Code No. LIT-1921160
                                                                                                                                                  Issued January 15, 2008

A-4000-139 to -145
Oil Removal and Pressure Reducing Stations
Description                                                      Note: The air supply to these stations must
                                                                 be from a properly broken in air compressor
The A-4000 -139 through -142 Oil Removal
                                                                 producing less than 6 ppm aerosol oil (as
and Pressure Reducing Stations provide
                                                                 measured by a Johnson Controls A-4000-120
clean, oil free air for pneumatic control
                                                                 Oil Indicator on the compressor tank outlet
systems.
                                                                 and must also pass through a properly
Refer to A-4000 Series Oil Removal and                           operating air dryer.
Pressure Reducing Stations & Air
Compressor Accessories (LIT-7188060) for                         Repair Information
important product information.
                                                                 If the A-4000 -139 through -142 Oil Removal
                                                                 and Pressure Reducing Station fails to
Features                                                         operate within its specifications, replace the
•   available in single or dual PRV models in                    unit. For a replacement oil removal and
    17 or 25 scfm (8.0 or 11.7 L/s) maximum                      pressure reducing station, contact the nearest
    flow capacities                                              Johnson Controls® representative.
•   includes a four-way bypass valve
•   equipped with coalescing and activated
    carbon oil removing filters                                                                                                             A-4000-142 Oil Removal and
•   piped with copper tubing for increased                                                                                                  Pressure Reducing Station
    durability

Selection Charts
A-4000 -139 through -142                                                                             Accessories/Maintenance Parts for A-4000 -139 through -142
Oil Removal and Pressure Reducing Stations                                                           Code Number Description
Code       Flow Consumption              Compressor                                 PRV               A-4000-632           Activated Carbon           Nominal 10 scfm (4.7 L/s)
Number                                   HP                                                                                Filter Elements            Maximum 17 scfm (8.0 L/s)
                                         (50%                                                         A-4000-633                                      Nominal 20 scfm (9.4 L/s)
                                         Running                                                                                                      Maximum 30 scfm (14.1 L/s)
                                         Time)
                                                                                                      A-4110-604           Coalescing Filter          Nominal 10 scfm (4.7 L/s)
A-4000-139 Designed Working 10 scfm (4.7 L/s)                  Up to 5 hp           SIngle                                 Elements                   Maximum 12 scfm (5.6 L/s)
A-4000-140 Maximum 17scfm (8.0 L/s)                                                 Dual              A-4000-604                                      Nominal 20 scfm (9.4 L/s)
A-4000-141 Designed Working 23 scfm (10.8 L/s)                 Up to 10 hp 1        SIngle                                                            Maximum 23 scfm (10.8 L/s)
A-4000-142 Maximum 25 scfm (11.7 L/s)                                               Dual              A-4000-138           3/8 in. Pressure Regulator with Bracket, Gauge,
A-4000-145 Accessory Oil Reserve                                                                                           and Safety Relief Valve
                                                                                                      A-4110-601           Four-Way Bypass Valve with 3/8 in. Compression Fittings
1. For installation with more than 25 scfm air consumption, use 2 or more stations.

Technical Specifications
                                                 A-4000-139 to -145 Oil Removal and Pressure Reducing Stations
Maximum Pressure Input Rating                                  150 psig (1,034 kPa)
Pressure            Temperature LImit                          120°F (52°C)
Setting             SIngle PRV                                 20 psig (138 kPa) Nominal; 25 psig (172 kPa) Maximum
                    Dual PRV                                   15 and 20 psig (103 and 138 kPa) Nominal; 25 psig (172 kPa) Maximum
Pressure            Dual 10 scfm                               Maximum of 1 psi (7 kPa)
Drop at             Dual 20 scfm                               2 psi (14 kPa)
10 scfm
                    Fittings                                   1/2 in. O. D. Compression Provides Dual Supply Air to System
                                                               1/2 in. Connection Provides Constant 20 psig (138 kPa) to Local Control Panels
                                                               3/8 in. Connection Provides Filtered High Pressure Air to Remote PRV Stations
Filters                                                        Replace After 1 Year

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.