The FX06 is a freely programmable compact field controller for commercial HVACR applications, with 17 physical I/O points and an onboard real-time clock for start-stop scheduling, time-stamped events and trend records. It integrates into a Building Automation System via an optional N2 Open or LONWORKS communication module, or sends SMS event notifications through an RS-232C module and GSM modem. An integral LCD user interface is included, with an optional remote Medium User Interface (MUI).
Ключові дані
| Power supply | 24 VAC/VDC ±15%, 50/60 Hz |
|---|---|
| Analog inputs | 4 (16-bit ADC, 13-bit effective resolution) |
| Binary inputs | 5 |
| Analog outputs | 2 x 0-10 VDC (3 mA max.) |
| Relay outputs | 6 SPST 3(1)A, 250 VAC (model P00) or 4 relays + 2 triacs (model P20) |
| Ambient operating conditions | -40 to 50°C (-40 to 122°F), 10 to 95% RH (noncondensing) |
| Protection class | Front plate IP55 (panel mounted); rear IP20, IEC 60529 |
| Network options | N2 Open or LONWORKS communication module; RS-232C module for SMS via GSM modem |
Застосування
- Small refrigeration compressors
- Close control units
- Packaged rooftop units
- Fan coil units
- Unit ventilators
- Chilling or heating ceiling beam installations
Особливості
- Freely programmable controller
- Network communication module options: N2 Open or LONWORKS protocols
- Remote communication services (SMS via GSM modem)
- Integral Liquid Crystal Display (LCD) user interface with four control buttons
- Optional remote user interface (MUI)
- Models with various output configurations of solid-state triacs and line voltage relays
- Network Room Module (NRM) support
Технічні дані
| Parameter | Value |
|---|---|
| Product codes | LP-FX06Pxx-xxxC |
| Power supply requirements | 24 VAC/VDC ±15%, 50/60 Hz - SELV (Europe), Class 2 North America |
| Power consumption | Controller: 7 VA maximum (additional 3 VA if MUI connected) |
| Housing material | ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating |
| Protection class | Front plate (when mounted in panel) IP55; Rear enclosure IP20, IEC 60529 |
| Ambient operating conditions | -40 to 50°C (-40 to 122°F), 10 to 95% RH (noncondensing); integral UI does not operate below -20°C (-4°F) |
| Ambient storage conditions | -40 to 70°C (-40 to 158°F), 10 to 95% RH (noncondensing) |
| Dimensions (H x W x D) | 44 mm (1.7 in.) x 70 mm (2.7 in.) x 95 mm (3.6 in.) |
| Weight | 0.32 kg (0.7 lb) incl. communication module; 0.68 kg (1.5 lb) incl. communication module and cable set |
| Real-time clock accuracy | Better than ±200 ms per day at constant ambient temperature of 25°C |
| RTC backup | Minimum 10 days without power at 25°C |
| Integral LCD display resolution | -999 to 999 or -99.9 to 99.9 (4 digits per row) |
| Analog inputs AI1–AI4 | Software configurable; temperature, humidity, pressure; 16-bit ADC, 13-bit effective resolution |
| AI power | +5 V at 15 mA max.; +15 V at 20 mA max. |
| Sensor input A99 | -50 to 100°C (-58 to 212°F), ±0.5°C (±1°F) accuracy at 20°C (68°F) |
| Sensor input NTC 10k | -40 to 150°C (-40 to 300°F), ±0.5°C (±1°F) |
| Sensor input PT1000 Extended | -50 to 160°C (-58 to 320°F), ±0.5°C (±1°F) |
| Sensor input Ni1000 (Johnson Controls) | -45 to 120°C (-49 to 248°F), ±0.5°C (±1°F) |
| Active voltage input | 0-10 VDC, ±0.05 VDC |
