Про документ
Installation manual for the Johnson Controls Activa series packaged rooftop air conditioners in sizes 045 to 090. The series covers four variants per size: ARC (cooling only), ARG (cooling + gas heating), ARH (heat pump) and ARD (heat pump + gas heating). Units are designed for outdoor installation only, with side or downward duct connections and a range of factory options.
Ключові дані
| Net cooling capacity | ARC/ARG: 45.1 / 61 / 71.5 / 84 kW; ARH/ARD: 47.6 / 61.9 / 71.4 / 83.4 kW |
|---|
| Power supply | 400 V / 3+N ph / 50 Hz |
|---|
| Refrigerant | R-410A (10.5–29 kg) |
|---|
| Compressors | SCROLL, 1 (TANDEM 50 % + 50 %), IP21 |
|---|
| Indoor fan motor | IP55, 3–7.5 kW standard; HPD optional up to 11 kW |
|---|
| Outdoor fan motor | IP54, 1.9 kW |
|---|
| Gas heating capacity (ARG/ARD) | 85 kW total LHV standard / 100 kW high power (optional) |
|---|
| Air filters | G4, 6 per unit, 470x550x48 mm or 565x594x48 mm |
|---|
Застосування
- Commercial rooftop air conditioning with cooling only or cooling + gas heating
- Heat pump operation for summer/winter cycles (ARH/ARD)
- Optional economiser, exhaust fan, hot water coil, auxiliary electric heating element, fixed outdoor air intake, barometric damper
- Natural gas operation as standard; convertible to propane (LPG) via conversion kit
Особливості
- Belt-driven indoor fan with adjustable variable-diameter motor pulley; standard and optional high-pressure (HPD) drives up to >500 Pa static pressure
- IE3 efficiency class motors, Class F insulation (IEC 60034–30–1)
- Eurovent Rooftop program certified performance data points
- YKNOpen electronic control board with red LED fault indication and green LED incident indication; DPC-1 thermostat; RS-485 connection [J12]; YKTOOL test device connection
- Two-stage scroll compressors (tandem); low ambient switch HP2
- Gas burner N320 with automatic lighting system, two heat stages, thermal breaker automatic reset at 82 °C / manual reset at 93 °C
- Micro-switch configurable defrosting time (0'/30'/60'/90'), coil configuration and compressor selection
Технічні дані
| Parameter |
ARC/ARG 045 |
ARC/ARG 060 |
ARC/ARG 075 |
ARC/ARG 090 |
| Net cooling capacity (kW) |
45.1 |
61 |
71.5 |
84 |
| Rated absorbed power cool mode (kW) |
16 |
23 |
30 |
36 |
| Optional electric heater capacity (400 V) (kW) |
12-25-37-50 |
12-25-37-50 |
12-25-37-50 |
12-25-37-50 |
| Gas heat capacity at 100% (LHV), total (kW) |
85 (standard) / 100 (optional high) |
— |
— |
— |
| Gas consumption 100% (2ND-H G20 @ 20 mbar, 15 °C) (m³/h) |
8.6 (std) / 9.8 (high cap.) |
8.6 / 9.8 |
8.6 / 9.8 |
8.6 / 9.8 |
| Refrigerant R-410A (kg) |
10.5 |
18.2 |
20.5 |
29 |
| Power supply (V/ph/Hz) |
400/3+N/50 |
400/3+N/50 |
400/3+N/50 |
400/3+N/50 |
| Rated air flow indoor fan (m³/h) |
8500 |
11500 |
13500 |
16000 |
| Max static pressure rated flow, standard (Pa) |
182 |
270 |
240 |
368 |
| Max static pressure rated flow, HPD option (Pa) |
368 |
430 |
>500 |
>500 |
| Indoor fan motor IP55, standard/HPD (kW) |
3 / 4 |
4 / 5.5 |
5.5 / 7.5 |
7.5 / 11 |
| Outdoor fan motor IP54 (kW) |
1.9 (800 mm, x1) |
1.9 (800 mm, x2) |
1.9 (800 mm, x2) |
1.9 (800 mm, x2) |
| Total rated power / current (kW / A) |
16 / 32 |
23 / 42 |
30 / 54 |
36 / 70 |
| Circuit breaker K curve (A) |
50 |
63 |
80 |
100 |
| Net dimensions H/L/W (mm) |
1316 / 3180 / 2337 |
1316 / 3180 / 2337 |
1367 / 3495 / 2337 |
1367 / 3495 / 2337 |
| Net weight basic unit ARC / ARG (kg) |
900 / 1010 |
945 / 1055 |
1118 / 1228 |
1142 / 1252 |
| Parameter |
ARH/ARD 045 |
ARH/ARD 060 |
ARH/ARD 075 |
ARH/ARD 090 |
| Net cooling capacity (kW) |
47.6 |
61.9 |
71.4 |
83.4 |
| Heat capacity thermodynamic (kW) |
45.2 |
58 |
71.7 |
86.5 |
| Refrigerant R-410A (kg) |
14.5 |
19 |
20.5 |
29 |
| Rated air flow indoor fan (m³/h) |
8500 |
11500 |
13500 |
16000 |
| Max static pressure rated flow, standard/HPD (Pa) |
168 / 335 |
242 / 402 |
240 / >500 |
368 / >500 |
| Net weight basic unit ARH / ARD (kg) |
930 / 1040 |
985 / 1095 |
1145 / 1255 |
1220 / 1330 |
Other data common to all models:
| Parameter |
Value |
| Compressors |
SCROLL, 1 (TANDEM 50% + 50%), degree of protection IP21 |
| Voltage limits min./max. (V) |
360/440 |
| Summer cycle max outdoor temperature full/partial load (°C) |
46 / 52 |
| Winter cycle outdoor temperature DB min/max (heat pump) |
-10/20 °C |
| Gas heating outdoor temperature DB min/max (ARG/ARD) |
-15/25 °C |
| Condensate drain connection |
1” BSP Female |
| Sound power level outdoor (dB(A)) |
80.8 (045) – 87.9 (090) |
| Sound pressure level at 10 m outdoor (dB(A)) |
50 (045) – 57.1 (090) |
| Weight options |
Economiser 65/73 kg; roof-curb base fixed/adjustable 81/157 – 85/165 kg; hot water coil 60 kg; heating element 20 kg |
Варіанти замовлення
- ARC-045, ARC-060, ARC-075: cooling only
- ARG (045/060/075/090): cooling + gas heating
- ARH-075, ARH-090 (and ARH 045/060): heat pump
- ARD-045 (and ARD 060/075/090): heat pump + gas heating
- Options: HPD drive motor (higher pressure), economiser, exhaust fan (axial), return fan (centrifuge), roof-curb mounting base, ERP adaptor for Roof Curb, heating element (12/25/37/50 kW stages), hot water coil, fixed outdoor air intake, barometric damper, copper fin coils (indoor/outdoor), F6/F7 filters
Допуски та стандарти
- IEC 60034–30–1 (indoor fan motor efficiency class IE3)
- DIN, VDE 0660-104 (K curve circuit breakers)
- BS6956 part 5 (gas thread sealing material)
- Eurovent Rooftop program certification conditions
Текст документа
ACTIVA SERIES ROOF TOP Air
Conditioners 045/090
Installation manual
Ref.: N-40357_EN 0915
Index
Index
