ARC-045 — Rooftop air conditioner Activa series 045/090, models ARC/ARG/ARH/ARD

Вид документаІнструкція
ВиробникJCI
МоделіARC-045, ARC-060, ARC-075, ARH-075, ARH-090, ARD-045
Група обладнанняautomation
Мова документаанглійська
Розмір файлу3.4 МБ

Про документ

Installation manual for the Johnson Controls Activa series packaged rooftop air conditioners in sizes 045 to 090. The series covers four variants per size: ARC (cooling only), ARG (cooling + gas heating), ARH (heat pump) and ARD (heat pump + gas heating). Units are designed for outdoor installation only, with side or downward duct connections and a range of factory options.

Ключові дані

Net cooling capacityARC/ARG: 45.1 / 61 / 71.5 / 84 kW; ARH/ARD: 47.6 / 61.9 / 71.4 / 83.4 kW
Power supply400 V / 3+N ph / 50 Hz
RefrigerantR-410A (10.5–29 kg)
CompressorsSCROLL, 1 (TANDEM 50 % + 50 %), IP21
Indoor fan motorIP55, 3–7.5 kW standard; HPD optional up to 11 kW
Outdoor fan motorIP54, 1.9 kW
Gas heating capacity (ARG/ARD)85 kW total LHV standard / 100 kW high power (optional)
Air filtersG4, 6 per unit, 470x550x48 mm or 565x594x48 mm

Застосування

  • Commercial rooftop air conditioning with cooling only or cooling + gas heating
  • Heat pump operation for summer/winter cycles (ARH/ARD)
  • Optional economiser, exhaust fan, hot water coil, auxiliary electric heating element, fixed outdoor air intake, barometric damper
  • Natural gas operation as standard; convertible to propane (LPG) via conversion kit

Особливості

  • Belt-driven indoor fan with adjustable variable-diameter motor pulley; standard and optional high-pressure (HPD) drives up to >500 Pa static pressure
  • IE3 efficiency class motors, Class F insulation (IEC 60034–30–1)
  • Eurovent Rooftop program certified performance data points
  • YKNOpen electronic control board with red LED fault indication and green LED incident indication; DPC-1 thermostat; RS-485 connection [J12]; YKTOOL test device connection
  • Two-stage scroll compressors (tandem); low ambient switch HP2
  • Gas burner N320 with automatic lighting system, two heat stages, thermal breaker automatic reset at 82 °C / manual reset at 93 °C
  • Micro-switch configurable defrosting time (0'/30'/60'/90'), coil configuration and compressor selection

Технічні дані

Parameter ARC/ARG 045 ARC/ARG 060 ARC/ARG 075 ARC/ARG 090
Net cooling capacity (kW) 45.1 61 71.5 84
Rated absorbed power cool mode (kW) 16 23 30 36
Optional electric heater capacity (400 V) (kW) 12-25-37-50 12-25-37-50 12-25-37-50 12-25-37-50
Gas heat capacity at 100% (LHV), total (kW) 85 (standard) / 100 (optional high)
Gas consumption 100% (2ND-H G20 @ 20 mbar, 15 °C) (m³/h) 8.6 (std) / 9.8 (high cap.) 8.6 / 9.8 8.6 / 9.8 8.6 / 9.8
Refrigerant R-410A (kg) 10.5 18.2 20.5 29
Power supply (V/ph/Hz) 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50
Rated air flow indoor fan (m³/h) 8500 11500 13500 16000
Max static pressure rated flow, standard (Pa) 182 270 240 368
Max static pressure rated flow, HPD option (Pa) 368 430 >500 >500
Indoor fan motor IP55, standard/HPD (kW) 3 / 4 4 / 5.5 5.5 / 7.5 7.5 / 11
Outdoor fan motor IP54 (kW) 1.9 (800 mm, x1) 1.9 (800 mm, x2) 1.9 (800 mm, x2) 1.9 (800 mm, x2)
Total rated power / current (kW / A) 16 / 32 23 / 42 30 / 54 36 / 70
Circuit breaker K curve (A) 50 63 80 100
Net dimensions H/L/W (mm) 1316 / 3180 / 2337 1316 / 3180 / 2337 1367 / 3495 / 2337 1367 / 3495 / 2337
Net weight basic unit ARC / ARG (kg) 900 / 1010 945 / 1055 1118 / 1228 1142 / 1252
Parameter ARH/ARD 045 ARH/ARD 060 ARH/ARD 075 ARH/ARD 090
Net cooling capacity (kW) 47.6 61.9 71.4 83.4
Heat capacity thermodynamic (kW) 45.2 58 71.7 86.5
Refrigerant R-410A (kg) 14.5 19 20.5 29
Rated air flow indoor fan (m³/h) 8500 11500 13500 16000
Max static pressure rated flow, standard/HPD (Pa) 168 / 335 242 / 402 240 / >500 368 / >500
Net weight basic unit ARH / ARD (kg) 930 / 1040 985 / 1095 1145 / 1255 1220 / 1330

