| Вид документа | Каталог технічних даних |
|---|---|
| Виробник | ETI |
| Код документа | 2781_TD |
| Група обладнання | LV Держатели предохранителей |
| Сторінок | 57 |
| Мова документа | англійська |
| Розмір файлу | 5.5 МБ |
Текст документа
Special Purpose Fuses
Multimeter and metering fuses 5
DC fuses, fuse bases and disconnectors 9
Mining fuses 20
Non standard higher voltage gG fuses and disconnectors 30
Safe Work Fuses 34
Power Capacitor Fuses 35
Fuses for TVSS products protection 37
Fuses for railway applications 39
Fuel Cell Protection Fuses 49
Minifuses 50
PROTECTION OF SPECIAL APPLICATIONS
POWER NEEDS CONTROL
Contents
MULTIMETER Fuse Links
CH gR SE (SPECIAL EDITION)
Fuse-link gG NV/NH 400V a.c. metering
Fuse-link gTr NV/NH 400V a.c. metering
DC fuses:
NH DC 80 V - Telecom fuse
NH DC 250 V
NH DC 440 V
NH DC 1000 V aR
NH DC 1100 V aR
NV Telecom fuse disconnectors
Fuse base PK00 1000V a.c./d.c. M8-M8
Fuse base PK1,2,3-100mm
Fuse base PK1L
Mining fuses:
Special Purpose Fuses
Fuse-link aM NV/NH 1000V a.c.
Fuse-link aM NV/NH 1000V a.c.
Fuse-link gB NV/NH 00 1000V a.c.
Fuse-link gB NV/NH 01L 1000V a.c.
Non standard higher voltage gG fuses:
Fuse-link gG NV/NH 1000 V a.c.
Fuse-link gG NV/NH 1200 V a.c.
Safe work fuses
NH Power capacitor fuse
Fuses for TVSS products protection:
CH SRF class II
CH SRF 25kA class I
CH SRF class II - DC
Fuses for railway applications:
NH1S/394/DC 4000V aR-fuse link
NH2 S/394/ DC 4000V aR - fuse link
NH1/350/DC 4000V aR-fuse link
NH1/130/DC 1000V gR - fuse link
Fuses for high-voltage switchgear
Fuses for protection of forklift batteries TRB
Fuel Cell Protection Fuses
Minifuses
4
MULTIMETER Fuse Links
General characteristics
Rated voltage 1000V a.c./d.c.
Breaking capacity 30kA a.c./d.c.
Characteristics gR
Standards IEC 60269-4, UL 248-1,UL 248-13
Application Multimeter fused
CH10 MULTI
Code No. Power
In Packaging Weight
Size standard dissipation
[A] [pcs] [g]
indicator [W]
0,5 002625410
1 002625411
2 002625400 0,9
4 002625401 1,2
6 002625402 1,6
10x38 10/500 10
8 002625403 1,8
10 002625404 2,1
12 002625405 1,7
16 002625406 2,3
20 002625407 3,15
Special Purpose Fuses
2
10
4 FUSED
6
t v/s 4
10A 16A
2 2A 4A 6A 8A 12A 20A
3
10
6
4
2
2
10
6
4
2
1
10
6
4
2
0
10
6
4
2
-1
10
6
4
2
-2
10
6
4 0 1 2 3
10 2 4 6 10 2 4 6 10 2 4 6 10
I p/A
5
CH gR SE (SPECIAL EDITION)
General characteristics
Rated voltage 690V a.c.
Breaking capacity 100kA AC
Characteristic gR, according to IEC 60269-4
Fuses are fast acting, full range. Used in protection of the inverters, variable
Application speed drives. Excellent cycling load capability (70 000 current cycling test).