1 Installation manual...................................................................................................................1
1.1 Safety instructions....................................................................................................................2
1.2 Icons used in this document.....................................................................................................2
1.3 Instructions for storage, transport and handling of the unit......................................................3
1.3.1 Disposal of packaging..............................................................................................................3
1.3.2 Hoisting points..........................................................................................................................3
1.4 Technical data..........................................................................................................................5
1.4.1 Technical and physical data for ARC (only cooling) and ARG (only cooling + gas heating)....5
1.4.2 ARH technical and physical data (heat pump) and ARD (heat pump + gas heating)..............7
1.4.3 Weight options and accessories...............................................................................................8
1.5 ARC units with auxiliary heating element.................................................................................8
1.6 ARH units with auxiliary heating element.................................................................................9
1.7 Limits of use.............................................................................................................................9
1.8 Capacities and application data for gas ARG/ARD................................................................10
1.9 Hot water coil, optional in ARC/ARH......................................................................................10
1.10 Measurements, clearances and accesses.............................................................................12
1.10.1 Connections for supply and return side ducts........................................................................12
1.10.2 General dimensions and accesses (models 045/060)...........................................................14
1.10.3 General dimensions and accesses (models 075/090)...........................................................16
1.11 ARC/ARG Performance.........................................................................................................17
1.11.1 ARC/ARG 045 Cooling capacities..........................................................................................17
1.11.2 ARC/ARG 060 Cooling capacities..........................................................................................18
1.11.3 ARC/ARG 075 Cooling capacities..........................................................................................18
1.11.4 ARC/ARG 090 Cooling capacities..........................................................................................19
1.12 ARH/ARD output....................................................................................................................19
1.12.1 ARH/ARD 045 Cooling capacities..........................................................................................19
1.12.2 ARH/ARD 060 Cooling capacities..........................................................................................20
1.12.3 ARH/ARD 075 Cooling capacities..........................................................................................20
1.12.4 ARH/ARD 090 Cooling capacities..........................................................................................21
1.12.5 ARH/ARD 045 Thermodynamic heat capacity.......................................................................21
1.12.6 ARH/ARD 060 Thermodynamic heat capacity.......................................................................22
1.12.7 ARH/ARD 075 Thermodynamic heat capacity.......................................................................22
1.12.8 ARH/ARD 090 Thermodynamic heat capacity.......................................................................23
1.13 Indoor fan...............................................................................................................................23
1.13.1 Features table........................................................................................................................23
1.13.2 Considerations when consulting the output tables.................................................................23
1.13.3 Output table for indoor fan, model ARC-045, applications with side ducts, standard drive motor
3 kW.......................................................................................................................................24
1.13.4 Output table for indoor fan, model ARC-045, applications with side ducts, optional HPD drive
motor 4 kW.............................................................................................................................24
1.13.5 Output table for indoor fan, model ARC-060, applications with side ducts, standard drive motor
4 kW.......................................................................................................................................25
i
Index
1.13.6 Output table for indoor fan, model ARC-060, applications with side ducts, optional HPD drive
motor 5.5 kW..........................................................................................................................25
1.13.7 Output table for indoor fan, model ARC-075, applications with side ducts, standard drive motor
