| Вид документа | Каталог технічних даних |
|---|---|
| Виробник | ETI |
| Код документа | 1787_TD |
| Група обладнання | LV-fuse rail |
| Сторінок | 5 |
| Мова документа | англійська |
| Розмір файлу | 0.7 МБ |
Текст документа
Technical data
NV fuse-rail sizes 00, 1, 2, 3
Technical data of insulated fuse-rails (in accordance with VDE 0636, part 201, IEC 60269-2-1)
Technical Specifications VL00/100 VL00/185 VL1 VL1H
Electrical Characteristics
Rated operational voltage Ue V 690 AC 690 AC 690 AC 690 AC
Rated operational current Ie A 160 160 250 250
Rated frequency - Hz 40-60 40-60 40-60 40-60
Rated insulation voltage Ui V 800 AC 1000 AC
Total power loss at Ith (without fuse) Pv W 18 23 23 29
Fuse links
Size - DIN 43 620, IEC 60269-2 - - 000/00 1
Max. rated current (gG) In A 160 160 250 250
Max. permissible power loss per fuse link Pv W 12 32 23
Dimensions
Mass - kg 100 mm = 0,8 185mm=1,5 3,5
Busbars (distance) - mm 100 185 185
Cable connection
Screw - - M8 M10
Torque Ma Nm 12-15 30-35
V-clip - mm2 10-95 25-300 25-240 / 25-300
Torque Ma Nm 10 32
Protection
Operational state - - IP10
Operating conditions
Ambient temperature Tu O
C -25 ... +55
Operating condition - - Continuous operation
Mounting - - vertical, horizontal
Altitude - m ≤ 2000
Pollution degree - - 3
Overvoltage category - - III IV
Technical data of insulated fuse-rails (in accordance with VDE 0636, part 201, IEC 60269-2-1)
Technical Specifications VL2 VL2H VL3
Electrical Characteristics
Rated operational voltage Ue V 690 AC 690 AC 690 AC
Rated operational current Ie A 400 400 630
Rated frequency - Hz 40-60 40-60 40-60
Rated insulation voltage Ui V 1000 AC
Total power loss at Ith (without fuse) Pv W 54 73 115
Fuse links
Size - DIN 43 620, IEC 60269-2 - - 2 3
Max. rated current (gG) In A 400 400 630
NV/NH
Max. permissible power loss per fuse link Pv W 45 34 48
Dimensions
Mass - kg 3,8 4,3
Busbars (distance) - mm 185
Cable connection
Screw - - M12 M12 M12
Torque Ma Nm 35-40 35-40 35-40
V-clip - mm2 25-300 25-240 / 25-300 25-300
Torque Ma Nm 32 32 32
Protection
Operational state - - IP10
Operating conditions
Ambient temperature Tu O
C -25 ... +55
Operating condition - - Continuous operation
Mounting - - vertical, horizontal
Altitude - m ≤ 2000
Pollution degree - - 3
Overvoltage category - - IV
661
Technical data
Dimensional overview of LV NV fuse-rails
size 00/100 size 00/185
NV/NH
size 1, 2, 3 (M terminal)
662
Technical data
size 1, 2, 3 (SP terminal)
Dimensional overview of accessories for LV NV fuse-rails
NV/NH
busbar covering PZ 00/100
busbar covering PZ 123/185, busbar covering PZ 00/185
663
Technical data
busbar support PP 100/185
busbar covering PZ 00/185
NV fuse-rail type VL00 EK
49 83
Technical data
Type VL00/100 EK
Conventional free air thermal current (Ith) A 160
100
Rated insulation voltage V AC690
Rated withstand impulse voltage Kv 6
Rated frequency Hz 50 (40-60)
Power dissipation (without fuse-links) W 16,6 O
9
NV/NH
Degree of protection ( cover closed ) IP20
409
Degree of protection ( cover opened ) IP20 100
Pollution degree 3
Permissible ambient temperature** °C -25°C ... +55°C
Storage temperature °C -30°C ... +70°C
Weight ( without fuse-links ) kg 0,86 9x16
Package pcs 1
** with ambient temperature between 40-45°C, reduce Ith by 5%;
with ambient temperature above 45°C, reduce Ith by 10%
160
33
8,8
36,5
18
7,3 17
6,3 43
69
8,8
111
664
Technical data
Pribor / Accessories
Pribor / Accessories
100 mm
Pribor / Accessories
3 x M8 185 mm
M=12Nm
100 mm 6 x M8
M=12Nm
185 mm
NV Strip type fuse-switch-disconnector sizes 00, 1, 2, 3
Technical data of NV strip type fuse-switch-disconnectors (in accordance with IEC/EN 60947-3)
Technical Specifications SL00/100 SL00/185 SL1
Electrical Characteristics
Rated operational voltage Ue V 500 AC 690 AC 400 AC 500 AC 690 AC 400 AC 500 AC 690 AC 400 AC
Rated operational current Ie A 160 100 160 160 160 160 250 250 250
Rated frequency - Hz 40-60 40-60 40-60 40-60 40-60 40-60 40-60 40-60 40-60
Rated insulation voltage Ui V AC 800 AC 1000
Total power loss at Ith (without fuse) Pv W 18 23
Utilization category - - AC22B AC22B AC22B AC23B AC22B AC23B AC22B AC22B AC23B
Fuse links
Size - DIN 43 620, IEC 60269-2 - - 000/00 1
Max. rated current (gG) In A 160 100 160 160 160 160 250 250 250
Max. permissible power loss per fuse link Pv W 12 32
Dimensions
NV/NH
Mass - kg 100 mm = 1,40 185mm=2,4 4,9
Busbars (distance) - mm 100 185 185
Cable connection
Screw - - M8 M10
Torque Ma Nm 12-15 30-35
V-clip - mm2 10-95 25-300
Torque Ma Nm 15 32
Protection
Operational state - - IP30 IP30
Cover open - - IP10 IP10
Operating conditions
Ambient temperature Tu O
C -25 ... +55 -25 ... +55
Operating condition - - Continuous operation
Mounting - - vertical, horizontal
Altitude - m ≤ 2000
Pollution degree - - 3
Overvoltage category - - III IV
665Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.