| Active ratiometric input | 0.5-4.5 VDC, ±0.05 VDC |
| Digital inputs DI1–DI5 | Potential free contacts; transition counter at 50 Hz max.; min. ON/OFF time 10 ms |
| Relay outputs (FX06P0x DO1–DO6) | SPST power relay 3(1)A, 250 VAC, independent contacts |
| Triac outputs (FX06P2x DO1, DO2) | 0.5 A/24 VAC triacs for 3-point incremental/thermal actuators |
| Relay dielectric strength coil-contacts | 4,000 V RMS for 1 minute |
| Dielectric test voltage on open relay contact | 1,000 VAC RMS |
| Max. relay switching rate at max. load | 6 operations/minute |
| Average relay contact life | 30,000 operations at maximum load |
| Analog outputs AO1, AO2 | 0-10 VDC (3 mA max.) |
| Power supply outputs | 24 VAC/DC for panel mount MUI; 15 VDC 20 mA for active sensors/PWM; 5 VDC 15 mA for ratiometric sensors |
| Connections | Removable plug connectors |
| Cable length for inputs | Max. 100 m (330 ft.) with cables ≥ 0.6 mm, 22 AWG |
| N2 Open bus | RS-485, 9600 baud; max. segment length without repeater 1,200 m (4,000 ft); max. 32 devices per segment; max. 2 repeaters (RP-9100 recommended) |
| N2 end-of-line termination | 220 ohm at each end of segment >100 m (300 ft); one 220 ohm if <100 m |
| Electrical isolation in FX06 (N2) | 500 V |
| LON topology | Daisy chained bus (two 100 ohm terminators) or free/star topology (single 50 ohm terminator) |
| LON number of nodes | 64 (without repeaters), FTT-10 nodes only |
| LON cable lengths (bus / free topology) | Belden 85102: 2,700 m / 500 m; Belden 8471: 2,700 m / 500 m; Level IV 22 AWG: 1,400 m / 400 m |
Варіанти замовлення
Controllers
| Code | Description |
|---|---|
| LP-FX06P00-020C | FX06 Compact Field Controller, new style wiring connector: 4 AIs, 5 BIs, 2 0-10 VDC analog outputs, 6 relay BOs |
| LP-FX06P20-020C | FX06 Compact Field Controller, new style wiring connector: 4 AIs, 5 BIs, 2 0-10 VDC analog outputs, 4 BOs, 2 triac BOs |
Communication modules
| Code | Description |
|---|---|
| LP-NET061-000C | N2 Open Communication Module |
| LP-NET062-000C | LONWORKS Communication Module |
| LP-NET063-000C | RS232C Communication Module |
User interfaces
| Code | Description |
|---|---|
| LP-DIS60P20-0C | Remote Medium User Interface (MUI V3) for FX06 - Panel Mount |
| LP-DIS60P21-0C | Remote Medium User Interface (MUI V3) for FX06 - Wall Mount |
| LP-KIT007-005C | Link cable FX06 to Panel Mount MUI display or NRM module, 3 m (9.8 ft) |
Accessories
| Code | Description |
|---|---|
| LP-KIT006-020C | Wiring Harness with new style wiring connector, 1.5 m length |
| LP-KIT006-025C | Wiring Harness with new style wiring connector, 5.0 m length |
| LP-KIT100-000C | FX Programming Key |
| DT-9100-8901 | Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe only) |
| NP-PWR1209 | Power Supply Adapter for Programming Key 120 VAC/12 VDC (North America only) |
| IU-9100-8401 | Converter RS-232C/RS-485 (N2) 230 VAC (Europe only) |
| LP-KIT007-001C | Interface cable for standard landline modem, 1.5 m (4.9 ft) |
| LP-KIT007-002C | Interface Cable for GSM modem to FX06, 1.5 m (4.9 ft) |
| LP-KIT007-013C | Null modem cable for computer connection, 3 m (9.8 ft) |
| LP-KIT007-014C | Null modem cable for computer connection, 15 m (49.2 ft) |
| LP-KIT007-020C | Bag of replacement communication wiring connectors (N2 and LON) |
