The FX06 is a freely programmable compact field controller for commercial HVACR applications, with 17 physical I/O points and an onboard real-time clock for start-stop scheduling, time-stamped events and trend records. It integrates into a Building Automation System via an optional N2 Open or LONWORKS communication module, or sends SMS event notifications through an RS-232C module and GSM modem. An integral LCD user interface is included, with an optional remote Medium User Interface (MUI).

Ключові дані

Power supply24 VAC/VDC ±15%, 50/60 Hz
Analog inputs4 (16-bit ADC, 13-bit effective resolution)
Binary inputs5
Analog outputs2 x 0-10 VDC (3 mA max.)
Relay outputs6 SPST 3(1)A, 250 VAC (model P00) or 4 relays + 2 triacs (model P20)
Ambient operating conditions-40 to 50°C (-40 to 122°F), 10 to 95% RH (noncondensing)
Protection classFront plate IP55 (panel mounted); rear IP20, IEC 60529
Network optionsN2 Open or LONWORKS communication module; RS-232C module for SMS via GSM modem

Застосування

  • Small refrigeration compressors
  • Close control units
  • Packaged rooftop units
  • Fan coil units
  • Unit ventilators
  • Chilling or heating ceiling beam installations

Особливості

  • Freely programmable controller
  • Network communication module options: N2 Open or LONWORKS protocols
  • Remote communication services (SMS via GSM modem)
  • Integral Liquid Crystal Display (LCD) user interface with four control buttons
  • Optional remote user interface (MUI)
  • Models with various output configurations of solid-state triacs and line voltage relays
  • Network Room Module (NRM) support

Технічні дані

Parameter Value
Product codes LP-FX06Pxx-xxxC
Power supply requirements 24 VAC/VDC ±15%, 50/60 Hz - SELV (Europe), Class 2 North America
Power consumption Controller: 7 VA maximum (additional 3 VA if MUI connected)
Housing material ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating
Protection class Front plate (when mounted in panel) IP55; Rear enclosure IP20, IEC 60529
Ambient operating conditions -40 to 50°C (-40 to 122°F), 10 to 95% RH (noncondensing); integral UI does not operate below -20°C (-4°F)
Ambient storage conditions -40 to 70°C (-40 to 158°F), 10 to 95% RH (noncondensing)
Dimensions (H x W x D) 44 mm (1.7 in.) x 70 mm (2.7 in.) x 95 mm (3.6 in.)
Weight 0.32 kg (0.7 lb) incl. communication module; 0.68 kg (1.5 lb) incl. communication module and cable set
Real-time clock accuracy Better than ±200 ms per day at constant ambient temperature of 25°C
RTC backup Minimum 10 days without power at 25°C
Integral LCD display resolution -999 to 999 or -99.9 to 99.9 (4 digits per row)
Analog inputs AI1–AI4 Software configurable; temperature, humidity, pressure; 16-bit ADC, 13-bit effective resolution
AI power +5 V at 15 mA max.; +15 V at 20 mA max.
Sensor input A99 -50 to 100°C (-58 to 212°F), ±0.5°C (±1°F) accuracy at 20°C (68°F)
Sensor input NTC 10k -40 to 150°C (-40 to 300°F), ±0.5°C (±1°F)
Sensor input PT1000 Extended -50 to 160°C (-58 to 320°F), ±0.5°C (±1°F)
Sensor input Ni1000 (Johnson Controls) -45 to 120°C (-49 to 248°F), ±0.5°C (±1°F)
Active voltage input 0-10 VDC, ±0.05 VDC
Active ratiometric input 0.5-4.5 VDC, ±0.05 VDC
Digital inputs DI1–DI5 Potential free contacts; transition counter at 50 Hz max.; min. ON/OFF time 10 ms
Relay outputs (FX06P0x DO1–DO6) SPST power relay 3(1)A, 250 VAC, independent contacts
Triac outputs (FX06P2x DO1, DO2) 0.5 A/24 VAC triacs for 3-point incremental/thermal actuators
Relay dielectric strength coil-contacts 4,000 V RMS for 1 minute
Dielectric test voltage on open relay contact 1,000 VAC RMS
Max. relay switching rate at max. load 6 operations/minute
Average relay contact life 30,000 operations at maximum load
Analog outputs AO1, AO2 0-10 VDC (3 mA max.)
Power supply outputs 24 VAC/DC for panel mount MUI; 15 VDC 20 mA for active sensors/PWM; 5 VDC 15 mA for ratiometric sensors
Connections Removable plug connectors
Cable length for inputs Max. 100 m (330 ft.) with cables ≥ 0.6 mm, 22 AWG
N2 Open bus RS-485, 9600 baud; max. segment length without repeater 1,200 m (4,000 ft); max. 32 devices per segment; max. 2 repeaters (RP-9100 recommended)
N2 end-of-line termination 220 ohm at each end of segment >100 m (300 ft); one 220 ohm if <100 m
Electrical isolation in FX06 (N2) 500 V
LON topology Daisy chained bus (two 100 ohm terminators) or free/star topology (single 50 ohm terminator)
LON number of nodes 64 (without repeaters), FTT-10 nodes only
LON cable lengths (bus / free topology) Belden 85102: 2,700 m / 500 m; Belden 8471: 2,700 m / 500 m; Level IV 22 AWG: 1,400 m / 400 m

