FANs 930, 930.5, 125, 121
                                                                                     Product/Technical Bulletin   A350
                                                                                                   Issue Date     0614

                                     System 350™
                         A350A/B Electronic Temperature Control

The A350A/B Series is an on/off electronic
temperature control with a Single-Pole, Double-Throw
(SPDT) relay output and a Light-Emitting Diode (LED)
relay status indicator. Designed to operate with both
heating and cooling equipment, this control includes
an adjustable differential and an interchangeable
temperature sensor.
As are all System 350™ products, the A350A/B is
housed in a NEMA 1, high-impact plastic enclosure.
The modular design provides easy, plug-together
connections for quick installation and future
expandability.

                                                                      Figure 1: A350 Series Electronic
                                                                           Temperature Control

                                           Features and Benefits
                   Modular Design                   Enables stage, display, and power modules to
                                                     be purchased and installed as needed
                   Plug-together Connectors         Eliminates wiring between modules and
                    and 35 mm DIN Rail               reduces installation costs
                    Mounting
                   Two Standard Models              Reduces inventory by encompassing
                    Cover Wide Setpoint              temperature ranges required to support the
                    Ranges                           majority of Heating, Ventilation, Air
                    -30 to 130°F (-34 to 55°C) or    Conditioning, and Refrigeration (HVAC/R)
                    90 to 250°F (32 to 121°C)        applications
                   Wide Adjustable Differential     Enables the user to match equipment cycle
                    of 1 to 30F° (0.6 to 16.7C°)     rate and/or sequencing for a given application
                   Field-Selectable Mode            Operates in both heating and cooling
                    Jumpers                          applications
                   Available with Either            Helps deter accidental and unauthorized
                    External or Concealed            adjustments
                    Setpoint
                   Interchangeable                  Increases versatility and serviceability
                    Temperature Sensors

© 2014 Johnson Controls, Inc.                                                                                            1
  Part No. 24-7664-44, Rev. D                                                                   www.johnsoncontrols.com
  Code No. LIT-930010
A pplication
The A350A/B Temperature Control can be used as           IMPORTANT: Use this A350A/B Electronic
a standalone device or in conjunction with other                    Temperature Control only as an
System 350 plug-together modules to control single or               operating control. Where failure or
multiple-stage HVAC or refrigeration equipment.                     malfunction of the A350A/B control
Typical applications include:                                       could lead to personal injury or
   frozen/refrigerated food cases                                  property damage to the controlled
                                                                    equipment or other property,
   cooling tower control                                           additional precautions must be
                                                                    designed into the control system.
   beverage/milk coolers                                           Incorporate and maintain other
   chiller staging                                                 devices, such as supervisory or
                                                                    alarm systems or safety or limit
   space temperature control                                       controls, intended to warn of or
                                                                    protect against failure or malfunction
A typical System 350 Temperature Control                            of the A350A/B control.
arrangement includes the following:
                                                         IMPORTANT: Utiliser ce A350A/B Electronic
   A350A/B Temperature Control                                     Temperature Control uniquement en
                                                                    tant que dispositif de régulation.
   S350 Stage Modules
                                                                    Lorsqu'une défaillance ou un
   D350 Digital Temperature Sensor/Setpoint Display                dysfonctionnement du
    Module                                                          A350A/B control risque de provoquer
                                                                    des blessures ou d'endommager
   Y350R Power Module (or Class 2                                  l'équipement contrôlé ou un autre
    24 VAC transformer)                                             équipement, la conception du
                                                                    système de contrôle doit intégrer des
   A99B Series Temperature Sensor                                  dispositifs de protection
                                                                    supplémentaires. Veiller dans ce cas
                                                                    à intégrer de façon permanente
                                                                    d'autres dispositifs, tels que des
                                                                    systèmes de supervision ou
                                                                    d'alarme, ou des dispositifs de
                                                                    sécurité ou de limitation, ayant une
                                                                    fonction d'avertissement ou de
                                                                    protection en cas de défaillance ou
                                                                    de dysfonctionnement du
                                                                    A350A/B control.