CH 10x38gR SE 690V
Pre-arcing Operating Power Power
Code Number Code Number
In Joule integral Joule integral dissipation dissipation Packaging Weight
Size “standard “type SU
[A] [A2s] [A2s] [0,8 x In] [1x In] [pcs] [g]
contacts” contacts”
L/R=10ms L/R=10ms Pd [W] Pd [W]
16 002625046 002625048 32 166 1,6 2,8 10/500
10x38 10/12
20 002625047 002625049 80 340 1,7 2,9 SU:10/380
Special Purpose Fuses
Simulating current of motor start
70.000 current cycle test at Tamb = 700C
IN = 6,5A
Max. permissible motor rated current
Standard
Contacts
Type SU
Contacts
6
Fuse Link gG NV/NH 400V a.c. metering
General characteristics
Rated voltage 400V a.c.
Breaking capacity 50kA a.c.
Standards IEC 60269-1, IEC 60269-2
Characteristic gG
As metering fuse with strip fuse switch disconnector and fuse switch
Application disconnector
NV/NH 400V a.c.
standard Power
In Packaging Weight
Size indicator dissipation
[A] [pcs] [g]
[W]
80 004113835 5,2
100 004113836 6,2
125 004113837 7,9
1 1/26 500
160 004113838 9
200 004113839 12
250 004113840 17
80 004113842 5,2
100 004113843 6,2
125 004113844 7,9
160 004113845 9
2 1/16 600
200 004113846 12
Special Purpose Fuses
250 004113847 17
315 004113848 20
400 004113849 24
200 004113851 12
250 004113852 17
315 004113853 20
3 1/9 1000
400 004113854 24
500 004113855 27
630 004113856 32
630 004113858 51
800 004113859 61
4a 1 2000
1000 004113860 72
1250 004113861 90
Amperemeter not included
7
Fuse Link gTr NV/NH 400V a.c. metering
General characteristics
Rated voltage 400V a.c.
Breaking capacity 25kA a.c.
Standards IEC 60269-1, IEC 60269-2, DIN VDE 0636-21 (VDE 0636-21) 2015-03
Characteristic gTr
As metering fuse with strip fuse switch disconnector and fuse switch
Aplication disconnector
NV/NH 400V a.c.
Nominal
standard Power
transformer In Packaging Weight
Size indicator dissipation
power [A] [pcs] [g]
[W]
[kVA]
100 144 004113865 11
1 125 180 004113866 13 1/26 500
160 231 004113867 17
100 144 004113872 11
125 180 004113873 13
2 160 231 004113874 17 1/16 600
200 289 004113875 20
250 361 004113876 25
125 180 004113881 13
160 231 004113882 17
Special Purpose Fuses
200 289 004113883 20
3 1/9 1000
250 361 004113884 25
315 455 004113885 32
400 577 004113886 40
250 361 004113890 25
315 455 004113891 32
400 577 004113892 40
4a 500 722 004113893 54 1 2000
630 909 004113894 71
800 1155 004113895 91
1000 1443 004113896 110
Size dimensions [mm]
a1 b1 c1 e1 G H a2 a4
1 135 24 40 52 67 112 75 65
2 150 30 48 60 74 119 75 65
3 150 32 60 74 89 134 75 65
4a 200 50 85 96 127 200 100 87
8
Telecom Fuses
FUSES FOR DC (Direct Current) APPLICATIONS -
ETI solution for TELECOM Power Supply Circuits
ETI d.d. developed specially designed fuse-Iinks for short circuit protection of d.c. telecom power supplies. They are typically
installed into rectifier outputs, battery feeders or d.c.power distribution for protection of the load circuits.
All their characteristics are optimized to correspond to the operating conditions of telecom power supply equipment. Power
dissipations and switching voltage provide optimal function and protection of telecom power supplies. The ETI TELECOM
NH00 fuse-Iink is a high breaking capacity current Iimiting fuse-Iink with pure silver, age-resistant melting element.
NH DC 80 V - Telecom fuse
General characteristics
Rated voltage 80 V d.c. (L/R = 20 ms)
Breaking capacity 25 kA d.c.
Standards IEC 60269-1
Fuse-link for battery and UPS protection. For installation in NV Telecom fuse
Application disconnector.
