| Вид документа | Технічний паспорт |
|---|
| Виробник | JCI |
|---|
| Моделі | DX-9100-8454, FA-DX9100-8454, DX-9100-8990, DX-9100-8991, DX-9100-8996, DT-9100-8104, XT-9100-8304, XP-9102-8304 |
|---|
| Група обладнання | automation |
|---|
| Мова документа | англійська |
|---|
| Розмір файлу | 0.1 МБ |
|---|
Про документ
The DX-9100 Extended Digital Controller is a standalone/networked digital controller for multiple chiller or boiler plant applications, air handling units, or distributed lighting control. It provides a real-time clock, extendable I/O via extension/expansion modules, and graphic software programming; it integrates with the Metasys network over the N2 Bus.
Ключові дані
| Source power | 24 VAC +/-10% at 50/60 Hz |
|---|
| Ambient operating conditions | 32 to 122°F (0 to 40°C), 10 to 90% Non-Condensing RH |
|---|
| Analog inputs | 8 (DX-9100), 6 (XT/XTM w/XPx) |
|---|
| Digital inputs | 8 (DX-9100), 4/8/16 (XT/XTM w/XPx) |
|---|
| Digital outputs | 6 (DX-9100), 3 to 4/8/16 (XTM), 4/8/16 (XT) |
|---|
| Analog outputs | 4 (DX-9100), 2 (XT/XTM w/XPx) |
|---|
| Size (H x W x D) | 7.9 in. x 7.2 in. x 3.9 in. (200 x 184 x 100 mm) |
|---|
| Agency listings | UL864, CSA, CE Directive 89/336/EEC, EN50081/2 and 2/1 |
|---|
Застосування
- Multiple chiller or boiler plant applications
- Air handling units
- Distributed lighting control
- Non-critical supervisory or control applications using unused points
Особливості
- Standalone control provides system reliability
- Network communications over N2 Bus for facility-wide control efficiencies and cost-effective sensor sharing
- Fully integrated modular packaging — purchase only needed parts
- Complete line of compatible sensors, actuators, and accessories; interfaces to both pneumatic and electric actuators
- Graphical configuration via GX-9100 software tool using Flow Chart Modules
- Built-in local status display
- Password and Trend Log features
- Preconfigured application examples plus fully customizable configuration
- Extension/expansion modules mountable on same DIN rail or remotely up to 4,000 feet from controller; up to eight submodules provide up to 64 additional I/O points
Технічні дані
| Parameter |
Value |
| Source power |
24 VAC +/-10% at 50/60 Hz |
| Ambient operating conditions |
32 to 122°F (0 to 40°C); 10 to 90% Non-Condensing RH |
| Ambient storage conditions |
0 to 160°F (-20 to 70°C); 5 to 95% RH |
| Size (H x W x D) |
7.9 in. x 7.2 in. x 3.9 in. (200 x 184 x 100 mm) |
| Weight |
FA-DX9100-8454, DX-9100-8454: 4.7 lbs (2.2 kg) |
| Agency listings |
UL864 (with DX-9100-8990 Base), CSA, CE Directive 89/336/EEC, EN50081/2 and 2/1 |
| Analog inputs (DX-9100 / XT-9100 w/XPx / XTM-905 w/XPx) |
8 / 6 / 6 — 0-10 VDC (impedance 300K ohm), 0/4-20 mA DC (impedance 100 ohm), RTD Ni1000 (JCI), A99 (JCI), Pt1000 (DIN) |
| Digital (binary) inputs |
8 / 4/8/16 / 4/8/16 — Dry contacts (potential free) |
| Digital (binary) outputs |
6 / 4/8/16 / 3 to 4/8/16 — 24 VAC Triacs (min 0.05 A, max 0.5A); XT/XTM only: relay contact (max 250 VAC 3A); XTM only: relays with magnetically latched or electrically held operation |
| Analog outputs |
4 / 2 / 2 — 0-10 VDC (10 mA maximum) or 0/4-20 mA DC; additional row: 4 / 0 / 0 — 0-10 VDC (10 mA maximum) only |
| Control blocks |
PID loops, remote reset logic, operation modes, control limits and alarms |
| Output blocks |
