Product/Technical Bulletin                  A419
                                                                                  Issue Date        August 13, 2014

        A419 Series Electronic Temperature Controls with Display
            and NEMA 1 or NEMA 4X Watertight Enclosures
The A419 series controls are single-stage, electronic
temperature controls with a Single-Pole, Double-Throw
(SPDT) output relay. They feature a lockable
front-panel touchpad for setup and adjustment, and an
LCD for viewing the temperature and status of other
functions. An LED indicates the controls’ output relay
On/Off status. The A419 controls are available in 24
VAC or 120/240 VAC powered models.
The A419 controls have heating and cooling modes,
adjustable setpoint and differential, an adjustable
anti-short cycle delay, and a temperature offset
function. The setpoint range is -30 to 212°F
(-34 to 100°C). The controls feature remote sensing
capability and interchangeable sensors. The
A419 controls are available in either NEMA 1,
high-impact plastic enclosure suitable for surface or
DIN rail mounting or NEMA 4X watertight,                    Figure 1: A419 Temperature Control with NEMA 1
corrosion-resistant surface-mount enclosures.                   Enclosure and A99 Temperature Sensor

                                             Features and Benefits
  Easy-to-Read Front-Panel                              Displays the sensed temperature and control-function
      Liquid Crystal Display                             status clearly; custom icons on the display indicate the
                                                         control and system status at a glance

  Wide Temperature Differential Adjustment              Allows the user to set a precise (1F° or C°) temperature
      Range (1 to 30F° or C°)                            differential from 1 to 30F° or C°; providing a much
                                                         tighter differential than electromechanical controls

  Adjustable Anti-Short Cycle Delay                     Ensures that the output relay remains off for a user-set
      (0 to 12 Minutes in 1-Minute Increments)           time delay, which helps avoid hard starts, nuisance
                                                         overload outages, and unnecessary equipment wear

  Switch-Activated Temperature Offset                   Allows the user to shift the cut-in and cutout setpoints
      Function                                           by an adjustable offset based on the status of a
                                                         user-installed, external switch, such as a time clock

  High-Impact, Thermoplastic NEMA 1 or                  Increase application options, allowing surface and
      NEMA 4X Watertight, Corrosion-Resistant            snap-fit DIN rail mount, or Watertight surface mount
      Enclosures

  Lockable Front Panel Touchpad                         Allows easy set up and adjustment of the A419 control
                                                         setpoint, differential, and other functions; a concealed
                                                         jumper locks the touchpad, and deters unauthorized
                                                         adjustment of the control settings

  Low- and Line-Voltage Models                          Provide options for most refrigeration and HVAC
                                                         control-voltage applications

© 2014 Johnson Controls, Inc.                                                                                        1
Code No. LIT-125188                                                                             www.johnsoncontrols.com
Application                                                  Dimensions
                                                                        9/64                 2-3/8
 IMPORTANT:            The A419 Series Temperature                      (3.7)                 (61)
 Controls are intended to control equipment under
 normal operating conditions. Where failure or
 malfunction of an A419 Series Control could lead to             1/2
                                                                (13)                                                            5
 an abnormal operating condition that could cause                                  DIN                            MENU
                                                                                                                              (127)
                                                             2-15/16               Rail
 personal injury or damage to the equipment or other           (75)
 property, other devices (limit or safety controls) or                                                                       4
                                                                                                                           (102)
 systems (alarm or supervisory) intended to warn of
 or protect against failure or malfunction of the A419
 Series Control must be incorporated into and
                                                                        1-9/16      7/16                         2-3/8
 maintained as part of the control system.                               (40)       (11)                         (61)

The A419 Electronic Temperature Control can be used                               Sensor
                                                                                                                           2-3/8
to control a wide variety of single-stage refrigeration or                           2                                     (61)
HVAC equipment. Typical applications include:                               1/4    (50)             7/8
                                                                            (6)                    (22)
•   retail store display freezers and reach-in coolers                                                    7/8 (1/2 in. Trade Size)
                                                                                                          (22) Conduit Hole
•   supermarket display cases for produce/meats
•   retail store walk-in coolers and freezers                     Figure 2: A419 Temperature Control with
                                                                  NEMA 1 Enclosure, Dimensions, in./(mm)
•   boiler operating control (used as a thermostat)
                                                                        2-1/4                                    1-1/16
•   condenser fan cycling or staging                                    (56)                                      (27)

•   cooling tower pump and fan control                                                        1-3/4
                                                                                               (44)
•   space and return air temperature control
                                                                       A419