Варіанти замовлення

Controllers

Code Description
LP-FX06P00-020C FX06 Compact Field Controller, new style wiring connector: 4 AIs, 5 BIs, 2 0-10 VDC analog outputs, 6 relay BOs
LP-FX06P20-020C FX06 Compact Field Controller, new style wiring connector: 4 AIs, 5 BIs, 2 0-10 VDC analog outputs, 4 BOs, 2 triac BOs

Communication modules

Code Description
LP-NET061-000C N2 Open Communication Module
LP-NET062-000C LONWORKS Communication Module
LP-NET063-000C RS232C Communication Module

User interfaces

Code Description
LP-DIS60P20-0C Remote Medium User Interface (MUI V3) for FX06 - Panel Mount
LP-DIS60P21-0C Remote Medium User Interface (MUI V3) for FX06 - Wall Mount
LP-KIT007-005C Link cable FX06 to Panel Mount MUI display or NRM module, 3 m (9.8 ft)

Accessories

Code Description
LP-KIT006-020C Wiring Harness with new style wiring connector, 1.5 m length
LP-KIT006-025C Wiring Harness with new style wiring connector, 5.0 m length
LP-KIT100-000C FX Programming Key
DT-9100-8901 Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe only)
NP-PWR1209 Power Supply Adapter for Programming Key 120 VAC/12 VDC (North America only)
IU-9100-8401 Converter RS-232C/RS-485 (N2) 230 VAC (Europe only)
LP-KIT007-001C Interface cable for standard landline modem, 1.5 m (4.9 ft)
LP-KIT007-002C Interface Cable for GSM modem to FX06, 1.5 m (4.9 ft)
LP-KIT007-013C Null modem cable for computer connection, 3 m (9.8 ft)
LP-KIT007-014C Null modem cable for computer connection, 15 m (49.2 ft)
LP-KIT007-020C Bag of replacement communication wiring connectors (N2 and LON)
LP-KIT200-000C N2 Commissioning Adapter: port powered RS-232C to RS-485 converter, 3 m (9.8 ft) cable, mating connectors for FX05/FX06/FX07/FX14/FX15/FX16/FXVMA
LP-KIT090-000C GSM 900/1800 Supreme 10 FastTrack Modem
LP-KIT090-001C GSM Modem Plug-in Antenna
LP-KIT090-003C GSM Modem Magnetic Mount Antenna with 2.5 m (8.2 ft) Cable
LP-KIT090-004C GSM Modem Panel Mount Antenna with 5 m (16.4 ft) Cable
LP-KIT090-005C GSM Modem Power Adapter, 230 VAC/12 VDC, Wall Plug
NS-WALLPLATE-0 Wall plate kit for mounting 80 x 80 mm sensor onto 51 x 102 mm wall box

Room Command Modules, TM Series without Display - 80 x 80 mm (3.15 x 3.15 in.), °C

Code Description
TM-2140-0000 Room Sensor Module, temperature sensor only
TM-2150-0000 Room Sensor Module, occupancy button and LED
TM-2160-0000 Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED
TM-2160-0002 Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED, fan speed override
TM-2160-0005 Room Sensor Module, +/- setpoint dial, occupancy button and LED
TM-2160-0007 Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override
TM-2190-0000 Room Sensor Module, 12-28°C setpoint dial
TM-2190-0005 Room Sensor Module, +/- setpoint dial