| LP-KIT200-000C | N2 Commissioning Adapter: port powered RS-232C to RS-485 converter, 3 m (9.8 ft) cable, mating connectors for FX05/FX06/FX07/FX14/FX15/FX16/FXVMA |
| LP-KIT090-000C | GSM 900/1800 Supreme 10 FastTrack Modem |
| LP-KIT090-001C | GSM Modem Plug-in Antenna |
| LP-KIT090-003C | GSM Modem Magnetic Mount Antenna with 2.5 m (8.2 ft) Cable |
| LP-KIT090-004C | GSM Modem Panel Mount Antenna with 5 m (16.4 ft) Cable |
| LP-KIT090-005C | GSM Modem Power Adapter, 230 VAC/12 VDC, Wall Plug |
| NS-WALLPLATE-0 | Wall plate kit for mounting 80 x 80 mm sensor onto 51 x 102 mm wall box |
Room Command Modules, TM Series without Display - 80 x 80 mm (3.15 x 3.15 in.), °C
| Code | Description |
|---|---|
| TM-2140-0000 | Room Sensor Module, temperature sensor only |
| TM-2150-0000 | Room Sensor Module, occupancy button and LED |
| TM-2160-0000 | Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED |
| TM-2160-0002 | Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED, fan speed override |
| TM-2160-0005 | Room Sensor Module, +/- setpoint dial, occupancy button and LED |
| TM-2160-0007 | Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override |
| TM-2190-0000 | Room Sensor Module, 12-28°C setpoint dial |
| TM-2190-0005 | Room Sensor Module, +/- setpoint dial |
Room Command Modules, TM Series without Display - North America - 120 x 80 mm (4.72 x 3.15 in.), °C/°F
| Code | Description |
|---|---|
| TM-2141-0000 | Room Sensor Module, temperature sensor only |
| TM-2151-0000 | Room Sensor Module, occupancy button and LED |
| TM-2161-0000 | Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED |
| TM-2161-0002 | Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED, fan speed override |
| TM-2161-0005 | Room Sensor Module, +/- setpoint dial, occupancy button and LED |
| TM-2161-0007 | Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override |
| TM-2191-0000 | Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial |
| TM-2191-0005 | Room Sensor Module, +/- setpoint dial |
Network Room Modules (Europe)
| Code | Size | Service Port | LCD | Temp Adjust Dial | Fan Speed Selector | °F/°C Button | Addressable |
|---|---|---|---|---|---|---|---|
| LP-NRM001-000C | 80 x 80 | No | No | No | No | No | No |
| LP-NRM002-000C | 80 x 80 | Yes | Yes | No | No | No | No |
| LP-NRM003-000C | 80 x 80 | Yes | Yes | Yes | No | No | No |
| LP-NRM511-000C | 80 x 80 | No | No | No | No | No | Yes¹ |
| LP-NRM502-000C | 80 x 80 | Yes | Yes | No | No | No | No |
| LP-NRM503-000C | 80 x 80 | Yes | Yes | Yes | No | No | No |
Network Room Modules (North America)
| Code | Size | Service Port | LCD | Temp Adjust Dial | Fan Speed Selector | °F/°C Button | Addressable |
|---|---|---|---|---|---|---|---|
| LP-NRM511-000C | 80 x 80 mm (3.15 x 3.15 in.) | No | No | No | No | No | Yes¹ |
| LP-NRM552-000C | 80 x 80 mm | Yes | Yes | No | Yes | No | No |
| LP-NRM553-000C | 80 x 80 mm | Yes | Yes | Yes | Yes | No | No |
| LP-NRM611-000C | 120 x 80 mm (4.72 x 3.15 in.) | No | No | No | No | No | Yes¹ |
| LP-NRM652-000C | 120 x 80 mm | Yes | Yes | No | Yes | No | No |
| LP-NRM653-000C | 120 x 80 mm | Yes | Yes | Yes | Yes | No | No |
¹ The FX06 controller only supports one connected NRM; the addressing feature is not used.