NH DC 80 V - Telecom fuse
Special Purpose Fuses
Code No. Power
In Packaging Weight
Size standard striker dissipation
[A] [pcs] [g]
indicator indicator [W]
160 004110106 004110101 9,0
200 004110120 004110119 10,5
250 004110107 004110102 12,5
00 400 004110108 004110103 17,5
3/90 173
630 004110109 004110104 28,0
800 004110110 004110105 37,5
Time-current characteristics
6
4
Pre-arcing time [s] tv/s
2 250 A 630 A
160 A 400 A 800 A
10 4
6
4
2
10 3
6 86,5 53 47
4
2
10 2
6
4
2
10 1
6
4
2
35
10 0
6 12 15
4
2
10 -1
6 28 6 9,8
4
2
10 -2
2 3 4 56
10 2 4 6 10 2 4 6 10 2
Prospective current [A] Ip/A
9
NH DC 250 V
General characteristics
Rated voltage 250 V d.c. (L/R = 20 ms)
Breaking capacity 25 kA d.c.
Standards IEC 60269-1
Application Fuse-link for DC application. For installation in NV Telecom fuse disconnector.
NH DC 250 V
Code No. Power
In standard striker dissipation Packaging Weight
Size [A] indicator indicator [W] [pcs] [g]
63 004110130 004110135 7,5
100 004110131 004110136 8,6
160 004110132 004110137 13,8
00 200 004110140 004110141 18,5
3 654
250 004110133 004110138 21,2
315 004110134 004110139 24,0
47 9,8
Special Purpose Fuses
35 56
15
12
53 6
86,5 28
10
NH DC 440 V
General characteristics Patented
technology
Rated voltage 440 V d.c. (L/R = 20 ms) by
Breaking capacity 50 kA d.c.
Standards IEC 60269-1
Application Fuse-link for DC application. Installation in PK or PT fuse bases.
NH DC 440 V
Power Pre-arcing Operating
In dissipation Joule integral Joule integral Packaging Weight
Size [A] Code No. [W] (I2t) (I2t) [pcs] [g]
20 004110200 5,3 360 648
25 004110201 6,4 710 1.278
00C 32 004110202 7,6 920 1.656 3/120 125
40 004110203 9,4 1.440 2.592
50 004110204 11,3 2.820 5.076
63 004110210 11,9 4.160 7.488
80 004110211 10,6 4.670 8.406
00 100 004110212 12,2 9.360 16.848 3/90 173
125 004110213 15,3 14.750 26.550
160 004110214 17,1 27.880 50.184
20 004110220 6,1 360 648
25 004110221 7,9 710 1.278
32 004110222 8,9 920 1.656
Special Purpose Fuses
40 004110223 12,0 1.440 2.592
50 004110224 14,8 2.820 5.076
1C 63 004110225 16,0 4.160 7.488
3/45 233
80 004110226 11,7 4.670 8.406
100 004110227 13,0 9.360 16.848
125 004110228 15,5 14.750 26.550
160 004110229 17,1 27.880 50.184
200 004110230 27,5 41.990 75.582
1 250 004110231 31,5 81.000 145.800
3/24 430
C 9,8
D G
E
H
B K
A F
type dimensions [mm]