Room Command Modules, TM Series without Display - North America - 120 x 80 mm (4.72 x 3.15 in.), °C/°F

Code Description
TM-2141-0000 Room Sensor Module, temperature sensor only
TM-2151-0000 Room Sensor Module, occupancy button and LED
TM-2161-0000 Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED
TM-2161-0002 Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED, fan speed override
TM-2161-0005 Room Sensor Module, +/- setpoint dial, occupancy button and LED
TM-2161-0007 Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override
TM-2191-0000 Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial
TM-2191-0005 Room Sensor Module, +/- setpoint dial

Network Room Modules (Europe)

Code Size Service Port LCD Temp Adjust Dial Fan Speed Selector °F/°C Button Addressable
LP-NRM001-000C 80 x 80 No No No No No No
LP-NRM002-000C 80 x 80 Yes Yes No No No No
LP-NRM003-000C 80 x 80 Yes Yes Yes No No No
LP-NRM511-000C 80 x 80 No No No No No Yes¹
LP-NRM502-000C 80 x 80 Yes Yes No No No No
LP-NRM503-000C 80 x 80 Yes Yes Yes No No No

Network Room Modules (North America)

Code Size Service Port LCD Temp Adjust Dial Fan Speed Selector °F/°C Button Addressable
LP-NRM511-000C 80 x 80 mm (3.15 x 3.15 in.) No No No No No Yes¹
LP-NRM552-000C 80 x 80 mm Yes Yes No Yes No No
LP-NRM553-000C 80 x 80 mm Yes Yes Yes Yes No No
LP-NRM611-000C 120 x 80 mm (4.72 x 3.15 in.) No No No No No Yes¹
LP-NRM652-000C 120 x 80 mm Yes Yes No Yes No No
LP-NRM653-000C 120 x 80 mm Yes Yes Yes Yes No No

¹ The FX06 controller only supports one connected NRM; the addressing feature is not used.

Software

Code Description
LP-FXTPRO-0 FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - New User Version
LP-FXTPRO-6 FX Tools Pro CD-ROM (same contents) - Upgrade Version

Допуски та стандарти

  • Europe: 2004/108/EEC EMC Directive: EN 61000-6-3, EN 61000-6-2; 2006/95/EEC Low Voltage Directive: EN 60730
  • Canada: UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada ICES-003
  • United States: UL Listed (PAZX), UL 916, Energy Management Equipment; FCC compliant to CFR 47, Part 15, Subpart B, Class A
  • FX Programming Key: 2004/108/EEC EMC Directive: EN 61000-6-3, EN 61000-6-2

Позиції каталогу з цим документом

Текст документа

                                                                                                                                                  Code No. LIT-1900406
                                                                                                                                                  Issued October 19, 2012

Facility Explorer
FX06 Field Controller
Description                                                      Using the FX Tools software package, you
                                                                 can program the FX06 field controller to
The FX06 is a high performance field
                                                                 operate a wide variety of commercial HVACR
controller designed specifically for commercial
                                                                 equipment; including small refrigeration
Heating, Ventilating, Air Conditioning, and
                                                                 compressors, close control units, packaged
Refrigeration (HVACR) applications.
                                                                 rooftop units, fan coil units, unit ventilators,
The FX06 supports 17 physical inputs and                         and chilling or heating ceiling beam
outputs including a wide range of sensors and                    installations.
actuating devices. The FX06 includes an
                                                                 Note: This document applies to the LP-
onboard real-time clock to support the
                                                                 FX06Pxx-020C models only.                                                       FX06 Field Controller
start-stop scheduling of equipment, real-time
based control sequences, and time stamping                       Refer to the FX06 Field Controller Product
events and trend records.                                        Bulletin (LIT-12011165) for important product                    Repair Information
                                                                 application information.
With the integral user interface, you can                                                                                         If the FX06 Field Controller fails to operate
locally monitor and adjust the FX06’s                            Features                                                         within its specifications, replace the unit. For a
operation. The FX06 also supports a remote                                                                                        replacement controller, contact the nearest
                                                                 •   freely programmable controller                               Johnson Controls® representative.
panel- or wall-mountable Medium User
Interface (MUI) for remote monitoring and                        •   network communication module options:
adjustment.                                                          N2 Open, or LONWORKS protocols
                                                                 •   remote communication services
The FX06 can be fitted with an N2 Open or
                                                                 •   integral Liquid Crystal Display (LCD) user
LONWORKS® communication module to                                    interface with four control buttons
integrate the controller into a compatible
                                                                 •   optional remote user interface
Building Automation System (BAS).
Alternatively, the FX06 can be fitted with an                    •   analog outputs
RS-232C serial communication module to                           •   models with various output configurations
transmit event notification messages via Short                       of solid-state triacs and line voltage relays
Messaging Service (SMS) through a Global                         •   Network Room Module (NRM)
System for Mobile (GSM) modem.