5.5 kW....................................................................................................................................25
1.13.8 Output table for indoor fan, model ARC/ARH-075, applications with side ducts, optional HPD
drive motor 7.5 kW.................................................................................................................26
1.13.9 Output table for indoor fan, model ARC/ARH-090, applications with side ducts, standard drive
motor 7.5 kW..........................................................................................................................26
1.13.10 Output table for indoor fan, model ARC/ARH-090, applications with side ducts, optional HPD
drive motor 11 kW..................................................................................................................26
1.14 Pressure drop of options/accessories, gas heating and vertical ducts..................................27
1.15 Instructions for installation and connection of the unit...........................................................27
1.15.1 Characteristics of the location................................................................................................27
1.15.2 Characteristics of the facility where the unit will be installed..................................................28
1.15.3 Specifications for the foundation or anchoring of the unit......................................................28
1.15.4 Installation on shock absorbers..............................................................................................29
1.15.5 Characteristics of utility provider connections........................................................................29
1.15.6 Connection and preparation of the various connections........................................................30
1.16 Instructions for starting up the unit.........................................................................................35
1.16.1 Electrical checks.....................................................................................................................35
1.16.2 Starting the gas heating, ARG/ARD.......................................................................................35
1.17 Unblocking the unit safely in case of breakdown...................................................................39
1.18 Regular maintenance tasks performed by specialised personnel..........................................39
1.18.1 Planned Maintenance Schedule.............................................................................................40
1.18.2 Maintenance tasks performed by specialised personnel........................................................40
1.18.3 Gas heating (ARG/ARD Models)............................................................................................43
1.19 Unit sound pressure data.......................................................................................................45
2 Unit installation data...............................................................................................................46
2.1 List of tests for unit start-up....................................................................................................47
2.2 Start-up data..........................................................................................................................48
3 Cooling diagrams...................................................................................................................52
3.1 ARC/ARG 045/060 Cooling diagrams....................................................................................53
3.2 ARC/ARG 075 Cooling diagrams...........................................................................................54
3.3 ARC/ARG 090 Cooling diagrams...........................................................................................55
3.4 ARH/ARD 045/060 Cooling diagrams....................................................................................56
3.5 ARH/ARD 075 Cooling diagrams...........................................................................................57
3.6 ARH/ARD 090 Cooling diagrams...........................................................................................58
4 Wiring diagrams ....................................................................................................................59
4.1 Micro switch configuration......................................................................................................60
4.2 Fault table..............................................................................................................................61
4.3 Incidents.................................................................................................................................62
4.3.1 Test button.............................................................................................................................63
4.4 DPC-1 thermostat..................................................................................................................63
4.5 Unit wiring diagrams...............................................................................................................64
ii
1
Installation manual
1 Installation manual
1.1 Safety instructions
1.1 Safety instructions
This document contains the necessary information for the safe and efficient transportation, assembly
and installation of the air conditioning unit. This guarantees the condition of the unit and its operating
safety.