2   System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin
                                                          Setpoint Adjustment
O   peration
                                                          Setpoint is defined as the temperature at which the
The A350A/B Temperature Control operates on               A350A/B’s relay de-energizes. Use the Setpoint Dial
24 VAC and provides an SPDT relay output. A front         on the front of the A350A/B to adjust setpoint. See
panel LED lights to indicate when the relay is            Figure 2.
energized. Adjustable features include:
   setpoint                                              Differential Adjustment
   differential                                          Differential is defined as the change in sensor
                                                          temperature between energization and de-
   heating/cooling mode                                  energization of the relay. Adjustment of the A350A/B
                                                          differential is made using the potentiometer marked
IMPORTANT:         All System 350 Controls are            DIFF. See Figure 2 for its location. Refer to Table 5 for
                   designed for use only as               adjustment ranges.
                   operating controls. Where an
                   operating control failure would
                                                                24V
                   result in personal injury and/or
                                                                COM
                   loss of property, it is the                  VDC
                                                                                 Setpoint
                   responsibility of the installer to                              Dial
                                                                SEN
                   add devices (safety, limit controls)                                      Module
                                                                                            Connector
                   that protect against, or systems
                   (alarm, supervisory systems) that                DIFF
                   warn of, control failure.                    (Differential
                                                               Potentiometer)                    Jumper Block
                                                                                                   Position
                                                                     Relay
                                                                LED Indicator     Relay                 Heating
                                                                                                        Cooling

                                                                            NC              NO

                                                                  Figure 2: A350A/B Board Layout and
                                                                           Terminal Locations

                                                          Heating/Cooling Mode Adjustment
                                                          With Heating mode selected, the differential is below
                                                          setpoint. The relay and LED indicator will de-energize
                                                          as the temperature rises to the setpoint. As the
                                                          temperature drops to the setpoint minus the differential
                                                          setting, the relay will energize and the LED illuminates.
                                                          Refer to Figure 6.
                                                          With Cooling mode selected, the differential is above
                                                          setpoint. The relay and LED indicator will de-energize
                                                          as the temperature drops to setpoint. As the
                                                          temperature rises to the setpoint plus differential
                                                          setting, the relay will energize and the LED illuminates.
                                                          As shipped from the factory, the heating/cooling
                                                          jumper blocks are installed in the horizontal (cooling)
                                                          position. See Figure 2.

                             System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin           3
                                                            S350C Slave Stage Modules
A     dd-On Modules
                                                            S350C Slave Stage Modules receive power and
The S350 Stage Modules, D350 Digital Temperature            sensor input from the A350 control. S350C Slave
Display Module, and Y350R Power Module connect              Stage Modules perform switching functions based
together and plug into the A350 via a connector on its      upon the A350’s sensor information. (Setpoint and
right side. The maximum number of add-on modules is         differential are selected independently at the S350C.)
listed in Table 1.                                          For more information on these modules, refer to the
                                                            System 350TM S350C Temperature Slave Stage
Table 1: Maximum Number of S350 Stage                       Module Product/Technical Bulletin (LIT-930084).
Modules per A350A/A350B
    Power           Number       Number       Number        S350P Proportional Stage Modules
    Source          of S350A     of S350A     of S350A      S350P Proportional Stage Modules receive power,
                    or S350C     or S350C     or S350C      setpoint, and sensor input from the A350 control.
                    Modules      Modules      Modules       The S350P responds with an analog 0-10 VDC and
                    Allowed        (with        (with       0-20 mA output signal. This is based upon the A350’s
                                 1 S350P)     2 S350P)      setpoint and sensor information, with the offset,
                                 Allowed      Allowed       throttling range, and minimum output selected at the
    Y350R               9            6            4         S350P.
    External            9            8            7         For more information on these modules, refer to the
    Class 2                                                 System 350TM S350P Proportional Plus Integral
    Transformer                                             Temperature Stage Module Product/Technical Bulletin
                                                            (LIT-930086).
Note:       For each S350P added, the number of S350A
            or S350C Stage Modules that can be used
            with a Y350R decreases by two. If an external   D350 Temperature Sensor/Setpoint
            transformer is used, the number of S350A and    Display Module
            S350C Stage Modules used decreases by           The D350 receives power, sensor, and setpoint
            one for each additional S350P.                  information from the A350. A 3-digit Liquid Crystal
                                                            Diode (LCD) gives continuous read-out of the sensed
S350A On-Off Stage Modules                                  temperature. Pushing the PRESS FOR SETPOINT
                                                            button on the front of the D350 causes the setpoint of
S350A On-Off Stage Modules receive power, setpoint,         the adjoining A350 to be displayed.
and sensor input from the A350 control. S350A Stage
Modules perform switching functions based upon the
A350’s setpoint and sensor information, with the offset     Y350R Power Module
and differential selected at the S350A.                     The Y350R provides a convenient method of powering
For more information on these modules, refer to the         System 350 modules from a 120 or 240 VAC power
System 350 S350 Temperature, S351 Humidity, and             source. The Y350R supplies power to the modules.
S352 Pressure On/Off Stage Modules                          See Figure 5 for a typical wiring diagram where a
Product/Technical Bulletin (LIT-930080).                    Y350R is used to power the A350.
                                                            For more information on this module, refer to
                                                            System 350TM Y350R Power Module
                                                            Product/Technical Bulletin (LIT-930090).