A B C D E F G H K
00 C 79 53 47 35 15 21 52 7,5 6
00 79 53 47 35 15 28 56 12 6
1C 135 68 65 40 15 28 61 12 6
1 135 72 65 40 20 46 65 14 6
11
Time-current characteristics
2
200 A 250 A
Pre-arcing time [s] tv/s
4 100 A 160 A
10
25 A 40 A 63 A 80 A 125 A
6 20 A 32 A 50 A
4
2
3
10
6
4
2
2
10
6
4
2
1
10
6
4
Special Purpose Fuses
2
0
10
6
4
2
-1
10
6
4
2
-2
10
1 2 3 4
10 2 4 6 10 2 4 6 10 2 4 6 10
Prospective current [A] Ip/A
12
2
100
6
4
2
NH DC 1000 V aR
10-1 General characteristics
6 Rated voltage 1000V d.c. (L/R=1ms)
Breaking capacity 30 kA d.c. Patented
4 technology
Standards IEC 60269-4 by
2 Application Fuse-link for DC application. Installation directly on copper rails.
10-2 NH DC 1000 V aR
6 Type with center Power Pre-arcing Operating
In trip indicator for dissipation Joule integral Joule integral Packaging Weight
4 Size [A] microswitch MK [W] (I2t) L/R=1ms (I2t) L/R=1ms [pcs] [g]
6 10 3
2800 4 004305636
6 104 139 2 500.000 4 6
1.000.000 105 2
Prospective current (A) Ip/A
3L 1000 004305637 154 900.000 1.600.000 1 1500
1250 004305635 201 1.500.000 3.000.000
Note: microswitch MK and adapter AMK2 must be ordered separately
6
10 5
114
Special Purpose Fuses
80
M12
73 106
Time-current characteristics
4
2 800A 1250A
Pre-arcing time (s) tv/s
103 1000A
6
4
2
102
6
4
2
101
6
4
2
100
6
4
2
10-1
6
4
2
-2
10
6 103 2 4 6 104 2 4 6 105 2
Prospective current (A) Ip/A
13
NH DC 1100 V aR
General characteristics Patented
technology
Rated voltage 1100V d.c. (L/R=10ms) by
Breaking capacity 70kA d.c.
Characteristics aR
Standards IEC 60269-4
Application Fuse link for battery charger.
NH DC 1100 V aR
Power Pre-arcing Operating
In U-170mm screw dissipation Joule integral Joule integral Packaging Weight
Size [A] contact [W] (I2t) L/R=1ms (I2t) L/R=1ms [pcs] [g]
3L 710 004725339 81 160.000 700.000 1/9 1970
Time-current characteristics
104
6
4
Pre-arcing time (s) tv/s
Special Purpose Fuses
2
103
6 710A
4
2
102
6
4
2
101
6
4
2
100
6
4
2
10-1
6
4
2
10-2
6
4
2 4 6 103 2 4 6 104 2 4
Prospective current (A) Ip/A
14
NV Telecom fuse disconnectors
Technical data for NV Telecom fuse disconnectors
Technical Specifications KVL00 Telecom
Electrical Characteristics
Rated operational voltage Ue V DC250
Rated operational current Ie A 750
Conventional free air thermal current with fuses Ith A 750
Rated insulation voltage Ui V 800
Rated conditional short-circuit current - kAeff 25
Utilization category (Switch without load!) Ie A DC 20-B/750 A
Rated impulse withstand voltage Uimp kV 8
Operating cycles with current - - 600
Fuse links
Size to DIN 43620 - - 00
Max. permis. power loss per fuse-link Pv W 35
Mechanical characteristics
Operating cycles without current - - 1000
Weight - kg 0,75
Cable connection
Flat terminal Bolt diameter - - M12
Cable lug (DIN 43620) - mm2 240
Flat bar - mm 30x10
Tightening torque Ma Nm 30-35
Type of protection
Special Purpose Fuses
Front side Operational state - - IP 20
Device fitted Front cover open - - IP 10
Operating conditions
Ambient temperature Tu C
O
-25 ... +55
Rated operating mode - - Continuous operation
Actuation - - dependent manual operation
Mounting position - - vertical, horizontal
Altitude - m ≤ 2000
Pollution degree - - 3
Overvoltage category - III
NV Telecom fuse disconnectors
type Code No.
KVL00 Telecom 1p M12, front connection 001690905
KVL00 Telecom 1p M12 MFM, front connection, striker pin (indication) 001690906
15
Special Purpose Fuses
16
Ø
Fuse base PK00-100mm
General characteristics
Rated voltage 1000V a.c./d.c.
Rated current 160A
Insulation class C-VDE 0110
Standards EN 60269, IEC 60269, DIN VDE 0636, DIN 43620,
DIN 43623
Fuse base PK00 1000V M8-M8
In Code Weight Packaging
Type
[A] No. [g] [pcs]
PK00 1000Va.c./d.c. M8-M8 160 004132026 190 3/120
Special Purpose Fuses
Dimensions [mm]
Type
A B C D E F H I J K M O
PK00 1000V M8-M8 136 94 121 58,5 M8 7,5 30 25 4,5 156 20 25,5
17
Fuse base PK1,2,3-100mm
General characteristics
Rated voltage 1000V a.c./d.c.