Only an authorised company may assemble the air conditioning unit.
ATTENTION
Only authorised companies with the appropriate technical resources and suitably trained personnel may
install the air conditioning unit.
CAUTION
The specialists responsible for installing the air conditioning unit must make sure they have all of the
information and knowledge required to correctly install, test and deliver the unit. Johnson Controls Inc.
shall not be considered responsible for any damage caused by installation of the unit that is no consistent
with that described in this document or others specifically provided with the unit.
During regular equipment installation, the fitter must pay special attention to certain situations in order
to prevent injuries or damage to the unit.
Situations that could jeopardise the safety of the fitter or that of others nearby or that could put the unit
itself at risk are clearly indicated in this manual.
A series of special symbols are used to clearly identify these situations.
Pay careful attention to these symbols and to the messages following them, as your safety and the safety
of others depends on it.
1.2 Icons used in this document
DANGER
• The text following this symbol contains information and instructions relating directly to your safety
and physical wellbeing.
• Not taking these instructions into account could lead to serious, very serious or even fatal injuries to
you and others in the proximities of the unit.
Information can also be found on safe procedures during unit handling. This will help reduce the risk of
accidents.
CAUTION
• The text following this symbol contains information and instructions relating directly to your safety
and physical wellbeing.
• Not taking these instructions into account could lead to minor injuries to you and others in the
proximities of the unit.
• Not taking these instructions into account could lead to unit damage.
Information can also be found on safe procedures during unit handling. This will help reduce the risk of
accidents.
NOTE
• The text following this symbol contains information or instructions that may be of use or that is worthy
of a more thorough explanation.
• Instructions regarding inspections to be made on unit parts or systems may also be included.
2
Installation manual 1
Instructions for storage, transport and handling of the unit 1.3
1.3 Instructions for storage, transport and handling of the unit
Delivery inspection
The unit should be carefully inspected for visible damage or abnormalities as soon as it is received.
Any abnormalities or damage to the unit should be communicated to both the transportation and
insurance company in writing.
Storage instructions
The unit should be stored in a place suitable to the purpose (warehouse or similar), protected from the
weather, water, humidity and dust.
Cover the unit with a canvas of a suitable size.
The unit should be appropriately protected from knocks and dust, ensuring the protective parts it was
supplied with remain in place. Where these are not in place, establish the necessary protections and/or
barriers to keep vehicles or fork-lift trucks away.
Transport and handling of the unit
The units should only be handled by personnel from the company responsible for their installation.
Transport of the unit should be in such a manner that no damage is caused by faulty or inadequate
mooring to the bed or body of the vehicle.
Where necessary, protect all of the edges of the unit against knocks and scratches and moor it to the
bed or body of the vehicle using suitable textile belts or slings to keep it perfectly still.
Loading and unloading the unit from a truck or trailer should be on flat, solid ground using an appropriate
crane with sufficient capacity.
CAUTION
It is strictly prohibited to use fork lifts to load, unload, or handle the unit.
1.3.1 Disposal of packaging
The packaging is recyclable. Dispose of it in the appropriate place or take it to an appropriate collection
centre. Respect the regulations in force for this type of waste in the country where the unit is being
installed.
Packaging remains must be correctly disposed of. Improper disposal of packaging generates
environmental problems that affect human life.
1.3.2 Hoisting points
The points designed for hoisting the unit are located
on the beams on its base -arrows-.
Before hoisting the unit, check that the cables or
slings are firmly hooked to these points and make
sure the crane and the cables or slings are capable of
lifting the weight.
3
1 Installation manual
1.3 Instructions for storage, transport and handling of the unit
Place spacers -1- at the top of the unit to prevent the
cables or slings from touching it.
1
Attach guide ropes so that the unit does not rotate
freely.
The cables or slings should be long enough to form
an angle of over 45º to the horizontal plane. Hoist the
unit keeping it in a horizontal position.
DANGER
There should not be onlookers within a radius of 10
m of the unit when it is being hoisted.
Centre of gravity of the unit
Models 045 060 075 090
A 1180 1180 1135 1080
B 1390 1425 1480 1540 1 2
C 3180 3180 3495 3495
D 2337 2337 2337 2337 B
D
A C
All measurements in mm.