Other data common to all models:

Parameter Value
Compressors SCROLL, 1 (TANDEM 50% + 50%), degree of protection IP21
Voltage limits min./max. (V) 360/440
Summer cycle max outdoor temperature full/partial load (°C) 46 / 52
Winter cycle outdoor temperature DB min/max (heat pump) -10/20 °C
Gas heating outdoor temperature DB min/max (ARG/ARD) -15/25 °C
Condensate drain connection 1” BSP Female
Sound power level outdoor (dB(A)) 80.8 (045) – 87.9 (090)
Sound pressure level at 10 m outdoor (dB(A)) 50 (045) – 57.1 (090)
Weight options Economiser 65/73 kg; roof-curb base fixed/adjustable 81/157 – 85/165 kg; hot water coil 60 kg; heating element 20 kg

Варіанти замовлення

  • ARC-045, ARC-060, ARC-075: cooling only
  • ARG (045/060/075/090): cooling + gas heating
  • ARH-075, ARH-090 (and ARH 045/060): heat pump
  • ARD-045 (and ARD 060/075/090): heat pump + gas heating
  • Options: HPD drive motor (higher pressure), economiser, exhaust fan (axial), return fan (centrifuge), roof-curb mounting base, ERP adaptor for Roof Curb, heating element (12/25/37/50 kW stages), hot water coil, fixed outdoor air intake, barometric damper, copper fin coils (indoor/outdoor), F6/F7 filters

Допуски та стандарти

  • IEC 60034–30–1 (indoor fan motor efficiency class IE3)
  • DIN, VDE 0660-104 (K curve circuit breakers)
  • BS6956 part 5 (gas thread sealing material)
  • Eurovent Rooftop program certification conditions

Текст документа

ACTIVA SERIES ROOF TOP Air
Conditioners 045/090




Installation manual
Ref.: N-40357_EN 0915
                                                                                                                                             Index



Index



1        Installation manual...................................................................................................................1

1.1      Safety instructions....................................................................................................................2
1.2      Icons used in this document.....................................................................................................2
1.3      Instructions for storage, transport and handling of the unit......................................................3
1.3.1    Disposal of packaging..............................................................................................................3
1.3.2    Hoisting points..........................................................................................................................3
1.4      Technical data..........................................................................................................................5
1.4.1    Technical and physical data for ARC (only cooling) and ARG (only cooling + gas heating)....5
1.4.2    ARH technical and physical data (heat pump) and ARD (heat pump + gas heating)..............7
1.4.3    Weight options and accessories...............................................................................................8
1.5      ARC units with auxiliary heating element.................................................................................8
1.6      ARH units with auxiliary heating element.................................................................................9
1.7      Limits of use.............................................................................................................................9
1.8      Capacities and application data for gas ARG/ARD................................................................10
1.9      Hot water coil, optional in ARC/ARH......................................................................................10
1.10     Measurements, clearances and accesses.............................................................................12
1.10.1   Connections for supply and return side ducts........................................................................12
1.10.2   General dimensions and accesses (models 045/060)...........................................................14
1.10.3   General dimensions and accesses (models 075/090)...........................................................16
1.11     ARC/ARG Performance.........................................................................................................17
1.11.1   ARC/ARG 045 Cooling capacities..........................................................................................17
1.11.2   ARC/ARG 060 Cooling capacities..........................................................................................18
1.11.3   ARC/ARG 075 Cooling capacities..........................................................................................18
1.11.4   ARC/ARG 090 Cooling capacities..........................................................................................19
1.12     ARH/ARD output....................................................................................................................19
1.12.1   ARH/ARD 045 Cooling capacities..........................................................................................19
1.12.2   ARH/ARD 060 Cooling capacities..........................................................................................20
1.12.3   ARH/ARD 075 Cooling capacities..........................................................................................20
1.12.4   ARH/ARD 090 Cooling capacities..........................................................................................21
1.12.5   ARH/ARD 045 Thermodynamic heat capacity.......................................................................21
1.12.6   ARH/ARD 060 Thermodynamic heat capacity.......................................................................22
1.12.7   ARH/ARD 075 Thermodynamic heat capacity.......................................................................22
1.12.8   ARH/ARD 090 Thermodynamic heat capacity.......................................................................23
1.13     Indoor fan...............................................................................................................................23
1.13.1   Features table........................................................................................................................23
1.13.2   Considerations when consulting the output tables.................................................................23
1.13.3   Output table for indoor fan, model ARC-045, applications with side ducts, standard drive motor
         3 kW.......................................................................................................................................24
1.13.4   Output table for indoor fan, model ARC-045, applications with side ducts, optional HPD drive
         motor 4 kW.............................................................................................................................24
1.13.5   Output table for indoor fan, model ARC-060, applications with side ducts, standard drive motor
         4 kW.......................................................................................................................................25