FCC Compliance                                                                       6-5/8
                                                                                     (168)
This device complies with Part 15 of the FCC Rules.                      MENU

Operation is subject to the following two conditions:                                      6-1/8
(1) this device may not cause harmful interference,                                        (155)
and (2) this device must accept any interference that
may cause undesired operation.
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of FCC rules. These limits are designed to                     2-13/16
                                                                         (71)                 Position the A99 sensor
provide reasonable protection against harmful
                                                                                              in the bracket at the bottom of
interference when this equipment is operated in a                                             the A419 NEMA 4X enclosure.
commercial environment. This equipment generates,                                     2-13/16
uses, and can radiate radio frequency energy and, if                                   (71)
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in
a residential area may cause harmful interference, in            Figure 3: A419 Temperature Control with
which case the users will be required to correct the             NEMA 4X Watertight, Corrosion-resistant,
interference at their own expense.                                   Enclosure, Dimensions, in./(mm)

Canadian Compliance Statement
This digital apparatus does not exceed the Class A
limits for radio noise emissions from digital apparatus
set out in the Radio Interference Regulations of the
Canadian Department of Communications.

2   A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
    Product/Technical Bulletin
                                                         Liquid Crystal Display
                                                         During normal operation, the LCD displays the
                                                         temperature at the sensor, the units of temperature
                                                         (°F or °C), and an icon indicating if the control is set for
                                                         Heating ( ) or Cooling ( ) mode. The LCD also
                                                         displays BIN if the Temperature Offset function is
                                                         activated. See Figure 5.
                                                         During control set up or adjustment, the LCD displays
                                                         the control functions and their values (settings). After
                                                         30 seconds of inactivity, the display returns to the
                                                         sensed-temperature display. See the Adjustments
                                                         section to adjust the control setting.

                                                         Output Relay Status Indicator LED
                                                         A green LED on the control’s front panel illuminates
                                                         when the SPDT output relay is energized and the
                                                         Normally Open (N.O.) contacts are closed.
                                                         See Figure 5.

                                                         A419 Control Definitions
Figure 4: A419 Temperature Control with NEMA 4X          Cut-in is the temperature at which the N.O. contacts
     Enclosure and A99 Temperature Sensor                on the SPDT output relay close.
                                                         Cutout is the temperature at which the N.O contacts
Operation Overview                                       on the SPDT output relay open.
The A419 control’s front-panel, LCD, LED, and the
A419 control functions are described below. See the      A419 Functions Set at the Front-Panel
Adjustments section for instructions on setting up and
                                                         Setpoint (SP) establishes the temperature value that
adjusting the A419 control.
                                                         energizes or de-energizes the output relay, depending on
A419 Control Front-Panel                                 the user selected mode of operation. The control may be
                                                         set either to cut in or to cut out at Setpoint. See the
The front panel of the A419 control has a three-button
                                                         Cooling/Heating and Setpoint Modes. The Setpoint range
touchpad and LCD for adjusting control function
                                                         is -30 to 212°F (-34 to 100°C).
values, and an LED indicator that displays the On/Off
status of the SPDT output relay. See Figure 5.           If Setpoint mode is Cut-in, Setpoint is the temperature
                                     Temperature         value that closes the N.O. contacts. If Setpoint mode is
                                    Offset Indicator     Cutout, Setpoint is the temperature value that opens
                                                         the N.O. contacts. See Figure 7 and Figure 8.
                                     Temperature
                         BIN        Units Indicator      Differential (dIF) establishes the difference in
                          F         Operating Mode
                                                         temperature (in F° or C°) between the cut-in and
                                       Indicator         cutout values. The differential is set relative to Setpoint
                                                         and may be set from 1 to 30F° or C°. See Figure 7 and
                                     Liquid Crystal      Figure 8.
                                        Display
                MENU                                     Anti-Short Cycle Delay (ASd) establishes the
                                     MENU Button         minimum time that the N.O. contacts remains open (after
                                                         reaching cutout) before closing again. The delay overrides
                                     DOWN Arrow
                                       Button            any Load Demand and does not allow the N.O. contacts
                                                         to close until the set time-delay value has elapsed. See
                                      UP Arrow           Figure 6. When the delay is activated, the LCD
                                       Button            alternately flashes the sensor temperature and ASd. The
                                     Output Relay        delay may be set for 0 to 12 minutes in 1-minute
                                    Status Indicator     increments.
                                         LED
 Figure 5: A419 Control Front-Panel with Display