1. Centre of gravity
2. End of the outdoor coil
4
Installation manual 1
Technical data 1.4
1.4 Technical data
1.4.1 Technical and physical data for ARC (only cooling) and ARG (only
cooling + gas heating)
Models ARC/ARG 045 060 075 090
Net cooling capacity kW 45.1 61 71.5 84
Cooling capacity (1)
Rated absorbed power in cool mode kW 16 23 30 36
Optional electric heater, heating capaci‐
Heating (ARC) kW 12-25-37-50
ty (400 V) (2)
(LHV) Total
85
Heat capacity at 100% power (standard) kW
Net (2) kW 76
Heat capacity at 100% power, high ca‐ Total kW 100
pacity (optional) Net (2) kW 90
Gas Heating (ARG) 100% gas consumption (2ND-H natural
gas, G20 at 20 mbar and 15 °C) (stand‐ m3/h 8.6
ard)
100% gas consumption (2ND-H natural
gas, G20 at 20 mbar and 15ºC) high ca‐ m3/h 9.8
pacity (optional)
Stages No. 2
Rated/start-up current A 2x12/95 2x15/118 2x20/140 2x25/198
Compressors Type and quantity SCROLL, 1 (TANDEM 50% + 50%)
Degree of protection IP21
Coolant (R-410A) kg 10.5 18.2 20.5 29
Power supply V/ph/Hz 400/3+N/50
Rated air flow m3/h 8500 11500 13500 16000
Maximum static pressure with rated flow
Pa 182 270 240 368
(standard)
Maximum static pressure with rated flow
Pa 368 430 >500 >500
(optional HPD drive)
Maximum flow rate m3/h 10000 13500 16000 18000
Indoor fan (3)
Minimum flow rate m3/h 7000 9500 11500 13000
IP55 motor (standard) kW 3 4 5.5 7.5
Rated current A 5.5 5.7 7.6 11.7
IP55 Motor (HPD optional) kW 4 5.5 7.5 11
Rated current A 5.7 7.6 11.7 14/17.4
Number of elements No. 2 3 3 4
Indoor coil (evaporator) Distance between fins mm 1.81 1.81 1.81 1.81
Front surface m2 1.44 1.58 1.95 1.06 (x 2)
Quantity per unit No. 6 6
Air filters (G4)
Dimensions mm 470x550x48 565x594x48
Diameter/number mm 800/1 800/2 800/2 800/2
Total rated flow m3/h 15000 23000 27000 27000
Outdoor fan
Motor (IP54) kW 1.9 1.9 1.9 1.9
Rated current A 3.5 2x3.5 2x3.5 2x3.5
Number of elements No. 2 3 2 3
Outdoor coil (condens‐
Distance between fins mm 1.81 1.81 1.81 1.81
er)
Front area m2 2.27 2.49 2.31 (x2) 2.31 (x2)
Height mm 1316 1367
Net dimensions (4) Length mm 3180 3495
Width mm 2337 2337
Net weight (basic unit ARC kg 900 945 1118 1142
without accessories) (4) ARG kg 1010 1055 1228 1252
5
1 Installation manual
1.4 Technical data
Models ARC/ARG 045 060 075 090
Total rated power kW 16 23 30 36
Total rated current A 32 42 54 70
Electrical features of Total maximum power kW 23 31 38 45
the unit Total maximum current A 42 56 70 83
Circuit breaker (K curve) (5) A 50 63 80 100
Minimum cable section (6) mm2 10 16 25 35
(1) Data in accordance with Eurovent conditions, summer: indoor 27 °C DBT / 19 °C WBT ‑ outdoor DBT 35 °C. (DBT Dry-bulb temperature; WBT Wet-bulb temperature).
(2) Add the inside motor consumption to find the total calorific capacity.
(3) See Indoor fan, see on page 23.
(4) Consider the additional weight of options and accessories. To do so, see Weight options and accessories, see on page 8.
LHV: Lower heating value.
(5) and (6) Circuit breaker with K curve, according to DIN, VDE 0660-104. Cable section for the power supply line based on copper conductors, 105 °C. The indicated circuit
breaker and the section of power supply cables are guidelines. They should be adjusted based on the requirements of each installation, distance between units, fall in
planned voltage and on the application of the current regulations with respect to the country where the unit is being installed.