                                                                                                                                                     i
Index


1.13.6  Output table for indoor fan, model ARC-060, applications with side ducts, optional HPD drive
        motor 5.5 kW..........................................................................................................................25
1.13.7 Output table for indoor fan, model ARC-075, applications with side ducts, standard drive motor
        5.5 kW....................................................................................................................................25
1.13.8 Output table for indoor fan, model ARC/ARH-075, applications with side ducts, optional HPD
        drive motor 7.5 kW.................................................................................................................26
1.13.9 Output table for indoor fan, model ARC/ARH-090, applications with side ducts, standard drive
        motor 7.5 kW..........................................................................................................................26
1.13.10 Output table for indoor fan, model ARC/ARH-090, applications with side ducts, optional HPD
        drive motor 11 kW..................................................................................................................26
1.14    Pressure drop of options/accessories, gas heating and vertical ducts..................................27
1.15    Instructions for installation and connection of the unit...........................................................27
1.15.1 Characteristics of the location................................................................................................27
1.15.2 Characteristics of the facility where the unit will be installed..................................................28
1.15.3 Specifications for the foundation or anchoring of the unit......................................................28
1.15.4 Installation on shock absorbers..............................................................................................29
1.15.5 Characteristics of utility provider connections........................................................................29
1.15.6 Connection and preparation of the various connections........................................................30
1.16    Instructions for starting up the unit.........................................................................................35
1.16.1 Electrical checks.....................................................................................................................35
1.16.2 Starting the gas heating, ARG/ARD.......................................................................................35
1.17    Unblocking the unit safely in case of breakdown...................................................................39
1.18    Regular maintenance tasks performed by specialised personnel..........................................39
1.18.1 Planned Maintenance Schedule.............................................................................................40
1.18.2 Maintenance tasks performed by specialised personnel........................................................40
1.18.3 Gas heating (ARG/ARD Models)............................................................................................43
1.19    Unit sound pressure data.......................................................................................................45

2            Unit installation data...............................................................................................................46

2.1          List of tests for unit start-up....................................................................................................47
2.2          Start-up data..........................................................................................................................48

3            Cooling diagrams...................................................................................................................52

3.1          ARC/ARG 045/060 Cooling diagrams....................................................................................53
3.2          ARC/ARG 075 Cooling diagrams...........................................................................................54
3.3          ARC/ARG 090 Cooling diagrams...........................................................................................55
3.4          ARH/ARD 045/060 Cooling diagrams....................................................................................56
3.5          ARH/ARD 075 Cooling diagrams...........................................................................................57
3.6          ARH/ARD 090 Cooling diagrams...........................................................................................58

4            Wiring diagrams ....................................................................................................................59

4.1          Micro switch configuration......................................................................................................60
4.2          Fault table..............................................................................................................................61
4.3          Incidents.................................................................................................................................62
4.3.1        Test button.............................................................................................................................63
4.4          DPC-1 thermostat..................................................................................................................63
4.5          Unit wiring diagrams...............................................................................................................64


ii
        1
Installation manual
1        Installation manual
1.1      Safety instructions


1.1 Safety instructions
This document contains the necessary information for the safe and efficient transportation, assembly
and installation of the air conditioning unit. This guarantees the condition of the unit and its operating
safety.
Only an authorised company may assemble the air conditioning unit.


        ATTENTION
Only authorised companies with the appropriate technical resources and suitably trained personnel may
install the air conditioning unit.

       CAUTION
The specialists responsible for installing the air conditioning unit must make sure they have all of the
information and knowledge required to correctly install, test and deliver the unit. Johnson Controls Inc.
shall not be considered responsible for any damage caused by installation of the unit that is no consistent
with that described in this document or others specifically provided with the unit.
During regular equipment installation, the fitter must pay special attention to certain situations in order
to prevent injuries or damage to the unit.
Situations that could jeopardise the safety of the fitter or that of others nearby or that could put the unit
itself at risk are clearly indicated in this manual.
A series of special symbols are used to clearly identify these situations.
Pay careful attention to these symbols and to the messages following them, as your safety and the safety
of others depends on it.


1.2 Icons used in this document

         DANGER
•     The text following this symbol contains information and instructions relating directly to your safety
      and physical wellbeing.
•     Not taking these instructions into account could lead to serious, very serious or even fatal injuries to
      you and others in the proximities of the unit.

Information can also be found on safe procedures during unit handling. This will help reduce the risk of
accidents.


         CAUTION
•     The text following this symbol contains information and instructions relating directly to your safety
      and physical wellbeing.
•     Not taking these instructions into account could lead to minor injuries to you and others in the
      proximities of the unit.
•     Not taking these instructions into account could lead to unit damage.