4     System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin
D imensions
        Mounting Slots
                                     3/16 (4)
       for No. 6 Screws

                                       1/2 (13)

                                      2 15/16
                                       (75)
                                                                        5 (127)

                                                                                  4 (102)

                          1 9/16                                                                  2 3/8 (61)
                                                            DIN Rail
                           (40)       7/16 (11)              Mount                             1 3/16 (31)

                        Sensor
                                                                       3 (76)                                  Conduit
                                                  1/4 (6)                                                       Hole
                                                                           2 3/8 (61)
                                                                                                                 7/8
          9 3/4 (248)                                                                                           (22)
                                                                                        7/8
                                                                                        (22)

                                 Figure 3: A350A/B Control Dimensions, in. (mm)

                             System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin                5
                                                                                                                     Sensor
I   nstallation and Wiring                                                          Note: If sensor is mounted less than 50 ft
                                                                                          (15.2 m) from the A350A/B,
The A350A/B Temperature Control is housed in a                                            shielded cable is not required.
compact NEMA 1 plastic enclosure designed for                                       A350A/B         S350A           D350
standard 35 mm DIN rail mounting. The A350A/B is not
position sensitive but should be mounted for convenient        L1           24
wiring and adjustment. Four key-slot mounting holes on           2          VAC
the back of the control case are provided for surface
mounting. Add-on modules must plug into the right side                    24V
of the A350A/B control.                                                   COM
                                                                          VDC
Note: When mounting the System 350 modules to rigid                       SEN
      conduit, attach the hub to the conduit before
      securing the hub to the control enclosure.
                                                                     L1
     !   WARNING: Risk of Electric Shock.
                                                                      2
                                                                                       Load            Load
                     Disconnect the power supply
                     before making electrical
                                                                Figure 4: Typical Wiring Diagram for A350A/B
                     connections. Contact with
                     components carrying hazardous               Powered by an External 10 VA Transformer
                     voltage can cause electric shock
                     and may result in severe                Sensor Connection
                     personal injury or death.               Shielded cable is not generally required for sensor
AVERTISSEMENT:Risque de décharge                             wiring on runs of less than 50 ft (15.2 m), but is
             électrique.                                     recommended for lengths greater than 50 ft (15.2 m).
                                                             When using shielded cable, isolate and tape the shield
                     Débrancher l'alimentation avant
                                                             at the sensor. Connect the shield to the COM sensor
                     de réaliser tout branchement
                                                             terminal on the A350A/B. (See Figure 2 for terminal
                     électrique. Tout contact avec des
                                                             location.) The A99BA-200C sensor, which includes
                     composants porteurs de tensions
                                                             shielded cable, is available if needed.
                     dangereuses risque d'entraîner
                     une décharge électrique et de           Note:        At the maximum cable lengths listed in Table 2,
                     provoquer des blessures graves,                      no more than 1F° (0.6C°) error in the sensed
                     voire mortelles.                                     temperature will result due to wire resistance.

    All wiring must conform to the National Electrical      Table 2: Recommended Maximum Sensor
     Code and/or local regulations.                          Cable Lengths
Note:     For maximum electrical rating of control, see           Wire                   Shielded Cable Length*
          label inside the control cover or Specifications
                                                                 Gauge                    Feet                   Meters
          section. Use copper conductors only.
    Consult the typical wiring diagrams (Figures 4 and 5)       14 AWG                   800                      244
     for proper wiring and terminal designations.                16 AWG                   500                      152
                                                                 18 AWG                   310                       94
                                                                 20 AWG                   200                       61
                                                                 22 AWG                   124                       38
                                                             * Values provided are for 2-wire stranded cable.