Selection Charts
FX06 Field Controller Ordering Information
Product Code Number Description
LP-FX06P00-020C                   FX06 Compact Field Controller with new style wiring connector: Includes 4 Analog Inputs (AIs), 5 Binary Inputs (BIs), 2 0-10 VDC
                                  Analog Outputs, and 6 relay Binary Outputs (BOs)
LP-FX06P20-020C                   FX06 Compact Field Controller with new style wiring connector: Includes 4 AIs, 5 BIs, 2 0-10 VDC Analog Outputs, 4 BOs, and 2 triac
                                  BOs

Communication Module Ordering Information
Product Code Number Description
LP-NET061-000C                     N2 Open Communication Module
LP-NET062-000C                     LONWORKS Communication Module
LP-NET063-000C                     RS232C Communication Module

User Interfaces
Product Code Number Description
LP-DIS60P20-0C                     Remote Medium User Interface (MUI V3) for FX06 - Panel Mount
LP-DIS60P21-0C                     Remote Medium User Interface (MUI V3) for FX06 - Wall Mount
LP-KIT007-005C                     Link cable for the connection of the FX06 to the Panel Mount MUI display or NRM module, 3 m (9.8 ft)

FX06 Accessories (Part 1 of 2)
Product Code Number Description
LP-KIT006-020C                     Wiring Harness with new style wiring connector, 1.5 m length
LP-KIT006-025C                     Wiring Harness with new style wiring connector, 5.0 m length
LP-KIT100-000C                     FX Programming Key
DT-9100-8901                       Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe only)
LP-KIT007-001C                     Interface cable for standard landline modem, 1.5 m (4.9 ft)
LP-KIT007-013C                     Null modem cable for computer connection, 3 m (9.8 ft)
LP-KIT007-014C                     Null modem cable for computer connection, 15 m (49.2 ft)
LP-KIT007-020C                     Bag of replacement communication wiring connectors (N2 and LON).
LP-KIT200-000C                     N2 Commissioning Adapter: Includes port powered RS-232C to RS-485 converter, 3 m (9.8 ft) cable, and mating connectors for
                                   FX05, FX06, FX07, FX14, FX15, FX16, and FXVMA.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       1 of 5
FX06 Field Controller (Continued)

FX06 Accessories (Part 2 of 2)
Product Code Number Description
 IU-9100-8401                       Converter RS-232C/RS-485 (N2) 230 VAC (Europe only)
 NP-PWR1209                         Power Supply Adapter for Programming Key 120 VAC/12 VDC (North America only)

GSM Modem and Accessories
Product Code Number Description
 LP-KIT007-002C                     Interface Cable for GSM modem to FX06, 1.5 m (4.9 ft)
 LP-KIT090-000C                     GSM 900/1800 Supreme 10 FastTrack Modem
 LP-KIT090-001C                     GSM Modem Plug-in Antenna
 LP-KIT090-003C                     GSM Modem Magnetic Mount Antenna with 2.5 m (8.2 ft) Cable
 LP-KIT090-004C                     GSM Modem Panel Mount Antenna with 5 m (16.4 ft) Cable
 LP-KIT090-005C                     GSM Modem Power Adapter, 230 VAC/12 VDC, Wall Plug

 Room Command Modules, TM Series without Display - 80 x 80 mm (3.15 x 3.15 in.), °C
 Product Code Number Description
 TM-2140-0000                       Room Sensor Module, temperature sensor only
 TM-2150-0000                       Room Sensor Module, occupancy button and Light-Emitting Diode (LED)
 TM-2160-0000                       Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED
 TM-2160-0002                       Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED, fan speed override
 TM-2160-0005                       Room Sensor Module, +/- setpoint dial, occupancy button and LED
 TM-2160-0007                       Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override
 TM-2190-0000                       Room Sensor Module, 12-28°C setpoint dial
 TM-2190-0005                       Room Sensor Module, +/- setpoint dial