6
Installation manual 1
Technical data 1.4
1.4.2 ARH technical and physical data (heat pump) and ARD (heat pump
+ gas heating)
Models ARH/ARD 045 060 075 090
Net cooling capacity kW 47.6 61.9 71.4 83.4
Cooling capacity (1) Rated absorbed power in cool
kW 17 20 28 36
mode
Heat capacity (2) kW 45.2 58 71.7 86.5
Rated power absorbed in heat
kW 16 19 27 33
Heat capacity mode
Optional electric heater, heat‐
kW 12-25-37-50
ing capacity (400 V) (ARH) (2)
Heat capacity at 100% power (LHV) Total kW 85
(standard) Net (2) kW 76
Heat capacity at 100% power, Total kW 100
high capacity (optional) Net (2) kW 90
100% gas consumption (2ND-
Gas Heating (ARG) H natural gas, G20 at 20 mbar m3/h 8.6
and 15 °C) (standard)
100% gas consumption (2ND-
H natural gas, G20 at 20 mbar
m3/h 9.8
and 15ºC) high capacity (op‐
tional)
Stages No. 2
Rated/start-up current A 2x12/95 2x15/118 2x20/140 2x25/198
Compressors Type and quantity SCROLL, 1 (TANDEM 50 % + 50 %)
Degree of protection IP21
Coolant
kg 14.5 19 20.5 29
(R-410A)
Power supply V/ph/Hz 400/3+N/50
Rated air flow m3/h 8500 11500 13500 16000
Maximum static pressure with
Pa 168 242 240 368
rated flow (standard drive)
Maximum static pressure with
Pa 335 402 >500 >500
rated flow (optional HPD drive)
Maximum flow rate m3/h 10000 13500 16000 18000
Indoor fan (3)
Minimum flow rate m3/h 7000 9500 11500 13000
IP55 motor (standard) kW 3 4 5.5 7.5
Rated current A 5.5 5.7 7.6 11.7
IP55 Motor (HPD optional) kW 4 5.5 7.5 11
Rated current A 5.7 7.6 11.7 14/17.4
Number of elements No. 3 4 3 4
Indoor coil (evaporator) Distance between fins mm 2.11 2.11 1.81 1.81
Front surface m2 1.44 1.58 1.95 1.06 (x 2)
Quantity per unit No. 6 6
Air filters (G4)
Dimensions mm 470x550x48 565x594x48
Diameter/number mm 800/1 800/2 800/2 800/2
Total rated flow m3/h 15000 23000 27000 27000
Outdoor fan
Motor (IP54) kW 1.9 1.9 1.9 1.9
Rated current A 3.5 2x3.5 2x3.5 2x3.5
Number of elements No. 3 4 2 3
Outdoor coil (condenser) Distance between fins mm 2.11 2.54 1.81 1.81
Front area m2 2.27 2.49 2.31 (x2) 2.31 (x2)
Height mm 1316 1367
Net dimensions (4) Length mm 3180 3495
Width mm 2337 2337
Net weight (basic unit with‐ ARH kg 930 985 1145 1220
out accessories) (4) ARD kg 1040 1095 1255 1330
7
1 Installation manual
1.5 ARC units with auxiliary heating element
Models ARH/ARD 045 060 075 090
Total rated power kW 17 22 28 36
Total rated current A 32 42 54 70
Electrical features of the Total maximum power kW 23 31 38 45
unit Total maximum current A 42 56 70 83
Circuit breaker (K curve) (5) A 50 63 80 100
Minimum cable section (6) mm2 10 16 25 35
(1) Data in accordance with Eurovent conditions, summer: indoor 27 °C DBT / 19 °C WBT ‑ outdoor DBT 35 °C. Winter: Indoor DBT 20 °C, outdoor DBT 7 °C/WBT 6 °C
(DBT Dry-bulb temperature; WBT Wet-bulb temperature).
(2) Add the inside motor consumption to find the total calorific capacity.
(3) See Indoor fan, see on page 23
(4) Consider the additional weight of options and accessories. To do so, see Weight options and accessories, see on page 8.
LHV: Lower heating value.
(5) and (6) Circuit breaker with K curve, according to DIN, VDE 0660-104. Cable section for the power supply line based on copper conductors, 105 °C. The indicated circuit
breaker and the section of power supply cables are guidelines. They should be adjusted based on the requirements of each installation, distance between units, fall in
planned voltage and on the application of the current regulations with respect to the country where the unit is being installed.