Software
| Code | Description |
|---|---|
| LP-FXTPRO-0 | FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - New User Version |
| LP-FXTPRO-6 | FX Tools Pro CD-ROM (same contents) - Upgrade Version |
Допуски та стандарти
- Europe: 2004/108/EEC EMC Directive: EN 61000-6-3, EN 61000-6-2; 2006/95/EEC Low Voltage Directive: EN 60730
- Canada: UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada ICES-003
- United States: UL Listed (PAZX), UL 916, Energy Management Equipment; FCC compliant to CFR 47, Part 15, Subpart B, Class A
- FX Programming Key: 2004/108/EEC EMC Directive: EN 61000-6-3, EN 61000-6-2
Позиції каталогу з цим документом
Текст документа
Code No. LIT-1900406
Issued October 19, 2012
Facility Explorer
FX06 Field Controller
Description Using the FX Tools software package, you
can program the FX06 field controller to
The FX06 is a high performance field
operate a wide variety of commercial HVACR
controller designed specifically for commercial
equipment; including small refrigeration
Heating, Ventilating, Air Conditioning, and
compressors, close control units, packaged
Refrigeration (HVACR) applications.
rooftop units, fan coil units, unit ventilators,
The FX06 supports 17 physical inputs and and chilling or heating ceiling beam
outputs including a wide range of sensors and installations.
actuating devices. The FX06 includes an
Note: This document applies to the LP-
onboard real-time clock to support the
FX06Pxx-020C models only. FX06 Field Controller
start-stop scheduling of equipment, real-time
based control sequences, and time stamping Refer to the FX06 Field Controller Product
events and trend records. Bulletin (LIT-12011165) for important product Repair Information
application information.
With the integral user interface, you can If the FX06 Field Controller fails to operate
locally monitor and adjust the FX06’s Features within its specifications, replace the unit. For a
operation. The FX06 also supports a remote replacement controller, contact the nearest
• freely programmable controller Johnson Controls® representative.
panel- or wall-mountable Medium User
Interface (MUI) for remote monitoring and • network communication module options:
adjustment. N2 Open, or LONWORKS protocols
• remote communication services
The FX06 can be fitted with an N2 Open or
• integral Liquid Crystal Display (LCD) user
LONWORKS® communication module to interface with four control buttons
integrate the controller into a compatible
• optional remote user interface
Building Automation System (BAS).
Alternatively, the FX06 can be fitted with an • analog outputs
RS-232C serial communication module to • models with various output configurations
transmit event notification messages via Short of solid-state triacs and line voltage relays
Messaging Service (SMS) through a Global • Network Room Module (NRM)
System for Mobile (GSM) modem.
Selection Charts
FX06 Field Controller Ordering Information
Product Code Number Description
LP-FX06P00-020C FX06 Compact Field Controller with new style wiring connector: Includes 4 Analog Inputs (AIs), 5 Binary Inputs (BIs), 2 0-10 VDC
Analog Outputs, and 6 relay Binary Outputs (BOs)
LP-FX06P20-020C FX06 Compact Field Controller with new style wiring connector: Includes 4 AIs, 5 BIs, 2 0-10 VDC Analog Outputs, 4 BOs, and 2 triac
BOs
Communication Module Ordering Information
Product Code Number Description
LP-NET061-000C N2 Open Communication Module
LP-NET062-000C LONWORKS Communication Module
LP-NET063-000C RS232C Communication Module
User Interfaces
Product Code Number Description
LP-DIS60P20-0C Remote Medium User Interface (MUI V3) for FX06 - Panel Mount
LP-DIS60P21-0C Remote Medium User Interface (MUI V3) for FX06 - Wall Mount
LP-KIT007-005C Link cable for the connection of the FX06 to the Panel Mount MUI display or NRM module, 3 m (9.8 ft)
FX06 Accessories (Part 1 of 2)
Product Code Number Description
LP-KIT006-020C Wiring Harness with new style wiring connector, 1.5 m length
LP-KIT006-025C Wiring Harness with new style wiring connector, 5.0 m length
LP-KIT100-000C FX Programming Key
DT-9100-8901 Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe only)
LP-KIT007-001C Interface cable for standard landline modem, 1.5 m (4.9 ft)
LP-KIT007-013C Null modem cable for computer connection, 3 m (9.8 ft)
LP-KIT007-014C Null modem cable for computer connection, 15 m (49.2 ft)
LP-KIT007-020C Bag of replacement communication wiring connectors (N2 and LON).