Network Room Modules Ordering Information (Available in Europe)
Product Code                                                                                                Features/Options
                                                   Size (mm)             Service Port           LCD Display Temperature                   Fan Speed          °F/°C        Addressable
                                                                         Type                               Adjust Dial                   Selector
                                                                                                                                          Button
 LP-NRM001-000C                                    80 x 80               Program Key            No                  No                    No                 No           No
 LP-NRM002-000C                                                                                 Yes                 Yes                   No                 No           No
 LP-NRM003-000C                                                                                 Yes                 Yes                   Yes                No           No
 LP-NRM511-000C                                                          MUI                    No                  No                    No                 No           Yes1
 LP-NRM502-000C                                                                                 Yes                 Yes                   No                 No           No
 LP-NRM503-000C                                                                                 Yes                 Yes                   Yes                No           No
1. The FX06 controller only supports one connected NRM and therefore the addressing feature is not used.

Room Command Modules - Available in North America - TM Series without Display - 120 x 80 mm (4.72 x 3.15 in.), °C/°F
Product Code Number Description
 TM-2141-0000                       Room Sensor Module, temperature sensor only
 TM-2151-0000                       Room Sensor Module, occupancy button and LED
 TM-2161-0000                       Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED
 TM-2161-0002                       Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED, fan speed override
 TM-2161-0005                       Room Sensor Module, +/- setpoint dial, occupancy button and LED
 TM-2161-0007                       Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override
 TM-2191-0000                       Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial
 TM-2191-0005                       Room Sensor Module, +/- setpoint dial

Network Room Modules Ordering Information (Available in North America)
Product Code                                                           Features/Options
                                                   Size, mm              Service Port           LCD Display Temperature                  Fan Speed           °F/°C      Addressable
                                                   (inch)                Type                               Adjust Dial                  Selector
                                                                                                                                         Button
 LP-NRM511-000C                                    80 x 80 mm            MUI                    No                  No                   No                  No          Yes1
 LP-NRM552-000C                                    (3.15 x 3.15 in.)                            Yes                 Yes                  No                  Yes        No
 LP-NRM553-000C                                                                                 Yes                 Yes                  Yes                 Yes        No
 LP-NRM611-000C                                    120 x 80 mm           MUI                    No                  No                   No                  No          Yes1
 LP-NRM652-000C                                    (4.72 x 3.15 in.)                            Yes                 Yes                  No                  Yes        No
 LP-NRM653-000C                                                                                 Yes                 Yes                  Yes                 Yes        No
1. The FX06 controller only supports one connected NRM and therefore the addressing feature is not used.


The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       2 of 5
FX06 Field Controller (Continued)

Sensor Accessories
Product Code Number Description
 NS-WALLPLATE-0                     Wall plate kit used to mount an 80 x 80 mm (3.15 x 3.15 in.) sensor onto a 51 x 102 mm (2 x 4 in.) wall box

Software Ordering Information
Product Code Number Description
 LP-FXTPRO-0                        FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - New
                                    User Version
 LP-FXTPRO-6                        FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - Upgrade
                                    Version

Technical Specifications
                                                                                  Analog Inputs (AI)
 Terminal/Channel                   Type                                                           Remark/Application
 AI1, AI2, AI3, AI4                 See Sensor Input Types in this table                           Software configurable. Application: temperature, humidity, pressure. 16-bit
                                                                                                   ADC, 13-bit effective resolution.
 AI Power                           +5 V at 15 mA max.                                             To power active or ratiometric sensors directly from the controller.
 AI/AO Power                        +15 V at 20 mA max.                                            To power active sensors directly from the controller.
 Sensor Input Types
 Sensor Type                        Full Linearization Range                                       Accuracy at 20°C (68°F) - Controller and Sensor
                                                                                                   (sensor accuracy not included)
 A99                                -50 to 100°C (-58 to 212°F)                                    ±0.5°C (±1°F)
 NTC 10k                            -40 to 150°C (-40 to 300°F)                                    ±0.5°C (±1°F)
 PT1000 Extended                    -50 to 160°C (-58 to 320°F)                                    ±0.5°C (±1°F)
 Ni1000                             -45 to 120°C (-49 to 248°F)                                    ±0.5°C (±1°F)
 (Johnson Controls®
 temperature sensor)
 Active Voltage                     0-10 VDC                                                       ±0.05 VDC
 Active Ratiometric                 0.5-4.5 VDC                                                    ±0.05 VDC