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
                                                                             Product/Technical Bulletin             3
For example, if the anti-short cycle delay is set for     This function enables the control to alternate between
7 minutes, the A419 control will not restart the          two temperature setpoints based on the position of the
equipment for 7 minutes after the equipment has cut       binary input switch. The difference between the
out, even if the cut-in temperature value is reached      primary and secondary setpoints (in F° or C°) is set in
during the delay. If the temperature reaches the cut-in   the Temperature Offset function (OFS) using the
value during the delay period, the display flashes        touchpad. See Setting Other Functions.
between the sensed temperature and ASd, indicating
                                                          Table 1 shows an example of Temperature Offset.
that the next On-cycle is being delayed. After the set
delay time has elapsed, the A419 control returns to
normal operation, restarts the equipment (if cut-in has   Table 1: Temperature Offset Example
been reached), ASd stops flashing, and the LCD              Mode of                     Temperature       Secondary
                                                                           Setpoint
reverts to the normal operating display.                   Operation                    Offset Value       Setpoint*
                                                               Cooling     70°         8°                78°
    Note: Any interruption in supply power to the
    A419 control activates the anti-short cycle delay.         Heating     70°         8°                62°
           Time                      Load Demand           *    Setpoint when circuit between binary input terminals
                                      Overridden                (BIN and COM) is closed
                  On
           Off                        Load Demand
                  On                                      When the circuit is closed between the binary input
           Off                        Output Status
                        Anti-short                        (BIN) common (COM) terminals, the offset function is
                       Cycle Delay                        enabled and the A419 control cycles on the secondary
                                                          setpoints. BIN is displayed on the LCD above the °F or
            Figure 6: Anti-short Cycle Delay              °C symbol when the offset is enabled. See Figure 5.
Sensor Failure Operation (SF) establishes how the
A419 control operates the equipment in the event of a     A419 Control Functions Set by Jumper Position
sensor or sensor-wiring failure. The A419 control may     For instructions on positioning jumpers, see
be set to run the equipment continuously or to shut it    Positioning the Jumpers in the Adjustments section.
down if the sensor or sensor wire fails. When a failure   See Figure 12 and Figure 13.
is detected the LCD flashes SF alternately with OP if     Touchpad Lock: The jumper at P5 establishes
the sensor circuit is open, or SF and SH if the sensor    whether the touchpad is locked or unlocked. Locking
circuit is shorted. The control implements a 1-minute     the touchpad deters accidental or unauthorized
delay before initiating a failure response to allow for   changes to all of the function parameters.
verification of the failure condition and to avoid
nuisance failure indications.                             Heating/Cooling Mode is established by positioning
                                                          the jumper on the top two pins of the P4 jumper. See
Temperature Units establishes the units of                Figure 13.
temperature (F° or C°) displayed on the LCD.
                                                          Setpoint Mode: Removing or installing the lower
Temperature Offset (OFS) establishes the value of         jumper at P4 establishes whether Setpoint is the cut-in
setpoint-shift (in F° or C°) applied to Setpoint (and     temperature or cutout temperature. See Figure 13.
Differential) when a (user-installed) circuit is closed
between the binary input (BIN) and common (COM)           Cooling/Heating and Setpoint Modes
terminals. The offset value may be set from 0 to 50F°
or C°.                                                    The A419 control may be in four operating modes:
                                                          Cooling/Cut-in, Cooling/Cutout, Heating/Cut-in, and
The Temperature Offset function is used to reset the      Heating/Cutout. Position the jumpers located on the
Heating Setpoint to a lower temperature (secondary)       circuit board under the A419 control cover to set the
setpoint or reset the Cooling Setpoint to a higher        desired mode of operation. See Positioning the
temperature (secondary) setpoint by the temperature       Jumpers.
value set in Temperature Offset.
                                                          In Cooling/Cut-in mode the differential is below
The BIN and COM terminals may be connected to a           Setpoint. The output relay energizes and the LED
(user-supplied) external switching device, such as a      illuminates when the temperature rises to Setpoint.
time clock, that has a set of Single-Pole, Single-Throw   When the temperature drops to Setpoint minus the
(SPST) contacts. Closing a circuit between the BIN        differential value, the relay and LED de-energize.
and COM terminals activates the Temperature Offset.
See Wiring.