Information can also be found on safe procedures during unit handling. This will help reduce the risk of
accidents.


         NOTE
•     The text following this symbol contains information or instructions that may be of use or that is worthy
      of a more thorough explanation.
•     Instructions regarding inspections to be made on unit parts or systems may also be included.




2
                                                                                   Installation manual      1
                                           Instructions for storage, transport and handling of the unit   1.3


1.3 Instructions for storage, transport and handling of the unit
Delivery inspection
The unit should be carefully inspected for visible damage or abnormalities as soon as it is received.
Any abnormalities or damage to the unit should be communicated to both the transportation and
insurance company in writing.

Storage instructions
The unit should be stored in a place suitable to the purpose (warehouse or similar), protected from the
weather, water, humidity and dust.
Cover the unit with a canvas of a suitable size.
The unit should be appropriately protected from knocks and dust, ensuring the protective parts it was
supplied with remain in place. Where these are not in place, establish the necessary protections and/or
barriers to keep vehicles or fork-lift trucks away.

Transport and handling of the unit
The units should only be handled by personnel from the company responsible for their installation.
Transport of the unit should be in such a manner that no damage is caused by faulty or inadequate
mooring to the bed or body of the vehicle.
Where necessary, protect all of the edges of the unit against knocks and scratches and moor it to the
bed or body of the vehicle using suitable textile belts or slings to keep it perfectly still.
Loading and unloading the unit from a truck or trailer should be on flat, solid ground using an appropriate
crane with sufficient capacity.


         CAUTION
It is strictly prohibited to use fork lifts to load, unload, or handle the unit.

1.3.1 Disposal of packaging
The packaging is recyclable. Dispose of it in the appropriate place or take it to an appropriate collection
centre. Respect the regulations in force for this type of waste in the country where the unit is being
installed.
Packaging remains must be correctly disposed of. Improper disposal of packaging generates
environmental problems that affect human life.

1.3.2 Hoisting points
The points designed for hoisting the unit are located
on the beams on its base -arrows-.
Before hoisting the unit, check that the cables or
slings are firmly hooked to these points and make
sure the crane and the cables or slings are capable of
lifting the weight.




                                                                                                           3
1     Installation manual
1.3   Instructions for storage, transport and handling of the unit


Place spacers -1- at the top of the unit to prevent the
cables or slings from touching it.
                                                                                             1
Attach guide ropes so that the unit does not rotate
freely.
The cables or slings should be long enough to form
an angle of over 45º to the horizontal plane. Hoist the
unit keeping it in a horizontal position.


       DANGER
There should not be onlookers within a radius of 10
m of the unit when it is being hoisted.


Centre of gravity of the unit

    Models       045         060     075       090
      A         1180         1180   1135      1080
      B         1390         1425   1480      1540                           1       2
      C         3180         3180   3495      3495
      D         2337         2337   2337      2337                                       B
                                                                     D
                                                                         A       C
All measurements in mm.

1. Centre of gravity
2. End of the outdoor coil




4
                                                                                                               Installation manual                     1
                                                                                                                   Technical data                    1.4


1.4 Technical data
1.4.1 Technical and physical data for ARC (only cooling) and ARG (only
cooling + gas heating)
Models                                                               ARC/ARG        045               060                   075               090
                         Net cooling capacity                               kW      45.1                61                 71.5                84
Cooling capacity (1)
                         Rated absorbed power in cool mode                  kW       16                 23                  30                 36
                         Optional electric heater, heating capaci‐
Heating (ARC)                                                               kW                                12-25-37-50
                         ty (400 V) (2)
                                                                     (LHV) Total
                                                                                                                  85
                         Heat capacity at 100% power (standard)             kW
                                                                     Net (2) kW                                   76

