Technical data
RCCBs - Residual current circuit breakers EFI
Features of residual current circuit breakers EFI
Rated conditional
short-circuit current :
10 kA
AC - pure sinus residual current,
A - AC + pulsating direct current
B - AC + A + smooth direct current +
high frequency (1kHz)
Quality seal for B+ - AC + A + smooth direct current +
tested reliability high frequency (20kHz)
Real contact position indica-
tion for easier contact status
identification
Test button enables user to
check residual functionality
Various quality marks
RCCBs can be supplied with
single phase and three phase
busbars
The terminals accept not
only wires but also time saving
busbars
Supply is possible both
from top and bottom terminals
55
Technical data
Residual current circuit breakers can be used in TN-S, TN-CS, TT and IT network systems, or with other words,
in all systems where neutral and protective conductors are separated. Residual current circuit breakers EFI are
used for protection against indirect contact (fault protection) and direct contact (additional protection) of parts
under voltage. In the case of protection against indirect contact (fault protection) you can use residual current
protective devices with a rated residual current of IΔn ≤ 300mA. Residual current protective devices with a rated
residual current of IΔn ≤ 30mA fulfil the conditions for protection against direct contact (additional protection).
For protection against fire, according to DIN VDE 0100-482 and IEC 60364-4-482, all cables and conductors in
TN and TT systems must be protected by means of residual current protective devices with rated residual current
of IΔn ≤ 300mA. In applications where resistive faults can cause a fire (radiant ceiling heating with panel heating
elements), the rated residual current must be IΔn = 30mA.
Types
AC Type: they are sensitive to alternating (sinusoidal) AC residual currents.
A Type: they are sensitive to alternating (sinusoidal) AC residual currents and pulsating DC residual currents.
B Type: they are sensitive to alternating (sinusoidal) AC residual currents, pulsating DC residual currents and
smooth DC residual currents. Tripping values are defined up to 1kHz.
B+ Type: they are sensitive to alternating (sinusoidal) AC residual currents, pulsating DC residual currents and
smooth DC residual currents. Tripping values are defined up to 20kHz and they are below 420mA.
Classification regarding break time
Instantaneous: max. break time 40ms (Inst.)
K-Short time delay: time delayed min. 10ms and max. 40ms (K)
S-Selective: time delayed min. 40ms and max. 150ms (S)
Type AC Type A
EFI 2 (2M)
Inst. Inst. K S
For alternating residual current
For alternating and pulsating direct
residual current
Short-circuit capacity with back-
up fuse
Lower temperature limit of applica-
tion -25°C
VDE 0664, part 1
(up to 80 A)
K Short time delayed (10 - 40 ms)
Selective (time delayed 40 -150 ms)
Type AC Type A Type B Type B+
EFI 4 (4M)
Inst. Inst. K S Inst. K S Inst. K S
For alternating residual current
For alternating and pulsating direct
residual current
For alternating, pulsating direct and
smooth DC residual current (up to 1kHz)
For alternating, pulsating direct and
smooth DC residual current (up to 20kHz)
Short-circuit capacity with back-up fuse
Lower temperature limit of application
-25°C
VDE 0664, part 1
(up to 80 A)
K Short time delayed (10 - 40 ms)
Selective (time delayed 40 -150 ms)
56
Technical data
Use of AC, A, and B type of RCCB’s in case of different fault
conditions
AC A B, B+
Connection Normal mains current Fault earth current
1 Single-phase
IL IF
L
IF
IL t t
N
PE
2 Single-phase with smoothing
IL IF
L
IF
IL
t t
N
PE
3 Three-phase star
IL IF
IL
L1
L2 IF
L3 t t
N
PE
4 Two-pulse bridge
IL IL IF
L IF
N
t t
PE
5 Two-pulse bridge, half-controlled
IL IF
IL
L IF
N t t
PE
6 Two-pulse bridge between phases
IL IF
IL
L1
IF
L2
t t
N
PE
7 Six-pulse bridge
IL IL IF
L1 IF
L2
t t
L3
PE
8 Phase control
IL IL IF
L
IF
t t
N
PE
9 Burst control
IL IL IF
L
IF
t t
N
PE
57
Technical data
Residual current circuit breaker EFI-2
Technical data
Rated voltage Un 230 V AC
Rated current In 16, 25, 40, 63, 80, 100 A
71.5
45 87.5 Rated residual current I∆n 0.03 , 0.1, 0.3, 0,5 A
Conditional short-circuit current 10 kA
Rated making and breaking capacity Im 800 A
Back-up fuse 100 A gG
monatlich Is kra
drücken
5 18
Degree of protection RCD IP 20 (IP40)
30.5
42.5 36 Insulating class NFI 2 100 /0,0 B 3
Cross-section of connecting lead 1 - 25 mm2 (1-35 mm2 - 100 A)
I
K R W37 423 471 / list 30/ izdaja 2/ NF I2
68
In 100A Un 230V
EFI-2 16-80 A Standards EN 61008, IEC 61008,
I n0,0 3A
2pol IP 40
10000
1 3
T
2 4
I V 0
EFI-2 100 A
EFI-2 100 A
EFI-2 100 A
Residual current circuit breaker EFI-4
Technical data
Rated voltage Un 230/400 V AC
71.5
45 87.5 Rated current In 16, 25, 40, 63, 80, 100 A
Rated residual current I∆n 0,03, 0,1, 0,3, 0,5 A
Conditional short-circuit current
Rated making and breaking capacity Im
Is kra 10 kA
800 A
monatlich
30.5 5 18
drücken
42.5 72 Back-up fuse R CgGD
100 A
68
Degree of protection
NF I 4 100/0,03
IP20 (IP40)
W37 423 778 / lis t 40/ izdaja 02/ NF I4
EFI-4 16-80 A
I
Insulating class B
Cross-section of connecting lead
I 100A U A)
1 -n25 mm2 (1-35 mm2 -n100230/400V
Standard ENI n 0,IEC03A
61008, 61008 4pol IP 4 0
10000
0
13 5 N
Naziv Projekt. Pregled
T
POKROV I V
Datum 01.03.07 01.03.07
Podpis
24 6 N
Pripadnost K Identifikac
NFI2 KR W 37
EFI-4 100 A
58
Technical data
Auxiliary switch PS EFI
The PS EFI is fixed to EFI series switches. The width of the device is 9 mm, other dimensions are in compliance with EFI
switches. The auxiliary switch PS EFI is used for the remote signalling of the state of contact’s condition (closed/open) of
EFI switches. During fitting, the EFI must be switched off.
87.5
Technical data 45 9
Rated current In 6 A (230 V AC), AC 12,
1 A (110 V DC), DC 12
Conditional short-circuit current 1 kA with fuse-link 20 A
Standards EN 62019
58
42.4
37.5