LP-KIT200-000C N2 Commissioning Adapter: Includes port powered RS-232C to RS-485 converter, 3 m (9.8 ft) cable, and mating connectors for
FX05, FX06, FX07, FX14, FX15, FX16, and FXVMA.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
1 of 5
FX06 Field Controller (Continued)
FX06 Accessories (Part 2 of 2)
Product Code Number Description
IU-9100-8401 Converter RS-232C/RS-485 (N2) 230 VAC (Europe only)
NP-PWR1209 Power Supply Adapter for Programming Key 120 VAC/12 VDC (North America only)
GSM Modem and Accessories
Product Code Number Description
LP-KIT007-002C Interface Cable for GSM modem to FX06, 1.5 m (4.9 ft)
LP-KIT090-000C GSM 900/1800 Supreme 10 FastTrack Modem
LP-KIT090-001C GSM Modem Plug-in Antenna
LP-KIT090-003C GSM Modem Magnetic Mount Antenna with 2.5 m (8.2 ft) Cable
LP-KIT090-004C GSM Modem Panel Mount Antenna with 5 m (16.4 ft) Cable
LP-KIT090-005C GSM Modem Power Adapter, 230 VAC/12 VDC, Wall Plug
Room Command Modules, TM Series without Display - 80 x 80 mm (3.15 x 3.15 in.), °C
Product Code Number Description
TM-2140-0000 Room Sensor Module, temperature sensor only
TM-2150-0000 Room Sensor Module, occupancy button and Light-Emitting Diode (LED)
TM-2160-0000 Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED
TM-2160-0002 Room Sensor Module, 12 to 28°C setpoint dial, occupancy button and LED, fan speed override
TM-2160-0005 Room Sensor Module, +/- setpoint dial, occupancy button and LED
TM-2160-0007 Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override
TM-2190-0000 Room Sensor Module, 12-28°C setpoint dial
TM-2190-0005 Room Sensor Module, +/- setpoint dial
Network Room Modules Ordering Information (Available in Europe)
Product Code Features/Options
Size (mm) Service Port LCD Display Temperature Fan Speed °F/°C Addressable
Type Adjust Dial Selector
Button
LP-NRM001-000C 80 x 80 Program Key No No No No No
LP-NRM002-000C Yes Yes No No No
LP-NRM003-000C Yes Yes Yes No No
LP-NRM511-000C MUI No No No No Yes1
LP-NRM502-000C Yes Yes No No No
LP-NRM503-000C Yes Yes Yes No No
1. The FX06 controller only supports one connected NRM and therefore the addressing feature is not used.
Room Command Modules - Available in North America - TM Series without Display - 120 x 80 mm (4.72 x 3.15 in.), °C/°F
Product Code Number Description
TM-2141-0000 Room Sensor Module, temperature sensor only
TM-2151-0000 Room Sensor Module, occupancy button and LED
TM-2161-0000 Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED
TM-2161-0002 Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial, occupancy button and LED, fan speed override
TM-2161-0005 Room Sensor Module, +/- setpoint dial, occupancy button and LED
TM-2161-0007 Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override
TM-2191-0000 Room Sensor Module, 54 - 82°F/12 - 28°C setpoint dial
TM-2191-0005 Room Sensor Module, +/- setpoint dial
Network Room Modules Ordering Information (Available in North America)
Product Code Features/Options
Size, mm Service Port LCD Display Temperature Fan Speed °F/°C Addressable
(inch) Type Adjust Dial Selector
Button
LP-NRM511-000C 80 x 80 mm MUI No No No No Yes1
LP-NRM552-000C (3.15 x 3.15 in.) Yes Yes No Yes No
LP-NRM553-000C Yes Yes Yes Yes No
LP-NRM611-000C 120 x 80 mm MUI No No No No Yes1
LP-NRM652-000C (4.72 x 3.15 in.) Yes Yes No Yes No
LP-NRM653-000C Yes Yes Yes Yes No
1. The FX06 controller only supports one connected NRM and therefore the addressing feature is not used.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
2 of 5
FX06 Field Controller (Continued)
Sensor Accessories
Product Code Number Description
NS-WALLPLATE-0 Wall plate kit used to mount an 80 x 80 mm (3.15 x 3.15 in.) sensor onto a 51 x 102 mm (2 x 4 in.) wall box
Software Ordering Information
Product Code Number Description
LP-FXTPRO-0 FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - New
User Version
LP-FXTPRO-6 FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - Upgrade
Version
Technical Specifications
Analog Inputs (AI)
Terminal/Channel Type Remark/Application
AI1, AI2, AI3, AI4 See Sensor Input Types in this table Software configurable. Application: temperature, humidity, pressure. 16-bit
ADC, 13-bit effective resolution.
