Installation Instructions
                                                                                    Issue Date     June 20, 2014

                         AS-CVTPRO300-1 and AS-CVTPRO400-1
                          Zone Bus/N2 Bus Interface Converters

Application
The AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone
Bus/N2 Interface Converters are portable converters
designed to provide a communication interface
between the room sensors and controllers operating
on a Zone Bus or N2 Bus and a computer. See
Table 3 for compatible tools, Operating Systems
(OSs), and controllers.
The AS-CVTPRO300-1 and AS-CVTPRO400-1
                                                                                                             FIG:cvtpro_2
converter can be used in place of the MM-CVT101-0
converter module. The MM-CVT101-0 converter is not
compatible with Windows NT®, Windows® 2000, and
later versions of Windows OSs.                                      Figure 2: CVTPRO Converter

Connection Ports
The sides of the CVTPRO converter have connections         !      CAUTION: Risk of Property Damage
to an External Power Adapter (Figure 1) and a Zone       Do not apply power to the system before checking
Bus/N2 Bus RJ11 6-pin network cable phone plug.          all wiring connections. Short-circuited or improperly
                                                         connected wires may result in permanent damage to
                                                         the equipment.

                                                         Mise En Garde: Risque dégâts matériels. Ne pas
                                                         mettre le système sous tension avant d'avoir vérifié
                                                         tous les raccords de câblage. Des fils formant un
                                                         court-circuit ou connectés de façon incorrecte
                                                         risquent d'endommager irrémédiablement
                                                         l'équipement.

         Figure 1: CVTPRO Converter Side
Figure 2 shows the RS-232 input. Green and yellow
Light-Emitting Diodes (LEDs) display the N2
communication status of the unit relative to the field
device. The red LED shows power status.

© 2014 Johnson Controls, Inc.                                                                                               1
  Part No. 24-10158-0, Rev. A                                                                 www.johnsoncontrols.com
Cable Connectors
Figure 3 shows the 6-pin phone plug end of the
N2 cable used by the CVTPRO converter for N2 Bus
communication. For Zone Bus communication, always
use standard Zone Bus cables.

          N2+ (Blue)              N2- (White)
                                                        FIG:N2_6pin
                    N2 Ref. (Red)

Figure 3: N2 Cable 6-Pin RJ11 Network Phone Plug

                 Pin Signal
                 1    N2+
                 2    Zone Bus Power
                 3    GND
                 4    N2 Ref

                                          FIG:pin_sig
                 5    Zone Bus Signal
                 6    N2-

     Figure 4: Zone Bus/N2 Bus RJ11 Network
           Phone-Jack Pin Designations

2   AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions
Table 1: Cable Connections for the AS-CVTPRO300-1 and ASCVTPRO400-1 Converters
 To Connect the CVTPRO                     Use This Cable:
 Converter To:
 Controller via the Zone Bus               8-pin RJ45 to 6-pin RJ11 phone cable (1.8 m/6 ft)
 Controller via the N2 Bus                 4-pin N2 socket/3-pin N2 plug to 6-pin RJ11 phone cable (1.8 m/6 ft)
                                           Note:    Remove the 4-pin N2 socket from the cable and use the bare wires to
                                           connect to N2 screw terminal devices.
 Controller Zone Bus (via TE-6x00/         6-pin to 6-pin RJ11 phone cable (1.8 m/6 ft)
 TMZ Sensor)

Table 2: CVTPRO Converter and Accessories Product Code Numbers
 Product Code                Description
 Number
 AS-CVTPRO300-1              Zone Bus/N2 Bus Interface Converter with 120 VAC/3 VDC power adapter (North American
                             version)
 AS-CVTPRO400-1              Zone Bus/N2 Bus Interface Converter without power adapter (European version)
 AS-CVTPRO-703               CVTPRO converter without cables or case
 AS-CVTCBL-700               Replacement set of cables used with the CVTPRO converter
 Edgeport/1*                 USB to RS232 adapter
 *    Manufactured by Inside Out Networks (www.ionetworks.com)

     AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions                     3
Connecting to the CVTPRO Converter
Figure 5 illustrates the potential connections
between a CVTPRO converter and other devices.
See Table 1 for more information on cables. See
Figure 6 and Figure 7 for more detail about N2 Bus
connections.
                                                                                                                   TE-6x00/TMZ
                                                                                                                   Room Sensor
                                                                                                                        RJ11 Jack,
                                                                                                                        6-Pin