6    System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin
   Various A99B Series Temperature Sensors               Table 3: Sensors Included With A350A/B
    and mounting hardware are available for use           Controls
    with A350 Series Controls. See Tables 3 and
    6. The sensor must be connected to the COM                  Control    Sensor Included
    and SEN terminals on the four-position                                 Sensor lead length is 9-3/4 in. (0.25 m)
    terminal strip located at the top left of the              A350AA-1C   A99BB-25C; Range: -40 to 212°F
    printed circuit board (Refer to Figures 2, 4,
                                                                           (-40 to 100°C)
    and 5.). The sensors are not polarity sensitive.
                                                               A350AA-2C   A99BC-25C; Range: -40 to 248°F
   The sensor must be mounted so that it can                              (-40 to 120°C)
    accurately sense the temperature of the
    controlled medium.                                         A350AA-3C   A99BB-25C; Range: -40 to 212°F
                                                                           (-40 to 100°C)
                                                               A350AB-1C   No Sensor Included
                                                               A350AB-2C   No Sensor Included
                                                               A350AB-5C   No Sensor Included
                                                               A350BA-1C   A99BB-25C; Range: -40 to 212°F
                                                                           (-40 to 100°C)
                                                               A350BA-2C   A99BC-25; Range: -40 to 248°F
                                                                           (-40 to 120°C)
                                                               A350BB-1C   No Sensor Included

                                                               For more information regarding sensor options
                                                                and installation, refer to the A99B Series
                                                                Temperature Sensors Product/Technical Bulletin
                                                                (LIT-125186).

                                                                                   Sensor
                       Shield (Connect
                       to COM on A350)
                          A350A/B        Y350R         S350A       S350A       S350A        D350

            120 VAC

                            Load                       Load         Load       Load

                           Figure 5: System 350 Powered by Y350R Module

                          System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin                7
A djustments
Follow this procedure to set up the A350A/B for the                                                                 Note:    The A350A/B setpoint is factory calibrated at
desired operation.                                                                                                           midscale to a tolerance of +/- 1F° (0.6C°).
                                                                                                                             Setpoint tolerance at the extreme ends of the
1. Remove the A350 cover by loosening the
                                                                                                                             setpoint ranges in relation to the printed scale
   four captive cover screws.
                                                                                                                             can be +/- 3F° (1.7C°). The D350 Display
2. Set the heating/cooling jumper blocks to the                                                                              Module is unaffected by this tolerance shift.
   desired mode of operation. Position the jumper                                                                            Use the D350 for the most accurate setpoint
   blocks vertically for heating or horizontally for                                                                         selection.
   cooling. (See Figure 2.)

 IMPORTANT:                        Verify that the heating/cooling
                                                                                                                    C heckout Procedure
                                   jumper blocks are in the proper                                                  Follow this procedure to verify that the A350A/B is
                                   position before powering the                                                     connected and functioning properly.
                                   System 350 modules. If the
                                   jumper blocks on the control or                                                  1. Make sure installation and wiring connections are
                                   staging modules are installed in                                                    according to job specifications before applying
                                   the wrong position, the device                                                      power. (Refer to Figure 6 for an example of a
                                   will activate the relay in response                                                 multistage application.)
                                   to the opposite signal. The                                                      2. Make the necessary adjustments and electrical
                                   heating or cooling equipment will                                                   connections.
                                   remain energized until the error                                                 3. Put the system in operation and observe at least
                                   is corrected.                                                                       three complete operating cycles before leaving the
                                                                                                                       installation.
3. Adjust the differential potentiometer (DIFF) on the
   A350 as needed. (Figure 6 is an example of a
   multistage application.) The stage module’s offset                                                               T roubleshooting
   and differential can be set independently.                                                                       If the control system does not function properly, verify
       (+)                                               ON                                                         that the proper mode is selected on each module
                                                                                                                    (Heat/Cool, Direct Acting/Reverse Acting). Proceed as

                                          Differential
                                                                                                                    follows to determine the cause of the problem:
                                   ON
                                                                                                                    1. Make sure proper voltage is applied to the A350
                    Differential
                                        OFF                                                                            control.
                                        OFFSET
  Setpoint                                                                                                              a. Connect a digital voltmeter (DVM) between
Temperature        OFF                                                                                                     the 24V and COM terminals located on the
                                                               OFFSET
                                                         OFF                   OFFSET
                                                                                                                           control’s left side terminal block (See Figure 2.)

