24- 4221- 9, Rev. B
                                                                                       Product Bulletin  C-5230
                                                                                       Issue Date February 2016

                                              C-5230
                                       Pneumatic Signal Limiter

Features                                  when the input signal is above
                                          the high limit setting. The output
•   Independently Adjustable              equals the input when the input
    High/Low Limits                       signal is between the set points.
•   Integral Hypodermic
                                          The C-5230-3 is shipped with
    Needle Test Points
                                          both of its pressure regulators
•   Field Chosen Supply
                                          preassembled on the unit. The
    Source
                                          C-5230-2 is shipped with its
•   Low Volume with Fast                  regulator mounted for the low
    Response                              limit application. For high limit
•   Compatible with Dual                  applications, the regulator must
    Supply Systems                        be removed and installed in the
                                          high limit location.
The C-5230 Pneumatic Signal
Limiter is designed to impose                                                          Fig. 1: C-5230 Pneumatic
high and/or low limits on any                                                                Signal Limiter
pneumatic signal. The limits
imposed depend on the model
used. The limiter is available in
two models; the C-5230-2 is
designed to impose high or low                Specifications
limits and the C-5230-3 is
designed to impose high and low
limits.
The low volume output
(45 SCIM) of the C-5230 is
isolated from the input and
repeats the input signal at a
1:1 ratio, limited by the high
and/or low adjustments.

Operation
The C-5230 contains an internal
pressure dropping orifice along
with one or two regulators
(depending on the model) for
adjusting the high and/or low
pressure limits. The high limit
regulator can be adjusted from
3 PSIG (21 kPa) to within 1 PSI
(7 kPa) of the supply pressure,
and the low limit regulator can be
adjusted from 2 PSIG
(14 kPa) to within 1 PSI (7 kPa)
of the supply pressure. The high
and low limits can operate within
0.25 PSI (1.7 kPa) of each other.
The output of the C-5230 equals
the low limit setting when the
input signal is below the low limit.
The output equals the high limit

© 2016 Johnson Controls, Inc.                                                                                     1
  Part No. 24-4221-9, Rev. B
  Code No. LIT-7171435
Note: To remove the
regulator, move it from side to
side 1/8 in. while pulling on
the knurled brass knob; do
not pull directly upward.
Before the regulator can be
reinstalled in the high limit
location, the 3/32 in.
polyurethane plug must be
removed. The plug should be
stored in one of the holes as
shown in Fig. 2. Simply push it
into the hole with a small probe
such as a paper clip, being
careful not to puncture the plug.
Note: The pressure regulator
is properly installed when the
action tab is positioned
toward its respective HI or LO
marking. The regulator
should be pushed in firmly.

Mounting
The C-5230 is designed for
surface mounting using the two
#8 sheet metal screws included
with the instrument. Air
connections are made to barbed
fittings for 5/32 in. O.D.
polytubing. Adapters for
converting 5/32 in. connections
to 1/4 in. connections are
included with the unit.
If the output “O” connection of
the C-5230 is being fed by a
restricted supply (for example
T-9000 manifold), the supply “S”
connection must be closed off
with the furnished 1/16 in. yellow
cap.

Repair Information
Field repairs must not be made.
For a replacement C-5230,
contact the nearest Johnson
Controls branch office.

Application and Drawing
Identification

2 C-5230 Product Bulletin
C-5230 Product Bulletin 3
Calibration                           C-5230-3 Adjustments for High           C-5230-2 Adjustments for High
                                      and Low Limits                          Limit Only (See Fig. 8)
High and/or low limits are an
integral feature of the C-5230.       4.   Turn the low limit regulator       Follow Steps 1 through 3 above.
The pressure regulator for the C-          fully clockwise
                                                                              4.   Remove the polyurethane
5230-2 is preassembled in the              (approximately two turns).
                                                                                   plug from hole #13 and
low limit configuration and preset    5.   Adjust the high limit                   store it in hole #9 (see
at approximately 9 PSIG (63                regulator until the desired             Fig. 3).
kPa). The high and low limits for          high limit is noted on the
the C-5230-3 are factory set at                                               5.   Remove the regulator from
                                           output gage.
approximately 15 and 5 PSIG                                                        the low position and relocate
(105 and 35 kPa) respectively. If     6.   Adjust the low limit regulator          it to the high position. Note:
adjustments are required,                  until the desired low limit             To remove the regulator,
proceed as follows:                        setting is noted on the                 move it from side to side
                                           output gage.                            1/8 in. while pulling on the
1.   Furnish 20 PSIG (140 kPa)
                                                                                   knurled brass knob; do
     supply air to the C-5230
                                      C-5230-2 Adjustments for Low                 not pull directly upward.
     supply “S” connection OR
                                      Limit Only                                   Install the regulator in the
     cap the “S” connection and
                                                                                   high position with the
     furnish a .007 in. restricted    Follow Steps 1 through 3 above.
     source of supply to the                                                       action tab pointing toward
     output “O” connection.           4.   Adjust the low limit regulator          the HI marking. The
                                           until the desired low limit             regulator should be
2.   Insert a hypodermic needle            setting is noted on the                 pushed in firmly.
     test probe (X-200-140                 output gage.
     ordered separately,                                                      6.   Close off hole #16 with a
     connected to a 0 to                                                           finger or temporarily plug it.
     30 PSIG gage using a 1 in.                                                    Doing so will allow the high
     length of polytubing) into                                                    limit adjustment to be made.
     output test point #1 (see Fig.                                           7    Adjust the high limit
     8).                                                                           regulator until the desired
3.   Set the input “I” connection                                                  high limit is noted on the
     to 0 PSIG.                                                                    output gage.
                                                                              8.   Reopen hole #16 to the
                                                                                   atmosphere.

                                                                            Note: Do not use Locktite in an
                                                                            attempt to seal the high and/or
                                                                            low limits of the C-5230 Signal
                                                                            Limiter; its chemical makeup is
                                                                            such that it will cause
                                                                            deterioration to the plastic
                                                                            components of the C-5230. If
                                                                            sealant is required, it is
                                                                            recommended that common
                                                                            fingernail polish be used.

4 C-5230 Product Bulletin
    European Single Point of Contact:   NA/SA Single Point of Contact:   APAC Single Point of Contact:
    JOHNSON CONTROLS                    JOHNSON CONTROLS                 JOHNSON CONTROLS
    WESTENDHOF 3                        507 E MICHIGAN ST                C/O CONTROLS PRODUCT
    45143 ESSEN                         MILWAUKEE WI 53202               MANAGEMENT
    GERMANY                             USA                              NO. 22 BLOCK D NEW DISTRICT
                                                                         WUXI JIANGSU PROVINCE 214142
                                                                         CHINA

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                        Printed in U.S.A.
Milwaukee, WI 53202

                                                                                  C-5230 Product Bulletin 5