Installation Instructions
Issue Date June 20, 2014
AS-CVTPRO300-1 and AS-CVTPRO400-1
Zone Bus/N2 Bus Interface Converters
Application
The AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone
Bus/N2 Interface Converters are portable converters
designed to provide a communication interface
between the room sensors and controllers operating
on a Zone Bus or N2 Bus and a computer. See
Table 3 for compatible tools, Operating Systems
(OSs), and controllers.
The AS-CVTPRO300-1 and AS-CVTPRO400-1
FIG:cvtpro_2
converter can be used in place of the MM-CVT101-0
converter module. The MM-CVT101-0 converter is not
compatible with Windows NT®, Windows® 2000, and
later versions of Windows OSs. Figure 2: CVTPRO Converter
Connection Ports
The sides of the CVTPRO converter have connections ! CAUTION: Risk of Property Damage
to an External Power Adapter (Figure 1) and a Zone Do not apply power to the system before checking
Bus/N2 Bus RJ11 6-pin network cable phone plug. all wiring connections. Short-circuited or improperly
connected wires may result in permanent damage to
the equipment.
Mise En Garde: Risque dégâts matériels. Ne pas
mettre le système sous tension avant d'avoir vérifié
tous les raccords de câblage. Des fils formant un
court-circuit ou connectés de façon incorrecte
risquent d'endommager irrémédiablement
l'équipement.
Figure 1: CVTPRO Converter Side
Figure 2 shows the RS-232 input. Green and yellow
Light-Emitting Diodes (LEDs) display the N2
communication status of the unit relative to the field
device. The red LED shows power status.
© 2014 Johnson Controls, Inc. 1
Part No. 24-10158-0, Rev. A www.johnsoncontrols.com
Cable Connectors
Figure 3 shows the 6-pin phone plug end of the
N2 cable used by the CVTPRO converter for N2 Bus
communication. For Zone Bus communication, always
use standard Zone Bus cables.
N2+ (Blue) N2- (White)
FIG:N2_6pin
N2 Ref. (Red)
Figure 3: N2 Cable 6-Pin RJ11 Network Phone Plug
Pin Signal
1 N2+
2 Zone Bus Power
3 GND
4 N2 Ref
FIG:pin_sig
5 Zone Bus Signal
6 N2-
Figure 4: Zone Bus/N2 Bus RJ11 Network
Phone-Jack Pin Designations
2 AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions
Table 1: Cable Connections for the AS-CVTPRO300-1 and ASCVTPRO400-1 Converters
To Connect the CVTPRO Use This Cable:
Converter To:
Controller via the Zone Bus 8-pin RJ45 to 6-pin RJ11 phone cable (1.8 m/6 ft)
Controller via the N2 Bus 4-pin N2 socket/3-pin N2 plug to 6-pin RJ11 phone cable (1.8 m/6 ft)
Note: Remove the 4-pin N2 socket from the cable and use the bare wires to
connect to N2 screw terminal devices.
Controller Zone Bus (via TE-6x00/ 6-pin to 6-pin RJ11 phone cable (1.8 m/6 ft)
TMZ Sensor)
Table 2: CVTPRO Converter and Accessories Product Code Numbers
Product Code Description
Number
AS-CVTPRO300-1 Zone Bus/N2 Bus Interface Converter with 120 VAC/3 VDC power adapter (North American
version)
AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converter without power adapter (European version)
AS-CVTPRO-703 CVTPRO converter without cables or case
AS-CVTCBL-700 Replacement set of cables used with the CVTPRO converter
Edgeport/1* USB to RS232 adapter
* Manufactured by Inside Out Networks (www.ionetworks.com)
AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions 3
Connecting to the CVTPRO Converter
Figure 5 illustrates the potential connections
between a CVTPRO converter and other devices.
See Table 1 for more information on cables. See
Figure 6 and Figure 7 for more detail about N2 Bus
connections.
