DX-9100 Extended Digital Controller

Вид документаТехнічний паспорт
ВиробникJCI
МоделіDX-9100-8454, FA-DX9100-8454, DX-9100-8990, DX-9100-8991, DX-9100-8996, DT-9100-8104, XT-9100-8304, XP-9102-8304
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.1 МБ

Про документ

The DX-9100 Extended Digital Controller is a standalone/networked digital controller for multiple chiller or boiler plant applications, air handling units, or distributed lighting control. It provides a real-time clock, extendable I/O via extension/expansion modules, and graphic software programming; it integrates with the Metasys network over the N2 Bus.

Ключові дані

Source power24 VAC +/-10% at 50/60 Hz
Ambient operating conditions32 to 122°F (0 to 40°C), 10 to 90% Non-Condensing RH
Analog inputs8 (DX-9100), 6 (XT/XTM w/XPx)
Digital inputs8 (DX-9100), 4/8/16 (XT/XTM w/XPx)
Digital outputs6 (DX-9100), 3 to 4/8/16 (XTM), 4/8/16 (XT)
Analog outputs4 (DX-9100), 2 (XT/XTM w/XPx)
Size (H x W x D)7.9 in. x 7.2 in. x 3.9 in. (200 x 184 x 100 mm)
Agency listingsUL864, CSA, CE Directive 89/336/EEC, EN50081/2 and 2/1

Застосування

  • Multiple chiller or boiler plant applications
  • Air handling units
  • Distributed lighting control
  • Non-critical supervisory or control applications using unused points

Особливості

  • Standalone control provides system reliability
  • Network communications over N2 Bus for facility-wide control efficiencies and cost-effective sensor sharing
  • Fully integrated modular packaging — purchase only needed parts
  • Complete line of compatible sensors, actuators, and accessories; interfaces to both pneumatic and electric actuators
  • Graphical configuration via GX-9100 software tool using Flow Chart Modules
  • Built-in local status display
  • Password and Trend Log features
  • Preconfigured application examples plus fully customizable configuration
  • Extension/expansion modules mountable on same DIN rail or remotely up to 4,000 feet from controller; up to eight submodules provide up to 64 additional I/O points

Технічні дані

Parameter Value
Source power 24 VAC +/-10% at 50/60 Hz
Ambient operating conditions 32 to 122°F (0 to 40°C); 10 to 90% Non-Condensing RH
Ambient storage conditions 0 to 160°F (-20 to 70°C); 5 to 95% RH
Size (H x W x D) 7.9 in. x 7.2 in. x 3.9 in. (200 x 184 x 100 mm)
Weight FA-DX9100-8454, DX-9100-8454: 4.7 lbs (2.2 kg)
Agency listings UL864 (with DX-9100-8990 Base), CSA, CE Directive 89/336/EEC, EN50081/2 and 2/1
Analog inputs (DX-9100 / XT-9100 w/XPx / XTM-905 w/XPx) 8 / 6 / 6 — 0-10 VDC (impedance 300K ohm), 0/4-20 mA DC (impedance 100 ohm), RTD Ni1000 (JCI), A99 (JCI), Pt1000 (DIN)
Digital (binary) inputs 8 / 4/8/16 / 4/8/16 — Dry contacts (potential free)
Digital (binary) outputs 6 / 4/8/16 / 3 to 4/8/16 — 24 VAC Triacs (min 0.05 A, max 0.5A); XT/XTM only: relay contact (max 250 VAC 3A); XTM only: relays with magnetically latched or electrically held operation
Analog outputs 4 / 2 / 2 — 0-10 VDC (10 mA maximum) or 0/4-20 mA DC; additional row: 4 / 0 / 0 — 0-10 VDC (10 mA maximum) only
Control blocks PID loops, remote reset logic, operation modes, control limits and alarms
Output blocks Sequencer and step control logic, incremental with or without feedback, duration adjust type, averaging, min/max select, enthalpy/wet bulb/dew point, input selector, arithmetic calculator, compare logic, line segment function, timer functions
Logic blocks AND, OR, NOT, state change detect, set and reset of parameters
Time schedule Yearly holiday calendar, start-stop times for days of week and holidays, optimal start/stop modules
Counters Pulse counters, run-time counter, totalizer and integrator