4    A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
     Product/Technical Bulletin
In Cooling/Cutout mode the differential is above                                 Mounting
Setpoint. The output relay energizes and LED
                                                                                 An A419 control has either a standard high-impact
illuminates when the temperature rises to Setpoint plus
                                                                                 plastic NEMA 1 or a NEMA 4X corrosion-resistant,
the differential value. When the temperature drops to
                                                                                 watertight enclosure.
Setpoint, the relay and LED de-energize.
      Temperature                                                                The A419 control is not position sensitive but should
        (+)                Cooling/Cut-out                                       be mounted for convenient wiring and adjustment.
                  Cut-in                                                         Note: When mounting the control to rigid conduit,
                   (On)                                                          attach the hub to the conduit before securing the hub
                             Differential                                        to the control enclosure.
                                             Cut-out
                                              (Off)                              The mounting hole pattern of the NEMA 1 enclosure is
                                                    Cooling/Cut-in
  Setpoint                                                                       identical to that of the System 350 controls, and most
                                             Cut-in                              models of the A19 control. The NEMA 1 enclosure
                                              (On)                               may also be mounted on 35 mm DIN rail. See Figure 1
                                                        Differential             and Figure 2.
                                                                                 The NEMA 4X models may be mounted to flat vertical
                                                                                 surfaces using the four screw holes at the enclosure
            (-)                                                       Cut-out    corners. See Figure 3 and Figure 4. To maintain the
                                                                       (Off)     watertight and corrosion resistant integrity of the
                                                                                 NEMA 4X enclosure, use a conduit fitting rated for the
                   Figure 7: Cooling Modes
                                                                                 environment in which the control is installed.
When the Heating/Cut-in mode is selected, the
                                                                                 An additional (low-voltage) two-wire cable is required
differential is above Setpoint. The output relay
                                                                                 to operate the temperature offset function. On
energizes and LED indicator illuminates when the
                                                                                 NEMA 4X enclosures you must install a suitable
temperature drops to Setpoint. When the temperature
                                                                                 liquid-tight fitting in an available knockout to pass the
rises to Setpoint plus the differential value, the output
                                                                                 two-wire cable through the enclosure wall.
relay and LED de-energize.
When Heating/Cutout mode is selected, the                                         IMPORTANT:           The short-lead A99 sensor,
differential is below Setpoint. The output relay                                  included with A419 NEMA 4X model controls, must
energizes and LED indicator illuminates when the                                  be mounted on the bottom of the control in the
temperature drops to Setpoint minus the differential                              bracket molded on the NEMA 4X housing. Mounting
value. When the temperature rises to Setpoint, the                                the sensor on top of the control may reduce the
output relay and LED indicator de-energize.                                       accuracy of the displayed temperature. See Figure 3
     Temperature
                                                                                  and Figure 4 for proper sensor position.
       (+)                                            Heating/Cut-in
                                                                       Cut-out
                                                                        (Off)

                                                       Differential
                                             Cut-in
                                              (On)
                     Heating/Cut-out
 Setpoint
                                            Cut-out
                                             (Off)
                           Differential

                  Cut-in
        (-)
                   (On)

                   Figure 8: Heating Modes

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
                                                                             Product/Technical Bulletin                                      5
Wiring
                                                                   (Optional)                           A419GBF-1
    !   WARNING: Risk of Electrical Shock.
                                                                  Binary Input
                                                                     Switch
                                                                                                 (+) BIN
                                                                                                        A419GEF-1

 To avoid the risk of electrical shock, disconnect all                                           (–) COM
 power sources to the control before wiring any                                                  (+) SEN
 connections. More than one disconnect may be                                    TB3
 required to completely de-energize the control and
                                                                  Cable
 equipment.                                                      Shield
                                                                (if used)          TB1
                                                                                                        TB2
                                                                       A99
 IMPORTANT:           All wiring must conform to local,               Sensor            T1                    NC
                                                                                                               C
                                                                                        T2                    NO
 national, and regional regulations. Use copper
 conductors only for all wire connections. Do not
 exceed the electrical ratings for the A419 control or               24 VAC
                                                                     Class 2                                  24 VAC
 the equipment it is wired to.                                     Transformer                                 Load

See Figure 9, Figure 10, and Figure 11 for typical          Figure 9: Wiring the 24 VAC A419 Control
examples of wiring an A419 control to the controlled
equipment.
                                                                   (Optional)
                                                                                                   A419ABC-1
Use wire no larger than 12 AWG when connecting to                 Binary Input
                                                                                                    A419AEC-1
the two lower terminal blocks (TB1 and TB2).                         Switch
                                                                                             (+) BIN
                                                                                             (–) COM
Note: Terminal block TB2 is an isolated SPDT                                                 (+) SEN
switch (dry contacts). The TB2 terminals have no                                 TB3
internal electrical connection to the A419 control.
Use wire no larger than 16 AWG when connecting to                 Cable
                                                                 Shield
the upper sensor terminal block (TB3).                          (if used)          TB1
                                                                                                        TB2
Wire insulation rating must be 90°C, minimum.                          A99