1.4.3 Weight options and accessories
Models 045 060 075 090
Economiser kg 65 65 73 73
Exhaust fan (axial) kg 54 54 63 63
Return fan (centrifuge) kg
Roof-curb mounting base (fixed/adjustable) kg 81/157 81/157 85/165 85/165
ERP adaptor for Roof Curb kg 177 177 190 190
Heating element kg 20 20 20 20
Hot water coil kg 60 60 60 60
Fixed outdoor air intake kg 9 9 9 9
Barometric damper kg 20 20 20 20
indoor 19 31 44 64
ARC/ARG
outdoor 30 49 70 104
Copper fin coil
indoor 29 48 44 64
ARH/ARD
outdoor 44 64 70 104
1.5 ARC units with auxiliary heating element
Heating element
Maximum total current Maximum circuit Minimum cable cross-
ARC Model Power supply V/Ph/Hz Power
Stages (No.) Current (A) of the unit (A) breaker (K Curve) (1) section (mm2) (2)
(kW)
12 1 18 32 50 10
25 2 36 38 50 10
045 400/3/50
37 2 54 60 80 25
50 2 72 78 100 35
12 1 18 42 50 10
25 2 36 42 50 10
060 400/3/50
37 2 54 60 80 25
50 2 72 78 100 35
12 1 18 54 63 16
25 2 36 54 63 16
075 400/3/50
37 2 54 62 80 25
50 2 72 80 100 35
12 1 18 70 80 25
25 2 36 70 80 25
090 400/3/50
37 2 54 70 80 25
50 2 72 84 100 35
8
Installation manual 1
ARH units with auxiliary heating element 1.6
(1) K Curve (DIN, VDE 0660-104).
(2) Based on copper conductors 105 °C.
1.6 ARH units with auxiliary heating element
Heating element
Maximum total current Maximum circuit Minimum cable cross-
ARC Model Power supply V/Ph/Hz Power
Stages (No.) Current (A) of the unit (A) breaker (K Curve) (1) section (mm2) (2)
(kW)
12 1 18 50 63 16
25 2 36 68 80 25
045 400/3/50
37 2 54 86 100 35
50 2 72 104 125 50
12 1 18 60 80 25
25 2 36 78 100 35
060 400/3/50
37 2 54 96 125 50
50 2 72 114 125 50
12 1 18 72 80 25
25 2 36 90 100 35
075 400/3/50
37 2 54 108 125 50
50 2 72 126 160 70
12 1 18 88 100 35
25 2 36 106 125 50
090 400/3/50
37 2 54 124 160 70
50 2 72 142 160 70
(1) K Curve (DIN, VDE 0660-104).
(2) Based on copper conductors 105 °C.
1.7 Limits of use
Model 045 060 075 090
Voltage limits Min./Max V 360/440
WB °C Min./Max. 15/23 15/23 15/23 15/23
Temperature of air inlet in indoor coil
DB °C Min/Max 20/32 20/32 20/32 20/32
Outdoor temperature (without condensa‐
TS °C Min. 7 7 7 7
tion control)
ARC/ARG
At full
TS °C 46 46 46 46
Maximum outdoor tempera‐ load
ture (1) At partial
TS °C 52 52 52 52
load
WB °C Min./Max. 15/23 15/23 15/23 14/23
Temperature of air inlet in indoor coil
DB °C Min/Max 20/32 20/32 20/32 20/32
Outdoor temperature (without condensa‐
TS °C Min. 7 7 7 7
tion control)
Summer cycle
At full
ARH/ARD TS °C 46 46 46 46
Maximum outdoor tempera‐ load
ture (1) At partial
TS °C 52 52 52 52
load
Temperature of air inlet in indoor coil DB °C Min/Max 10/25 10/25 10/25 10/25
Winter cycle
Outdoor temperature DB °C Min/Max -10/20 -10/20 -10/20 -10/20
Indoor temperature TS °C Max 30 30 30 30
ARG/ARD (2) Gas heating
Outdoor temperature DB °C Min/Max -15/25 -15/25 -15/25 -15/25
1. Direct sunlight on the unit should be prevented when temperatures are higher than 43ºC. If placed under some kind of protective cover, the cover should not interfere
with the flow of outdoor ventilation.
2. The gas heating units (ARG/ARD) are only appropriate for use with gas. In LPG (Liquefied Petroleum Gas, propane) installations, it must be ensured that in no case
should gasoline in liquid form reach the gas group.