Варіанти замовлення

Code Number Description
DX-9100-8454 Extended Digital Plant Controller, Version 2
FA-DX9100-8454 Extended Digital Plant Controller, Version 2 (Facilitator)
DX-9100-8990 Wall Mounting Base
DX-9100-8991 Terminal Covers for wall mounting base
DX-9100-8996 Door Mounting Base
DT-9100-8104 LCD Display Unit for DX-9100
XT-9100-8304 Extension Module
XP-9102-8304 2 Analog Outputs and 6 Analog Inputs
XP-9103-8304 8 Digital Outputs (triacs)
XP-9104-8304 4 Digital Inputs, 4 Digital Outputs (triacs)
XP-9105-8304 8 Digital Inputs
XP-9107-8304 4 Digital Outputs (24V Relay)

Order DX-9100-8454 controller (FA-DX9100-8454 for Facilitator version) with mounting base DX-9100-8990 or DX-9100-8996.

Допуски та стандарти

  • UL864 (with DX-9100-8990 Base)
  • CSA
  • CE Directive 89/336/EEC
  • EN50081/2 and 2/1

Позиції каталогу з цим документом

Текст документа

                                                                                                                                                       Code No. LIT-1928135
                                                                                                                                                       Issued September 7, 2004

DX-9100 Series

Extended Digital Controller
Description                                                       •  Complete line of compatible sensors,
The DX-9100 Extended Digital Controller is                           actuators, and accessories for a total
the ideal digital control solution for multiple                      system solutionInterfaces to both
chiller or boiler plant applications, air handling                   pneumatic and electric actuators to provide
units, or distributed lighting control.                              low cost installation for both new
                                                                     construction and retrofit applications
As a standalone controller, the DX-9100                           • Graphical configuration via GX-9100
provides a real-time clock, extendable I/O, and                      software tool allows easy connection of
graphic software programming to target a                             Flow Chart Modules to obtain desired
variety of applications. Individual point                            control sequence
monitoring and control is available through the
                                                                  • Built-in local status display makes it
front panel LED display.
                                                                     convenient and easy to use
The DX-9100 also connects to the system                           • Password and Trend Log features
over the N2 Bus, integrating its point and                        Options (Part 1 of 2)
control information with the entire controller                     Application Configuration Options
network.                                                           Modules
Preconfigured examples are available for                          Analog Inputs      Sensor/Transmitter ranging
common applications to use as a foundation                                           High/Low limits                                                      DX-9100
for customizing to your particular facility. If the                                  Filter constants
preconfigured examples don’t cover your                                              Square root                                 Options (Part 2 of 2)
requirements, you can configure a totally                         Control Blocks PID Loops                                       Application Configuration Options
customized process. In addition, points                                          Remote reset logic                              Modules
                                                                                 Operation modes                                  Analog              High/Low ranging
unused in the control scheme can be used in                                      Control limits and alarms
non-critical supervisory or control applications                                                                                  Outputs
                                                                                 Sequencer and step control logic
by the Network.                                                                                                                   Digital Outputs Incremental with or without
                                                                  Digital Inputs     Source points for logic functions            (DX Controller) feedback
Order DX-9100-8454 controller (FA-DX9100-                                            Pulse counters                                               Duration adjust type
8454 for Facilitator version) with mounting                       Calculation        Averaging                                                    On/Off logic, including pulse
base DX-9100-8990 or DX-9100-8996.                                Blocks             Minimum or maximum select                    Digital Outputs On/Off logic, including pulse
                                                                                     Enthalpy, wet bulb and dew point             (XT Modules)
Features                                                                             Input selector                               Time Schedule Yearly holiday calendar
•    Standalone control provides system                                              Arithmetic calculator                        Blocks        Start-stop times for days of week
                                                                                     Compare logic                                              and holidays
     reliability
                                                                                     Line segment function                                      Optimal start/stop modules
•    Network communications over N2 Bus                                              Timer functions                                            (2 modules available)
     provides facility-wide control efficiencies                                     Run-time counter
     and cost effective sensor sharing                                               Totalizer and Integrator
•    Fully integrated modular packaging allows                    Logic Blocks       AND, OR, NOT
     you to purchase only needed parts                                               State change detect
                                                                                     Set and reset of parameters

