncontrols.com
4 of 4
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.