                                                                                        AC COM
                                                                                                              NC
                                                                      Sensor
                                                                                  240             120
                                                                                                               C
                                                                                                              NO
A99 temperature sensors are not polarity sensitive.
Wire the leads to (+) SEN and (-) COM on the sensor
terminal block (TB3). See Figure 9, Figure 10, and                   120 VAC
Figure 11.                                                                                                    120 VAC
                                                                      Neutral
                                                                                                                Load
Keep the leads between the control and sensor as
short as possible/practical in your application. The       Figure 10: Wiring the 120 VAC A419 Control
additional resistance in long sensor leads creates error
between the actual temperature and the displayed                   (Optional)
temperature. See Table 1 when extending sensor                                                     A419ABC-1
                                                                  Binary Input
                                                                     Switch                         A419AEC-1
leads.                                                                                       (+) BIN
                                                                                             (–) COM
Temperature sensor signals may be affected by
                                                                                             (+) SEN
electrical interference. When extending sensor cable                             TB3
beyond 50 ft (15.2 m) use a twisted-pair, shielded
cable to reduce electrical interference.                          Cable
                                                                 Shield
If the Temperature Offset function is used, wire a              (if used)          TB1
switch (such as a switching time clock) between the                    A99
                                                                                                        TB2
binary input terminal (BIN) and the common terminal                   Sensor

                                                                                        AC COM
                                                                                                              NC
(COM). See Figure 9, Figure 10, and Figure 11 for                                 240             120
                                                                                                               C
                                                                                                              NO
terminal strip location.
                                                                      240 L1
                                                                      VAC L2                                  240 VAC
                                                                                                                Load

                                                           Figure 11: Wiring the 240 VAC A419 Control
6   A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
    Product/Technical Bulletin
Adjustments
This section provides instructions for setting up and
adjusting the A419 controls using the jumpers and
touchpad.
                                                                                                          =
                                                                         Jumper
                                                                                                        Installed
                                                                                             (Jumper Positioned on Both Pins)
Positioning the Jumpers
The P5 Jumper Pin Block has a single set of jumper
pins and is used to lock or unlock the touchpad. The
P4 Jumper Pin Block has two sets of jumper pins.                          Pins
                                                                                                          =
The top set of pins at P4, labeled JUMP1, is used to                                                    Removed
                                                                                              (Jumper Positioned on One Pin)
set the control for Heating or Cooling mode. The
bottom set of pins, labeled JUMP2, is used to establish
                                                                          Figure 12: Positioning the Jumpers
Setpoint at cut-in or at cutout. See Figure 12.
To position a jumper in the Installed position, place the
jumper on both pins. To position a jumper in the                           Touchpad Touchpad              Heating Mode
Removed position, place the jumper on only one pin.                         Locked Unlocked              Cut-in at Setpoint
(Save the jumper in case it is required in the future.)
See Figure 12.
Position the jumpers as follows. See Figure 12, Figure
                                                                                                          Cooling Mode
13, and Table 2.                                                                         JUMP1
                                                                                                         Cut-in at Setpoint
                                                                                         JUMP2
1.    Verify that all power sources to the A419 control                             P5           P4
      have been disconnected.
2.    Remove the control’s cover by loosening the four                                                     Heating Mode
                                                                                                             (Standard)
      captive cover screws.                                                                              Cut-out at Setpoint
3.    Position the jumpers to set Cooling/Heating,
      Setpoint, and Touchpad Lock functions.
                                                                                                           Cooling Mode
4.    Replace the cover and fasten in place with the                                                         (Standard)
      four screws.                                                                                       Cut-out at Setpoint

5.    Restore power to the control.                             Figure 13: Jumper Positions and Control Settings
 IMPORTANT: Verify that the Cooling/Heating
 jumper is positioned properly before powering the
 A419 control, to ensure that the relay operates as
 intended. See Figure 13 and Table 2.

Table 2: Jumper Designations, Jumper Positions and Control Settings
                         Jumper Pins Designation                                 Jumper               Factory Default Setting
 Function                                                    Setting
                         on Control                                              Position*            (and Jumper Position)
     Operating Mode      JUMP1                               Cooling             Removed              Cooling
     Cooling/Heating     (Top Pair of Pins on Block P4)      Heating             Installed            (Removed position)

                         JUMP2                               At Cut-in           Removed              Cut-in
        Setpoint
                         (Bottom Pair of Pins on Block P4)   At Cut-out          Installed            (Removed Position)
                                                             Locked              Removed              Unlocked
     Touchpad Lock       P5-Touchpad Unlock
                                                             Unlocked            Installed            (Installed Position)

 Note: The touchpad cannot be unlocked without a jumper. Do not discard any jumpers in case they are required in the
 future.