Point Configuration
Point Type                                                    Quantity                                  Characteristics
                                  DX-9100          XT-9100 w/XPx             XTM-905 w/XPx 1
Analog Inputs                            8                    6                          6              0-10 VDC (impedance 300K ohm)
                                                                                                        0/4-20 mA DC (impedance 100 ohm)
                                                                                                        RTD Ni1000 (JCI), A99 (JCI), and Pt1000 (DIN)
Digital (Binary) Inputs                  8                 4/8/16                     4/8/16            Dry Contacts (potential free)
Digital (Binary) Outputs                 6                 4/8/16                  3 to 4/8/16          24 VAC Triacs (minimum 0.05 amperes [A], maximum 0.5A)
                                                                                                        XT/XTM only: Relay Contact (maximum 250 VAC 3A)
                                                                                                        XTM only: relays with magnetically latched or electrically held operation
Analog Outputs                           4                    2                          2              0-10 VDC (10 mA maximum) or
                                                                                                        0/4-20 mA DC
                                         4                    0                          0              0-10 VDC (10 mA maximum) only
    1. The specifications of this table only pertain to modules available in North America.




The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2004 Johnson Controls, Inc.                      www.johnsoncontrols.com

                                                                                       1 of 2
                                                                                                                                                       Code No. LIT-1928135



Extended Digital Controller (Continued)

Selection Chart                                                                                 Specifications
Code Number              Description                                                                                       Extended Digital Controller
DX-9100-8454             Extended Digital Plant Controller, Version 2                            Source Power                24 VAC +/-10% at 50/60 Hz
FA-DX9100-8454           Extended Digital Plant Controller, Version 2 (Facilitator)              Ambient Operating           32 to 122°F (0 to 40°C)
DX-9100-8990             Wall Mounting Base                                                      Conditions                  10 to 90% Non-Condensing RH
DX-9100-8991             Terminal Covers for wall mounting base                                  Ambient Storage             0 to 160°F (-20 to 70°C)
                                                                                                 Conditions                  5 to 95% RH
DX-9100-8996             Door Mounting Base
                                                                                                 Size (H x W x D)            7.9 in. x 7.2 in. x 3.9 in.
Accessories                                                                                                                  200 x 184 x 100 mm
Code Number             Description                                                              Weight                      FA-DX9100-8454, DX-9100-8454 4.7 lbs (2.2 kg)
DT-9100-8104            LCD Display Unit for DX-9100                                             Agency Listings             UL864 (with DX-9100-8990 Base
                                                                                                                             CSA
                      Extension and Expansion Modules                                                                        CE Directive 89/336/EEC
XT-9100-8304            Extension Module                                                                                     EN5008 1/2 and 2/1
XP-9102-8304            2 Analog Outputs and 6 Analog Inputs
XP-9103-8304            8 Digital Outputs (triacs)
XP-9104-8304            4 Digital Inputs, 4 Digital Outputs (triacs)
XP-9105-8304            8 Digital Inputs
XP-9107-8304            4 Digital Outputs (24V Relay)


XTM-905/XT-9100 Extension Module/XP910x
Expansion Modules                                                                                                                  DX-9100
Extension Modules (XT-9100/XPx or XTM-905/XPx) are submodules
that provide various combinations of analog and binary input/output
points. They may be mounted next to the controller on the same DIN
rail, or remotely, up to 4,000 feet from the controller. Up to eight
submodule combinations can connect to the XT Bus of the controller,
providing up to 64 additional I/O points. The XT Bus has the same
physical characteristics as the Metasys N2 Bus.




                                                                                                                                                 XT / XP
                                                                                                                       N2 Bus




                                                AO7
                                                min

                                                                                                                                              XTM 905 / XP/ XP
                                                AO8
                                                min




                                                                                                                                                                    dx9100xp
                                                                                                                                     XT Bus
                                       XT-9100                                                                                          DX-9100




The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2004 Johnson Controls, Inc.                      www.johnsoncontrols.com