                                                                            Digital (Binary) Inputs (DI)
 Terminal/Channel                  Type                                                            Remark/Application
 DI1, DI2, DI3, DI4, DI5           Potential free contacts for status monitoring                   Status and events
                                   Transition Counter at 50 Hz max.                                Minimum Time ON: 10 ms
                                                                                                   Minimum Time OFF: 10 ms

                                                                           Digital (Binary) Outputs (DO)
 Digital (Binary)             Model                       Channel                   Type                               Remark/Application
 Outputs for
 Selected Models
                              FX06P0x                     DO1 - DO6                 SPST 3(1)A, 250 VAC                Each relay contact is independent with its own terminals
                                                                                    power relay
                              FX06P2x                     DO1, DO2                  0.5A/24 VAC triacs                 3-point incremental actuators, thermal actuators, and other
                                                                                                                       actuators
                                                          DO3 - DO6                 SPST 3(1)A, 250 VAC                Each relay contact is independent with its own terminals.
                                                                                    power relay
 Relay Outputs                Dielectric strength coil-contacts: 4,000 V RMS for 1 minute
                              Dielectric test voltage on open relay contact:1,000 VAC RMS
                              Maximum relay switching rate at maximum load: 6 operations/minute
                              Average relay contact life: 30,000 operations at maximum load

                                                                                 Analog Output (AO)
 Terminal/Channel                         Type                                                                       Remark/Application
 AO1, AO2                                 0-10 VDC (3 mA max.)                                                       Actuators and control devices

                                                                                     FX06 Controller
 Product Codes                                        LP-FX06Pxx-xxxC
 Power Supply Requirements                            24 VAC/VDC ±15%, 50/60 Hz - Safety Extra-Low Voltage (SELV) (Europe) - Class 2 North America
 Power Consumption                                    Controller: 7 VA maximum (Additional 3VA if MUI is connected)
 Housing Material                                     ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating
 Protection Class                                     Front Plate (when mounted in panel) IP55; Rear Enclosure IP20, IEC 60529
 Ambient Operating Conditions                         -40 to 50°C (-40 to 122°F), 10 to 95% RH (noncondensing)
                                                      Note that the integral user interface does not operate below -20°C (-4°F).


The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       3 of 5
FX06 Field Controller (Continued)

                                                                                    FX06 Controller
Ambient Storage Conditions                           -40 to 70°C (-40 to 158°F), 10 to 95% RH (noncondensing)
Dimensions (H x W x D)                               44 mm (1.7 in.) x 70 mm (2.7 in.) x 95 mm (3.6 in.)
Weight (with package)                                0.32 kg (0.7 lb) including communication module
                                                     0.68 Kg (1.5 lb) including communication module and cable set
Real-Time Clock                                      Accuracy: Better than ± 200 ms per day at constant ambient temperature of 25°C
                                                     Backup: Minimum 10 days without power at 25°C
Integral LCD Display Resolution                      -999 to 999 or -99.9 to 99.9 (4 digits for each row)
I/O Ratings                                          See the I/O tables in the Technical Specifications section.
Power Supply Outputs                                 24 VAC/DC for panel mount MUI (from controller power supply input)
                                                     15 VDC 20 mA power supply for active sensors and PWM output
                                                     5 VDC 15 mA power supply for ratio-metric sensors
Connections                                          Removable plug connectors. Mating connectors and cables provided with controller or available to order. See FX06
                                                     Field Controller Ordering Information and FX06 Accessories.
Cable Length for Inputs                              Max. 100 m (330 ft.) with cables ≥ 0.6 mm, 22 AWG
Agency Compliance                                    Europe
                                                     2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000 6 2
                                                     2006/95/EEC, Low Voltage Directive: EN 60730.
                                                     Canada
                                                     UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
                                                     Industry Canada, ICES-003
                                                     United States
                                                     UL Listed (PAZX), UL 916, Energy Management Equipment
                                                     FCC compliant to CFR 47, Part 15, Subpart B, Class A

