Code No. LIT-1921225
Issued January 15, 2008
C-9506
Air Switching Cumulator
Description Features
The C-9506 Air Switching Cumulator switches • ideally suited for exhaust damper
output pressure from zero to full supply applications requiring high output volume
pressure when the pilot pressure reaches the for quick operation
switch point. • adjustable switch point
Refer to C-9506 Air Switching Cumulator • mounts in any position with integral
Product Bulletin (LIT-7171455) for important mounting holes in base
product information.
Selection Charts
Technical Specifications C-9506 Air Switching Cumulator
Code Number Description
C-9506 Air Switching Cumulator
C-9506-1 Two-Position Cumulator
Action Two Position DA
Switch Point Adjustable from 2 to 12 psig Accessories for C-9506
(14 to 84 kPa) Code Number Description
Factory Set at 9 psig (63 kPa)
T-3100-6005 Air Connection Filter, 50/Pkg
Differential 1 psig (7 kPa) C-9506-1
Maximum Supply 25 psig (175 kPa)
Pressure
Repair Information
If the C-9506 Air-Switching Cumulator fails to operate within its specifications, replace the unit.
For a replacement cumulator, contact the nearest Johnson Controls® representative.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc. www.johnsoncontrols.comПозиції каталогу з цим документом