                                                                Differential
                                                                                               OFFSET
               ON = Energized
                                                                                                                             If an external transformer is used, select AC
                                                                               OFF                                           volts on the DVM and verify that the voltage is
              OFF= De-energized

                                                                                Differential
                                                                                                                             between 20 and 30 VAC.
        (-)                                                    ON                              OFF
                                                                                                                             If a Y350R Power Module is used, select DC

                                                                                                Differential
                                                                                                                             volts on the DVM and verify that the voltage is
                                                                               ON
                                                                                                                             between 16 and 38 VDC.
                                                                                                               ON       b. If the DVM reading is within the indicated
                A350    S350A S350A S350A S350A                                                                            voltage range, proceed to Step 2.
               Stage 1 Stage 2 Stage 3 Stage 4 Stage 5
                   Cooling             Heating                                                                          c.   If the DVM reading is not within the indicated
                                        Jumper Set To                                                                        voltage range, correct the wiring, replace the
                                                                                                                             Y350R, or replace the external transformer.
           Figure 6: Typical Multistage
           Heating/Cooling Application
4. Replace the cover, and secure in place with the
   four captive screws. Move the setpoint dial to the
   desired position.

8   System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin
2. Check temperature sensor for proper resistance.             3. Check the A350 for proper operation.
   a. Take an accurate, independent temperature                Note:     Steps 1 and 2 must be performed first.
      reading at the sensor location.
                                                                    a. Adjust the setpoint dial to at least 40°F (22°C)
   b. Disconnect the sensor from the control. Using                    below the sensor temperature determined in
      an ohmmeter, measure the resistance across                       Step 2.
      the two sensor leads. Consult Figure 7 to
                                                                    b. Increase setpoint by slowly turning the dial
      verify sensor conformance.
                                                                       until the control relay and LED turn On and
       °F             Temperature                °C                    Off.
    260
    240                                         120                 c.   If the relay does not perform as indicated in
    220                                         100                      Table 4, replace the A350.
    200
    180                                          80
    160                                                        Table 4: A350 Relay Troubleshooting
    140                                          60
    120                                                                                  N.O. Contact          Setpoint
    100                                          40             Action          LED
      80                                                                                    Status           Dial Setting*
      60                                         20
     40                                                         Heating          On      Closed             (Ts) = Sp - Diff
                                                  0
     20
      0                                         -20             Heating          Off     Open               (Ts) = Sp
     -20
     -40                                        -40             Cooling          On      Closed             (Ts) = Sp + Diff
        500 700 900 1100 1300 1500 1700 1900 2100
                                                                Cooling          Off     Open               (Ts) = Sp
                 Resistance (Ohms)
     Figure 7: Temperature vs. Resistance                      *(Ts) is sensed temperature, and (Sp) is setpoint
        Chart for the A99B Series Sensor                       temperature.
   c. If the resistance varies substantially from the
      optimal resistance for that temperature, the
      sensor or wiring must be replaced.
                                                               R epairs and Replacement
                                                               Do not make field repairs or perform calibration.
Note:       The sensor reading indicated by the D350 may       Replacement controls and A99B Temperature Sensors
            differ from thermometer readings due to sensor     are available through the nearest Johnson Controls
            tolerances, time constants, accuracy of            representative. See Tables 5 and 6 for ordering
            thermometer, and other factors.                    information.