Sequencer and step control logic, incremental with or without feedback, duration adjust type, averaging, min/max select, enthalpy/wet bulb/dew point, input selector, arithmetic calculator, compare logic, line segment function, timer functions |
| Logic blocks |
AND, OR, NOT, state change detect, set and reset of parameters |
| Time schedule |
Yearly holiday calendar, start-stop times for days of week and holidays, optimal start/stop modules |
| Counters |
Pulse counters, run-time counter, totalizer and integrator |
Варіанти замовлення
| Code Number |
Description |
| DX-9100-8454 |
Extended Digital Plant Controller, Version 2 |
| FA-DX9100-8454 |
Extended Digital Plant Controller, Version 2 (Facilitator) |
| DX-9100-8990 |
Wall Mounting Base |
| DX-9100-8991 |
Terminal Covers for wall mounting base |
| DX-9100-8996 |
Door Mounting Base |
| DT-9100-8104 |
LCD Display Unit for DX-9100 |
| XT-9100-8304 |
Extension Module |
| XP-9102-8304 |
2 Analog Outputs and 6 Analog Inputs |
| XP-9103-8304 |
8 Digital Outputs (triacs) |
| XP-9104-8304 |
4 Digital Inputs, 4 Digital Outputs (triacs) |
| XP-9105-8304 |
8 Digital Inputs |
| XP-9107-8304 |
4 Digital Outputs (24V Relay) |
Order DX-9100-8454 controller (FA-DX9100-8454 for Facilitator version) with mounting base DX-9100-8990 or DX-9100-8996.
Допуски та стандарти
- UL864 (with DX-9100-8990 Base)
- CSA
- CE Directive 89/336/EEC
- EN50081/2 and 2/1
Позиції каталогу з цим документом
Текст документа
Code No. LIT-1928135
Issued September 7, 2004
DX-9100 Series
Extended Digital Controller
Description • Complete line of compatible sensors,
The DX-9100 Extended Digital Controller is actuators, and accessories for a total
the ideal digital control solution for multiple system solutionInterfaces to both
chiller or boiler plant applications, air handling pneumatic and electric actuators to provide
units, or distributed lighting control. low cost installation for both new
construction and retrofit applications
As a standalone controller, the DX-9100 • Graphical configuration via GX-9100
provides a real-time clock, extendable I/O, and software tool allows easy connection of
graphic software programming to target a Flow Chart Modules to obtain desired
variety of applications. Individual point control sequence
monitoring and control is available through the
• Built-in local status display makes it
front panel LED display.
convenient and easy to use
The DX-9100 also connects to the system • Password and Trend Log features
over the N2 Bus, integrating its point and Options (Part 1 of 2)
control information with the entire controller Application Configuration Options
network. Modules
Preconfigured examples are available for Analog Inputs Sensor/Transmitter ranging
common applications to use as a foundation High/Low limits DX-9100
for customizing to your particular facility. If the Filter constants
preconfigured examples don’t cover your Square root Options (Part 2 of 2)
requirements, you can configure a totally Control Blocks PID Loops Application Configuration Options
customized process. In addition, points Remote reset logic Modules
Operation modes Analog High/Low ranging
unused in the control scheme can be used in Control limits and alarms
non-critical supervisory or control applications Outputs
Sequencer and step control logic
by the Network. Digital Outputs Incremental with or without
Digital Inputs Source points for logic functions (DX Controller) feedback
Order DX-9100-8454 controller (FA-DX9100- Pulse counters Duration adjust type
8454 for Facilitator version) with mounting Calculation Averaging On/Off logic, including pulse