                                                                             N2 Open Communication
RS-485 Bus - 9600 Baud                              Maximum bus segment length without repeater: 1,200 m (4,000 ft), 0.8/0.6 mm diameter (20/22 AWG) 2 x twisted pair
                                                    with shield. Use the same cable type throughout segment.
Number of Devices                                   Maximum of 32 devices on a bus segment without repeater
Repeaters                                           Maximum 2 repeaters between the master (supervisory) device and any slave (FX controller) device on the network.
                                                    RP-9100 is recommended.
End-of-Line Termination                             220 ohm at each end of segment >100 m (300 ft). For segment <100 m (300 ft), only one 220 ohm termination is
                                                    required.
RS-485/RS-232C Converter for FX                     IU-9100 or LP-KIT200-000C. (Other converters must support automatic Data Send Control [DSC]. RTS is not
CommPro N2                                          supported by FX CommPro.)
Electrical Isolation in FX06                        500 V

                                                                               LON Communication
LON Network Topology and Line                      Daisy chained Bus Topology: two terminators of 100 ohm required - one at each end of the bus.
Terminators                                        Free (star) topology: single terminator of 50 ohm required at a central point in network.
                                                   Use the same cable type throughout bus or network.
Number of Nodes                                    64 (if repeaters are not used), FTT-10 nodes only.
Cable Type                                         Length with FTT-10 devices
                                                   Bus Topology                                                          Free Topology
Belden® 85102                                      2,700 m (8,900 ft)                                                    500 m (1,640 ft)
Belden 8471                                        2,700 m (8,900 ft)                                                    500 m (1,640 ft)
Level IV 22 AWG                                    1,400 m (4,600 ft)                                                    400 m (1,300 ft)

Note:     For full technical details of LONWORKS networks, refer to the LONMARK® Guidelines at www.lonmark.org.

                                                                               FX Programming Key
Power Supply                                       Directly powered from the Display Bus port of the FX06 or from an AC/DC adapter 230 V/12 to 15 VDC 2 VA minimum
Memory Type and Size                               Flash memory 1 MB
Connection to controller                           RS-485, not isolated. Cable (10 cm/4 in.) provided with connector for FX06 front display socket, and a screw terminal
                                                   block for connection to an RS485 converter.
Enclosure IP Class                                 IP40
Ambient Limits                                     Operating: 0 to 40°C (32 to104°F), 10-95% RH (noncondensing)
                                                   Storage: -20 to 70°C (-4 to 158°F), 10-95%
                                                   RH (noncondensing)
Compliance                                         2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000 6-2




The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       4 of 5
FX06 Field Controller (Continued)

                                                                                   GSM Connection
 GSM Modem - Supreme 10                                                   GSM 900                                             GSM 1800/1900
 Voltage Range                                      5 to 32 VDC
 Power Supply @25°C                                                       Min.             Typ.            Max.               Min.           Typ.              Max.
 Input Supply voltage                                                     5                13.2            32                 5              13.2              32
 Input Peak Supply Current (in                      @5 V                                                   1.8 A                                               1.1 A
 Communication)                                     @13.2 V                                                0.7 A                                               0.4 A
                                                    @32 V                                                  0.4 A                                               0.2 A
 Input Average Supply Current (in                   @5 V                                                   330 mA                                              220 mA
 Communication)                                     @13.2 V                                                130 mA                                              95 mA
                                                    @32 V                                                  65 mA                                               50 mA
 Input Average Supply Current (in Idle              @5 V                                                   31.4 mA                                             31.4 mA
 Mode)                                              @13.2 V                                                13.2 mA                                             13.2 mA
                                                    @32 V                                                  5.6 mA                                              5.6 mA
 Ambient Operating Conditions                       -20 to 55°C (-4 to 131°F)
 Ambient Storage Conditions                         -25 to 70°C (-13°F to 158°F)
 Housing Material                                   Aluminum profiled
 Volume                                             12.2 cm³ (0.7 in.³)
 Weight                                             < 130 g (0.3 lb)
 Dimensions                                         98 mm (3.9 in.) x 54 mm (2.1 in.) x 25 mm (1 in.) (excluding connectors)
 Overall Dimensions                                 110 mm (4.3 in.) x 54 mm (2.1 in.) x 25 mm (1 in.)




The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       5 of 5


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.