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
                                                                             Product/Technical Bulletin                         7
Changing Temperature Units                               Table 3: Function Ranges and Settings
The A419 control is set at the factory to display in                                                 Factory
Fahrenheit temperature units.                             Function               Range
                                                                                                     Setting
                     To convert to Celsius units,                                -30 to 212°F
                                                              SP: Setpoint       (-34 to 100°C)
                                                                                                     30
                     press the Up and Down buttons
                     simultaneously. Press them             dIF: Differential    1 to 30° (F or C)   5
                     again to return to Fahrenheit
                                                            ASd: Anti-short      0 to 12 minutes     1
                     units.                                   Cycle Delay
Notes: Make sure the Touchpad Lock jumper is in the        OFS: Temperature
unlocked (installed) position before adjusting the                               0 to 50° (F or C)   0
                                                                 Offset
control. See Figure 13.
                                                                                 0 = output
Verify that the A419 control is displaying the desired     SF:Sensor Failure     de-energized
                                                                                                     1
temperature units (F° or C°) before establishing the           Operation         1 = output
setpoint value.                                                                  energized
                                                         Operation at Extremes: If the combination of setpoint
Setting the Setpoint                                     plus or minus the differential falls outside the
                                                         temperature range (-30 to 212°F [-34° to 100°C]), the
To view and adjust the temperature setpoint, follow
                                                         A419 control operates as follows:
these steps and see Table 3:
                                                         Cooling/Cut-in: If the control is operating in
                1. Press and hold the MENU button
                                                         Cooling/Cut-in mode and setpoint minus differential is
                until the display changes to flashing
                                                         less than -30°F, the control switches on at setpoint
                SP. This will take about 2 seconds.
                                                         and off when the temperature drops below -30°F
                2. Press the MENU button again.          (-34°C).
                The current setpoint is displayed.       Heating/Cut-in: If the control is operating in
                                                         Heating/Cut-in mode and setpoint plus differential is
                                                         greater than 212°F (100°C), the control switches on at
                3. Press the Up or Down button to        setpoint and off when the temperature exceeds 212°F
                adjust the setpoint temperature.         (100°C).
                                                         Cooling/Cutout: If the control is operating in
                4. Press the MENU button to save.        Cooling/Cutout mode and setpoint plus differential is
                The display then returns to the sensor   greater than 212°F (100°C), the control switches on
                temperature.                             when the temperature exceeds 212°F (100°C) and off
                                                         at setpoint.
Notes: If no entries are made for 30 seconds while
                                                         Heating/Cutout: If the control is operating in
programming is in progress, the control reverts to the
                                                         Heating/Cutout mode and setpoint minus differential is
normal temperature display.
                                                         less than -30°F (-34°C), the control switches on when
If the MENU button is not pressed after changing the     the temperature drops below -30°F (-34°C) and off at
setpoint value, the new value is not saved and the       setpoint.
A419 control reverts to the previously saved setpoint
value.
Any saved A419 control setting values are
non-volatile and remain in the control’s memory
during power interruptions.

8   A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
    Product/Technical Bulletin
Setting Other Functions                                    Checkout
To set the Differential (dIF), Anti-short Cycle Delay      Before applying power, make sure installation and
(ASd), Temperature Offset (OFS), or Sensor Failure         wiring connections are according to job specifications.
(SF) operation, use the method illustrated and outlined    After necessary adjustments and electrical
below.                                                     connections have been made, put the system in
Figure 14 illustrates the order of functions shown using   operation and observe the control for at least three
the Up or Down button. The Up button accesses              complete operating cycles before leaving the
functions in the clockwise direction; the Down button      installation.
accesses functions in the counterclockwise direction.
See Table 3 for function ranges and factory settings.      Troubleshooting
                                                           If the control system does not function properly, verify
               Up                 d I F                    that the unit is wired, configured, and set properly. If
            Button                                         the problem persists, use the following procedures to
                                                           determine the cause of the problem:
                     S P                    A S d
                                                           1. Check for proper supply voltage to the A419
                                 Down                         control.
                                 Button
                                                               a. Remove the cover by loosening the four
                                          OF S                    captive cover screws.
                           S F