O rdering
Table 5: System 350 Products
Item                           Product Code     Description
                               Number
A350 Temperature Controls A350AA-1C             Range: -30 to 130°F; Adjustable Differential: 1 to 30F°
(With Temperature Sensors) A350AA-2C            Range: 90 to 250°F; Adjustable Differential: 1 to 30F°
                           A350AA-3C            Range: -30 to 130°F; Adjustable Differential: 1 to 30F° (concealed setpoint)
                           A350BA-1C            Range: -35 to 55°C; Adjustable Differential: 0.5 to 17C°
                           A350BA-2C            Range: 30 to 120°C; Adjustable Differential: 0.5 to 17C°
A350 Controls Without          A350AB-5C        Range: 90 to 150°F; Adjustable Differential: 1 to 30F°
Sensors                        A350AB-1C        Range: -30 to 130°F; Adjustable Differential: 1 to 30F°
                               A350AB-2C        Range: 90 to 250°F; Adjustable Differential: 1 to 30F°
                               A350BB-1C        Range: -30 to 130°F; Adjustable Differential: 1 to 30F°
Digital Temperature Setpoint D350AA-1C          Fahrenheit Scale
Display Modules              D350BA-1C          Celsius Scale
On/Off Stage Modules           S350AA-1C        Fahrenheit Scale
                               S350AB-1C        Celsius Scale
Slave Stage Modules            S350CC-1C        Dual Scale (°F and °C)
Proportional Stage Modules S350PQ-1C            Dual Scale (°F and °C)
Power Module                   Y350R-1C         120/240 VAC, 50/60 Hz Input; Rectified Class 2, 24 VAC Output

                                System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin                   9
Table 6: System 350 Accessories
Item                              Product Code Description
                                  Number
Enclosure                         BOX10A-600R          Outdoor PVC sensor enclosure; includes wire nuts
Wall Mount Plate                  TE-6001-4            Includes sensor mounting clip
Cover                             T-4000-2644          For wall mount plate
Mounting Clip                     A99-CLP-1            Surface mounting clip for the A99B Temperature Sensor
Duct Mounting                     TE-6001-1            Duct-mounting hardware with handy box for A99B sensor
Duct Mounting                     TE-6001011           Duct-mounting hardware without handy box for A99B sensor
Conduit Adaptor                   ADP11A-600R          1/2 in. Snap-fit EMT conduit adaptor (box of 10)
Immersion Well             WEL11A-601R                 For liquid sensing applications
Sun Shield                 SHL10A-603R                 For use with outside sensors in sunny locations
DIN Rail Sections          BKT287-1R                   12 in. (0.3 m) long
                           BKT287-2R                   39-1/3 in.(1.0 m) long
DIN Rail End Clamp         PLT344-1R                   Consists of two end clamps
Cables for Remote Mounting WHA29A-600R                 3 ft (0.9 m) This can also be used to daisy chain S350 Stage Modules together.
of D350 Display Module     WHA29A-603R                 25 ft (7.6 m)
                           WHA29A-604R                 50 ft (15.2 m)

S pecifications
                           Product        A350A/B Electronic Temperature Control
                     Supply Voltage       Y350R Power Module:     Input:   120/240 VAC 50/60 Hz
                                                                  Output: 24 VDC, unfiltered, 10 VA, Class 2
                                          External Source:        24 VAC, 50/60 Hz Class 2 (20-30 VAC)
                                          Note: Only one supply voltage source may be used.
             Power Consumption            1.4 VA
            Ambient Temperatures          Operating: -30 to 150°F (-34 to 66°C)
                                          Shipping:    -40 to 185°F (-40 to 85°C)
                          Humidity        0 to 95% RH non-condensing; maximum dew point: 85°F (29°C)
        Setpoint Adjustment Range         See Table 5.
     Differential Adjustment Range        See Table 5.
                 SPDT Relay Output                           120V              208 to 240V
                                          Horsepower:        1/2               1/2
                                          Full Load:         9.8A              4.9A
                                          Locked Rotor:      58.8A             29.4A
                                          Non-Inductive:     10A at 24 to 240 VAC
                                          Pilot Duty:        125 VA at 24 to 240 VAC
                               Sensor     Replaceable positive temperature coefficient sensor
                                          Reference resistance: 1035 ohms at 77°F (25°C)
                           Material       Case and cover: NEMA 1 high-impact thermoplastic
                    Agency Listings       UL Listed, CCN XAPX, File E27734
                                          UL Listed for Canada, CCN XAPX7, File E27734
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls Application Engineering at 1-414-524-5535. Johnson Controls, Inc. shall not be liable for damages
resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                               Printed in U.S.A.
Milwaukee, WI 53201                                                                                                www.johnsoncontrols.com

10     System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin