                                                                                   Filter Stations Section
                                                                                           Product Bulletin A-4000
                                                                                               Issue Date 0984

                                                A-4000
                                             Oil Indicator

The A-4000 Oil indicator is a           Operation
calibrated measuring instrument
used to detect aerosol-mist             When the needle valve of the oil
levels of oil entrainment that may      indicator is open, less than
be present in compressed air            2 SCIM/PSIG (.08 mL/s/kPa) will
systems. Sensitivity of the             flow through the calibrated
indicator is limited only by the        plastic tube. Any oil present in
total number of hours it is             the air will then carry a red oil
allowed to remain on the air            soluble dye up the tube, coloring
supply system. The indictor is          a white material in the tube. The
sensitive enough to measure a           rate of color travel will be
concentration of oil entrainment        proportional to the amount of oil
as low as .01 PPM (.012 mg/m3)          present. The parts per million
in a compressed air system. It          (PPM) value of oil entrained in
can be used in systems with line        the air can be determined using
pressures between 10 and                the conversion chart included
125 PSIG (70 and 875 kPa).              with the instrument. After use,
                                        the needle valve should be                   Fig. 1: A-4000 Oil Indicator
                                        closed and left in the line and the              Installed in Air Line
Application                             cartridge removed. At the time of
Oil entrainment in the control air      the next test, a replacement
supply to the pressure reducing         cartridge will need to be installed
valve may eventually have an            on the needle valve fitting.
adverse effect on the control
system performance. Since
some oil entrainment is inherent
to lubricated compressors, all oil
lubricated compressor
installations must include factory
approved oil filters to be reliably
acceptable. The indicator can
be used in two ways. Either it
can be used to check for oil          Specifications
carryover from the compressor
or it can be used to check out
any filtered air supply source
before connecting it to the
system and also every few
months after the system
becomes operative. Once the
needle valve of the oil indicator
has been opened, one
continuous uninterrupted
exposure is recommended for
greatest accuracy.

© 1984 Johnson Controls, Inc.                                                                                       1
  Part No. 64-272-0, Rev. A
  Code No. LIT-718070
Installation                         Before installing a replacement       4.    Judging from the rate of
                                     cartridge, first check that the             color travel established at
In order for the oil indicator to    needle valve on the existing                the time of the first
properly measure a given oil         installation is closed all the way          inspection, schedule the
entrainment, sufficient exposure     by making sure that the needle              final reading of the indicator
time is required. The length of      valve handle (see Fig. 2) is fully          (and needle valve shut-off)
exposure time is inversely           rotated in a clockwise direction.           at approximately 1 unit
proportional to the pressure at      Install the replacement cartridge           (marked "1.0" on the scale),
the point of installation. When      (see Fig. 3) by tightening the              and preferably not more
using the indicator to check for     lower 1/8 in. nut in place.                 than 1-1/2 units (marked
oil carryover from the                                                           "1.5" on the scale).
compressor, it should be             Note: Do not disturb the
installed at the discharge of the                                          5.    Close the needle valve,
                                     factory adjusted torque on the              remove the oil indicator
tank. When using the indicator       upper 3/16 in. retaining nut
to measure oil entrainment in the                                                cartridge, and record the
                                     that holds the plastic tube in              time. Leave the needle
air supply system, it should be      place. Also make sure that
installed between the oil filter                                                 valve in the air line for future
                                     the indicator scale can be                  testing purposes.
and the pressure reducing valve      conveniently viewed before
(PRV). At this point, dry high       tightening the cartridge in           6.    Record the units of color
pressure air will be present,        place.                                      travel (as read from the
resulting in the best accuracy                                                   indicator scale) and the total
and fastest indication.                                                          time in hours.
                                     Readings and
Note: In humid air, moisture         Measurements
may wash traces of dye up the
tube, creating a light pink area     1.   Before taking a
above the dark red area.                  measurement, fill out the
When calculating oil                      record tag furnished with the
entrainment, measure only to              oil indicator. Record the line
the top of the dark red                   pressure or the average
column. Locations involving               pressure (if it varies at the
excessive moisture,                       point of installation).
temperature, or velocity
                                     2.   Fully rotate the needle valve
should be avoided. The
                                          handle (see Fig. 2)
indicator valve should remain
                                          counterclockwise to open it
closed except during the
                                          and record the time that the
measuring period. For
                                          needle valve was opened
pressures above 125 PSIG
                                          on the record tag. Slide the
(875 kPa) or below 10 PSIG
                                          record tag over the oil
(70 kPa), consult the factory.
                                          indicator to avoid
                                          misplacing it.
 ! WARNING: If the pressure
    exceeds 125 PSIG or the          3.   At the following times and
    retaining nut is loosened,            locations, visual inspections
    the oil indicator tube could          of the oil indicators should
    blow out of the compression           be made:
                                                                                Fig. 2: Dimensions in./mm
    fitting, creating a hazardous
    condition.                            A.   When checking for
                                               compressor oil
                                               carryover, inspection
The indicator must be mounted                  should be made after
within 45° of an upright position              4 hours at the
for best possible performance.                 compressor discharge.
Fittings (1/8 in N.P.T.) are
provided on both high and low             B.   When checking for oil
pressure sides of all A-4000                   entrainment in the air
series filter and reducing station             supply, inspection
assemblies. Any other mounting                 should be made after
location will require a 1/8 in.                40 hours between the
N.P.T. mounting tee as shown in                oil filter and the PRV.
Fig. 1.

2 A-4000 Product Bulletin
Fig. 3: A-4000-121 Replacement
            Cartridge

Oil Concentration
Determination (See Fig. 4)
1.   If color travel is 1 unit at the
     final reading time, find the
     Total Hours on the right side
     of the conversion chart and
     the Pressure on the bottom
     of the chart. The point
     where Hours and Pressure
     intersect is the parts per
     million of oil concentration.
2.   If the final reading occurs at
     other than 1 unit of color
     travel, divide the units
     traveled by the total hours to
     find the Rate of Color
     Travel.
                                        Example: The Rate of Travel
3.   Find the Rate of Color             on the high pressure side of a
     Travel on the left side of the     PRV (80 PSIG [560 kPa]) is
     conversion chart and the           found to be 0.5 units/hr. Divide
     Pressure on the bottom of          this rate by five (0.5 ÷ 5 = 0.1
     the chart. The point where         units/hr) to bring it into the range
     Rate and Pressure intersect        of the conversion chart. Locate
     is the parts per million of oil    this new rate on the chart,
     concentration.                     showing a concentration of 1.4
For any Rate of Color Travel            PPM. Multiply this concentration
beyond 0.24 units/hr., the              by the previous factor
measured rate should be divided         (1.4 × 5 = 7.0 PPM) to obtain the
by any factor which will bring it       actual oil concentration in the air
into the range of the chart. This       being tested.
number should then be used to
determine the oil concentration
(PPM). This concentration must
then be multiplied by the same
factor used previously to
determine the actual oil
concentration.

                                                                               A-4000 Product Bulletin   3
                            Notes

Controls Group
507 E. Michigan Street
P.O. Box 423                        Printed in U.S.A.
Milwaukee, WI 53202

4 A-4000 Product Bulletin