Product Bulletin
                                                                                Issue Date      June 18, 2015

                AP-TMZ1600 Room Sensor with LCD Display

The AP-TMZ1600 room sensor is compact, with a
Liquid Crystal Display (LCD) and keypad control
selection. You can use the AP-TMZ1600 with several
controllers including the Variable Air Volume (VAV)
controllers (Revision D or later), Unitary (UNT)
controllers (Revision D or later), and VAV Modular
Assembly (VMA) controllers (Revision C00 or later).
This compact room sensor provides a visual display of
room conditions, and allows adjustments at the touch
of a button.
The AP-TMZ1600 room sensor is easy to use and
understand. It displays information to help occupants
control their environment and uses a password level to
provide additional control selections.

                                                                 Figure 1: AP-TMZ1600 Room Sensor

                                            Features and Benefits
                   LCD Display                    Uses icons that are easy to understand and
                                                   provide the user with a quick indication of
                                                   operation. Nonglare bezel for easy viewing.

                   Keypad Control                 Offers the user menu selections for optimal
                                                   environmental control.

                   Password Level                 Prevents user access to make adjustments
                                                   and provides additional control options.

                   Temporary Occupancy or         Provides a timed override command, which
                       Mode Override               temporarily initiates an alternate mode.
                                                   A Light-Emitting Diode (LED) indicates this
                                                   alternate mode is active.

                   Sleek Appearance               Offers a compact style and blends with the
                                                   environment.

                   Versatile Application          Works with the controllers used in most
                                                   common Heating, Ventilating, and Air
                                                   Conditioning (HVAC) applications. The
                                                   AP-TMZ1600 sensor works with the UNT,
                                                   VMA, and VAV controllers.

© 2015 Johnson Controls, Inc.                                                                                       1
  Code No. LIT-635027                                                                          www.johnsoncontrols.com
Product Overview                                               Person-Machine Interface (PMI)
The AP-TMZ1600 room sensor is attractive and                   The LCD display (Figure 2) shows text and symbols to
user-friendly, with an easy-to-read nonglare display           indicate the operational status of the connected
and compact styling. This sensor features room                 controller.
comfort at the touch of a button and an LCD for
convenient feedback on changing room conditions.                          OUT                           TMP
The AP-TMZ1600 is designed to communicate data
over a communication network from a remotely located                      RM                            UN-
controller.                                                               AIR                           OCC
The AP-TMZ1600 room sensor communicates on the                                                      OFF SBy
Zone Bus and works with several controllers including
the UNT (Revision D or later), VMA (Revision C00 or                Figure 2: AP-TMZ1600 LCD Display Symbols
later), and VAV (Revision D or later). Configure
all controllers used with the AP-TMZ1600 sensor with           Use the four-button keypad to select several different
HVAC PRO Release 8.01 or later (part of M-Tool                 functions (Table 1). An additional button offers timed
Release 1.0 [MW-MTOOL-0]).                                     override capability.

                                                               Remote Sensing
                                                               With HVAC PRO software, customers can use a
                                                               remote sensor instead of the sensor on the
                                                               AP-TMZ1600 room sensor to read zone temperature.

Table 1: AP-TMZ1600 Button Interface
 Button           Operation
 Menu             Cycles through the following display options: room air temperature, outdoor air temperature, comfort
                  setpoint temperature, and fan operation.
                  In Password mode, cycles through these additional display options: comfort setpoint temperature
                  access status, fan access status, timed override duration, heating setpoint temperature, and cooling
                  setpoint temperature.
 Down Arrow       Displays the comfort setpoint temperature if pushed while the room air (RM AIR) temperature is
                  displayed.
                  Lowers the setpoint temperature if the setpoint is displayed and blinking.
                  Toggles fan operation mode between On and Auto if the fan mode is displayed and blinking.
                  In Password mode, sets user access to UnLK (unlock).
 Up Arrow         Displays the comfort setpoint temperature if pushed while the room air (RM AIR) temperature is
                  displayed.
                  Raises the setpoint temperature if the setpoint is displayed and blinking.
                  Toggles fan operation mode between On and Auto if the fan mode is displayed and blinking.
                  In Password mode, sets user access to LOCK.
 °F/°C            Toggles temperature display between degrees Fahrenheit (°F) and degrees Celsius (°C).
 Temporary        Toggles the VAV, VMA, or UNT controller between Standby or Unoccupied mode and Temporary
 Occupancy        Occupancy mode. The LED lights when Temporary Occupancy mode is active for the VAV and UNT.
 Notes: Press the Menu and °F/°C buttons simultaneously for approximately 10 seconds to access Password mode.
 Setpoint adjustments only affect the setpoints for the Occupied mode of operation.