                         Heat capacity at 100% power, high ca‐         Total kW                                  100
                         pacity (optional)                           Net (2) kW                                   90
Gas Heating (ARG)        100% gas consumption (2ND-H natural
                         gas, G20 at 20 mbar and 15 °C) (stand‐            m3/h                                   8.6
                         ard)
                         100% gas consumption (2ND-H natural
                         gas, G20 at 20 mbar and 15ºC) high ca‐            m3/h                                   9.8
                         pacity (optional)
                         Stages                                             No.                                   2
                         Rated/start-up current                                A   2x12/95          2x15/118            2x20/140           2x25/198
Compressors              Type and quantity                                                    SCROLL, 1 (TANDEM 50% + 50%)
                         Degree of protection                                                                    IP21
Coolant (R-410A)                                                             kg     10.5              18.2                 20.5                29
Power supply                                                            V/ph/Hz                               400/3+N/50
                         Rated air flow                                    m3/h     8500             11500               13500              16000
                         Maximum static pressure with rated flow
                                                                             Pa     182               270                   240               368
                         (standard)
                         Maximum static pressure with rated flow
                                                                             Pa     368               430                >500                >500
                         (optional HPD drive)
                         Maximum flow rate                                 m3/h    10000             13500               16000              18000
Indoor fan (3)
                         Minimum flow rate                                 m3/h     7000             9500                11500              13000
                         IP55 motor (standard)                              kW       3                  4                   5.5                7.5
                         Rated current                                         A     5.5                5.7                 7.6              11.7
                         IP55 Motor (HPD optional)                          kW       4                  5.5                 7.5                11
                         Rated current                                         A     5.7                7.6                11.7             14/17.4
                         Number of elements                                 No.      2                  3                    3                 4
Indoor coil (evaporator) Distance between fins                              mm      1.81              1.81                 1.81              1.81
                         Front surface                                       m2     1.44              1.58                 1.95            1.06 (x 2)
                         Quantity per unit                                  No.                6                                      6
Air filters (G4)
                         Dimensions                                         mm             470x550x48                             565x594x48
                         Diameter/number                                    mm      800/1            800/2               800/2               800/2
                         Total rated flow                                  m3/h    15000             23000               27000              27000
Outdoor fan
                         Motor (IP54)                                       kW       1.9                1.9                 1.9                1.9
                         Rated current                                         A     3.5             2x3.5               2x3.5               2x3.5
                         Number of elements                                 No.      2                  3                    2                 3
Outdoor coil (condens‐
                         Distance between fins                              mm      1.81              1.81                 1.81              1.81
er)
                         Front area                                          m2     2.27              2.49              2.31 (x2)          2.31 (x2)
                         Height                                             mm               1316                                   1367
Net dimensions (4)       Length                                             mm               3180                                   3495
                         Width                                              mm               2337                                   2337

Net weight (basic unit   ARC                                                 kg     900               945                1118                1142
without accessories) (4) ARG                                                 kg     1010             1055                1228                1252




                                                                                                                                                        5
1        Installation manual
1.4      Technical data

Models                                                                           ARC/ARG               045                060                075                090
                               Total rated power                                           kW           16                 23                 30                 36
                               Total rated current                                           A          32                 42                 54                 70

Electrical features of         Total maximum power                                         kW           23                 31                 38                 45
the unit                       Total maximum current                                         A          42                 56                 70                 83
                               Circuit breaker (K curve) (5)                                 A          50                 63                 80                100
                               Minimum cable section (6)                                 mm2            10                 16                 25                 35



(1) Data in accordance with Eurovent conditions, summer: indoor 27 °C DBT / 19 °C WBT ‑ outdoor DBT 35 °C. (DBT Dry-bulb temperature; WBT Wet-bulb temperature).
(2) Add the inside motor consumption to find the total calorific capacity.
(3) See Indoor fan, see on page 23.
(4) Consider the additional weight of options and accessories. To do so, see Weight options and accessories, see on page 8.
LHV: Lower heating value.
(5) and (6) Circuit breaker with K curve, according to DIN, VDE 0660-104. Cable section for the power supply line based on copper conductors, 105 °C. The indicated circuit
breaker and the section of power supply cables are guidelines. They should be adjusted based on the requirements of each installation, distance between units, fall in
planned voltage and on the application of the current regulations with respect to the country where the unit is being installed.




6
                                                                                                          Installation manual                    1
                                                                                                              Technical data                   1.4


1.4.2 ARH technical and physical data (heat pump) and ARD (heat pump
+ gas heating)
Models                                                        ARH/ARD          045                 060                075               090
                           Net cooling capacity                         kW     47.6                61.9               71.4             83.4
Cooling capacity (1)       Rated absorbed power in cool
                                                                        kW      17                 20                  28                36
                           mode
                           Heat capacity (2)                            kW     45.2                58                 71.7             86.5
                           Rated power absorbed in heat
                                                                        kW      16                 19                  27                33
Heat capacity              mode
                           Optional electric heater, heat‐
                                                                        kW                              12-25-37-50
                           ing capacity (400 V) (ARH) (2)

                           Heat capacity at 100% power       (LHV) Total kW                                 85
                           (standard)                            Net (2) kW                                 76

                           Heat capacity at 100% power,           Total kW                                 100
                           high capacity (optional)              Net (2) kW                                 90
                           100% gas consumption (2ND-
Gas Heating (ARG)          H natural gas, G20 at 20 mbar              m3/h                                  8.6
                           and 15 °C) (standard)
                           100% gas consumption (2ND-
                           H natural gas, G20 at 20 mbar
                                                                      m3/h                                  9.8
                           and 15ºC) high capacity (op‐
                           tional)
                           Stages                                       No.                                 2
                           Rated/start-up current                        A    2x12/95          2x15/118           2x20/140           2x25/198
Compressors                Type and quantity                                            SCROLL, 1 (TANDEM 50 % + 50 %)
                           Degree of protection                                                            IP21
Coolant
                                                                        kg     14.5                19                 20.5               29
(R-410A)
Power supply                                                       V/ph/Hz                              400/3+N/50
                           Rated air flow                             m3/h     8500             11500                 13500           16000
                           Maximum static pressure with
                                                                        Pa     168                 242                 240              368
                           rated flow (standard drive)
                           Maximum static pressure with
                                                                        Pa     335                 402                >500             >500
                           rated flow (optional HPD drive)
                           Maximum flow rate                          m3/h    10000             13500                 16000           18000
Indoor fan (3)
                           Minimum flow rate                          m3/h     7000             9500                  11500           13000
                           IP55 motor (standard)                        kW      3                   4                  5.5               7.5
                           Rated current                                 A      5.5                5.7                 7.6             11.7
                           IP55 Motor (HPD optional)                    kW      4                  5.5                 7.5               11
                           Rated current                                 A      5.7                7.6                11.7            14/17.4
                           Number of elements                           No.     3                   4                   3                4
Indoor coil (evaporator)   Distance between fins                       mm      2.11                2.11               1.81             1.81
                           Front surface                                m2     1.44                1.58               1.95           1.06 (x 2)
                           Quantity per unit                            No.               6                                     6
Air filters (G4)
                           Dimensions                                  mm             470x550x48                            565x594x48
                           Diameter/number                             mm      800/1            800/2                 800/2            800/2
                           Total rated flow                           m3/h    15000             23000                 27000           27000
Outdoor fan
                           Motor (IP54)                                 kW      1.9                1.9                 1.9               1.9
                           Rated current                                 A      3.5             2x3.5                 2x3.5            2x3.5
                           Number of elements                           No.     3                   4                   2                3
Outdoor coil (condenser)   Distance between fins                       mm      2.11                2.54               1.81             1.81
                           Front area                                   m2     2.27                2.49           2.31 (x2)          2.31 (x2)
                           Height                                      mm               1316                                  1367
Net dimensions (4)         Length                                      mm               3180                                  3495
                           Width                                       mm               2337                                  2337

Net weight (basic unit with‐ ARH                                        kg     930                 985                1145             1220
out accessories) (4)         ARD                                        kg     1040             1095                  1255             1330




                                                                                                                                                  7
1        Installation manual
1.5      ARC units with auxiliary heating element

Models                                                                       ARH/ARD                    045                   060               075               090
                                   Total rated power                                      kW             17                   22                   28                36
                                   Total rated current                                        A          32                   42                   54                70

Electrical features of the         Total maximum power                                    kW             23                   31                   38                45
unit                               Total maximum current                                      A          42                   56                   70                83
                                   Circuit breaker (K curve) (5)                              A          50                   63                   80             100
                                   Minimum cable section (6)                             mm2             10                   16                   25                35



(1) Data in accordance with Eurovent conditions, summer: indoor 27 °C DBT / 19 °C WBT ‑ outdoor DBT 35 °C. Winter: Indoor DBT 20 °C, outdoor DBT 7 °C/WBT 6 °C
(DBT Dry-bulb temperature; WBT Wet-bulb temperature).
(2) Add the inside motor consumption to find the total calorific capacity.
(3) See Indoor fan, see on page 23
(4) Consider the additional weight of options and accessories. To do so, see Weight options and accessories, see on page 8.
LHV: Lower heating value.
(5) and (6) Circuit breaker with K curve, according to DIN, VDE 0660-104. Cable section for the power supply line based on copper conductors, 105 °C. The indicated circuit
breaker and the section of power supply cables are guidelines. They should be adjusted based on the requirements of each installation, distance between units, fall in
planned voltage and on the application of the current regulations with respect to the country where the unit is being installed.




1.4.3 Weight options and accessories
Models                                                                                             045                 060                    075                 090
Economiser                                                                               kg         65                  65                    73                  73
Exhaust fan (axial)                                                                      kg         54                  54                    63                  63
Return fan (centrifuge)                                                                  kg
Roof-curb mounting base (fixed/adjustable)                                               kg       81/157             81/157                  85/165             85/165
ERP adaptor for Roof Curb                                                                kg        177                 177                    190                 190
Heating element                                                                          kg         20                  20                    20                  20
Hot water coil                                                                           kg         60                  60                    60                  60
Fixed outdoor air intake                                                                 kg         9                     9                    9                     9
Barometric damper                                                                        kg         20                  20                    20                  20
                                                                                   indoor           19                  31                    44                  64
                                                            ARC/ARG
                                                                                 outdoor            30                  49                    70                  104
                  Copper fin coil
                                                                                   indoor           29                  48                    44                  64
                                                            ARH/ARD
                                                                                 outdoor            44                  64                    70                  104