DB: Dry-bulb Thermometer; TH: Wet-bulb thermometer.
9
1 Installation manual
1.8 Capacities and application data for gas ARG/ARD
1.8 Capacities and application data for gas ARG/ARD
Heat capacity Gas consumption m3/h
Temperature rise in ºC at full
L.P.G. pro‐ power (4)
Total (LHV) (1) kW Net kW Natural gas (2)
Model pane (3)
Optional (on‐
Standard High power Standard High power Standard High power Min. Max.
ly standard)
045 85 100 76 90 8,6 9,8 3,6 17 33
060 85 100 76 90 8,6 9,8 3,6 17 33
075 85 100 76 90 8,6 9,8 3,6 17 33
090 85 100 76 90 8,6 9,8 3,6 17 33
(1) LHV: Lower heating value.
(2) Natural gas 2ND-H, G20, at 20 mbar and 15 ºC
(3) Propane gas, G31, at 37 mbar and 15 ºC.
(4) The air flow should be regulated so as to increase temperature within the specified limits. Units with optional high power burners should have a minimum air flow of
10000 m3/h.
Note: The gas units are shipped ready to operate with natural gas. A conversion kit can be used to convert them to propane gas (L.P.G.).
1.9 Hot water coil, optional in ARC/ARH
Data with water, without glycol
090
ARC/ARH 075
060
045
Water temperature °C 90 ÷ 70
Air flow rate m3 7000 8500 10000 11500 13500 15000 16000 17000 18000
Heat capacity kW 71,1 79,5 87,0 93,7 101,7 107,3 111 114,2 117,4
Water flow rate m3/h 3 3,3 3,7 4 4,3 4,5 4,7 4,8 5
Pressure drop kPa 9,5 11 14 16 19 21 22 23 25
Air temperature rise K 30 27 25 24 22 21 20 19 18
Water temperature °C 80 ÷ 60
Air flow rate m3 7000 8500 10000 11500 13500 15000 16000 17000 18000
Heat capacity kW 58,6 65,4 71,5 77 83,5 88,1 90,8 93,7 96,3
Water flow rate m3/h 2,5 2,8 3 3,3 3,5 3,7 3,9 4 4,1
Pressure drop kPa 7,5 9 9,5 11 13 14 16 16 18
Air temperature rise K 24 22 21 20 18 17 17 16 15
Water temperature °C 70 ÷ 50
Air flow rate m3 7000 8500 10000 11500 13500 15000 16000 17000 18000
Heat capacity kW 46,0 51,2 55,8 61,1 65,1 68,7 71 73 75
Water flow rate m3/h 1,9 2,2 2,4 2,6 2,8 2,9 3 3,1 3,2
Pressure drop kPa 4,5 6 6,5 7,5 9 9,5 10,5 11 11
Air temperature rise K 19 18 16 15 14 13 13 12 12
- Pressure drop of coil + 3-way valve.
- Coil air inlet: 18 °C.
- Total volume of water in circuit 10 l.
- See air pressure drop, Pressure drop of options/accessories, gas heating and vertical ducts., see on page 27.
10
Installation manual 1
Hot water coil, optional in ARC/ARH 1.9
Data with a mix of water and 35% glycol
090
ARC/ARH 075
060
045
Water temperature °C 90 ÷ 70
Air flow rate m3 7000 8500 10000 11500 13500 15000 16000 17000 18000
Heat capacity kW 68,5 76,3 83,6 89,8 97,5 102,8 106,3 109,4 112,4
Water flow rate m3/h 3,2 3,6 4 4,2 4,6 4,8 5 5,1 5,3
Pressure drop kPa 12 15 17 20 23 25 27 28 30
Air temperature rise K 28 26 24 22 21 20 19 18 17
Water temperature °C 80 ÷ 60
Air flow rate m3 7000 8500 10000 11500 13500 15000 16000 17000 18000
Heat capacity kW 55,6 62 67,7 72,8 79 83,3 85,9 88,5 91
Water flow rate m3/h 2,6 2,9 3,2 3,5 3,7 4 4,1 4,2 4,3
Pressure drop kPa 9 10 12 14 16 18 19 20 21
Air temperature rise K 23 21 20 18 17 16 16 15 14
Water temperature °C 70 ÷ 50
Air flow rate m3 7000 8500 10000 11500 13500 15000 16000 1700 18000
Heat capacity Показано початок документа. Повний текст — у PDF за посиланням вище.