Текст документа
Code No. LIT-1927385
Issued August 13, 2014
A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X
Watertight Enclosures
Description Features
The A419 Series controls are single-stage, • low- and line-voltage models provide
electronic temperature controls with a Single options for almost any refrigeration or
Pole, Double Throw output relay. They feature HVAC control-voltage application
a lockable front-panel touchpad for setup and • easy-to-read LCD displays the sensed
adjustment, and an LCD for viewing the temperature and control-function status
temperature and status of other functions. An clearly, and custom icons on the display
LED indicates the controls’ output relay (On/ indicate the control and system status at a
Off) status. The A419 controls are available in glance
24 VAC or 120/240 VAC models. • 30° (F° or C°) temperature differential
The A419 controls have heating and cooling adjustment range allows precise (1F° or C°)
modes, adjustable setpoint and differential, an temperature differential settings that are
adjustable anti-short cycle delay, and a much tighter than electromechanical
temperature offset (setback) function. The controls
setpoint range is -30 to 212°F (-34 to 100°C). • Adjustable Anti-Short Cycle Delay
The controls feature remote sensing capability (0 to 12 Minutes in 1-Minute Increments)
and interchangeable sensors. The A419 ensures that the output relay remains off for
controls are available in either NEMA 1 high- a user-set time delay, and helps avoid hard
impact plastic enclosure suitable for surface or starts, nuisance overload outages, and
DIN rail mounting, or NEMA 4X Watertight unnecessary equipment wear
A419 Control and Sensor
surface-mount enclosures. • Temperature Offset Function shifts the cut-
in and cut-out setpoints by an adjustable
Applications offset when a user-installed, external switch
The A419 can be used to control a wide variety closes the A419 control’s binary input circuit
of single-stage refrigeration or HVAC • high-impact thermoplastic type NEMA 1
equipment. Typical applications include: allows surface or snap-fit DIN rail mount;
LEXAN® 950 high-impact thermoplastic
• freezer control in convenience stores type NEMA 4X enclosures allow watertight
• reach-in coolers surface mount
• supermarket display cases for produce or • lockable front-panel touchpad allows easy
meats setup and adjustment of the A419 control
• restaurant or convenience store walk-in setpoint, differential, and other functions; a
coolers concealed jumper locks the touchpad to
• boiler control deter unauthorized adjustment of the
• compressor lockout (disables the control settings
compressor when temperature exceeds
limits)
• condenser fan cycling
• pump control for cooling towers
• space and return air temperature
Selection Chart
A419 Series Electronic Temperature Control with NEMA 1 or NEMA 4X Watertight Enclosure
Code Number Item Lead Length Description
A419ABC-1C1 Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display 6-1/2 ft (2 m)
A419ABC-2C1 Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display 9-3/4 ft (3 m)
A419ABC-3C1 Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display 13 ft (4 m) Supply Voltage: 120 or 240 VAC
Range: -30 to 212°F (-34 to 100°C)
A419ABC-4C 1 Line Voltage, NEMA 1 Enclosure Electronic Temperature Control with Display 19-1/2 ft (5 m) Differential: 1 to 30F° (1 to 30C°)
A419AEC-1C1 Line Voltage, NEMA 4X Enclosure Electronic Temperature Control with Display 9-3/4 in. (0.25 m)
A419AEC-2C1 Line Voltage, NEMA 4X Enclosure Electronic Temperature Control with Display 6-1/2 ft (2 m)
A419GBF-1C 1 24 VAC, NEMA 1 Enclosure Electronic Temperature Control with Display 6-1/2 ft (2 m) Supply Voltage: 24 VAC, Class 2
Range: -30 to 212°F (-34 to 100°C)
A419GEF-1C 1 24 VAC, NEMA 4X Enclosure Electronic Temperature Control with Display 9-3/4 in. (0.25 m) Differential: 1 to 30F° (1 to 30C°)
1. A99 Sensor included with all models
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc. www.johnsoncontrols.com
1
A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight
Enclosures (Continued)
Accessories and Replacement Parts
Code Number Item Description
A99BB-200C Replacement Temperature Sensors1 PTC Sensor with 6-1/2 ft (2 m) Leads
A99BA-200C PTC Sensor with 6-1/2 ft (2 m) Shielded Leads
A99BB-25C PTC Sensor with 9 in (0.25 m)
BKT287-1R Accessory Mounting Hardware 12 in. (305 mm) long DIN Rail
BKT287-2R 36 in. (914 mm) long DIN Rail
PLT344-1R Two End Clamps for DIN Rail Mounting
CLK350-2 Digital Clock 7-Day Programmable Digital Clock for controlling Temperature Offset Function
WEL11A-601R Immersion Well Immersion Well for applying sensor in fluid applications
1. For other available sensors, refer to the A99B Series Temperature Sensor Catalog Page (LIT-1900006).
Technical Specifications and Electrical Ratings
A419 Series Electronic Temperature Controls
with NEMA 1 General Purpose or NEMA 4X Watertight, Corrosion-Resistant Enclosures
Setpoint Range -30 to 212°F (-34 to 100°C)
Differential Range 1 to 30F° (1 to 30C°)
Supply Voltage 24 VAC, 60 Hz, Class 2 A419GBF (NEMA 1 Enclosure Model)
A419GEF (NEMA 4X Watertight Enclosure Model)
120 or 240 VAC, 60 Hz A419ABC (NEMA 1 Enclosure Model)
A419AEC (NEMA 4X Watertight Enclosure Model)
Power Consumption 1.8 VA Maximum
Output Relay Contacts 24 VAC models A419GBF (NEMA 1 Enclosure)
Electrical Ratings A419GEF (NEMA 4X Watertight Enclosure)
100 VA, 30 VAC maximum, Class 2
120/240 VAC models A419ABC (NEMA 1 Enclosure)
A419AEC (NEMA 4X Watertight Enclosure)
Applied Voltage 120 VAC 208 VAC 240 VAC
Horsepower N.O. (N.C.) 1 (0.25) hp 1 (0.33) hp 1 (0.5) hp
Full Load Amperes N.O. (N.C.) 16 (5.8) A 9.2 (4.0) A 8.0 (4.9) A
Locked Rotor Amperes N.O. (N.C.) 96 (34.8) A 55.2 (24) A 48 (29.4) A
Non-inductive Amperes N.O. (N.C.) 15 (10) A 10 (10) A 10 (10) A
Pilot Duty 125 VA (N.O. contacts) at 24 to 240 VAC
125 VA (N.C. contacts) at 120 to 240 VAC
50 VA (N.C. contacts) at 24 VAC
Sensor Type A99BB Type PTC Sensor
Control Ambient Operating -26 to 140°F (-32 to 60°C)
Temperature Shipping -40 to 185°F (-40 to 85°C)
Ambient Humidity 0 to 95% RH Noncondensing; Maximum Dew Point: 85°F (29°C)
Control Material Case and Cover NEMA 1 High-impact Thermoplastic
NEMA 4X Watertight Corrosion-Resistant, High-Impact Thermoplastic Polycarbonate
Agency Listings UL: File E27734; CCN’s XAPX (US), XAPX7 (Canada)
FCC: CFR 47, Part 15, Class A. DOC, Class A
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc. www.johnsoncontrols.com
2Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.