1.5 ARC units with auxiliary heating element
                                                              Heating element
                                                                                                  Maximum total current          Maximum circuit        Minimum cable cross-
    ARC Model     Power supply V/Ph/Hz       Power
                                                          Stages (No.)          Current (A)          of the unit (A)           breaker (K Curve) (1)      section (mm2) (2)
                                              (kW)
                                               12               1                   18                        32                        50                      10
                                               25               2                   36                        38                        50                      10
       045                400/3/50
                                               37               2                   54                        60                        80                      25
                                               50               2                   72                        78                       100                      35
                                               12               1                   18                        42                        50                      10
                                               25               2                   36                        42                        50                      10
       060                400/3/50
                                               37               2                   54                        60                        80                      25
                                               50               2                   72                        78                       100                      35
                                               12               1                   18                        54                        63                      16
                                               25               2                   36                        54                        63                      16
       075                400/3/50
                                               37               2                   54                        62                        80                      25
                                               50               2                   72                        80                       100                      35
                                               12               1                   18                        70                        80                      25
                                               25               2                   36                        70                        80                      25
       090                400/3/50
                                               37               2                   54                        70                        80                      25
                                               50               2                   72                        84                       100                      35




8
                                                                                                                   Installation manual                                    1
                                                                                             ARH units with auxiliary heating element                                   1.6


(1) K Curve (DIN, VDE 0660-104).
(2) Based on copper conductors 105 °C.




1.6 ARH units with auxiliary heating element
                                                             Heating element
                                                                                                 Maximum total current      Maximum circuit          Minimum cable cross-
 ARC Model        Power supply V/Ph/Hz     Power
                                                        Stages (No.)           Current (A)          of the unit (A)       breaker (K Curve) (1)        section (mm2) (2)
                                            (kW)
                                             12               1                    18                     50                       63                        16
                                             25               2                    36                     68                       80                        25
      045                400/3/50
                                             37               2                    54                     86                      100                        35
                                             50               2                    72                    104                      125                        50
                                             12               1                    18                     60                       80                        25
                                             25               2                    36                     78                      100                        35
      060                400/3/50
                                             37               2                    54                     96                      125                        50
                                             50               2                    72                    114                      125                        50
                                             12               1                    18                     72                       80                        25
                                             25               2                    36                     90                      100                        35
      075                400/3/50
                                             37               2                    54                    108                      125                        50
                                             50               2                    72                    126                      160                        70
                                             12               1                    18                     88                      100                        35
                                             25               2                    36                    106                      125                        50
      090                400/3/50
                                             37               2                    54                    124                      160                        70
                                             50               2                    72                    142                      160                        70




(1) K Curve (DIN, VDE 0660-104).
(2) Based on copper conductors 105 °C.




1.7 Limits of use
Model                                                                                                    045              060                075                  090
Voltage limits                                                                    Min./Max V                                      360/440
                                                                               WB °C Min./Max.          15/23            15/23              15/23              15/23
                                 Temperature of air inlet in indoor coil
                                                                                DB °C Min/Max           20/32            20/32              20/32              20/32
                                 Outdoor temperature (without condensa‐
                                                                                  TS °C Min.              7                 7                 7                    7
                                 tion control)
            ARC/ARG
                                                                  At full
                                                                                     TS °C                46               46                46                   46
                                 Maximum outdoor tempera‐         load
                                 ture (1)                         At partial
                                                                                     TS °C                52               52                52                   52
                                                                  load
                                                                               WB °C Min./Max.          15/23            15/23              15/23              14/23
                                 Temperature of air inlet in indoor coil
                                                                                DB °C Min/Max           20/32            20/32              20/32              20/32
                                 Outdoor temperature (without condensa‐
                                                                                  TS °C Min.              7                 7                 7                    7
                                 tion control)
                 Summer cycle
                                                                  At full
 ARH/ARD                                                                             TS °C                46               46                46                   46
                                 Maximum outdoor tempera‐         load
                                 ture (1)                         At partial
                                                                                     TS °C                52               52                52                   52
                                                                  load
                                 Temperature of air inlet in indoor coil        DB °C Min/Max           10/25            10/25              10/25              10/25
                  Winter cycle
                                 Outdoor temperature                            DB °C Min/Max           -10/20           -10/20             -10/20             -10/20
                                 Indoor temperature                               TS °C Max               30               30                30                   30
ARG/ARD (2)      Gas heating
                                 Outdoor temperature                            DB °C Min/Max           -15/25           -15/25             -15/25             -15/25




1. Direct sunlight on the unit should be prevented when temperatures are higher than 43ºC. If placed under some kind of protective cover, the cover should not interfere
with the flow of outdoor ventilation.
2. The gas heating units (ARG/ARD) are only appropriate for use with gas. In LPG (Liquefied Petroleum Gas, propane) installations, it must be ensured that in no case
should gasoline in liquid form reach the gas group.
DB: Dry-bulb Thermometer; TH: Wet-bulb thermometer.