Rated current 250A, 400A, 630A
Terminal torque 32 Nm
Degree of protection IP00
Standards IEC 60269-2, DIN VDE 0636-21 (VDE 0636-21) 2015-03, DIN 43620
Application For use with aM and gB fuse-links
100
Fuse base PK-100mm
Cable lugs
In according to Weight Packaging
Type Code No.
[A] DIN 46235 [g] [pcs]
[mm2]
PK1-100 M10-M10 1p 1000V 250 25-150 004123400 623 3 100
35
PK2-100 M10-M10 1p 1000V 400 25-240 004123401 878 3
10
PK3-100 M12-M12 1p 1000V 630 25-300 004123402 1132 3
Sizes 1 & 2 16,5*
35
Special Purpose Fuses
10,5
10
35 30 H
Size 3
*PK1 1000V = 10,5
10,5
35
35 35 30
16,5
30 35 35
16,5* 100
10,5
30
16,5
100
H
10
10,5
Dimensions [mm]
Type
A C D E H K
PK1-100 M10-M10 1p 1000V 193 160 84 M10-M10 55,5 220
PK2-100 M10-M10 1p 1000V 220 186 90 M10-M10 65 245
PK3-100 M12-M12 1p 1000V 230 186 101 M12-M12 65 260 10
18
Fuse base PK1L
General characteristics
Rated voltage 1500V d.c.
Rated current 250A
Conv. free air thermal current with fuse links 250A
Max. permissible power dissipation per fuse link 32W
Max. breaking capacity per fuse link 200kA
Ambient temperature -5...+40 0C
Rated operating mode uninterrupted
Mounting position vertical, horizontal
Pollution degree 3
Overvoltage category III
Degree of protection IP00 without covers; IP20 with covers fitted
Standards DIN VDE 0636-21 (VDE 0636-21) 2015-03
Application For use with gB fuse-links size 1L
Fuse base PK-100mm
Cable lugs
In according to Weight Packaging
Type Code No.
[A] DIN 46235 [g] [pcs]
[mm2]
Special Purpose Fuses
PK1L M10-M10 1p 1500V 250 25-300 004132035 670 3
19
Fuse-link aM NV/NH 1000V a.c.
General characteristics
Rated voltage 1000V a.c.
Breaking capacity 25kA a.c.
Standards DIN VDE 0636-21 (VDE 0636-21) 2015-03
Characteristic aM
Application For equipment protection in mining industry. For relays, contactors and motors protection in
case of short-circuit. Used with fuse base PK00 1000V.
1000V a.c. aM
Operating Operating
Pre-arcing
Joule Joule Power
In Standard Joule Weight Packaging
Size integral integral dissipation
[A] indicator integral [g] [pcs]
[A2s] at [A2s] at [W]
[A s]
2
635V 1100V
25 004182485 1.500 5.000 9.000 9
32 004182486 2.500 9.500 15.000 10
35 004182487 3.500 12.000 20.000 10,5
40 004182488 4.000 15.000 25.000 11
50 004182489 7.000 23.000 40.000 13
00 350 3/45
63 004182490 11.000 40.000 60.000 15
80 004182491 17.000 63.000 100.000 17
100 004182492 32.000 110.000 170.000 19
125 004182493 45.000 150.000 230.000 21
Special Purpose Fuses
160 004182494 65.000 230.000 400.000 25
C 9,8
D G
E
H
B K
A F
Dimensions [mm]
Size
A B C D E F G H K
00 117 92 85 35 15 30 60 12 6
20
Time-current characteristics
4
2
Pre-arcing time (s) tv/s
103
6
4
2
102
6
4
2
101
6
4
2
100
6
4
2
10-1
6
4
Special Purpose Fuses
2
-2
10
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
Cut-off characteristics
2
105
I0/A
6
4
160A
125A
2 100A
80A
63A
50A
104 40A/35A
32A
25A
6
4
Показано початок документа. Повний текст — у PDF за посиланням вище.
Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.