AI Power +5 V at 15 mA max. To power active or ratiometric sensors directly from the controller.
AI/AO Power +15 V at 20 mA max. To power active sensors directly from the controller.
Sensor Input Types
Sensor Type Full Linearization Range Accuracy at 20°C (68°F) - Controller and Sensor
(sensor accuracy not included)
A99 -50 to 100°C (-58 to 212°F) ±0.5°C (±1°F)
NTC 10k -40 to 150°C (-40 to 300°F) ±0.5°C (±1°F)
PT1000 Extended -50 to 160°C (-58 to 320°F) ±0.5°C (±1°F)
Ni1000 -45 to 120°C (-49 to 248°F) ±0.5°C (±1°F)
(Johnson Controls®
temperature sensor)
Active Voltage 0-10 VDC ±0.05 VDC
Active Ratiometric 0.5-4.5 VDC ±0.05 VDC
Digital (Binary) Inputs (DI)
Terminal/Channel Type Remark/Application
DI1, DI2, DI3, DI4, DI5 Potential free contacts for status monitoring Status and events
Transition Counter at 50 Hz max. Minimum Time ON: 10 ms
Minimum Time OFF: 10 ms
Digital (Binary) Outputs (DO)
Digital (Binary) Model Channel Type Remark/Application
Outputs for
Selected Models
FX06P0x DO1 - DO6 SPST 3(1)A, 250 VAC Each relay contact is independent with its own terminals
power relay
FX06P2x DO1, DO2 0.5A/24 VAC triacs 3-point incremental actuators, thermal actuators, and other
actuators
DO3 - DO6 SPST 3(1)A, 250 VAC Each relay contact is independent with its own terminals.
power relay
Relay Outputs Dielectric strength coil-contacts: 4,000 V RMS for 1 minute
Dielectric test voltage on open relay contact:1,000 VAC RMS
Maximum relay switching rate at maximum load: 6 operations/minute
Average relay contact life: 30,000 operations at maximum load
Analog Output (AO)
Terminal/Channel Type Remark/Application
AO1, AO2 0-10 VDC (3 mA max.) Actuators and control devices
FX06 Controller
Product Codes LP-FX06Pxx-xxxC
Power Supply Requirements 24 VAC/VDC ±15%, 50/60 Hz - Safety Extra-Low Voltage (SELV) (Europe) - Class 2 North America
Power Consumption Controller: 7 VA maximum (Additional 3VA if MUI is connected)
Housing Material ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating
Protection Class Front Plate (when mounted in panel) IP55; Rear Enclosure IP20, IEC 60529
Ambient Operating Conditions -40 to 50°C (-40 to 122°F), 10 to 95% RH (noncondensing)
Note that the integral user interface does not operate below -20°C (-4°F).
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
3 of 5
FX06 Field Controller (Continued)
FX06 Controller
Ambient Storage Conditions -40 to 70°C (-40 to 158°F), 10 to 95% RH (noncondensing)
Dimensions (H x W x D) 44 mm (1.7 in.) x 70 mm (2.7 in.) x 95 mm (3.6 in.)
Weight (with package) 0.32 kg (0.7 lb) including communication module
0.68 Kg (1.5 lb) including communication module and cable set
Real-Time Clock Accuracy: Better than ± 200 ms per day at constant ambient temperature of 25°C
Backup: Minimum 10 days without power at 25°C
Integral LCD Display Resolution -999 to 999 or -99.9 to 99.9 (4 digits for each row)
I/O Ratings See the I/O tables in the Technical Specifications section.
Power Supply Outputs 24 VAC/DC for panel mount MUI (from controller power supply input)
15 VDC 20 mA power supply for active sensors and PWM output
5 VDC 15 mA power supply for ratio-metric sensors
Connections Removable plug connectors. Mating connectors and cables provided with controller or available to order. See FX06
Field Controller Ordering Information and FX06 Accessories.