         Figure 14: Order of the Functions                    !    WARNING: Risk of Electrical Shock.
                                                            High voltages may be present at electrical terminals
               1. Press and hold the MENU button
                                                            and other exposed internal metal surfaces. Avoid
                  until the display changes to
                                                            contact with all metal surfaces on control when cover
                  flashing SP. This will take about 2
                                                            is removed.
                  seconds.
               2. Press the Up or Down button                  b. Use a reliable AC voltmeter to check the
                  repeatedly until the desired                    voltage between the COM and 120V or 240V
                  function is displayed.                          terminals on line voltage models and the two
                  See Table 3.                                    24V terminals on low-voltage models. See
                                                                  Figure 9, Figure 10, and Figure 11.
               3. Press the MENU button to display
                  the function’s current value.                c.   The voltage must be between: 20 and 30 VAC
                                                                    for 24 volt applications, 102 and 132 VAC for
                                                                    120 volt applications, 177 and 264 VAC for
               4. Press the Up or Down button                       208/240 volt applications
                  until the desired value is
                  displayed.                                        Notes: If the voltage reading is within the
                                                                    required range, proceed to Step 2.
               5. Press the MENU button to save
                  the new value. The display then                   If the voltage reading is not within the required
                  returns to the sensor temperature.                range, check the power source and input
                                                                    power wires for problems.
Notes: If no entries are made for 30 seconds while
programming is in progress, the control reverts to the
normal temperature display.
If the MENU button is not pressed after setting a new
value, the new value is not saved and the A419 control
reverts to the previously saved value for that function.
Any saved A419 control setting values are
non-volatile and remain in the control’s memory
during power interruptions.

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
                                                                             Product/Technical Bulletin               9
2. Check for proper sensor operation.                              g. Press and hold the MENU button until Setpoint
                                                                      appears (occurs in about 2 seconds).
Disconnect all power sources to control.
                                                                   h. Use the Up and Down buttons to change the
     a.      Take a temperature reading at the sensor
                                                                      Setpoint temperature above and below the
             location, using an accurate thermometer.
                                                                      current sensor temperature until the output
     b.      Disconnect the sensor from the control.                  relay energizes and de-energizes as shown in
                                                                      Table 4.
     c.      Use a reliable ohmmeter, to measure the
             resistance across the two sensor leads while               If the anti-short cycle delay has a time greater
             the sensor is at the temperature taken in                  than 0 minutes, the relay will not energize until
             Step b.                                                    the timed delay has elapsed.
     d.      See Figure 15 to verify that the measured             i.   If the output relay does not perform as
             temperature and resistance conform to                      indicated in Table 4, replace the A419 control.
             established temperature and resistance
                                                                   j.   If proper operation of the A419 control is
             values.
                                                                        verified, reconnect the load and consult the
     e.      If the measured values conform to the values               equipment manufacturer’s instructions for
             in Figure 15, proceed to Step 3.                           troubleshooting the controlled equipment.
     f. If the sensor’s measured resistance value is
                                                               Table 4: A419 Output Relay Operation
             substantially different from the expected value
             for that temperature, check the sensor wiring.                                Output
                                                                                                          Output Relay
             If sensor wiring is okay, replace the sensor.      Setpoint     Operating     Relay
                                                                                                          De-energized
                                                                Mode         Mode          Energized
     Temperature (°F)                     Temperature (°C)                                                at…
                                                                                           at…
          260                                                                              Setpoint
          240                                          120
          220
                                                                             Cooling       plus           Setpoint
                                                       100                                 differential
          200
          180                                          80
                                                                 Cutout
          160                                                                              Setpoint
          140                                          60                    Heating       minus          Setpoint
          120                                                                              differential
          100                                          40
           80                                                                                             Setpoint
           60                                          20
           40                                                                Cooling       Setpoint       minus
                                                       0                                                  differential
           20                                                    Cut-in
            0                                          -20
          -20                                                                                             Setpoint plus
                                                                             Heating       Setpoint
          -40                                          -40                                                differential
             500   700 900 1100 1300 1500 1700 1900 2100        Note:    When the relay is energized, the N.O. contacts
                        Resistance in Ohms                      are closed and the LED is illuminated.

             Figure 15: Nominal Temperature vs.
                     Sensor Resistance
3. Check the A419 for proper operation.
     a. Perform Troubleshooting Steps 1 and 2 before
        performing this step.
     b. Disconnect the load from the output relay
        terminals.
     c.      Ensure that the Touchpad Lock jumper is
             installed, so that the touchpad is unlocked.
     d. Reconnect the sensor leads and supply power
        to the control.
     e. Replace the cover.
     f.      Check the control settings for proper values.

10    A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
     Product/Technical Bulletin
Fault Codes
A419 controls are programmed to display certain fault
codes on the LCD as described in Table 5.