TE-6x00/TMZ
Room Sensor
RJ11 Jack,
6-Pin
Compatible
RJ11 6-pin Jack Controller
for Zone Bus/N2 Bus
Connection RJ45 Jack,
8 Pin
DB9 Port or
CVTPRO Serial Port LED LEGEND
GREEN = TRANSMIT
Personal Computer Serial Cable RED = POWER
or
YELLOW = RECEIVE Zone Bus
or
DB9
Connector
N2 Bus
N2 Bus Interface,
i 4-Pin N2 Socket/
3-Pin N2 Plug with Tab
External Power
Adapter
USB to RS-232
1
Adapter (optional)
Notes:
1. The CVTPRO400-1 (European version) does not ship with an external power adapter.
Figure 5: Overview of Possible CVTPRO Converter Connections
4 AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions
Connecting the CVTPRO Converter to a Controller
with N2 Screw Terminals
To connect the CVTPRO converter to a controller with To scan an N2 Bus:
screw terminals (Figure 6):
1. Disconnect the N2 Bus from the N2 master
1. Disconnect the three N2 wires from the controller controller.
screw terminals and temporarily isolate the
2. Remove the N2 plug (with attached N2 wires)
individual bare wires with insulating tape.
from the controller (4-pin plug on the VMA and
2. Remove the 4-pin N2 socket from the CVTPRO 3-pin plug on other controllers).
N2 cable to expose the three wires (Figure 6 and
3. Connect the 3-pin or 4-pin N2 plug that was
Figure 7).
disconnected from the controller in Step 2 to the
3. Connect the exposed N2+ (blue), N2- (white), and 4-pin N2 socket on the CVTPRO converter cable.
Ref (red) wires from the CVTPRO N2 cable to the (See Figure 7.) Observe proper polarity (N2+ is
controller screw terminals. Observe proper blue, N2- is white, Ref is red).
polarity.
4. Connect the 6-pin RJ11 phone plug on the
4. Connect the 6-pin RJ11 phone plug on the opposite end of the CVTPRO N2 cable to the
opposite end of the CVTPRO N2 cable to the CVTPRO converter (Figure 3 and Figure 5).
CVTPRO converter (Figure 3 and Figure 5).
CVTPRO N2 Cable
3-Pin N2 Plug
Cable to the VMA
6-Pin RJ11 Phone Plug 4-Pin Jack
and CVTPRO Converter S
H
L
D
R
E
F
N N
2 2
- + Connect these
Ref (Red) components
N2- (White) to communicate
Remove N2+ (Blue) with the controller
FIG:N2_conn
4-Pin N2 via the CVTPRO
Wire Directly to Converter.
Socket Controller Terminals CVTPRO N2 Cable
3-Pin N2 Plug
Figure 6: CVTPRO N2 Connection to Controllers
with Screw Terminals
Cable to the
Connecting the CVTPRO Converter to a Controller 6-Pin RJ11 Phone Plug
with a N2 Jack and CVTPRO Converter
To connect the CVTPRO converter to a controller with 4-Pin N2 Socket on the
a removable N2 plug: CVTPRO N2 Cable
1. Remove the 3 or 4-pin N2 plug from the
controller. 4-Pin N2 Plug Connect these
SH
Unplugged LD REF N2- N2+
components
2. Plug the 3-pin plug CVTPRO N2 cable into the from the VMA to scan the N2 Bus
jack on the controller (The Variable Air Volume via the CVTPRO
Modular Assembly [VMA] has 4-pin jack, and Converter.
other N2 controllers have 3-pin jacks). Observe To To
N2 REF N2+
proper polarity (N2+ is blue, N2- is white, Ref is Next Next
FIG:N2_VMA
N2 N2- N2- N2
red).
Device N2+ N2 REF Device
3. Connect the 6-pin RJ11 phone plug on the
opposite end of the CVTPRO N2 cable to the
CVTPRO converter (Figure 3). Figure 7: CVTPRO N2 Connection to a VMA with a
Removable N2 Plug
Figure 7 shows the possible connections with a VMA
controller with a removable 4-pin N2 plug.
AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions 5
Compatibility Compatible controllers include the Air Handling Unit
Table 3 lists compatible tools, Operating Systems, and (AHU), Unitary Controller (UNT), Variable Air Volume
controllers used over the Zone Bus and N2 Bus with Controller (VAV), Network Dialer Module (NDM),
the CVTPRO converter. and VMA.
Table 3: Compatibility Chart
Tool Bus Operating System Compatible Controller
1
HVAC PRO Software (part of N2 Bus Windows 98 SE/Windows NT / AHU1xx
M-Tool Release 5.0 or later) Windows 2000PE2 OS UNT1xx
Zone Bus Windows 98 SE/Windows 2000PE2, 3 UNT11xx
OS
VAV1xx
VMA14x0
Zone Bus Windows NT1 VMA14x0*
VBT1400 Zone Bus Palm™ OS simulator and VMA14x0
Windows 2000 or Windows XP OS
GX-9100 Software N2 Bus Windows 98 SE/Windows NT1/ DT-9100
2
Configuration Tool (part of Windows 2000PE OS DX-9100
M-Tool Release 5.0 or later)
XT9100 (XP91xx)
XTM-905 (XPx-xxx)
XTM Configuration Tool N2 Bus Windows 98 SE1/Windows NT1/ XTM-105 (XPx-xxx)
Windows 2000PE2 OS
NDM Configuration Tool N2 Bus Windows 98 SE/ Windows NT1/ NDM
Windows 2000PE2 OS
Note: The CVTPRO converter is not compatible with Zone Terminal Units (ZTUs). For ZTUs, use the CBLPRO-2
converter. Refer to the Auxiliary Gear Technical Bulletin (LIT-6363080) for details on Johnson Controls®
converters.
1. For proper CVTPRO converter operation when running on Windows NT OSs, Service Pack 6 must be installed.
2. For proper CVTPRO converter operation when running on Windows 2000 OSs, use the Professional Edition only, and
Service Pack 2 must be installed.
3. On Zone Bus applications running on Windows 2000 OSs, HVAC PRO Version 8.04B or later must also be installed.
* When using the VMA14x0 with HVAC PRO software (versions prior to Version 8.04B only) over the Zone Bus with
Windows NT OSs, a Device Conflict box appears whenever the user attempts an operation (for example, upload or
download). To bypass the box, select Yes or No and the box disappears. The selected operation continues as
expected.
6 AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions
Technical Specifications
Product AS-CVTPROx00-1 Zone Bus/N2 Bus Interface Converter
AS-CVTPRO300-1 with 120VAC/3VDC External Power Adapter (North American version) with
USB/RS-232
AS-CVTPRO400-1 without power adapter (European version)
Power Requirements Zone Bus: Controller Supplied Power: Stand-Alone or via Thermostat - 24 VAC or
VMA applications - 15 VDC
N2 Bus: External Power Adapter: 120 VAC to +3 VDC 200 mA Class 2 Transformer
(Included with CVTPRO Converter in North America only)
Agency Listings FCC Part 15 Subpart B, Class A
CE Mark: EN50081-2 (Electromagnetic Compatibility, EN55011, Class A)
EN50082-2 (Electromagnetic Compatibility, EN61000-3-2 and EN61000-3-3)
Ambient Operating 0 to 50°C (32 to 122°F) 20-80% RH (Relative Humidity)
Conditions 30°C (86°F) Maximum Dew Point
Ambient Storage -40 to 60°C (-40 to 140°F) 5-95% RH
Conditions 30°C (86°F) Maximum Dew Point
Shipping Weight 0.227 kg (0.5 lb)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Refer to the Auxiliary Gear Technical Bulletin (LIT-6363080) for necessary information on ordering, operation, and performance specifications
of this product.