Cable Length for Inputs Max. 100 m (330 ft.) with cables ≥ 0.6 mm, 22 AWG
Agency Compliance Europe
2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000 6 2
2006/95/EEC, Low Voltage Directive: EN 60730.
Canada
UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003
United States
UL Listed (PAZX), UL 916, Energy Management Equipment
FCC compliant to CFR 47, Part 15, Subpart B, Class A
N2 Open Communication
RS-485 Bus - 9600 Baud Maximum bus segment length without repeater: 1,200 m (4,000 ft), 0.8/0.6 mm diameter (20/22 AWG) 2 x twisted pair
with shield. Use the same cable type throughout segment.
Number of Devices Maximum of 32 devices on a bus segment without repeater
Repeaters Maximum 2 repeaters between the master (supervisory) device and any slave (FX controller) device on the network.
RP-9100 is recommended.
End-of-Line Termination 220 ohm at each end of segment >100 m (300 ft). For segment <100 m (300 ft), only one 220 ohm termination is
required.
RS-485/RS-232C Converter for FX IU-9100 or LP-KIT200-000C. (Other converters must support automatic Data Send Control [DSC]. RTS is not
CommPro N2 supported by FX CommPro.)
Electrical Isolation in FX06 500 V
LON Communication
LON Network Topology and Line Daisy chained Bus Topology: two terminators of 100 ohm required - one at each end of the bus.
Terminators Free (star) topology: single terminator of 50 ohm required at a central point in network.
Use the same cable type throughout bus or network.
Number of Nodes 64 (if repeaters are not used), FTT-10 nodes only.
Cable Type Length with FTT-10 devices
Bus Topology Free Topology
Belden® 85102 2,700 m (8,900 ft) 500 m (1,640 ft)
Belden 8471 2,700 m (8,900 ft) 500 m (1,640 ft)
Level IV 22 AWG 1,400 m (4,600 ft) 400 m (1,300 ft)
Note: For full technical details of LONWORKS networks, refer to the LONMARK® Guidelines at www.lonmark.org.
FX Programming Key
Power Supply Directly powered from the Display Bus port of the FX06 or from an AC/DC adapter 230 V/12 to 15 VDC 2 VA minimum
Memory Type and Size Flash memory 1 MB
Connection to controller RS-485, not isolated. Cable (10 cm/4 in.) provided with connector for FX06 front display socket, and a screw terminal
block for connection to an RS485 converter.
Enclosure IP Class IP40
Ambient Limits Operating: 0 to 40°C (32 to104°F), 10-95% RH (noncondensing)
Storage: -20 to 70°C (-4 to 158°F), 10-95%
RH (noncondensing)
Compliance 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000 6-2
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
4 of 5
FX06 Field Controller (Continued)
GSM Connection
GSM Modem - Supreme 10 GSM 900 GSM 1800/1900
Voltage Range 5 to 32 VDC
Power Supply @25°C Min. Typ. Max. Min. Typ. Max.
Input Supply voltage 5 13.2 32 5 13.2 32
Input Peak Supply Current (in @5 V 1.8 A 1.1 A
Communication) @13.2 V 0.7 A 0.4 A
@32 V 0.4 A 0.2 A
Input Average Supply Current (in @5 V 330 mA 220 mA
Communication) @13.2 V 130 mA 95 mA
@32 V 65 mA 50 mA
Input Average Supply Current (in Idle @5 V 31.4 mA 31.4 mA
Mode) @13.2 V 13.2 mA 13.2 mA
@32 V 5.6 mA 5.6 mA
Ambient Operating Conditions -20 to 55°C (-4 to 131°F)
Ambient Storage Conditions -25 to 70°C (-13°F to 158°F)
Housing Material Aluminum profiled
Volume 12.2 cm³ (0.7 in.³)
Weight < 130 g (0.3 lb)
Dimensions 98 mm (3.9 in.) x 54 mm (2.1 in.) x 25 mm (1 in.) (excluding connectors)
Overall Dimensions 110 mm (4.3 in.) x 54 mm (2.1 in.) x 25 mm (1 in.)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
5 of 5
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.