Table 5: Fault Codes Defined
Fault Code               Definition            System Status                    Solution
                         Open temperature      Output functions according to    See Troubleshooting section.
SF     flashing
                         sensor or sensor      the selected sensor failure
alternately with OP                                                             Cycle power to reset the control.
                         wiring                mode (SF setting)
                         Shorted temperature   Output functions according to    See Troubleshooting section.
SF     flashing
                         sensor or sensor      the selected sensor failure
alternately with SH                                                             Cycle power to reset the control.
                         wiring                mode (SF setting)
                                                                                Reset the control by pressing the Menu
EE                       Program failure       Output is off                    button. If problems persist, replace the
                                                                                control.

Repairs and Replacement                                        Ordering Information
Do not attempt to repair or recalibrate the                    See Table 6 to order controls and accessories.
A419 Control. In case of a defective or improperly
functioning control, contact your nearest Authorized
Johnson Controls/PENN® Distributor or Sales
Representative.
When contacting your Johnson Controls/PENN
distributor, have the model number of the control
available. This number can be found on the label
inside the cover of the control.

Table 6: Ordering Information
  Product Code        Item                                          Description
  Number
   A419ABC-1C         Line Voltage, NEMA 1 Enclosure                Supply Voltage:        120 or 240 VAC
                      A419 Series Electronic Temperature Control
                                                                    Range:                 -30 to 212°F (-34 to 100°C)
                      with Display, A99 Sensor Included
                                                                    Differential:          1 to 30F° (1 to 30C°)
   A419AEC-1C         Line Voltage, NEMA 4X Enclosure
                      A419 Series Electronic Temperature Control    Sensor Lead Length:    NEMA 1 Models 6-1/2 ft (2 m),
                      with Display, A99 Sensor Included                                    NEMA 4X Models 9 in (0.25 m)
   A419GBF-1C         24 VAC, NEMA 1 Enclosure                      Supply Voltage:        24 VAC, Class 2
                      A419 Series Electronic Temperature Control
                                                                    Range:                 -30 to 212°F (-34 to 100°C)
                      with Display, A99 Sensor Included
                                                                    Differential:          1 to 30F° (1 to 30C°)
   A419GEF-1C         24 VAC, NEMA 4X Enclosure
                      A419 Series Electronic Temperature Control    Sensor Lead Length:    NEMA 1 Models 6-1/2 ft (2 m),
                      with Display, A99 Sensor Included                                    NEMA 4X Models 9 in (0.25 m)
   A99BB-200C         Replacement Temperature Sensors               PTC Sensor with 6-1/2 ft (2 m) Leads
   A99BA-200C                                                       PTC Sensor with 6-1/2 ft (2 m) Shielded Leads
   A99BB-25C                                                        PTC Sensor with 9 in (0.25 m)
     BKT287-1R        Accessory Mounting Hardware                   12 in. (305 mm) long DIN Rail
     BKT287-2R                                                      36 in. (914 mm) long DIN Rail
     PLT344-1R                                                      Two End Clamps for DIN Rail Mounting
     CLK350-2C        Digital Clock                                 7-Day Programmable Digital Clock for controlling
                                                                    Temperature Offset Function
  WEL11A-601R         Immersion Well                                Immersion Well for applying sensor in fluid applications

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures
                                                                             Product/Technical Bulletin                    11
Technical Specifications
                   Product    A419 Series Electronic Temperature Controls with NEMA 1 General Purpose or NEMA 4X
                              Watertight, Corrosion-Resistant Enclosures
            Setpoint Range    -30 to 212°F (-34 to 100°C)
         Differential Range   1 to 30F° (1 to 30C°)
            Supply Voltage    24 VAC, 60 Hz, Class 2:       A419GBF-1 (NEMA 1 Enclosure Model)
                                                            A419GEF-1 (NEMA 4X Watertight Enclosure Model)
                              120 or 240 VAC, 60 Hz:        A419ABC-1 (NEMA 1 Enclosure Model)
                                                            A419AEC-1 (NEMA 4X Watertight Enclosure Model)
       Power Consumption      1.8 VA Maximum
     Output Relay Contacts    24 VAC Models:                A419GBF-1 (NEMA 1 Enclosure)
         Electrical Ratings                                 A419GEF-1 (NEMA 4X Watertight Enclosure)
                                                            100 VA, 30 VAC maximum, Class 2
                              120/240 VAC Models:       A419ABC-1 (NEMA 1 Enclosure)
                                                        A419AEC-1 (NEMA 4X Watertight Enclosure)
                              Applied Voltage:                       120 VAC             208 VAC          240 VAC
                              Horsepower N.O. (N.C.) : 