                                                                                                                                                                         9
1         Installation manual
1.8       Capacities and application data for gas ARG/ARD


1.8 Capacities and application data for gas ARG/ARD
                                                          Heat capacity                                         Gas consumption m3/h
                                                                                                                                                        Temperature rise in ºC at full
                                                                                                                                        L.P.G. pro‐             power (4)
                               Total (LHV) (1) kW                             Net kW                       Natural gas (2)
       Model                                                                                                                            pane (3)
                                                                                                                                        Optional (on‐
                           Standard             High power         Standard        High power          Standard        High power                           Min.            Max.
                                                                                                                                        ly standard)
         045                  85                   100                   76             90               8,6              9,8               3,6              17              33
         060                  85                   100                   76             90               8,6              9,8               3,6              17              33
         075                  85                   100                   76             90               8,6              9,8               3,6              17              33
         090                  85                   100                   76             90               8,6              9,8               3,6              17              33




(1) LHV: Lower heating value.
(2) Natural gas 2ND-H, G20, at 20 mbar and 15 ºC
(3) Propane gas, G31, at 37 mbar and 15 ºC.
(4) The air flow should be regulated so as to increase temperature within the specified limits. Units with optional high power burners should have a minimum air flow of
10000 m3/h.
Note: The gas units are shipped ready to operate with natural gas. A conversion kit can be used to convert them to propane gas (L.P.G.).




1.9 Hot water coil, optional in ARC/ARH
                                                                                                 Data with water, without glycol
                                                                                                                                                  090
                 ARC/ARH                                                                                                        075
                                                                                                060
                                                                    045
Water temperature                          °C                                                                  90 ÷ 70
Air flow rate                              m3       7000           8500         10000        11500             13500            15000          16000         17000          18000
Heat capacity                              kW       71,1            79,5         87,0           93,7           101,7            107,3             111         114,2          117,4
Water flow rate                       m3/h           3              3,3           3,7            4               4,3             4,5              4,7          4,8             5
Pressure drop                          kPa           9,5             11           14            16               19              21               22           23             25
Air temperature rise                        K        30              27           25            24               22              21               20           19             18
Water temperature                          °C                                                                  80 ÷ 60
Air flow rate                              m3       7000           8500         10000        11500             13500            15000          16000         17000          18000
Heat capacity                              kW       58,6            65,4         71,5           77              83,5            88,1            90,8          93,7           96,3
Water flow rate                       m3/h           2,5            2,8           3             3,3              3,5             3,7              3,9             4           4,1
Pressure drop                          kPa           7,5             9            9,5           11               13              14               16           16             18
Air temperature rise                        K        24              22           21            20               18              17               17           16             15
Water temperature                          °C                                                                  70 ÷ 50
Air flow rate                              m3       7000           8500         10000        11500             13500            15000          16000         17000          18000
Heat capacity                              kW       46,0            51,2         55,8           61,1            65,1            68,7              71           73             75
Water flow rate                       m3/h           1,9            2,2           2,4           2,6              2,8             2,9               3           3,1            3,2
Pressure drop                          kPa           4,5             6            6,5           7,5               9              9,5            10,5           11             11
Air temperature rise                        K        19              18           16            15               14              13               13           12             12




- Pressure drop of coil + 3-way valve.
- Coil air inlet: 18 °C.
- Total volume of water in circuit 10 l.
- See air pressure drop, Pressure drop of options/accessories, gas heating and vertical ducts., see on page 27.




10
                                                                                                                    Installation manual                1
                                                                                                  Hot water coil, optional in ARC/ARH                1.9


                                                                                     Data with a mix of water and 35% glycol
                                                                                                                               090
                 ARC/ARH                                                                                            075
                                                                                         060
                                                             045
Water temperature                          °C                                                        90 ÷ 70
Air flow rate                              m3   7000        8500          10000         11500         13500        15000       16000   17000   18000
Heat capacity                              kW   68,5        76,3           83,6          89,8          97,5        102,8       106,3   109,4   112,4
Water flow rate                       m3/h      3,2          3,6            4            4,2            4,6         4,8          5      5,1     5,3
Pressure drop                          kPa       12          15            17             20            23           25         27      28      30
Air temperature rise                        K    28          26            24             22            21           20         19      18      17
Water temperature                          °C                                                        80 ÷ 60
Air flow rate                              m3   7000        8500          10000         11500         13500        15000       16000   17000   18000
Heat capacity                              kW   55,6         62            67,7          72,8           79          83,3       85,9    88,5     91
Water flow rate                       m3/h      2,6          2,9           3,2           3,5            3,7          4          4,1     4,2     4,3
Pressure drop                          kPa       9           10            12             14            16           18         19      20      21
Air temperature rise                        K    23          21            20             18            17           16         16      15      14
Water temperature                          °C                                                        70 ÷ 50
Air flow rate                              m3   7000        8500          10000         11500         13500        15000       16000   1700    18000
Heat capacity     