base DX-9100-8990 or DX-9100-8996. Blocks Minimum or maximum select Digital Outputs On/Off logic, including pulse
Enthalpy, wet bulb and dew point (XT Modules)
Features Input selector Time Schedule Yearly holiday calendar
• Standalone control provides system Arithmetic calculator Blocks Start-stop times for days of week
Compare logic and holidays
reliability
Line segment function Optimal start/stop modules
• Network communications over N2 Bus Timer functions (2 modules available)
provides facility-wide control efficiencies Run-time counter
and cost effective sensor sharing Totalizer and Integrator
• Fully integrated modular packaging allows Logic Blocks AND, OR, NOT
you to purchase only needed parts State change detect
Set and reset of parameters
Point Configuration
Point Type Quantity Characteristics
DX-9100 XT-9100 w/XPx XTM-905 w/XPx 1
Analog Inputs 8 6 6 0-10 VDC (impedance 300K ohm)
0/4-20 mA DC (impedance 100 ohm)
RTD Ni1000 (JCI), A99 (JCI), and Pt1000 (DIN)
Digital (Binary) Inputs 8 4/8/16 4/8/16 Dry Contacts (potential free)
Digital (Binary) Outputs 6 4/8/16 3 to 4/8/16 24 VAC Triacs (minimum 0.05 amperes [A], maximum 0.5A)
XT/XTM only: Relay Contact (maximum 250 VAC 3A)
XTM only: relays with magnetically latched or electrically held operation
Analog Outputs 4 2 2 0-10 VDC (10 mA maximum) or
0/4-20 mA DC
4 0 0 0-10 VDC (10 mA maximum) only
1. The specifications of this table only pertain to modules available in North America.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2004 Johnson Controls, Inc. www.johnsoncontrols.com
1 of 2
Code No. LIT-1928135
Extended Digital Controller (Continued)
Selection Chart Specifications
Code Number Description Extended Digital Controller
DX-9100-8454 Extended Digital Plant Controller, Version 2 Source Power 24 VAC +/-10% at 50/60 Hz
FA-DX9100-8454 Extended Digital Plant Controller, Version 2 (Facilitator) Ambient Operating 32 to 122°F (0 to 40°C)
DX-9100-8990 Wall Mounting Base Conditions 10 to 90% Non-Condensing RH
DX-9100-8991 Terminal Covers for wall mounting base Ambient Storage 0 to 160°F (-20 to 70°C)
Conditions 5 to 95% RH
DX-9100-8996 Door Mounting Base
Size (H x W x D) 7.9 in. x 7.2 in. x 3.9 in.
Accessories 200 x 184 x 100 mm
Code Number Description Weight FA-DX9100-8454, DX-9100-8454 4.7 lbs (2.2 kg)
DT-9100-8104 LCD Display Unit for DX-9100 Agency Listings UL864 (with DX-9100-8990 Base
CSA
Extension and Expansion Modules CE Directive 89/336/EEC
XT-9100-8304 Extension Module EN5008 1/2 and 2/1
XP-9102-8304 2 Analog Outputs and 6 Analog Inputs
XP-9103-8304 8 Digital Outputs (triacs)
XP-9104-8304 4 Digital Inputs, 4 Digital Outputs (triacs)
XP-9105-8304 8 Digital Inputs
XP-9107-8304 4 Digital Outputs (24V Relay)
XTM-905/XT-9100 Extension Module/XP910x
Expansion Modules DX-9100
Extension Modules (XT-9100/XPx or XTM-905/XPx) are submodules
that provide various combinations of analog and binary input/output
points. They may be mounted next to the controller on the same DIN
rail, or remotely, up to 4,000 feet from the controller. Up to eight
submodule combinations can connect to the XT Bus of the controller,
providing up to 64 additional I/O points. The XT Bus has the same
physical characteristics as the Metasys N2 Bus.
XT / XP
N2 Bus
AO7
min
XTM 905 / XP/ XP
AO8
min
dx9100xp
XT Bus
XT-9100 DX-9100
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2004 Johnson Controls, Inc. www.johnsoncontrols.com
2 of 2
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.