                                                                                                                     Compatible
                                                                                           RJ11 6-pin Jack           Controller
                                                                                        for Zone Bus/N2 Bus
                                                                                             Connection               RJ45 Jack,
                                                                                                                      8 Pin
                DB9 Port                                                                        or
                              CVTPRO        Serial Port        LED LEGEND
                                                               GREEN = TRANSMIT
Personal Computer            Serial Cable                      RED = POWER
                                                                                              or
                                                               YELLOW = RECEIVE                         Zone Bus
        or
             DB9
           Connector
                                                                                                     N2 Bus
                                                                                                                   N2 Bus Interface,
                                    i                                                                               4-Pin N2 Socket/
                                                                                                                 3-Pin N2 Plug with Tab
                                                                                          External Power
                                                                                             Adapter
                                USB to RS-232
                                                 1
                               Adapter (optional)

                                   Notes:
                                   1. The CVTPRO400-1 (European version) does not ship with an external power adapter.

                           Figure 5: Overview of Possible CVTPRO Converter Connections

4   AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions
Connecting the CVTPRO Converter to a Controller
with N2 Screw Terminals
To connect the CVTPRO converter to a controller with                  To scan an N2 Bus:
screw terminals (Figure 6):
                                                                      1.   Disconnect the N2 Bus from the N2 master
1. Disconnect the three N2 wires from the controller                       controller.
   screw terminals and temporarily isolate the
                                                                      2.   Remove the N2 plug (with attached N2 wires)
   individual bare wires with insulating tape.
                                                                           from the controller (4-pin plug on the VMA and
2. Remove the 4-pin N2 socket from the CVTPRO                              3-pin plug on other controllers).
   N2 cable to expose the three wires (Figure 6 and
                                                                      3.   Connect the 3-pin or 4-pin N2 plug that was
   Figure 7).
                                                                           disconnected from the controller in Step 2 to the
3. Connect the exposed N2+ (blue), N2- (white), and                        4-pin N2 socket on the CVTPRO converter cable.
   Ref (red) wires from the CVTPRO N2 cable to the                         (See Figure 7.) Observe proper polarity (N2+ is
   controller screw terminals. Observe proper                              blue, N2- is white, Ref is red).
   polarity.
                                                                      4.   Connect the 6-pin RJ11 phone plug on the
4. Connect the 6-pin RJ11 phone plug on the                                opposite end of the CVTPRO N2 cable to the
   opposite end of the CVTPRO N2 cable to the                              CVTPRO converter (Figure 3 and Figure 5).
   CVTPRO converter (Figure 3 and Figure 5).
                   CVTPRO N2 Cable
                     3-Pin N2 Plug

           Cable to the                                                         VMA
      6-Pin RJ11 Phone Plug                                                  4-Pin Jack
     and CVTPRO Converter                                                                                S
                                                                                                         H
                                                                                                         L
                                                                                                         D
                                                                                                             R
                                                                                                             E
                                                                                                             F
                                                                                                                 N N
                                                                                                                 2 2
                                                                                                                 - +           Connect these
                                      Ref (Red)                                                                                 components
                                    N2- (White)                                                                               to communicate
                    Remove     N2+ (Blue)                                                                                    with the controller

                                                        FIG:N2_conn
                    4-Pin N2                                                                                                 via the CVTPRO
                                    Wire Directly to                                                                             Converter.
                     Socket      Controller Terminals                      CVTPRO N2 Cable
                                                                             3-Pin N2 Plug
 Figure 6: CVTPRO N2 Connection to Controllers
              with Screw Terminals
                                                                            Cable to the
Connecting the CVTPRO Converter to a Controller                        6-Pin RJ11 Phone Plug
with a N2 Jack                                                        and CVTPRO Converter

To connect the CVTPRO converter to a controller with                   4-Pin N2 Socket on the
a removable N2 plug:                                                     CVTPRO N2 Cable

1.     Remove the 3 or 4-pin N2 plug from the
       controller.                                                         4-Pin N2 Plug                                        Connect these
                                                                                           SH
                                                                             Unplugged     LD   REF   N2- N2+
                                                                                                                                  components
2.     Plug the 3-pin plug CVTPRO N2 cable into the                        from the VMA                                       to scan the N2 Bus
       jack on the controller (The Variable Air Volume                                                                         via the CVTPRO
       Modular Assembly [VMA] has 4-pin jack, and                                                                                  Converter.
       other N2 controllers have 3-pin jacks). Observe                  To                                                 To
                                                                             N2 REF                                N2+
       proper polarity (N2+ is blue, N2- is white, Ref is              Next                                               Next

                                                                                                                                                   FIG:N2_VMA
                                                                        N2    N2-                                  N2-     N2
       red).
                                                                      Device  N2+                                 N2 REF Device
3.     Connect the 6-pin RJ11 phone plug on the
       opposite end of the CVTPRO N2 cable to the
       CVTPRO converter (Figure 3).                                   Figure 7: CVTPRO N2 Connection to a VMA with a
                                                                                    Removable N2 Plug
Figure 7 shows the possible connections with a VMA
controller with a removable 4-pin N2 plug.

      AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions                                             5
Compatibility                                                  Compatible controllers include the Air Handling Unit
Table 3 lists compatible tools, Operating Systems, and         (AHU), Unitary Controller (UNT), Variable Air Volume
controllers used over the Zone Bus and N2 Bus with             Controller (VAV), Network Dialer Module (NDM),
the CVTPRO converter.                                          and VMA.

Table 3: Compatibility Chart
 Tool                             Bus             Operating System                        Compatible Controller
                                                                              1
 HVAC PRO Software (part of       N2 Bus          Windows 98 SE/Windows NT /              AHU1xx
 M-Tool Release 5.0 or later)                     Windows 2000PE2 OS                      UNT1xx
                                  Zone Bus        Windows 98 SE/Windows 2000PE2, 3        UNT11xx
                                                  OS
                                                                                          VAV1xx
                                                                                          VMA14x0
                                  Zone Bus        Windows NT1                             VMA14x0*
 VBT1400                          Zone Bus        Palm™ OS simulator and                  VMA14x0
                                                  Windows 2000 or Windows XP OS
 GX-9100 Software                 N2 Bus          Windows 98 SE/Windows NT1/              DT-9100
                                                                 2
 Configuration Tool (part of                      Windows 2000PE OS                       DX-9100
 M-Tool Release 5.0 or later)
                                                                                          XT9100 (XP91xx)
                                                                                          XTM-905 (XPx-xxx)
 XTM Configuration Tool           N2 Bus          Windows 98 SE1/Windows NT1/             XTM-105 (XPx-xxx)
                                                  Windows 2000PE2 OS
 NDM Configuration Tool           N2 Bus          Windows 98 SE/ Windows NT1/             NDM
                                                  Windows 2000PE2 OS
 Note:     The CVTPRO converter is not compatible with Zone Terminal Units (ZTUs). For ZTUs, use the CBLPRO-2
           converter. Refer to the Auxiliary Gear Technical Bulletin (LIT-6363080) for details on Johnson Controls®
           converters.
 1.    For proper CVTPRO converter operation when running on Windows NT OSs, Service Pack 6 must be installed.
 2.    For proper CVTPRO converter operation when running on Windows 2000 OSs, use the Professional Edition only, and
       Service Pack 2 must be installed.
 3.    On Zone Bus applications running on Windows 2000 OSs, HVAC PRO Version 8.04B or later must also be installed.
 *     When using the VMA14x0 with HVAC PRO software (versions prior to Version 8.04B only) over the Zone Bus with
       Windows NT OSs, a Device Conflict box appears whenever the user attempts an operation (for example, upload or
       download). To bypass the box, select Yes or No and the box disappears. The selected operation continues as
       expected.

6     AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions
Technical Specifications
  Product                            AS-CVTPROx00-1 Zone Bus/N2 Bus Interface Converter
                                     AS-CVTPRO300-1 with 120VAC/3VDC External Power Adapter (North American version) with
                                     USB/RS-232
                                     AS-CVTPRO400-1 without power adapter (European version)
  Power Requirements                 Zone Bus: Controller Supplied Power: Stand-Alone or via Thermostat - 24 VAC or
                                     VMA applications - 15 VDC
                                     N2 Bus: External Power Adapter: 120 VAC to +3 VDC 200 mA Class 2 Transformer
                                     (Included with CVTPRO Converter in North America only)
  Agency Listings                    FCC Part 15 Subpart B, Class A
                                     CE Mark: EN50081-2 (Electromagnetic Compatibility, EN55011, Class A)
                                     EN50082-2 (Electromagnetic Compatibility, EN61000-3-2 and EN61000-3-3)
  Ambient Operating                  0 to 50°C (32 to 122°F) 20-80% RH (Relative Humidity)
  Conditions                         30°C (86°F) Maximum Dew Point
  Ambient Storage                    -40 to 60°C (-40 to 140°F) 5-95% RH
  Conditions                         30°C (86°F) Maximum Dew Point
  Shipping Weight                    0.227 kg (0.5 lb)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Refer to the Auxiliary Gear Technical Bulletin (LIT-6363080) for necessary information on ordering, operation, and performance specifications
of this product.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                                 Published in U.S.A.
Milwaukee, WI 53201                                                                                                    www.johnsoncontrols.com

     AS-CVTPRO300-1 and AS-CVTPRO400-1 Zone Bus/N2 Bus Interface Converters Installation Instructions                                           7