2   AP-TMZ1600 Room Sensor with LCD Display Product Bulletin
Table 2: AP-TMZ1600 Sensor Symbol                           •   Password mode allowing user locks on comfort
Descriptions                                                    setpoint, fan speed adjustments, time selection for
                                                                Temporary Occupied mode, and selection of heating
    Symbol       Description
                                                                and cooling setpoints for dual-setpoint applications
    RM AIR       Room Air Temperature – Not adjustable          (40-95°F [4.5-35°C] maximum range)
    OUT AIR      Outside Air Temperature – Not
                 adjustable                                 •   single- or dual-setpoint adjustments that allow
                                                                separate heating and cooling setpoints
                 Fan Symbol – Indicates fan operation.
                 Not used with VAV or VMA.                  •   phone jack connection at the bottom of casing that
                 Heating (flame) and Cooling (snowflake)        connects to a laptop or Zone Terminal Unit (ZTU) to
                 – Comfort value adjustable when                the Zone Bus (via the Cable PRO interface)
                 numbers blink. Static indicates
                 operation. Appears when device is in       Refer to the AP-TMZ1600 Room Sensor with LCD
                 Password mode.                             Display Installation Instructions (LIT-6363110) for further
    TMP OCC,     Mode of operation – TMP OCC appears        product information.
    OCC,         on display when Timed Override Mode
    UN OCC,      button is pressed and LED is lighted.       IMPORTANT: AP-TMZ1600 Firmware Revision A07
    SBy, OFF                                                 and earlier supports a narrower setpoint range of
                                                             18.3 to 29.4ºC (65 to 85ºF). Use TMZ Firmware
                                                             Revision A08 or later along with HVAC PRO Release
You can lock comfort setpoint and fan speed                  8.04 or later to take full advantage of the wider
adjustments from user access if selected in the              setpoint ranges described in this literature.
Password mode. You can lock adjustments of all
functions from user access by relocating a jumper on
the electronics board.                                      Installation
                                                            The AP-TMZ1600 room sensor is easy to install and
Additional Features                                         comes with both surface and wallbox mounting plates.
                                                            The AP-TMZ1600 sensor, used with the VAV, VMA, and
Both models of room sensors share the following
                                                            UNT controllers, connects to the Zone Bus with an 8-pin
features:
                                                            phone jack connection.
•     display of room and outdoor temperatures
                                                                      N2
•     RM AIR that is used as a default screen when
      no selections are made for 30 seconds
•     comfort setpoint temperature control with 45 to
      90°F (7 to 32°C) maximum range. Comfort
      setpoint is the average of the heating and                                       UNT
                                                                           VAV
      cooling setpoints selected in dual setpoint                                                    VMA
      applications, or it is the actual occupied setpoint
      in single setpoint applications.
•     maximum comfort setpoint range of 45 to 90°F
      (7 to 32°C). To adjust this range, use the                                   AP-TMZ1600
                                                                    AP-TMZ1600        Room
      HVAC PRO Parameters screen to limit the                          Room                   AP-TMZ1600
                                                                                     Sensor
      comfort setpoint range available at the                         Sensor                     Room
      thermostat. For example, you can set the low                                              Sensor
      limit to 68°F (19°C) and the high limit to 72°F
      (22°C).
•     fan speed selection based on fan operation                                    CBLPRO-1 or later
      allowed by the controller

                                                                                                             F IG : tm x ov erv ie w
•     Mode Override button for selecting a timed
      Temporary Occupancy mode
                                                                                               Laptop

                                                                         Figure 3: AP-TMZ1600 Sensor

                                                    AP-TMZ1600 Room Sensor with LCD Display Product Bulletin                           3
Technical Specifications
 Product Code Number                  AP-TMZ1600-0 (for VAV, VMA, UNT)
 Operating Environment                32 to 122°F (0 to 50°C)
                                      10 to 90% noncondensing humidity
 Storage Environment                  -40 to 140°F (-40° to 60°C), 10 to 90% noncondensing humidity
 Input Supply Voltage                 7.2 to 8.8 VDC (TMS1600)
                                      12 to 30 VAC or 12 to 40 VDC
 Input Current Required               10 mA maximum
 Housing Material                     ABS + polycarbonate, self-extinguishing UL 94-V0
 Housing Protection                   IP 30 (IEC 529)
 Dimensions                           3.15 x 3.15 x 1.26 in. (80 x 80 x 32 mm)
 Weight                               5.3 oz (0.15 kg)
 Override Button                      Momentary contact
 Mode Indicator                       Red LED
 Temperature Sensor
                                      Sensor Type:                    Nickel PTC
                                      Range:                          32 to 122°F (0 to 50°C)
                                      Reference Resistance:           1,000 ohm at 70°F (21.1°C)
                                      Accuracy:                       +/-0.3°F (0.2°C) at 70°F (21.1°C)
                                                                      +/-1°F (0.6°C) at 32 to 122°F (0 to 50°C)

 Software                             HVAC PRO Release 8.01 or later (part of M-Tool Release 1.0 [MW-MTOOL-0])

 Interface                            AS-CBLPRO-1 or later (use with Zone Terminal Unit)
 Agency Compliance                    UL Listed, File E107041, CCN PAZX, UL916
                                      cUL Listed, File E107041, CCN PAZX7, CSA C22.2 No. 205-M1983
                                      CE Compliant to EMC Directive 89/336/EEC, EN50081-1 and EN50082-1
                                      FCC Compliant to CFR47, Part 15, Class A
                                      FCC Compliant to CFR47, Part 15, Class B (not applied for)
                                      Canadian ICES-003 Compliant, C-Tick
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202

                                              Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                     All other marks herein are the marks of their respective owners. © 2015 Johnson Controls, Inc.

4   AP-TMZ1600 Room Sensor with LCD Display Product Bulletin